AZE 1000BTU Outdoor Cabinet Air Conditioner Instruction Manual
- June 3, 2024
- AZE
Table of Contents
- 1000BTU Outdoor Cabinet Air Conditioner
- Introduction
- Feature
- Air Conditioner Specification
- Air Conditioner Parameter Selection Method
- Installation Instruction
- Installation Steps
- Instruction of Control System
- Introduction of parameter code and settings
- Cooling System
- Air Conditioner Operation
- Fault Analysis & Handling
- Check and Maintenance
- After-sale Service and Warranty
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IP Rated Air-Conditioner AC Power Type Outdoor Cabinet Manual
IP Rated Air-Conditioner AC Power Type
Outdoor Cabinet Manual
1000BTU Outdoor Cabinet Air Conditioner
Thank you for buying our air-con. outdoor cabinet,this manual introduces important methods to use cabinet air conditioner,please read carefully the manual before using and following the usage/note to make sure use air conditioner safely and correctly. After reading, please keep the manual safe for reference at any time.
Introduction
Different from the traditional commercial and household air conditioner, outdoor cabinet air conditioner is a full automation temperature control product, it used intelligent controller to control the whole system of the air conditioner and widely deployed in telecommunication outdoor base stations, power station outdoor cabinet, outdoor LED screen, where require the temperature level below than 35℃ situation.
Feature
- This series of products can be widely used for outdoor communication cabinets, battery cabinets, electric cabinets and industry control cabinets etc.
- The protective level of internal and external circulation is IP55, which can protect cabinet to avoid moisture, dust, water. The air conditioner can also be indoor or outdoor installed.
- R134a system.
- R134a system fits working conditions of high/low temperature 55℃/-5℃.
- Digital temperature controller and high precision of temperature control.
(The image shown above is of the 1500W air conditioner)
Air Conditioner Specification
**Cooling Option| ****AC 300W| ****AC 400W| ****AC 500W|
****AC 600W| ****AC 800W| ****AC 1000W| ****AC 1200W| AC
1500W
---|---|---|---|---|---|---|---|---
Cooling capacity (L35/L35) (W)| ** 300| 400| 500|
600| 800| 1000| 1200| 1500
**Voltage| 110~120V AC ± 15%, 60Hz / 220~240V AC ± 15% ,50Hz
Rated Power (L35/L35) (W)| ** 220| 240| 320| 360|
410| 426| 485| ** 605
Refrigerant| R134a
Working Temperature| -5~55℃
-40~55℃ (with heater)
Heater Power (Optional Function)| ** 300W| 400W| 800W
**Noise (dB)| ** 55| 55| 55| 56| 58|
60| 62| 63
**IP Grade| IP55 Rated
Dimension (W×D×H) (mm)| ** 353×165×583| 455×155×692|
491×187×751
Model| **AC 2000W| ****AC 2500W| ****AC 3000W
---|---|---|---
****Cooling capacity (L35/L35) (W)| ** 2000| 2500|
3000
**Voltage| 110~120V AC ± 15%, 60Hz / 220~240V AC ± 15% ,50Hz
****Rated Power (L35/L35) (W)| ** 745| 900| 1240
Refrigerant| R134a
Working Temperature| -5~55℃
-40~55℃ (with heater)
**Heater Power (Optional Function)| ** 800W| 1000W
**Noise (dB)| 68| 68| 70
****IP Grade| IP55 Rated
****Dimension (W×D×H) (mm)| ** 460x188x1100| **** 569×220×1308
Note:
- Above model are powered by AC power, if you need DC powered or other parameter, please contact the representative or other distributors from whom you purchased your product.
- Heating function is optional, and the heater power is manufacturer’s default (heater power capacity also can be customized), please consult the representative or other distributors from whom you purchased your product.
Air Conditioner Parameter Selection Method
Formula:
Qt = (Qi + Qr) ×1.2
Qt: Heat released by the cabinet (W)
Qi: Heat released by the inner cabinet (W)
Qr: Heat spreads from outside to the inside of cabinet (W)
Qi: Heat released by the inside of the cabinet (W)
The calculation of the heat released by the components in the cabinet is based on the following (related to the components installation):
- Heating of variable-frequency drive, transformer, drive and servo amplifier etc.If the equipment is rated power 1K, it will generate approx. 30~50W heat (depending on the load and divided by fan pump load and mechanical load);
- PLC is about 35~50W heating(group as a unit), heat of industrial personal computer is controlled by its size. All calculated of 300W/ unit;
- Heat of contact components: rated power 1KW is about 5~20W heat, can be ignored compared with large power components;
- Heat of common server is about 280-500W. Heat of UPS is 20% of its power; When the variable-frequency drive is working with load, its loss (transformed into heating) is about 3%~5% of system rated power, which can be calculated. When the variable-frequency drive is of 1KW, the loss maybe 30W to 50W;
- Heat of SCR: 2W/A,1KW DC Drive is about 7W~10W.
Qr =k×A×ΔT
k—Heat transfer coefficient
k=5.5W/ m2 Steel cabinet
k=12.0W/ m2 Aluminum-magnesium alloy enclosure
k=0.2W/ m2 Plastic material cabinet
A —Surface area of the cabinet(unit—m2)
ΔT=T1 – T2 (unit—℃)
T1—maximum temperature of outside cabinet
T2—controlled temperature of inside cabinet
The air-con. outdoor cabinet cooling requirement:
Steel cabinet dimension(L×H×D):1500×2000×800 mm
Heat of the inside element is 1000W,controlled temperature inside cabinet is
28 ℃, outside temperature is 35 ℃
The calculation process of air conditioner parameter :
Surface area of the cabinet—A=1.5×2×2+0.8×2×2+ 1.5×0.8=10.4 m2.
Heat rumored from out to inside of cabinet—Qr = k ×A×Δ T = 5.5×10.4×(35-28)
=400.4 W
Total heat produced by the cabinet—Qt =( Qi + Qr) ×1.2=(1000+400.4)×1.2 =
1680.48 W
So choose the cabinet air conditioner with cooling capacity of 2000W.
Installation Instruction
Terms of Usage(Important ! Suggest to read carefully before operation)
Important Safety Information
Read the instructions carefully to become familiar with the equipment before
trying to install, operate, service, or maintain it. The following special
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or
simplifies a procedure.
Installation instruction
- Please do not use this equipment in hot, dusty, moist or corrosive environment. The ambient temperature should not be higher than 45℃ and also should not be less than 0℃. The humidity should not be more than 85%. Starting voltage should not be higher or lower than 10% of the rated voltage.
- Follow the instruction, otherwise inappropriate installation will cause leakage、electric shock、fire and equipment loosening etc.
- The air conditioner should not be pressed or heat. Never pull the power cable or the drainpipe heavily.
- the ground wire cannot be connected to gas pipe, water pipe, lightning rods and telephone line etc.
- Use screws to fix the air conditioner on the cabinet.
- The drainpipe of the cabinet air conditioner should not be warped or pressed heavily. After the installation, please make sure the drainpipe can drain water smoothly.
Note
- Please keep the right side up. Do not tilt or collide.
- The installation and circuit connection must be operated by the professionals according to the instructions strictly.
Security Alarms
- Putting goods on the air conditioner is strictly prohibited. No pressing.
- Please cut off the power before cleaning, dis-assembly or maintenance in case of electric shock accident.
- Installation or usage is strictly prohibited when there is flammable gas, aggressive gas, oil mist or electrically conductive powder in the air.
- If smoke, abnormal noise or not work long time after starting up, cut off the power ,stop unit running and turn to the professionals for examine and fix.
Installation Drawing
|
---|---
Installation Steps
a. Dig square holes on the installation place (the oblique part) of the base
metal (usually control box) according to the dimension of the air conditioner.
Please check the dimension before digging.
b. Drilling M6 holes next to the square hold according to the dimension of the
flange (door mounted) and cover (side mounted).
c. Label sponge on the edge of the square holes.
d. Push the air conditioner by its positive side through the inside of the
square holes and then fix it with bolt.
e. Connect the power (according to the following terminals)
Fixed Terminal
L — live wire
N — zero wire
E — ground wire
NC/COM/NO — alarm
AB — RS485
Removal Terminal
a. After stripping 7mm plastic insulation of power cable, insert it into the
cable hole, use a screwdriver to tighten the screw thread (same way to
sensor).
b. Fix the mobile terminal into the fixed terminal with a flat-head
screwdriver
c. Finishing power cable and ensure their safety and aesthetics.
Note: The power must be shut off before installation. Choose appropriate
cables and circuit protection device according to the nameplate.
Connect the Water Tube
Screw the water tube to the bottom of the drain, connect the drain with the
water tube and tighten them with a hoop (install the drain at a proper
position, not exceed the bottom of the air conditioner).
Electrical Diagram
Instruction of Control System
Function Button
Indicator lights — L1, L2, L3 L4
“1” | Set turn on or turn off temperature of cooling function. |
---|---|
“2” | Set turn on or turn off temperature of heating function. (heating |
function is optional).
“A”| Set alarm of high and low temperature.
“+”| Increase setting parameter.
“-”| Reduce setting parameter.
****| Power switch.
Introduction of LED lights on control plate.
Name | Light | On | Off | Flash |
---|---|---|---|---|
Compressor Light | L1 | Start | Stop | On time-lapse protection |
Heater Light | L2 | Start | Stop |
Control System Operation
When power on, the screen displays “OFF”,press “ ” (Power key)for 2 seconds
and then it will display ambient temperature the sensor tests.
a. Set up of cooling
Under the state of power on, press Key [1] for 3 seconds, after the screen
displays “C1”, then enter the state of cooling settings.
Press Key [+] or [-] to adjust setting options and setting parameters.
Press Key [A] to switch setting options and setting parameter.
Press the Power Key to exit cooling setting.
After finish the settings, press Key [1] for a long time to confirm and then
exit settings.
b. Set up of heating
Under the state of power on, press Key [2] for 3 seconds, after the screen
displays “H1”, then enter the state of heating settings.
Press Key [+] or [-] to adjust setting options and setting parameters.
Press Key [A] to switch setting options and setting parameter.
Press the Power Key to exit heating settings.
After finish the settings, press Key [2] for a long time to confirm and then
exit settings.
c. Enter parameter settings
Use a set of pass word to enter parameter settings. Control parameter setting
user password: “11”.
Under the state of displaying present temperature, press Key [A] for 3
seconds, the screen will display『–』.Then press Key [+] or [-] to input pass
word. Finally press [A] to confirm.
If input pass word is not correct, the screen will display 『 Er 』 and then it
will return the state of temperature testing.
If input pass word is correct, the screen will display『A1』and then it enter
the state of parameter settings. Press Key [+] or [-] to choose parameter
code. When choose a parameter, press Key [A], it will display the setting data
of the parameter, then press Key [+] or [-] to adjust the parameter settings.
After finish the settings, press Key [A] to return the state of displaying
parameter code.
d. Exit parameter settings
After finish the settings, you must press Key [A] for 3 seconds to exit
parameter settings. It will return the state of temperature testing and store
the setting parameters of this time.
If not press any key in 60 seconds, it will exit parameter settings
automatically. And the setting parameters of this time are invalid. The
controller will still run according to original setting data.
Introduction of parameter code and settings
**No.| Parameter Code| ****Setting Option|
****Original Data| Setting Range| ****Unit| ****Remark
---|---|---|---|---|---|---
000| A1| Start temperature of cooling function| 30| 21~50| ℃|
001| A2| Stop temperature of cooling function| 25| 20~50| ℃|
002| A3| Start temperature of heating function| -5| -9~19| ℃|
003| A4| Stop temperature of heating function| 5| -9~19| ℃|
006| A7| High temperature alarm| 45| 25~70| ℃|
007| A8| Low temperature alarm| -5| -9~19| ℃|
008| A9| Start temperature of Dehumidification| 75| 25~70| ℃| Unavailable
temporarily
009| AA| 45| 25~70| ℃| Unavailable temporarily
010| AB| Calibration temperature of RT1| 0| -9~+9| ℃|
011| AC| Calibration temperature of RT2| 0| -9~+9| ℃|
012| B1| Open & Close setting of pressure alarm| 2| 0| ~| 2| | 0:Forbidden
1:Open 2:Close
013| B2| Make RT1 be set| 1| 0| ~| 1| | ** 0:Forbidden, 1:Start
014| B3| Make RT2 be set| 0| 0| ~| 1|
015| B4| Make humidity sensor be set| 0| 0| ~| 1|
016| B5| Setting of compressor mode| 0| 0| ~| 2| | 0:Normal control
1:Force start 2:Force stop
017| B6| Setting of heater model| 0| 0| ~| 2|
018| B7| Setting of inside fan| 0| 0| ~| 2|
019| B8| Setting of outside fan| 0| 0| ~| 2|
020| C1| Setting of RT1 failure| 1| 0| ~|
1| | 0:Forbidden, not test failure alarm of RT1
021| C2| Setting of RT2 failure| 0| 0| ~|
1| | 0: :Forbidden, not test failure alarm of RT2
022| C3| Setting of temperature sensor failure| 0|
0| ~| 1| | 0: :Forbidden, not test failure alarm of
temperature sensor
023| C4| Setting of high temperature alarm failure| 1|
0| ~| **** 1| | 0: Forbidden, not test failure
alarm of high temperature
024| C5| Setting of low temperature alarm failure| 1|
0| ~| 1| | 0: Forbidden, not test failure alarm of low
temperature
025| C6| Setting of pressure alarm failure| 1|
0| ~| 1| | 0: Forbidden, not test failure alarm of pressure
026| Pr| System(controller) start & stop| 0| 0| ~| 1| | 0:Stop| 1:Start
027| P1| Pass word| 11| 0| ~| 99| |
028| P2| Equipment address| 1| 1| ~| 99| |
029| P3| RS485 bps| 3| 0| ~| **** 3| | 0:
2400bps, 1:4800bps, 2:9600bps, 3:19200bps
030| Ed| Exit parameter settings.
Note: The air conditioner has function of starting automatically if power is on, don’t need to operate power Key frequently.
Cooling System
Basic Components
Air conditioner is composed of compressor, condenser, evaporator, electric
control system, expansion valve and capillary tube, dry filter and fans etc.
Cooling Theory
A. The compressor takes in the gas refrigerant from the evaporator and
compresses it into high temperature and high pressure then sends it into the
condenser. The refrigerant will release heating in the condenser and then the
cold high pressure liquid goes through capillary throttling and turns into low
temperature and low pressure
and then flows in to the evaporator. The refrigerant will absorb heat and then
turns into gas in the evaporator. Thus forms the cooling cycle system.
B. The condenser and evaporator has circulation fan to enhance air convection
and heat exchange efficiency. The heat exchange between condenser and air is
outside the control box and that of evaporator and air is inside the control
box.
C. The electrical system is mainly monitoring the temperature of the cooled
closed cabinet and controls the cooling circulation by setting temperature.
Air Conditioner Operation
Check before Operation
Please check the following after the electrical and air conditioner
installation:
a. No barrier before air inlet and outlet.
b. The air conditioner is installed vertically, and all mounting screws have
been tightened.
c. Air conditioner drain has been securely mounted and connected with the
drain line cabinet (optional).
d. Connecting power cord has been connected reliably.
e. Fans can freely rotate with no strange noise.
f. AC input voltage matches with the contents of the nameplate parameters
Start to Operate
a. Turn on the power breaker and start running.
b. AC input power closed, the inside fan runs. If the inside temperature
reaches the operation conditions, the cooling and heating systems start to
operate. When the cooling system starts to operate, the outside circulation
fan is controlled by condenser thus it will start after the compressor.
Fault Analysis & Handling
Error | Cause Analysis & Handling |
---|---|
E1: failure of Sensor 1. | The sensor of RT1 is damaged or loose. |
E2: failure of Sensor 2. | The sensor of RT2 is damaged or loose. |
Hi: high temperature alarm | Temperature exceeds setting alarm temperature. |
Lo: low temperature alarm | Temperature is below setting alarm temperature. |
HP: pressure protection | Alarm of switch open or close. |
EE: data storage failure. | The function of data storage failure. |
After power on, the cabinet temperature is higher than setting temperature and
the air conditioner doesn’t work.| 1.Check the power supply and circuit.
2.Contact professional people for help.
The air conditioner runs normally but the cooling effect is not ideal.|
1. Choose another air conditioner or correct cooling capacity according to
the heat loading.
2. Make sure the air conditioner works within its normal working temperature
range.
3. Contact professional people for help.
**** The air conditioner runs normally, it suddenly stops cooling and no
electrical control system failures.| **** 1.Normal phenomenon. It monitor the
temperature inside the cabinet temperature and then decides whether star or
stop cooling according it. 2.Contact professional people for help.
The air conditioner runs normally, it suddenly stops running
with no electrical control system failures.| 1. Check the power supply.
2. Contact professional people for help.
Notes :
- Please install leakage circuit breaker
- Do not put your fingers or objects in the air outlet because the running air conditioner will cause injury to human beings or damage to the air
- Do not repair without
- The air conditioner can not be inverted in any case, otherwise it may cause damage to the
- Try to remain stable during handling The tilt angle should not exceed 45 degrees.
Check and Maintenance
Regular Inspection
A. Check whether cabinet air conditioner power supply wire and communication
wire is ok or not;
B. Check whether cabinet air conditioner running is normal, whether the air
inlet and air outlet mouth temperature difference is obvious when starting
refrigeration system;
C. Check whether fan and compressor work normally and whether there is obvious
noise or shake;
D. Check whether mechanical structural parts are damaged or deformed;
E. Check whether air conditioner inner and outer circulation air inlet and
outlet, cabinet outer protective cover air inlet and outlet screen are jammed;
F. According to the actual air quality, please arrange maintenance personnel
to inspect cabinet air conditioner every 3-6 months;
Regular Maintenance
During air conditioner running, dust may cover on the fins of heat exchange,
which may affect the heat exchange and even cause degradation of air
conditioner performance seriously. It is suggested to clean and maintain heat
exchange for each 3-6 months. The cleaning and maintaining interval depend on
the air pollution and running time in different regions. When cleaning, do not
use hot water or gasoline and other organic solvent
After-sale Service and Warranty
Warranty Period- One Year
Under the condition using cabinet air conditioner correctly, the contracted
warranty period shall prevail. During warranty period ,the electronic
components are free of charge for replacing if damaged occur.
Warranty Range
During warranty period, the manufacturer will repair for free the quality
faults caused by product
Itself and customer should provide the S/N. But the faults under below
conditions are out of warranty for free:
A. Warranty period expire;
B. S/N cannot be provided;
C. Faults caused under abnormal condition or circumstance, or caused by
improper installation, maintenance or other operations;
D. Faults not caused by air conditioner itself, such as the user’s equipment,
software and others;
E. Damaged caused by replacing or disassembling by user, or by unauthorized
repairing service persons;
F. Faults caused by majeure force such as fire, earthquake, flood and others.
Disclaimer
The warranty is only for the delivered products. Air conditioner manufacturer
is not responsible for any loss which is derived from equipment fault.
For information on how to obtain local customer support, contact the
representative or other distributors from whom you purchased your product.
Wiring Diagram for A/C Unit and Sensors
WARNING: PROFESSIONAL INSTALLATION REQUIRED
CAUTION: Please read the complete operation manual prior to use to avoid accidents and injury.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>