INDOL EH130UV4 EcoHeat Pump User Manual
- May 15, 2024
- INDOL
Table of Contents
INSTALLATION AND USER MANUAL
INDOL
EH100UV4
EH130UV4
Version 1
INTRODUCTION
This product has been manufactured according to the European Quality
Standards, incorporates prime grade materials and its correct working has been
tested before it leaves our facilities.
Through this Installation and User Manual, you will be guide towards the
correct and safety installation of the product. It is necessary to carefully
read this manual before making any handling to avoid problems arising from the
misuse of the product.
The company reserves the right to modify the information included in this
document at any time without prior notice.
GENERAL INDICATIONS
2.1. Safety notes
The incorrect or inappropriate use of this product could lead to hazardous
situations, causing damage or injuries to the user, third parties or even to
the product itself or material goods.
- The installer has the responsibility to install the minimum safety devices (hydraulic and electrical) set out in this Manual. In case of failure, the lack of any device may cause burns or other injuries.
- The installer has the responsibility to inform the user about the function and placement of the safety devices installed into the device and the installation.
- The water outlet temperature could reach 70 degrees. Do not touch the pipes while the system is working to avoid any risk of burns.
2.3. Package contents
The INDOL-UV4 system comprises the following components:
- INDOL-UV4 (according to model)
- Silent-Blocks
- Anchor screws
- Safety valve
- User Manual
2.4. Indications about transport and unpacking the unit
The unit is supplied packed into a wooden pallet properly secured to prevent
damage during transport.
The materials used for packing are recyclables, so dispose it in an
appropriate container.
Use a forklift or hand pallet truck to transport the unit to the installation
site, always introducing the forks into the bottom of the pallet being careful
not to damage the unit.
In case you identify any damage at the time of the reception of the unit, it
is mandatory to register it in the reception note of the transport company,
and then, submit the complaint.
For this reason, it is recommended to make a thorough visual inspection of the
goods before signing the reception note.
TECHNICAL INFORMATION
3.1. Operating Principle
- The evaporator captures the thermal energy from the air through the refrigerant.
- The compressor compresses the refrigerant, increasing its temperature and pressure.
- The collected energy is transferred to water in the condenser. The accumulated water in- creases its temperature reaching up to 55 ºC.
- The refrigerant circulates to the expansion valve, where its pressure decreases to achieve the optimum conditions before entry into the evaporator.
3.2. Dimension drawings
1 Hot water outlet, 3/4″ | 5Exhaust air connection (160 mm) |
---|---|
2 Cold water inlet, 3/4 | 6 lntake air connection (10 mm) |
3 Condensate drain | 7 Electrical heater, 1500 W |
4 Power spply, 230 V/ 1PH / 50 Hz |
3.3. Technical data
Model | EHI0OUV1 EH130UV4 |
---|
Cylinder
Capacity, L| 100130
Maximum operating pressure, bar| 10
Heat pump data|
Heating capacity range, W| 700— 1200
Input power, W| 180 — 300
Energy Efficiency Class| A+
Load profile| M
SCOP (14 °C)| 3,02| I 3,24
Refrigerant / Charge, g| RI 34a / 750
Minimum ambient temperature, ‘C Maximum water temp. HP, •C| -5
55
Maximum water temp. electrical heater, °C| 70
Electric data|
Power supply, V/ph/Hz| 230 / 1 / 50
Electric heater power, W| 1500
Maximum absorbed power, W| 1800
Air data|
Air flow, &fit| 200
Maximum pressure drop, Pa| 50
Intake/Exhaust connection, mm| 160
Other data|
Water connections, inch| 3 / 4
INSTALLATION STEPS
Before starting the installation, check the availability of all the necessary components and tools:
- Drill
- Screwdriver
- Hydraulic installation components
- Electric installation components
Once it has been checked that it is available all the necessary components and tools, the installer should follow the next steps:
- Placing the unit
- Hydraulic installation
- Air connections
- Electric installation
- Commissioning
PLACING INDOL-UV4 UNIT
The place where the system will be installed should allow an easy access to
make maintenance work or inspection.
Air outlet of the unit is around 5-IO degrees below inlet temperature, so in
case that the exhaust air would not be ducted, the room temperature will be
considerably reduced.
Beside these factors, it is important to consider the following indications
regards the installation site:
The system has been designed and manufactured for it indoors utilization.
Install the system in a dry, frost-free room at a minimum temperature of 5 °C.
Installer must install the supplied silent blocks to avoid the transmission of
vibration.
The wall where the system will be installed has to bear the weight of the
system full of water.
WALL INSTALLATION
The device is designed for wall-mounting installation, therefore is supplied
two brackets in the back. The installer has to fix coach screws M10x80, lock
washer M10 and screw anchors 12×60.
In addition, there are two holes on each side to adjust and regulate the
silent blocks supplied to the wall.
AIR CONNECTION
Indol-UV4 unit has two air connections located at the top cover of the system.
There are different installations possibilities:
Since the temperature of the exhaust air is lower than the intake air flow, the user can recover this cold air to refresh a room. In this case, it is recommended to install a double duct, one to the room and other to outdoors. Using a gate, the user can stop the air flow conducting it to outdoors when cooling isn’t needed.
IMPORTANT:
- Do not use flexible duct! Only smooth PVC pipe is allowed.
- Do not use anti-insect grid.
When the inlet and outlet ducting is needed, use only rigid smooth PVC be.
The pressure drop in the whole air circuit (pipes and accessories) must be
lower than the static pressure of the system, 50 Pa. In the following table is
shown the allowed total pipe length (intake + exhaust). The equivalent length
of any accessory installed in the circuit must be subtract to the maximum
allowed pipe length:
Maximum length (PVC rigid pipe) 160 nm | 14 m |
---|---|
Elbow 90° PVC 160 mm | 3 equivalent meters |
External grid | 2 equivalent meters |
SUCTION FILTER
The system includes in the air intake a filter for the protection of all the
elements of the refrigeration circuit.
This filter should be checked every 6 months to verify that is has not been
clogged. To do this, remove the filter from the suction duck and check if the
channels allow air passage, Otherwise, wash it with water or replace with a
new one.
If you notice_that the system does no heat up, check_the condition of
the_filter.A_clogged filter gffects the life-cycle performance_and_hot water
production_of the_system.
ELECTRICAL CONNECTION
The electrical connection of the equipment is 230 V/1/50 Hz.
PV: Photovoltaic connection
LPS: Low pressure switch
HPS: High pressure switch
NTC1: Water temperature probe
NTC2: Ambient temperature probeAND: Not used
D: Display
VS: Solenoid valve
R: Electrical heater
K: Compressor
F: Fan
230 VAC: Power supply
COMISSIONING. CONTROLLER.
10.1. User interface description
Symbol | Meaning when it lights |
---|---|
Compressor switched on |
Defrost active
Fan switched on
Alarm active
Compressor working hours exceeded
Unit in °C
Unit in “F
Electric heater switched on
Stand by
10.2. INSTALLATION. Switching on
After full installation of the water heater (power and water pipes connected) and after the water heater tank is full of water, power can be turn ON.
| 1. After filling the tank of water, connect the mains plug to the mains
supply.
The screen will show the symbol.
2. Hold the key for 4 seconds. The
display will show the icons.
3. The screen will show the water temperature.
---|---
10.3. Switching OFF
To switch off the system, hold the key for 4 seconds.
10.4. Unlocking the keypad
When 30 have elapsed without the keys being pressed, the display will show the
“Loc” label and the keypad will lock automatically.
Touch any key until the screen shows “Unl”, to unlock the keypad.
10.5. Displaying the operating mode
At trst imal power ON, the product goes, by default, in Eco mode. By touching
one time the V key, the controller will show the mode in operation in this
moment.
10.6. Changing operating mode
10.7. ECO Mode
ECO mode: Maximum savings. The system heats water only by heat pump
technology.
This is the factory default mode.
Setting the ECO temperature setpoint
The water temperature set point in ECO mode can be changed with the SPl
parameter.
10.8. AUTO Mode
It maintains a steady temperature by the heat pump and only use the electrical
heater if the temperature falls drastically.
Setting the AUTO temperature setpoint
The water temperature set point in AUTO mode can be changed with the SP2
parameter.
10.9. OVERBOOST Mode
Select this mode to achieve a fast heating by using simultaneously heat pump
and electric heater.
This mode Works as a rapid heating. Once the setpoint temperature is reached,
the system returns to the initial mode.
If Overboost mode is switched on when the system Works from ECO node. The
system heats the water up to SPl, and then returns to ECO again
If Overboost mode is switched on when the system Works from Auto mode:. The
system heats the water up to SP2, and then returns to Auto again
When Overboost mode is active, the display automatically changes showing the
water temperature and Obs.
Cancelling the Overboost Mode
Parameter SP3 allows to set the minimum temperature that Overboost can be
actived.
To change it value, follow the procedure:
10.10. Photovoltaic input
Working on this mode, the system automatically heats the water due to electric
energy surplus or by Off Peak rate.
The parameters of this mode can only be changed by the Installer’s Menu.
Contact with the technician for more information.
The system can be combined with and Photovoltaic Inverter to take advantage of
the surplus energy generated by the panels, by forcing the system working and
storing this energy in useful hot water.
The system has in the electric boar two terminals to connect a zero-voltage
contact.
When the contact is closed, the system automatically changes to Photovoltaic
mode and the heat pump and electric heater work to achieve the programmed
temperature. When the contact is opened, the system returns to the previous
mode.
This contact can be also used for Of Peak Rates. To do it, connect into the
contact a timer with a zero voltage output.
10.11. Displaying/deleting compressor functioning hours
10.12. Antilegionella
The anti-legionnella feature reduces the risk of development of bacteria in
the tank.
The system performs a thermal shock disinfection to avoid any risk conditions
that might cause the development of bacteria. The disinfection is made
automatically once a month, reaching a temperature of 65 °C.
Anti-legionella can be disable or enable in the installer menu.
IMPORTANT: When the system is switched off from electrical supply, the internal hour-counter for antilegionella disinfection is reset. For this reason, the system will perform a thermal shock disinfection before the time expected.
10.13. Alarms
Alarms | Meaning |
---|---|
Pr1 | Water temperature probe alarm. |
Check the temperature probe integrity and the electrical connection
Pr2| Water temperature probe alarm.
Check the temperature probe integrity and the electrical connection
Pr3| Evaporator temperature probe alarm.
Check the temperature probe integrity and the electrical connection
AL| Low temperature alarm
AH| High temperature alarm
LHP| Low pressure switch alarm/ Device blocked
Switch the device off and on
HP| High pressure switch alarm
Switch the device off and on
FIL| Compressor maintenance alarm
By silencing the buzzer, you delete the compressor functioning hours
Utl| Evaporator failure alarm
Switch the device off and on