Splus AFTF-T3-MB Humidity and Temperature Sensor Instruction Manual
- May 15, 2024
- Splus
Table of Contents
Splus AFTF-T3-MB Humidity and Temperature Sensor
Product Information
Model: AFTF-T3-MB
Specifications
- Dimensions: 116mm x 106mm x 78.5mm
- Type: On-wall-sensor, measuring transducer
- Measurements: Temperature, relative/absolute humidity, dew point, enthalpy, the mixture ratio Calibratable with Modbus connection
Product Usage Instructions
Installation
- Mount the sensor on the desired wall location using appropriate mounting hardware.
- Ensure the sensor is securely fixed to the wall to prevent any movement.
- Connect the Modbus cable to the sensor for data communication.
Configuration
- Set the bus address using the DIP switches according to the provided instructions.
- Adjust the bus parameters for baud rate and parity based on your requirements.
Calibration
- Perform calibration as per the specific calibration instructions provided in the manual.
- Verify the accuracy of temperature, humidity, and other measurements after calibration.
Data Reading
- Use the provided telegram codes to read specific data points such as temperature, humidity, dew point, etc.
- Refer to the manual for interpreting the data values and units.
(FAQ)
- Q: How do I change the Modbus address of the sensor?
- A: To change the Modbus address, adjust the DIP switches according to the provided instructions. For example, setting DIP 1 to ON, DIP 2 to ON, and DIP 8 to ON would result in a Modbus address of 193.
- Q: What is the default bus parameter configuration?
- A: The default bus parameter configuration includes a baud rate of 9600 Baud, Even parity, and other settings as specified in the manual.
Type AFTF-T3-MB
Calibratable outside humidity and temperature sensor Type AFTF – T3 – MB,
with Modbus connection, in an impact-resistant plastic housing with quick-
locking screws, with a plastic sinter filter (exchangeable), to exactly detect
the relative humidity (0…100% RH) and the temperature (–35…+80 °C) and to
detect various parameters in humidity measurement. The international system of
units SI (default) can be switched to Imperial (via Modbus). The on-wall
sensor is applied in a non-aggressive, dust-free environment. It is used in
refrigeration, air conditioning and clean room technology, engineering rooms,
hotels and conference facilities.
A long-term stable, digital humidity and temperature sensor guarantees exact
measurement results. These measurands are used to internally calculate the
following parameters that can be retrieved via Modbus: relative humidity,
absolute humidity, mixture ratio, dew point, enthalpy (ignoring atmospheric
air pressure) and ambient temperature. Innovative Modbus sensor with
galvanically separated RS485-Modbus interface, selectable bus termination
resistance, DIP switch for setting the bus parameters and bus address in
current-free state, internal LEDs for telegram status display, and two
separate push-in terminals. The sensor is factory-calibrated; an environmental
precision adjustment by an expert is possible.
TECHNICAL DATA
AFTF-T3-MB | On-wall humidity- | and | temperature sensors |
---|---|---|---|
Type | Measuring Range |
Humidity (switchable)
|
Temperature
| Danfoss
Part Number
Schematic diagram
Manual offset adjustment
- The sensors are pre-set and calibrated at the factory.
- For subsequent adjustment of the measured value,
- there are two offset potentiometers (A and B) available.
- Range of adjustment:
- (A) approx. ± 5 °C ⁄ ± 9 °F
- (B) approx. ± 10 % RH
Switchable system of units
Configuration
The device address in the range of 1 to 247 is set at DIP switch [A]. For switch positions 1 to 8 see the table on the back!
- Address 0 is reserved for broadcast messages.
- Addresses greater than 247 must not be assigned and are ignored by the device.
The DIP switches are binary-coded with the following values:
- DIP 1 = 128 ………… DIP 1 = ON
- DIP 2 = 64 ………… DIP 2 = ON
- DIP 3 = 32 ………… DIP 3 = OFF
- DIP 4 = 16 ………… DIP 4 = OFF
- DIP 5 = 8 ………… DIP 5 = OFF
- DIP 6 = 4 ………… DIP 6 = OFF
- DIP 7 = 2 ………… DIP 7 = OFF
- DIP 8 = 1 ………… DIP 8 = ON The switch positions shown here result in the Modbus address 128 + 64 + 1 = 193
BUS PARAMETERS
The baud rate (speed of transmission) is set at DIP switches 1 and 2 of DIP
switch block [B]. Selectable are 9600 baud, 19200 baud, or 38400 baud – see
table! Parity is set at DIP switch 3 of DIP switch block [B]. Selectable are
EVEN or ODD – see the table! Parity check is activated via DIP switch 4 of DIP
switch block [B]. Selectable are active (1 stop bit), or inactive (2 stop
bits), i.e. no parity check – see table! The 8N1 mode is activated via DIP
switch 5 of DIP switch block [B].
The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of
DIP switch block [B] is therefore deactivated. Selectable are 8N1 active or
inactive (default) – see table !. Bus termination is activated via DIP switch
6 of DIP switch block [B] Selectable are active (bus termination resistance
of 120 Ohm), or inactive (no bus termination) – see table!
COMMUNICATION INDICATOR
Communication is indicated via two LEDs. Error-free received telegrams are
signalized by the green LED lighting up, regardless of the device address.
Faulty telegrams or triggered Modbus exception telegrams are depicted by the
red LED lighting up
DIAGNOSTICS
An error diagnostic function is integrated
Telegrams
Register | Parameter | Data Type | Value | Range |
---|---|---|---|---|
3×0001 | Temperature | Sampling 4 s | Signed 16 Bit | – 350… +800 |
– 310…+1760
| – 35.0… +80.0 °C
– 31.0…+176.0 °F
3×0002| Temperature| Filtering 32 s| Signed 16 Bit| – 350… +800
– 310…+1760
| – 35.0… +80.0 °C
– 31.0…+176.0 °F
3×0003| Relative humidity| Sampling 4 s| Signed 16 Bit| 0…1000| 0.0. 100.0 %
RH
3×0004| Relative humidity| Filtering 32 s| Signed 16 Bit| 0…1000| 0.0. 100.0
% RH
3×0005| Dew point| Computed value| Signed 16 Bit| 0… 500
320…1220
| 0.0… +50.0 °C
32.0…+122.0 °F
3×0006| Absolute humidity| Computed value| Signed 16 Bit| 0…800
0…349
| 0.0. 80.0 g / m³
0.0. 34.9 gr / ft³
3×0007| Mixing ratio| Computed value| Signed 16 Bit| 0… 800
0…5600
| 0.0….. 80.0 g / kg
0.0. 560.0 gr / lb
3×0008| Enthalpy| Computed value| Signed 16 Bit| 0…850
0…360
| 0.0. 85.0 kJ / kg
0.0. 36.0 Btu / lb
Function 05 Write Single Coil
Register | Parameter | Data Type | Value | Range |
---|---|---|---|---|
0x0001 | reserved | |||
0x0002 | System of units | SI | → | Imperial |
1 | SI (Default) – Imperial | |||
Temperature Relative humidity | [°C] [% RH] | → | [°F] [% RH] | |
Dew point Absolute humidity Mixing ratio Enthalpy | [°C] |
[g / m³] [g / kg] [kJ / kg]| →
→
→
→
| [°F] [gr / ft³] [gr/lb] [Btu / lb]| | |
Function 08 Diagnostics
The following sub-function codes are supported
Sub Function Code | Parameter | Data Type | Answer |
---|---|---|---|
00 | Echo of transmission data (Loopback) | Echo data | |
01 | Restart Modbus |
(Reset listen-only mode)
| | Echo telegram
04| Activation listen-only mode| | No answer
10| Delete counter| | Echo telegram
11| Counter bus telegrams| Unsigned 16 Bit| All valid bus telegrams
12| Counter communication errors (Parity, CRC, frame errors, etc.)| Unsigned
16 Bit| Faulty bus telegrams
13| Counter exception telegrams| Unsigned 16 Bit| Error counter
14| Counter slave telegrams| Unsigned 16 Bit| Slave telegrams
15| Counter telegrams without answer| Unsigned 16 Bit| Broadcast messages
(address 0)
Function 17 Report Slave ID Composition of answer telegram
Byte No. | Parameter | Data Type | Answer |
---|---|---|---|
00 | Number of bytes | Unsigned 8 Bit | 6 |
01 | Slave ID (device type) | Unsigned 8 Bit | 16 = Type AFTF-T3-MB |
02 | Slave ID (device class) | Unsigned 8 Bit | 30 = Humidity |
03 | Status | Unsigned 8 Bit | 255 = RUN, 0 = STOP |
04 | Version number (release) | Unsigned 8 Bit | 1…9 |
05 | Version number (version) | Unsigned 8 Bit | 1…99 |
06 | Version number (index) | Unsigned 8 Bit | 1 |
Installation
Terminating resistors may only be installed at the ends of the bus line. In
networks with repeaters not more than two line terminations are allowed. Line
termination at the device can be activated via DIP switch 6.
The bias resistors for bus level definition in the resting state are usually
activated at the Modbus master/repeater. The maximum number of subscribers per
Modbus segment is 32 devices. When the number of subscribers is greater, the
bus must be subdivided into several segments separated by repeaters. The
subscriber address can be set from 1 to 247. For the bus line, a twisted-pair
cable data line / power supply line and copper mesh wire shield must be used.
Therefore, the line capacitance should be less than 100 pF / m (e.g. Profibus
cable).
Installation and Commissioning
Devices are to be connected under dead-voltage conditions. Devices must only be connected to safety extra-low voltage. Consequential damages caused by a fault in this device are excluded from warranty or liability. These devices must be installed and commissioned by authorised specialists. The technical data and connecting conditions shown on the device labels and in the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products. In case of any modifications made by the user, all warranty claims are forfeited. Operating this device close to other devices that do not comply with EMC directives may influence functionality. This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes. Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions. Modifications of these records are not permitted. In case of a complaint, only complete devices returned in original packing will be accepted.
Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations and
standards applicable to the place of measurement (e.g. such as welding
instructions, etc.). Particularly the following shall be regarded:
- VDE ⁄ VDI directive technical temperature measurements, measurement set-up for temperature measurements.
- The EMC directives must be adhered to.
- It is imperative to avoid parallel laying of current-carrying lines.
- We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC.
Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:
- Measuring range
- Oscillations, vibrations, and shocks are to be avoided (< 0.5 g)
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions.
When operating under deviating conditions, we recommend performing an initial
manual adjustment on-site during commissioning and subsequently at regular
intervals. Commissioning is mandatory and may only be performed by qualified
personnel!
Important notes
Our “General Terms and Conditions for Business“ together with the “General
Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry“ (ZVEI conditions) including supplementary clause
“Extended Retention of Title“ apply as the exclusive terms and conditions. In
addition addition, the following points are to be observed:
- These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
- A suitable weather and sun protection hood must be used when installed outdoors.
- Devices must only be connected to safety extra-low voltage and under dead-voltage conditions. To avoid damages and errors the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
- This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
- No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
- Consequential damages caused by a fault in this device are excluded from warranty or liability.
- These devices must be installed and commissioned by authorised specialists.
- The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
- In case of any modifications made by the user, all warranty claims are forfeited.
- This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat i rradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
- Operating this device close to other devices that do not comply with EMC directives may influence functionality.
- This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
- Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
- Modifications of these records are not permitted.
- In case of a complaint, only complete devices returned in original packing will be accepted.
Commissioning is mandatory and may only be performed by qualified personnel! These instructions must be read before installation and commissioning and all notes provided therein are to be regard!
DIMENSION
Copyright by S+S Regeltechnik GmbH
subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to i nform about our products and their application potential but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions
Bus address, binary coded
Documents / Resources
|
Splus AFTF-T3-MB Humidity and Temperature
Sensor
[pdf] Instruction Manual
AFTF-T3-MB, AFTF-T3-MB Humidity and Temperature Sensor, Humidity and
Temperature Sensor, Temperature Sensor, Sensor
---|---