Jaga Micro Canal Small Powerful Low Flow Trench Heating Unit User Manual
- May 15, 2024
- jaga
Table of Contents
- USED SYMBOLS
- WARNINGS AND SAFETY
- PACKAGING AND COMPONENTS
- INSTALLATION
- GENERAL INFORMATION
- PRODUCT DESCRIPTION
- TECHNICAL DATA
- INSTALLATION
- INITIAL START
- MAINTENANCE
- WARRANTY
- DISSASSEMBLY INSTRUCTIONS
- DECLARATION OF CONFORMITY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Jaga Micro Canal Small Powerful Low Flow Trench Heating Unit
USED SYMBOLS
the DANGER sign warns the operator and maintenance staff about risks that
may cause death, physical injury or illnesses of any kind.
DANGER: ELECTRICAL HAZARD
DANGER: SHARP EDGES
DANGER: HOT SURFACES
DANGER: MOVING PARTS
ATTENTION: IMPORTANT WARNING
the ENVIROMENTAL SAFEGUARD sign provides instructions on how to use the unit
in an ECO-friendly manner.
Important info
The unit must be installed by a certified installer in accordance with the
installation instructions and the local building codes. Please follow this
instruction manual and file it somewhere safe! The unit must always be
accessible for maintenance and inspection.
The warranty is void when:
- the installation, maintenance or operation instructions in this manual are not respected.
- modifications have been made to the product, before, during or after product installation.
- maintenance has been carried out by unauthorized people.
- maintenance has been carried out by someone other than Jaga.
- access to the unit has been restricted due to on-site conditions.
- the initial start-up has been carried out before a general cleaning of both the fan and the coil.
WARNINGS AND SAFETY
Handling guidelines:
The unit must be handled with care in order to avoid damage to the unit’s
interior and exterior parts.
The unit might have sharp edges; use gloves during installation/adjustment.
All the operations listed below must be carried out in accordance with local
health and safety regulations.
Storage conditions:
Up to four packaged units may be stacked on top of each other. All units must
be stored in a dry area.
Technical spaces and positioning:
Incorrect installation of the unit may cause noise and vibrations issues.
PACKAGING AND COMPONENTS
Follow these instructions when removing the packaging:
- check for any visible damage
- open the packaging
- check if the manual is in the package
- remove the packaging material and put it in the appropriate collection point or recycling facility, in compliance with the local regulations.
Dispose of the packaging materials in compliance with the national or local
regulations.
Do not leave the packaging within reach of children.
INSTALLATION
- installation must be carried out by certified technicians. Incorrect installation could cause product failure, a reduced performance or an increased noise level.
- the unit must be installed in accordance with the local building codes.
- Always use personal protective equipment.
- the unit must remain accessible for inspection and maintenance, the trench must be removable at all times.
-
ACOUSTIC INSULATION
Sound absorption
Sound is reflected by hard materials. Soft, porous materials are best suited for sound absorption. A combination of different materials can reduce the reflection of sound.
Contact noise insulation
Sound travels very easily through hard materials. Soft rubber material can be used to reduce contact noise. The effect of this insulation strongly depends on:- installation method: make sure that vibrations cannot be transferred between different elements, e.g. between the built-in heaters and other metallic parts, through pipes, along air ducts etc.
- installation of acoustic insulation in hollow acoustic spaces. Avoid cavities between insulation and pipes.
GENERAL INFORMATION
DANGER
The unit is not intended for industrial applications.
Do not insert objects into the supply and return air openings.
IMPORTANT!
- the unit will only function correctly if the installation and operation manual is strictly followed.
- all clearances indicated in the manual must be respected in order to guarantee performance, and to allow installation and maintenance.
- in case valve packages are to be installed, make sure that there is enough room left.
- periodic access to the unit is required for inspection, maintenance and repairs.
- pay attention to the signs and symbols indicated on the fan coil units.
Unit identification:
The serial number is tagged on unit’s right side (on the left if the
connections are on the unit’s right side).
Information regarding unintended use:
The unit has been designed to function as a fan coil for both heating and
cooling applications; any other use is strictly forbidden. Installing the unit
in an explosive environment is prohibited.
Decommissioning:
When the unit is not used for long periods of time, it must be disconnected
from the mains electrical connection.
If the unit is not used during the winter period, the water in the system may
freeze. A suitable quantity of anti-freeze liquid should be mixed with the
water.
Mixing the water with glycol modifies the unit’s performance. Pay attention to
the safety instructions on the packaging regarding glycol.
Restart after prolonged shutdown:
Before restarting:
- clean or replace the stainless steel fan guard.
- clean the coil.
- clean or unclog the condensate drain.
- bleed the air from the hydronic system.
- it is advisable to run the unit at maximum speed and to check for abnormalities.
PRODUCT DESCRIPTION
The Micro Canal is only223/64 inch in height and 51/8 inch in width. It is fitted with small but powerful dynamic coils and quiet fans with EC-motors. Micro Canal combines minimalistic aesthetics and architectural freedom with an unprecedented heat output. Micro Canal can be integrated into any interior. By making use of the latest EC-motors, the Micro canals use 50% less power.
OVERVIEW OF THE DIFFERENT PARTS
- Polyethylene protection block
- Stainless steel grille
- Control board
- Water temperature sensor
- End cap
- Hydraulic connection ( always on the left hand side)
- Electrical connection (always on the left hand side)
- Tangential fans with EC-motor
- Dynamic coil
- Inner trench with stainless steel grille holder
- Outer trench
- Internal height adjustment
TECHNICAL DATA
DIMENSIONS OF THE INNER TRENCH
*Continuous installation: Do not assemble the end caps on the sides where the units need to be connected to each other. Keep in mind that the units are 1/8 inch shorter without the end caps.
DIMENSIONS OF THE OUTER TRENCH
HEIGHT ADJUSTMENT
OPTION: ADJUSTABLE RAISED FLOOR PEDESTALS
MAX CABLE LENGTH – 24 VDC ELECTRICAL CONNECTION
DISTANCE FROM POWER SUPPLY IN FT.| 30| 60| 100| 130| 160| | 200| 230| 260|
300| 330
---|---|---|---|---|---|---|---|---|---|---|---
Ø| TYPE 1 (1.3W) NUMBER OF MICRO CANALS
17 AWG| 63| 32| 21| 16| 12| 10| 9| 8| 7| 6
16 AWG| 95| 48| 32| 23| 19| 16| 13| 12| 10|
9
14 AWG| 160| 80| 53| 40| 32| 26| 22| 20| 17|
16
Ø| TYPE 2 (1.7W) NUMBER OF MICRO CANALS| | | | | |
17 AWG| 48| 24| 16| 12| 9| 8| 7| 6| 5| 4
16 AWG| 73| 36| 24| 18| 14| 12| 10| 9| 8| 7
14 AWG| 120| 60| 40| 30| 24| 20| 17| 15| 13|
12
Ø| TYPE 3 (2W) NUMBER OF MICRO CANALS| | | | | |
17 AWG| 41| 20| 13| 10| 8| 6| 5| 4
16 AWG| 62| 31| 20| 15| 12| 10| 8| 7| 6
14 AWG| 102| 51| 34| 25| 20| 17| 14| 12| 11|
10
Ø| TYPE 4 (3.4W) NUMBER OF MICRO CANALS| | | | | |
17 AWG| 24| 12| 8| 6| 4| 3| 2
16 AWG| 36| 18| 12| 9| 7| 6| 5| 4| 3
14 AWG| 60| 30| 20| 15| 12| 10| 8| 7| 6
Ø| TYPE 5 (3.7W) NUMBER OF MICRO CANALS| | | | | |
17 AWG| 22| 11| 7| 5| 4| 3| 2
16 AWG| 33| 16| 11| 8| 6| 5| 4| 3
14 AWG| 56| 28| 18| 14| 11| 9| 8| 7| 6| 5
INSTALLATION
ALWAYS SWITCH OFF THE MAINS SUPPLY BEFORE INSTALLATION!
-
Place the mounting strips on the unit’s outer trench.
-
Bend the mounting strips (max.25/32 inch).
-
Multiple Micro Canals: make sure that the unit is correctly positioned and that the grille holders are tightly connected. Use the provided connectors to connect the different units to each other.
-
Position the units correctly, with the coil towards the wall.
Position the unit at a distance of at least 7 7/8 inch from a window wall. -
Mark the drill holes. Drill the holes (drill dia.5/16inch) and insert the plugs
Make sure to use the correct type of plug for your floor type!
-
Secure the unit to the floor with mounting strips.
-
Fill the cavities underneath the trench with a solid mass.
-
Place both the supply and return hoses as well as the power cable.
Make sure that there is at least 2 23/64 inch of both hose and cable inside the trench.
-
Cover the unit with the protection block.
-
With screed (concrete or cement), installation of edge insulation is required around the unit in order to protect it from stress.
-
Remove the protection block. Assemble the end cap and place the inner trench in the outer trench.
-
Use the adjustment-screws to adjust the unit’s height. Make sure that the top is level with the finished floor.
-
Secure the inner trench.
-
Connect with flexible hoses (supplied by others) to the coil’s supply and return connections.
-
[+] and [-] need to be connected to the unit’s electrical connectional.
Always switch off the mains supply before installation!
-
Click the water temperature sensor on top of the coil. The water temperature should be at least 340C. If it is lower, remove the sensor and turn on/off the fans by means of a potential free thermostat.
-
After placing the subfloor and the finished floor: remove the protective cover and the foil, place the grille and then apply the finishing touches.
INITIAL START
IMPORTANT!
Start-up and Commissioning of the fan coil must be carried out by skilled
staff, qualified to work on this type of product.
DANGER!
Before start-up, make sure the installation has been carried out in compliance
with in this manual.
Before start-up the fan coil unit, check if:
- the unit is positioned correctly
- the supply and return pipes are properly connected and insulated
- the pipes are clean and air is removed
- the inclination of the unit towards the drain and the p-trap are correct
- the coils are clean
- the wiring connections are correct and properly tightened
- the supply voltage is correct
- the electric power consumption is correct and does not exceed the maximum value indicated in the catalog
Run the fan for minimal 3 hours and check for abnormalities.
MAINTENANCE
DANGER!
- maintenance must be carried out by qualified technicians.
- do not insert sharp objects into the supply and return grilles
- the unit has sharp edges; use gloves during maintenance!
DANGER!
Always use the main disconnect switch to isolate the unit from the mains
before carrying out any maintenance or inspection work. Make sure that no one
accidentally turns on the power to the unit; lock the master switch in the off
position.
-
SPECIAL NOTE
Maintenance and cleaning of the stainless steel protection grille: a dirty grille obstructs the air flow, so clean the grille at regular intervals, depending on the room’s purpose and how it’s used. The grille should never be disassembled for maintenance and can be easily cleaned by using a vacuum cleaner.
Cleaning the unit
always disconnect the power supply before servicing the fan!!- cleaning at regular intervals is important, depending on the room’s purpose and how it’s used
- clean with a vacuum cleaner or air compressor. Do not use solvent- or detergent based products.
-
ROUTINE MAINTENANCE
Every 6 months: Check the condition of the coil and condensate drain: If necessary:- remove any dirt from the coil surface
- remove dust using an air compressor
- wash with water and brush gently
- dry by using compressed air
- keep the condensate drain free from any obstructions that may prevent normal water flow
Bleed air from the system.
- start the circulation pump and open the supply valve for a few minutes.
- stop the circulation pump.
- loosen the vent screw on the inlet collector and bleed the air.
- repeat steps 1 to 3 until there is no more air escaping the system
-
ELECTRICAL CIRCUIT
The following steps are recommended to perform maintenance on the electrical circuit:- check the unit’s power consumption using a clip-on meter and compare the reading with the values shown in the documentation;
- inspect the electrical contacts for corrosion and loose wires.
WARRANTY
The fan coil unit is intended strictly for conditioning the indoor climate.
Any unintended use is strictly forbidden and voids all warranty on the
product. Installation, maintenance and operation of the unit is only allowed
for authorized staff.
Please follow these instructions carefully
The warranty is void when:
- the installation procedure has not been followed,
- the fan coil has not been periodically cleaned,
- the unit has been used in an improper or irresponsible manner,
- repairs have been carried out by others than Jaga,
- product modifications have been carried out by others, before or after the installation,
- the product is not accessible for cleaning or maintenance.
If you have any questions or complaints, please contact your supplier or installer. The copyright of these instructions is the property of Jaga.
DISSASSEMBLY INSTRUCTIONS
SAFEGUARD THE ENVIROMENT
Jaga cares about protecting the environment.
When the unit is dismantled it is important to strictly follow these procedures:
- the unit must be dismantled by a firm that is authorized to dispose of scrap machinery/products The unit as a whole is composed of secondary raw materials and the following conditions must be met:
- if the unit contains antifreeze, then dispose of the antifreeze as indicated in the glycol supplier’s instructions.
- the electronic components are considered special waste, and must be recycled as such
- the pipe insulation and the sound-absorbing lining must be removed and processed as urban waste Please follow and file these instructions!
Jaga Canada Climate Systems www.jaga-canada.com
DECLARATION OF CONFORMITY
JAGA N.V. – Verbindingslaan 16 – B 3590, declares under its sole
responsibility that the product to which this declaration relates: MICRO CANAL
is in conformity with the following standards or documents provided that these
are used in accordance with our instructions: NBN EN 60335-1 based on EN
60335-1:2002 + A11:2004 + A1:2004 + A12:2006 + A2:2006 + A13:2008 + A14:2010
+A15:2011
NBN EN 60335-2-80 based on EN 60335-2-80:2003 + A1:2004 + A2:2009
Following the provision of Directives as amended:
CEO JAGA N.V. Jan Kriekels
08/01/2015
- Low Voltage 2014/35/EC
- EMC 2014/30/EC
- Machinery 2006/42/EC
Jaga N.V.
+32 (0)11 29 41 11
As product deCvelopment is a continuous process, all mentioned data are subject to change.
augustus 9, 2021 2:24 p.m. – Jaga Inc.