Specifications:

  • Input: 220-240 Vac 50Hz

  • Operating Frequencies: 2.4 – 2,483 GHz

  • Max. Output Power: +4 dBm

  • Lux Parameters Range: 5 – 2000 lux

  • Dimensions: 79mm x 85mm x 85mm

  • Weight: 95g (unpacked)

  • Degree of Protection: IP20

  • Material (Casing): Flame-retardant
    polycarbonate

  • Finish/Colour: Matt/White (RAL 9003)

Product Usage Instructions

Installation:
To install the CBU-CEFL, follow these steps:

  1. Ensure the ceiling void is at least 78mm deep.
  2. Drill a 73/75mm diameter hole in the ceiling for mounting.
  3. Connect the device by following the wiring diagram provided in the manual.
  4. Use the Casambi APP on Google Play or Apple APP Store for configuration.

Operation:
To operate the CBU-CEFL:

  1. Adjust settings such as time out and daylight threshold using the Casambi APP.
  2. Ensure proper connection to Live (L) and Neutral (N) terminals.

Precautions:
Follow these precautions for safe usage:

  • Installation should be done by a competent person following relevant standards.
  • If unsure, consult a qualified electrician.

Maintenance:
Regularly check for any loose connections or signs of damage. Clean the device as needed with a dry cloth.

FAQ:

  1. Q: What is the recommended mounting height for optimum coverage?
    A: The recommended mounting height is between 2.4 to 5 meters for optimum coverage.

  2. Q: How do I adjust the time out and daylight threshold settings?
    A: Use the Casambi APP on Google Play or Apple APP Store to configure these settings.

  3. Q: What is the warranty period for the CBU-CEFL?
    A: The CBU-CEFL comes with a 5-year warranty from the date of manufacture and is CE marked.

CBU-CEFL
Ceiling Flush Mount Passive Infra Red (PIR) Occupancy Detector & Photocell

  • Input: 220-240 Vac 50Hz
  • PLEASE READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRODUCT NOTE: CBU-CEFL is only compatible to work with CASAMBI enabled equipment

This flush mounted CBU-CEFL is suitable for easy mounting through a 73/75mm diameter hole into a ceiling void which is at least  78mm deep. Configurable for any  room occupancy style, via the free  to download Casambi APP on Google Play or Apple APP Store.DANLERS-CBU-CEFL-Ceiling-Flush-Mount-Passive-
Infra-Red- \(2\)

INSTALLATION

To be installed by a competent person with reference to BS 7671 or equivalent local standards. If in doubt consult a qualified electrician.

  • Plan where the CBU-CEFL is to be located (see diagram 1). Switch off supply and check for hidden cables and pipes. Make a 73/75mm diameter hole through a standard ceiling board.
  • The CBU-CEFL should be connected as shown in diagram 2:
    • L – Live in. N – Neutral in.
    • Ensure both springs are fitted to the molding in the correct orientation (see diagram 3).DANLERS-CBU-CEFL-Ceiling-Flush-Mount-Passive-Infra-Red- \(5\)
    • Push the CBU-CEFL into the ceiling void, making reference to diagram 4.DANLERS-CBU-CEFL-Ceiling-Flush-Mount-Passive-Infra-Red- \(6\)

OPERATION

To check the operation of the CBU-CEFL:

  • Turn on the supply then after 20 seconds if the sensor has recognised movement of a person within its zone of detection the integral red LED on CBU-CEFL will stay illuminated for 4 seconds before the red LED turns off.
  • Thereafter, every time movement is detected by CBU-CEFL the integral red LED will stay illuminated for 4 seconds.
  • The control also features adjustable time out (time lag) control and daylight threshold control which are configured by the Casambi APP.

PRECAUTIONS

  • Do not place the CBU-CEFL near heat sources, fans or in ventilated ceiling voids.
  • CBU-CEFL can be wired in parallel (sharing the same Live and Neutral).
  • Do not place close to, or positioned such that, any light source points directly into the CBU-CEFL.
  • Ensure wires and cables are securely held within the connection terminals.
  • The CBU-CEFL should be protected by a 5 or 6 Ampere mcb or fuse.
  • Disconnect the CBU-CEFL from the circuit before performing insulation testing of the wiring circuit.

TECHNICAL DETAILS

INPUT

Voltage:| 220 – 240Vac
Frequency:| 50Hz
Max. mains current:| 0.05A
Standby current:| 0.05A
RADIO TRANSCEIVER
Operating frequencies:| 2.4… 2,483 GHz
Max. output power:| +4 dBm
LUX PARAMETERS
Range:| 5 – 2000 lux
OPERATING CONDITIONS
Note: The temperature difference between the detection target and the background must be at least 4 °C.
Ambient temperature:| -20… +40 °C (lout 0.05 A)
Max. case temperature:| +70 °C
Storage temperature:| -25… +75 °C
Max. relative humidity:| 0… 80%, non cond.
CONNECTORS
Terminal block Wire size:| 0.5mm2 – 2.5mm2 solid or stranded
Wire strip length:| 6-7mm
Tightening torque:| 0,4 Nm/4 Kgf.cm
MECHANICAL DATA
Dimensions:| 79mm x 85mm x 85mm
Weight:| 95g (unpacked)
Degree of protection:| IP20
Protection class:| Built-in Class 2
Material (casing)| Flame-retardant polycarbonate
Finish / Colour| Matt /White (RAL 9003)
Protection class:| Built-in Class 2
CONFORMITY AND STANDARDS
EMC emission:| EN60669-2-1:2004 inc. A12:2010
EMC immunity:| EN60669-2-1:2004 inc. A12:2010
Safety:| EN60669-2-1:2004 inc. A12:2010
Environment:| Complies with WEEE and RoHS directives

5 YEAR WARRANTY

CBU-CEFL comes with a 5 year warranty from the date of manufacture and is CE marked

  • DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
  • Telephone: +44 (0)1249 443377
  • Fax: +44 (0)1249 443388
  • E-mail: sales@danlers.co.uk
  • www.danlers.co.uk
  • Company Registered Number 2570169 VAT Registration Number 543 5491 38
  • 18/07/18

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals