PERRY TE541 Digital Thermostat User Manual

May 15, 2024
PERRY

PERRY TE541 Digital Thermostat

Product Information

Specifications:

  • Product: Digital Thermostat
  • Model: TE541 Series: V003
  • Power Supply: 230V~
  • Features: Menu Driven with Backlit Display
  • Installation: Flush-mounted, 3 modules for civil series
  • Input: Remote external contact

Product Usage Instructions

1. Installation

Before installation, make sure to follow the provided installation instructions carefully. Ensure proper electrical connections and compliance with installation regulations.

2. Starting the Thermostat

After installation, power up the thermostat by connecting it to a 230V~ power supply.

3. Using the Thermostat

To set the temperature, follow these steps:

  • Set the T set temperature of the current level.
  • Choose and set the desired temperature level (T set) between Comfort (t1), Economy (t2), or OFF.
  • Set the Current Winter/Summer season using the Quick Command feature.

4. Menu Structure and Configuration

The thermostat offers various menus for configuration. Navigate through menus to access and adjust settings according to your preferences.

5. Configuration Menu (Installer)

Within this menu, you can:

  • Set Winter or Summer mode.
  • Correct room temperature reading.
  • Lock max and min set temperatures for winter and summer modes.

Frequently Asked Questions

  • Q: How do I reset the thermostat to factory settings?
    • A: To restore factory settings, access the RESTORE option in the configuration menu.
  • Q: What should I do if the display backlight is too bright?
    • A: You can adjust the brightness of the display backlight using the Brightness Adjustment feature in the configuration menu.

“`

DIGITAL THERMOSTAT

ENGLISH

MENU DRIVEN with BACKLIT DISPLAY

Flush-mounted installation 3 modules for civil series

Mod. TE541 Series: V003

Power supply
230V~

Power supply: 230V~ Winter / Summer 2 temperature levels (t1 = Confort, t2 = Economy) + OFF temperature level = antifreeze or thermal protection Input for remote external contact

FULL instructions
for installation, settings and use

www.perry.it

PERRY ELECTRIC Srl Via Milanese, 11 22070 VENIANO (Como) ITALY

PE – DETIPE026EN 01/24

www.perry.it

PRESENTATION

Dear Customer, thank you for choosing our product.
The thermostat, suitable for all heating and/or cooling system, is fitted with a large and clear backlit display to keep all its functions under control in real time. The fundamental feature is its easy to use menu navigation, which makes it extremely user-friendly despite its comprehensive range of functions. The thermostat is factory-set to adjust temperature in a modulating Proportional operation may be selected with settable duration cycles (from 7 to 20 minutes): this system ensures the desired temperature is maintained more stable, increasing user comfort and is particularly suitable for installations with high thermal inertia such as, for instance, for underfloor radiant panels; alternatively it is possible to select temperature regulation in Differential ON/OFF mode with the hysteresis settable from 0.2°C to 1.2°C to adapt to the thermal inertia of your specific system. The set temperature scale is in degrees Centigrade with the option to calibrate room temperature measurement setting a correction value (from -6 to +6 °C). Special attention was devoted to energy saving: optional Set temperature (MAX/MIN) lock, adjustable antifreeze/thermal protection temperature value, control through an remote external contact, are conducive to avoiding wasting energy with consequent savings.
WARNINGS!
Read this manual carefully before using the product as it provides important guidelines regarding safety, installation and use.
& The manual must be preserved with care for future reference. The manufacturer reserves the right to make all the technical and construction changes it deems necessary without prior notice.
The installation and electrical connection of the programmable thermostat must be implemented only by a qualified electrician and in conformity with current laws and regulations.
Before starting any operations on the device, disconnect the 230V~ mains power supply
The thermostat is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or by those with a lack of experience and knowledge of the instructions, unless they are supervised or have received the necessary instructions concerning use of the device by a person responsible for their safety. Children should be supervised to ensure that they do not play with the device. If 0.0 °C or 45.0 °C room temperature flashes on the display, the measured temperature is beyond the scale, the device is still operational. In the event of a temperature probe failure, code E1 will be shown on the display (see par. 11). IMPORTANT: in case of a power black-out (230V~), the thermostat guarantees retention in memory of all the data entered. When mains power is restored, the display turns on and the device returns to the active operating mode before the power failure. If necessary, gently clean the thermostat and the display with a soft, dry cloth.
3

TECHNICAL DATA

Power supply:
Display and key back-lighting: Type of action, disconnection and device:
Type of output:
Keeping memory setting during power failure:
Software: Rated impulse voltage: Cross-section of wires to terminals: Contact input for remote thermostat deactivation: Type of insulation: Degree of protection: Pollution rating: Operating mode: Number of temperature levels: Ambient temperature display range: Relay ON signal: Room temperature indicator resolution: Temperature Set adjustment range: Setting temperature Set: Temperature correction (Offset) separated by seasons: Antifreeze Tset temperature OFF (Winter): Thermal protection Tset temperature OFF (Summer): Type of temperature adjustment:
– Proportional with control period (default) – DIFFERENTIAL ON/OFF Thermal gradient: Temperature reading tolerance: Operating temperature limits:: Storing temperature limits: Type of installation: Type of use: ErP energy classification:
Reference regulations for CE markings:
4

230V~ +/- 10% 50Hz timed 6 secs. / always on / always off / brightness reduction after 6 sec. 1 B / Electronic voltage free relay with COM / NO / NC changeover contact, max 5(3)A/250 V ~
Yes
class A 4 kV 1,5 mm2 ÷ 2,5 mm2 for contact free from potential, minimum insulation 250V~, maximum cable length 15 m.
class II IP 30 (recessed wall-mounted with wall plate) 2 Winter heating (default) / Summer cooling n° 2 « t1 = CONFORT», «t2 = ECONOMY» + OFF antifreeze/thermal protection 0 °C ÷ +45 °C
+ ON (Winter) o + ON (Summer) 0.1 °C +4 °C ÷ +37.7 °C (limitable with Max and Min temperature blocks) a step di 0.1 °C adjustable from -6.0 °C to +6.0 °C (default 0.0 °C) adjustable from + 4 °C to t2 (default 5 °C) adjustable from t2 included to +37,7 °C (default «disabled»)
cycles adjustable from 7 to 20 minutes (default 7 minutes) adjustable from 0.2 °C to 1.2 °C (default 0,3 °C) max 1°K / 15 min ± 1°C
0 °C ÷ +45 °C -10 °C ÷ +60 °C Built-in civil and tertiary sectors ErP: Class I; 1% Reg. EU 811/2013
LVD – EMC EN60730-1 EN60730-2-9

FACTORY SETTINGS

The data entered in the thermostat called «FACTORY SETTINGS» refer to operation defined as «Standard». The following chapters describe all customisable functions, in order to satisfy any ambient comfort need.

FACTORY SETTINGS TABLE (default)

PARAMETER

DEFAULT

Active season Set t1 COMFORT Winter

Winter 20.0°C

Set t2 ECONOMY Winter

17.0°C

Set tOFF antifreeze (Winter) 5.0°C Set t1 COMFORT Summer 24.0°C

Set t2 ECONOMY Summer Set tOFF thermal protection(Summer) Room temp. correction

27.0°C Disabled 0,0 °C

Room temp. correction

0,0 °C

Temp. locks Winter

Disabled

Temp. locks Summer

Disabled

Temp. adjustment mode

Modulating proportional

Modulating period

7 min.

Thermal differential On:OFF On:OFF (not active)

Differential hysteresis

0.3°C (not active)

External input

not active

Back-lighting

Switched off after 6 sec.

Display brightness

Level 7

Installer password

none

Keyboard lock

not active

RESTORE
Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default Default

RESTORE «Installer RESET» Restore many factory settings (default) RESTORE brings the thermostat back to factory settings with the exception of some items as shown in the table. The Restore operation is recommended to be carried out by the qualified installer or experienced user, as indicated in paragraph 10.9 of the menu:
RESTART It does not cancel the entered settings Should the thermostat feature malfunctioning, wrong displays or other incorrect conditions, perform a «User reset». Simultaneously press for 4 secs. the Mode and OK keys. The thermostat resumes normal operation.
Normal operation
Press simultaneously

It will be possible to perform the same operation by following the instructions in paragraph 10.10 of the menu:

IMPORTANT: in case of a power black-out (230V~), the thermostat guarantees retention in memory of all the data entered.

In case of absence of power supply the display switches off saving all the programmed settings effected, when power supply is

reinstated, the display switches back on and the device returns to its normal functions.

5

KEY FUNCTION LEGEND

DISPLAY AND KEY BACK-LIGHTING Touching any key activates back-lighting, displaying the words selection and navigation, press the desired key within 6 secs. to vary the settings (touching any key reactivates a 6 sec timeout).
Note: setting the backlight always on (par. 10.7) the words selection and navigation will also always be visible.
Note: more particular button functions are described in the specific paragraphs.

A

BCD

A

Multifunction Key Mode / back its use changes depending on function or active menu:

Mode = short pulse pressure switch from Tset t1 temperature (comfort) to t2 (economy) to OFF

prolonged pressure (6 sec.) access to Prog menus.

short press within menus = return (back) to previous item, exit from Prog menus.

B

Key increases the desired Set temperature;

navigation through the menus: to increase a setting value;

C

Key decreases the desired Set temperature;

navigation through the menus: to decrease a setting value;

D OK Key (confirm setting)
Level confirmation and T set selected (t1 or t2 or OFF) access to selected menu / confirm function or set value (within the menus)

Press the pulse arrow key for single increase/decrease, in some settings it will be possible to keep pressed for fast increase/decrease

6

DISPLAY FEATURES

1 Display Set temperature

2

Currently active set temperature depending on the desired setting: t1 Confort or t2 Economy (saving) or OFF (antifreeze/thermal protection)

3 Detected room temperature

4 Remote thermostat control (connected to an external contact)

5 Heating mode ( Winter) active

T 86 Signalling operating user = ON and fixed (e.g. boiler on) Signalling operating user = and ON fixed (e.g. conditioner on)
T 87 Cooling mode ( Summer) active

8 Night reduction icon (indicates the selection of the temperature set T: t2 «Economy»)

3
Note: further displays are described in the specific operation paragraphs.
7

INSTALLATION

5.1 – DIMENSIONS

43,5 47

65

52

5.2 – INSTALLATION REGULATIONS
Important: the installation and electrical connection of the devices and appliances must be implemented by qualified personnel and in conformity with current laws and regulations. The manufacturer declines all liability in connection with the use of products subject to special environmental and/or installation standards.

WARNING! When mounting the front panel on the thermostat module, take care NOT to remove the heat-conducting part, see the warning and instructions on the accompanying lea et.

Thermostat installation: independent – fixed
recessed in rectangular box 3 civil modules or higher.
Install the thermostat at a height of 1,50 m ÷ 1,70 m from the floor, far from heat sources, air vents, doors or windows and anything else that could affect its operation.

5.3 – INSTALLATION EXAMPLES Disconnect the 230V~ mains power supply
Examples of installation in heating systems with a thermostat that controls: A) Wall mounted boiler. B) Burner or Circulation pump or Motorized solenoid valve. C) Zone solenoid valve.
(example for floor system or other)
N.B.: the examples contained in this documentation are in principle.
A B BB

C

C

IMPORTANT: for the assembly procedure

of the thermostat with the chosen

h 1,5 m

residential plate, follow instructions

contained in the specific compatibility

sheet contained in the package.

8

5 – INSTALLATION 5.4 – ELECTRICAL CONNECTIONS
ATTENTION! Disconnect the 230V~ mains voltage
230V~ 50Hz power supply terminals Connect line voltage power supply to the terminals:
n° 3 – NEUTRAL n° 4 – LINE
Relay terminals

Examples of electrical connections
Connection to a boiler and to a external contact

8 9

AUX

1 2

10 11

230V~N L

3 4

12

C

5

13

NO

NC

6

14

7

Contact for remote thermostat control

230V~

BOILER

230V~

AUX Terminals (remote contact)
terminals 1 and 2 may be connected to a external contact for thermostat remote deactivation (see paragraph 10.6 for external contact setting)
AWARNING: only connect switches and contacts with insulation suitable to work at 230Vac mains voltage.
MULTIPLE INSTALLATIONS – It is NOT permitted to connect the remote contact on more than one thermostat; each thermostat must have its AUX input operated independently of the others.

N 230V~
L

Connection to amotorized valve and to a external contact

8 9

AUX

1 2

10 11

N 230V~ L

3

4

230V~

12

C

5

13

NO

NC

6

closes

14

7

opens

Contact for remote thermostat control

230V~ LN

M
LOAD

230V~

NB: with strong inductive loads (pumps and solenoid valves) it is recommended to connect an RC filter in parallel to the load.
9

START THE THERMOSTAT

The first time mains voltage is engaged, the thermostat performs a lamp-test by switching on all display segments, displaying the installed software version for a few seconds. When this phase is over, the thermostat displays the normal operation screen.
Normal operation

Winter mode (heating) ON + = e.g. operating boiler

The thermostat is operational, it shows on the display: the Winter “heating” mode, the Temperature Set t1 (Confort) at 20°C, the detected room temperature.

USE OF THE THERMOSTAT

From normal thermostat operation in stand-by, pressing a key, the backlight activates (if not excluded) and the words selection and navigation (if backlighting is not set to always on) appear. Within 6 secs., a variation is made the second time the desired key is pressed.
Each press of or results in a change of 0.1 degrees.
Example: changed Set t1 (Comfort) from 20.0°C to 21.4°C.

Note: if the keyboard lock is engaged (see par. 10.12) or deactivated the thermostat by remote contact as described in par. 10.6.3 and 10.6.4, when any key is pressed, the word “bLOC” will appear flashing for a few seconds; it will not be possible to make any changes directly from the normal operation screen.
10

7.1 – SETTING THE “T SET” TEMPERATURE OF THE CURRENT

LEVEL

in the absence of temperature locks, it will be possible to

change directly by pressing the keys

the new current

T set value will be saved automatically.

To select the desired temperature level and change the T set, see the next paragraph.

7 – USE OF THE THERMOSTAT
7.2 – SELECTING AND SETTING THE DESIRED TEMPERATURE LEVEL: t1 (Comfort), t2 (Economy), OFF (Antifreeze or Thermal protection) From normal operation of the device, pulse the Mode button, display the desired temperature level t1 or t2 or OFF, confirm this by pressing the OK button.
Confirm with OK button the desired level
example: t2 (Economy)

It will be possible to change the current T set value directly by pressing

the buttons

, which will be saved automatically.

Changing the value of T set level OFF (Antifreeze or Thermal protection) will ONLY be possible by accessing the dedicated menu (see par. 10.5).

Factory preset T Set temperatures (can be changed as required)

in Winter mode
Example: boiler in operation with room temperature below:
t1 = 20,0 C – Confort t2 = 17,0 C – Economy
OFF = 5.0 C – Antifreeze
The Tset value of the OFF (Anti-Freeze) level can ONLY be changed by accessing the dedicated menu (see par. 10.5).

in Summer mode

Example: air conditioner operating with room temperature higher than:

t1 = 24,0 C – Confort

t2 = 27,0 C – Economy

OFF = **

C – Thermal protection (disabled)

**Enabling and changing the Tset value of the OFF (Thermal protection) level will ONLY be possible by accessing the dedicated menu (see par. 10.5).

Each press of or results in a change of 0.1 degrees;
Normal operation

It will be possible to change the preset Set temperatures according to the level chosen, bearing in mind that: in WINTER operation T set t1 must be greater than or equal to t2; t2 must be greater than or equal to OFF. in SUMMER operation T set t1 must be less than or equal to t2; t2 must be less than or equal to OFF (if enabled).
If a Max. and/or Min. temperature lock has been set, it will also be possible to change the temperature T set within these locks (see par. 10.3).
11

7 – USE OF THE THERMOSTAT

7.3 – SETTING THE CURRENT WINTER/SUMMER SEASON (Quick Command)

With the device in normal operation, press and hold the OK button for at least 6 seconds. The product will present the proposed season change so if for example

Example: normal operation WINTER season
(heating)

the current season is Winter (heating), it will show the icon

flashing and the corresponding level and T set.

Confirm with OK button.

If no confirmation is made within 5 seconds by pressing the OK button, the device returns to normal operation without making any changes.
The season change request is prevented in the case of active external contact (see par. 10.6 onwards).

Press and hold for 6 sec.

Confirm with OK button

At the change of season, the t1 level (with its corresponding T set value) of the incoming season will be taken over, regardless of the active level in the previous season.

Example: normal operation SUMMER season
(cooling)

Changing the season from Winter (heating) to Summer (cooling) or vice versa can also be done from the appropriate menu item “Prog”, see paragraph 10.1.

12

STRUCTURE OF MENUS AVAILABLE

WARNING: access to the Prog menu (configuration) is recommended for the qualified installer or experienced user since the modification of some settings might affect correct system operation. Access to the menu can be password-protected (see par. 10.11 ).

The following menus are available sequentially:

1

= Season WINTER (heating) / SUMMER (cooling)

2

= Correction of room temperature reading (OFFSET)

3

= MAX and/or MIN set temperature loks

4

= Type of temperature adjustment mode: Proportional modulating «PrOP» (Default) or Differential ON /OFF «On:OF»

5

= Setting period duration for modulating Proportional ( if Prop has been set in the SEt rEG menu )

6

= Hysteresis value for Differential ON/OFF (Screen visible if the SEt rEG menu has been set to On:OF)

7

= Antifreeze Protection (INV ) Thermal protection (EST )

8

= Input for external contact (deactivating the thermostat remotely)

9

= Display backlighting

10

= Brightness setting (menu visible if backlighting has not been switched off)

11

= Installer Reset (returns the device to factory settings)

12

= Restart (does not delete entered settings)

13

= Password setting

14

= Keyboard lock (menu only visible if a Password has been entered)

8.1 – How to navigate within Menus

From normal thermostat operation (with button symbols visible), press and

hold the Mode button for at least 6 seconds to access the PROG menu.

Access to menus can be password-protected (see par. 10.11 ).

Press

to scroll through the various menu items.

Normal stand-by device operation

When the desired menu item is displayed, press OK, the current setting flashes,

press

to change the chosen menu parameter or setting.

Briefly press a button

NOTE: pressing the Mode button returns to the previous screen.

Confirm with the OK button (the display shows a clockwise rotation of the following segments

Normal operation reactive device within 6 sec. press desired key
to indicate successful saving.

Proceed to change another parameter or briefly press the Mode button to exit the menus and return to normal operation of the device, the display briefly

shows the flashing message

.

The automatic exit from the menus «

» is also obtained when 60 seconds (Time-out) have elapsed since the last key was pressed, the thermostat

returns to normal operation, any unconfirmed last modification will not be retained..

13

9 – ACCESS TO THE CONFIGURATION MENU

Normal operation

With previously entered password (see par. 10.11 )

Press and hold at least 6 sec.

No password entered

scroll through the menus

with the

keys

Enter with buttons each digit confirming with OK (in the event of an error, briefly press the Mode button to return to the previous screen)

Screen only visible if a password was previously entered

is displayed for a few seconds after pressing the OK button to indicate incorrect password.

Example password entered

Confirm

10 – CONFIGURATION MENU (Installer)
10.1 – SETTING WINTER or SUMMER MODE
From normal thermostat operation, access the menus by pressing and holding the «Mode» key as explained in chapter 9.

· Under item Set SEAS confirm with OK.

·Select with the

keys the WINTER

mode

·Confirm with OK key.

(heating) or SUMMER

(cooling)

·Use the

buttons to select another menu item or press the Mode button to exit the menus

and return to normal operation.

It will be possible to change the season between Winter/Summer and vice versa, without entering the menu (see par. 7.3)

10.2 – CORRECTION OF ROOM TEMPERATURE READING
If for any reason the thermostat must be installed in a position where the measured room temperature might be affected (e.g. perimeter wall which is on average colder in winter and warmer in summer than the rest of the dwelling) the device has 2 separate parameters to adjust the room temperature measured in the Winter and Summer modes.
Possible correction: -6.0 °C ÷ 6.0 °C (default 0.0 °C).
From normal thermostat operation, access the menus by pressing and holding the «Mode» key as explained in chapter 9.

· Under item Set Corr, confirm with OK, the displayed value flashes.

· Use the buttons

to select the room temperature correction for the

WINTER or SUMMER mode .

· Change the required temperature value with the buttons

.

· Confirm with OK key.

·Press the Mode button briefly and use the

buttons to select another

menu item, or press the “Mode” button twice to exit the menus and return to

normal operation.

select with

with the

key

Current season flashing

select with the

keys

Confirm

2° 15

CONFIGURATION MENU

10.3 – MAX AND MIN SET TEMPERATURE LOCK (Winter and Summer mode)

In certain device installations (public buildings, hotels, etc.) it might be useful to limit the maximum and/or minimum temperature set points. This avoids incorrect settings by unauthorised personnel (energy savings).

MAX temp. lock Winter mode

set and confirm

It is possible to limit (lock) the MAXIUM, MINIMUM or BOTH temperature values settable (T set) on the device. The restriction may be applied either to the Winter or Summer distinctly.

Note: by default, no temperature lock is entered

.

From normal operation of the thermostat, access the menus by holding down

the Mode button as described in Chap. 9.

·Under the SEt bLOC menu item, confirm with OK.

·Pressing the buttons

, sequentially displays the MAX and MIN

temperature locks for Winter and Summer mode.

If there are no locks already inserted, the display shows

.

·Select the desired lock, confirm with OK the 3 dashes flash, using the buttons

enter the desired temperature value.

·Confirm with the OK button.

·Press the Mode button briefly and use the

buttons to select another

menu item, or press the Mode button twice to exit the menus and return to

normal operation.

GENERAL RULE: if Set temperature t1 (comfort) is greater than the maximum entered lock, it will level out with it. If Set OFF o t2 temeperature setting is less than the minimum entered lock, it will level out with it.
The following rule will apply to all other temperatures: WINTER ( )= t1 >
than t2; t2 > than OFF – SUMMER ( ) = t1 than t2; t2 OFF.

During thermostat operation, the user may not set a tSEt higher or lower than the max and min. locks entered. The display will signal impossibility to perform the operation by displaying .

To cancel any previously set locks bring the MAX/MIN set

16

points back to

MIN temp. lock Winter mode MAX temp. lock Summer mode MIN temp. lock Summer mode

set and confirm

set and confirm

set and confirm

10 – CONFIGURATION MENU (Installer)
10.4 – TYPE TEMPERATURE ADJUSTMENT METHODS
The thermostat is factory set to work in MODULATING PROPORTIONALLY °C (PrOP) mode; setting cycles from 7 to 20 minutes (default 7 minutes). This system maintains the desired temperature more stable, whilst increasing T SET the user’s comfort sensation and saving on energy consumption.

thermal inertia over temperature of the heating element

OFF ON

OFF ON

OFF ON

A long cycle is recommended for systems with high thermal inertia (cast iron radiators, floor systems) and a short cycle for systems with low thermal inertia (fan coils).
As opposed to the Modulating Proportionally, the temperature can be adjusted THERMAL DIFFERENTIAL mode ON/OFF with a preset thermal differential value (Hysteresis) of 0,3 °C (default). Note: adjustable from 0,2 °C to 1,2 °C. The hysteresis value must be set according to the system’s thermal inertia; a low value is recommended for systems with radiators made of e.g. cast iron and a high value for systems with fan coils.

time example of modulating proportional adjustment

°C
T SET isteresi OFF
ON

thermal inertia over temperature of the heating element
OFF ON

time example of differential adjustment

10.4.1 – SELECTION OF THE TEMPERATURE ADJUSTMENT MODE (PROPORTIONAL OR DIFFERENTIAL ON/OFF)

From normal thermostat operation access the menus by pressing

and holding the «Mode» key as described in Chap. 9, select Set

rEG, confirm with OK (the current setting flashes).

It will be possible to select temperature adjustment mode between Modulating proportional (PrOP) factory setting, or Thermal differential (On:OFF).

Use the

keys, to select the desired temperature

adjustment mode.

Press OK to confirm.

.
Depending on the chosen mode, the next menu displays the

setting of the PERIOD if you have opted for PrOP (see paragraph

10.4.2) or to set HYSTERESIS if you have opted for On:OFF (see

paragraph 10.4.3).

Select with

the

keys

If you wish to exit the menus, press the Mode button to return to normal operation.

press OK key to confirm the desired setting

Follows 17

10 – CONFIGURATION MENU (Installer)
10.4.2 – SETTING PERIOD DURATION FOR MODULATING PROPORTIONAL IN TIME

·Select the SEt rEG PrOP, menu screen, as described in paragraph

10.4.1. ·Press the

button to display the next menu SEt Per (period

duration). ·Confirm with OK if you want to change the period duration, the current

value flashes.

·With the

buttons, enter the duration of the desired period

(settable from 7 to 20 minutes, default 7 minutes). ·Press OK to confirm. ·Press to select another menu item or press the Mode button to exit

the menus and return to normal operation.

10.4.3 – SETTING HYSTERESIS FOR THERMAL DIFFERENTIAL ON-OFF

·Select the SEt rEG On:OF menu screen, as described in paragraph

10.4.1. ·Press the button to display the next menu SEt Ist (Hysteresis). ·Confirm with OK if you want to change the hysteresis, the current

value flashes. ·Use the buttons

to enter the desired hysteresis value, which

can be set from 0.2 °C to 1.2 °C (default 0.3 °C). ·Press OK to confirm. ·Press to select another menu item or press the Mode button to exit

the menus and return to normal operation..

18

10 – CONFIGURATION MENU (Installer)

10.5 – SET OFF, Anti-freeze protection (Winter) or Thermal protection (Summer) ·From normal operation of the thermostat, access the menus by holding down the Mode button as described in Chap. 9, the SEt OFF screen appears, confirm with OK.

·Select the SET OFF to be changed for WINTER mode (antifreeze) or SUMMER mode (thermal protection) using the buttons

.

·Confirm with the OK button, OFF flashes.

·With the buttons

set the desired antifreeze or thermal protection T Set OFF temperature. Press OK to confirm.

To DEACTIVATE Tset OFF (antifreeze), go below +4.0 °C = Antifreeze OFF temperature deactivated

In this case, the system will be exposed to possible frost damage.

Example: Default value 5.0C Set OFF in WINTER mode

Example: TSET OFF (antifreeze) modified

Select with the buttons
Example: Set OFF deactivated (default) in SUMMER mode

Each press of or results in a change of 0.1 degrees; tress and hold to scroll quickly through the values. Antifreeze OFF protection range: +4 °C at t2 Thermal protection OFF range: +37.7 °C at t2
Example: TSET OFF (thermal protection) modified

If the OFF level of antifreeze or thermal protection is deactivated and the user sets a minimum lock for Winter or a maximum lock for Summer (see par.10.3), the

OFF level is automatically re-enabled and automatically sets the minimum lock value for Winter or maximum lock value for Summer; it will be prevented

for the user to attempt to disable (

) the OFF protection level again.

·Press the Mode button and then

to select another menu item or press the Mode button twice to exit the menus and return to normal operation.
19

10 – CONFIGURATION MENU (Installer)
10.6 – MANAGEMENT OF EXTERNAL CONTACT for remote thermostat switching on/off
The thermostat is equipped with an input (AUX) for an external contact, it will be possible to connect accessory equipment (e.g. time switch, switch, window contact, etc.) that can deactivate the thermostat remotely, whose control must necessarily be potential-free. A typical use is the window contact that can be connected to this input e.g. to switch off the temperature control in Winter (or Summer) when a window is opened.

Before enabling any item of the «Set GAtE» menu listed below ensure you have connected an external contact potential-free to the terminals 1 and 2 (AUX) see par. 5.4.
WARNING: only connect switches and contacts with insulation suitable to work at 230Vac mains voltage to terminals 1 and 2 AUX.
MULTIPLE INSTALLATIONS: It is NOT permitted to connect the remote contact on more than one thermostat; each thermostat must have its AUX input operated independently of the others.

·From normal operation of the thermostat, access the menus by holding down

the “Mode” button as described in Chap. 9.

The SEt GAtE screen is displayed.

·Confirm by pressing OK, the dashes

flash.

·Using the buttons

, select the desired external contact management

mode screen (see table below).

·press OK to confirm.

·press the Mode button to exit the menus and return to normal thermostat operation.

Press the OK button to confirm the desired management of the external contact

= No external contact enable (default);

= RESETTABLE command on N.O. external contact “Normally Open”

= RESETTABLE command on N.C. external contact “Normally Closed”

= Command NOT RESETTABLE on N.O. external contact “Normally Open”

= Command NOT RESETTABLE on N.C. external contact “Normally Closed”

20

Follows

10 – CONFIGURATION MENU (Installer)

10.6.1 – RESETTABLE COMMAND on N.O. external contact “Normally Open”

Confirmed screen

for the management of the resettable N.O. external contact with a command on the thermostat

as per the procedure in paragraph 10.6, the following operation is obtained::

e.g. external contact N.A. Contact closure
Contact opening

Thermostat operation activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER ( ) return to the level and Tset active before closing the contact

example from mode: WINTER

Level OFF

Return to the level before contact closure

flashes

example with open window closing the N.O. contact

The change of state from open contact to closed contact

causes the thermostat to be forced into the permanent

manual OFF state with the icon

flashing (to signal an

active forcing situation).

The OFF level (antifreeze or thermal protection) can result in

actual temperature control at a certain Tset value (e.g. 5°C) or

temperature control switched off, see par. 10.5.

The subsequent change of state from closed contact to open

contact causes the end of the manual forcing OFF and the

automatic loading of the level that was active before the

forcing; the icon will be switched off.

OR the user can cancel the forcing OFF at any time without

opening the remote contact by pressing the MODE button

when the thermostat is already reactive (key reference

display). This type of command is called “RESETTABLE”, the

icon

will be displayed permanently lit (to indicate that

the remote contact is still closed), automatically restoring

the level that was active before the forcing to OFF. The

subsequent reopening of the remote contact will only result in

the icon being switched off.

steady

Resettable by briefly pressing the Mode button

Note: contact opening and closure controls are operative within max 60 sec.

closing the window opens the N.O. contact.

closing the window opens the N.O. contact.

return to normal thermostat operation 21

10 – CONFIGURATION MENU (Installer)

10.6.2 – RESETTABLE COMMAND on N.C. external contact “Normally Closed”

Confirmed screen

for the management of the resettable N.C. external contact with a command on the thermostat

as per the procedure in paragraph 10.6, the following operation is obtained:

Do not enable the

item prior to connecting a switch or other device that allows change of state

from OFF mode to current operating mode and vice versa to terminals 1 and 2 (AUX)..

e.g. external contact N.C. Contact opening Contact closure

Thermostat operation activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER ( ) return to the level and Tset active before closing the contact

For the operating principle procedure and the displays on the display when the state of the external contact changes and/or reset with control directly on the thermostat, see images shown in the previous paragraph 10.6.1. taking into account that the contact is normally closed N.C. and not N.A.

10.6.3 – NON-RESETCABLE COMMAND on external N.O. contact. «Normally Open»

Confirmed screen

of external contact management N.A. as per the procedure in paragraph 10.6 the following operation is obtained:

e.g. external contact N.A.

Thermostat operation

Contact closure

activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER ( )

Contact opening

return to the level and Tset active before closing the contact

example from mode: WINTER

Livello OFF

Return to the level before contact closure

flashes

example with open window which closes the N.O. contact.

Note: a flashing “bLOC” will Closing the window appear when any button is opens the N.A. contact. pressed.

contact opening and closure controls are operative within max 60 sec.

The change of state from open remote contact to closed contact causes forcing into the permanent manual OFF state (antifreeze or thermal protection) with the display of the flashing ” ” icon (to indicate an active forcing situation). The OFF level can result in actual temperature control at a certain Tset value (e.g. 5°C) or temperature control switched off, see par. 10.5.
The subsequent change of state from closed contact to open contact causes the end of the manual forcing OFF and the automatic loading of the 22 level that was active before the forcing; the icon will be switched off.

10 – CONFIGURATION MENU (Installer)

10.6.4 – COMMAND NOT RESETTABLE on N.C. external contact “Normally Closed”

Confirmed screen

for the management of the N.C. external contact as per the procedure in paragraph 10.6, the following operation is obtained:

Do not enable the

item prior to connecting a switch or other device that allows change of state from OFF

mode to current operating mode and vice versa to terminals 1 and 2 (AUX).

e.g. external contact N.C. Contact opening Contact closure

Thermostat operation activates level and Tset OFF ANTI-FREEZE if in WINTER ( ) or THERMAL PROTECTION in SUMMER ( ) return to the level and Tset active before closing the contact

For the operating principle procedure and the displays when the external contact changes state, see the images in the previous paragraph 10.6.3, bearing in mind that the contact is normally closed N.C. and not N.O.

10.7 – DISPLAY AND KEY BACK-LIGHTING

The menu the display.

,allows you to manage the backlighting of

·From normal operation of the thermostat, access the menus by holding down the Mode button as described in Chap. 9, the Set Led screen appears, confirm with OK. The currently active setting flashes on the display, example in the figure: 6 SEC=timing at 6 seconds (default)..

Example with default setting

Select with

the

keys

·With the

keys select the desired item

6SEC = Backlight off after 6 sec. (default). OFF = Disabled backlighting. ON = Backlight always ON. LO = Backlighting with mild intensity (cannot be changed) after 6 sec.

·Press OK key to confirm the desired setting. ·Press to select another menu item or press the Mode button to exit the menus and return to normal operation.

Press the OK button to confirm the desired setting.
23

10 – CONFIGURATION MENU (Installer)
10.8 – BRIGHTNESS ADJUSTMENT (back-light)
Example: 7 default value This setting is only accessible if the SEt Led parameter is not set to OFF (backlight always off) see par. 10,7)

·From normal operation of the thermostat, access the menus by holding

down the Mode button as described in Chap. 9.

The SEt LUMI screen is displayed.

·Confirm with the OK button, the set brightness value flashes

·Using the buttons

, choose the intensity of the backlight, which

can be set from 1 to 10 levels (default 7).

·Press the OK button to confirm the desired setting..

·Press to select another menu item or press the Mode button to exit

the menus and return to normal operation..

Select with the buttons

24

10 – CONFIGURATION MENU (Installer)

10.9 – RESTORE (

) factory reset

IMPORTANT! The RESTORE (Reset) operation is recommended for the installer or expert user. In fact, this operation deletes many previous settings and programs carried out also according to the type of system.

·From normal operation of the thermostat, access the menus by holding down the Mode button as described in Chap. 9..

·When the FACtOrY screen is displayed, confirm with OK, the word nO flashes..

·Using the buttons

choose “YES” to perform the Restore or “NO”.

·Confirming YES by pressing the OK button, the display shows all lit segments for a few seconds, then the thermostat restores the factory settings (see summary table in par. 2), positioning yourself on the normal operation screen.

The RESTORE operation deletes any password entered.

·Confirming with OK “NO” cancels the Restore operation. ·Press the button to move to the next menu or press the Mode button
to exit the menus and return to normal operation.

Normal operation

10.10 – RESET (Restart)

Does not cancel ANY previously entered or modified settings

Should the thermostat feature malfunctioning, wrong displays or other incorrect conditions, perform a “rESEt”.

·From normal operation of the thermostat, access the menus by holding down the Mode button as described in Chap. 9.
·When the rESET screen is displayed, confirm with OK, the word NO flashes.

·Using the buttons

choose “YES” to perform the Reset or “NO”.

·Confirming YES by pressing the OK button, the display shows all lit segments for a few seconds, then the thermostat returns to normal operation without changing any previous settings.

Example if you confirm YES by pressing the OK key
The thermostat is operating, in Winter mode “heating”, Temperature Set t1 (Comfort) at 20°C.

·If you opt for NO the display exits the function and goes back to the initial rESEt screen..

·Press to select another menu item or press the Mode button to exit the menus and return to normal operation.

25

10 – CONFIGURATION MENU (Installer)

10.11 – ENTERING AND MANAGING PASSWORDS TO ACCESS THE MENUS
·From normal thermostat operation, access the menus by holding down the “Mode” key as described in Chap. 9. ·When the SEt COdE screen is displayed, confirm with OK, the first dash flashes.

·Using the

keys, enter 4 digits (dashes not included) between 0000 and 9999, individually confirm them with «OK».

Note: press the Mode key to return to the previous screen in the event of an error or to exit the SEt COdE menu.

·Confirming the last digit with the OK button, the desired password is saved.

·Press to select another menu item or press the Mode button to exit the

menus and return to normal operation.

The «Installatore» password allows access to all menu PROG (configuration functions.

From normal operation of the thermostat, pressing and holding the “Mode” button will request the previously entered password before accessing the PROG menus (see par. 8).

Confirm

10.11.1 – PASSWORD MODIFICATION OR CANCELLATION

·To CHANGE the password already entered, from normal operation of the thermostat, access the menus by holding down the “Mode” button as

described in Chap. 9.

·When the SEt COdE screen is displayed, confirm with OK

will be displayed with the first dash flashing.

·Using the buttons

,enter the 4 digits of the NEW password (excluding dashes) between 0000 and 9999, confirming them individually with

the “OK” button or if you wish to CANCEL IT, enter the 4 dashes instead of the numbers:

(note: if a dash is entered as the first digit in

this situation, the other 3 digits can only be set as dashes).

Information reserved to installer or expert user only

in the event of FORGOTTEN password enter the reset code menus (see par. 8). The password will be CANCELED!
26

to the request to access the PROG configuration

10 – CONFIGURATION MENU (Installer) 10.12 – KEYBOARD LOCK (menu displayed ONLY with password set)

IMPORTANT: this SEt LOC menu will only be VISIBLE if a Password has previously been set (see par. 10.11).

This function serves to prevent unauthorised persons from modifying any thermostat settings.

·From normal operation of the thermostat, access the menus by holding down the Mode button as described in Chap. 9. ·Enter the Password previously set. ·On the SEt LOC menu screen, confirm with OK, nO flashes..

Normal operation

·With the buttons

choose “YES” to enable the lock or “NO” to

disable it.

·Press OK to confirm.

·Press the Mode button to exit.

Consequently, when the keyboard lock is engaged, from the Normal thermostat operation screen, pressing any key will show “bLOC” flashing on the display for a few seconds.

Normal operation

Keyboard lock engaged

To temporarily disable the keyboard lock, it is necessary to access the PROG menus by holding down the “Mode” button, enter the Password and return to Normal thermostat operation by briefly pressing the Mode button. Any user setting of the thermostat, will be possible within 120 seconds of the last pressing of any key and will then be reset to “Keyboard lock” again.

To permanently disable the “Keyboard lock”, in the SEt LOC menu screen confirm with OK, the word NO as described above.

FAULT SIGNALLING

In the event of a malfunction of the room temperature probe (shortcircuited or open probe), it is identified on the display by the fixed text “E1”, instead of the room temperature (TA) reading. A qualified installer will be required to replace or repair the device. The thermostat deactivates the temperature control and the relay.

Thermostat in “Normal operation” with fault
indication on display E1
27

12 – POSSIBLE PROBLEMS AND SOLUTIONS

PROBLEM

CAUSE

SOLUTION

The thermostat display is OFF

No power supply
Electrical cables not properly tightened in the terminals

Checl that the switch or protection differential isn’t on OFF
After you turn off the power supply of 230V ~ check the power cables if tightened to the appropriate terminals on the wall base.

The thermostat works but the system does not start
The temperature fluctuates too much between hot and cold

No power to the system
The thermostat is not connected properly
The thermostat is not set correctly for the type of system

In OFF operation (Winter ), the Set The antifreeze temperature has antifreeze temperature is not displayed been excluded

Make sure the switch or differential protection device is not set to OFF Contact the installer
Contact the installer
Set the antifreeze temperature by following the instructions in paragraph 10.5

DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT When this symbol is found on the product or on its packaging, it indicates that this product cannot be disposed of as household waste. It must be delivered to a specific collection point where electrical and electronic equipment is recycled, such as: – retail outlets, if a new product is bought, similar to that being disposed of. – local collection points (waste collection centres, local recycling centres, etc). By ensuring that the product is disposed of correctly, you will help prevent potential negative consequences for the environment and health, which can be caused by this product being disposed of inappropriately. Recycling the materials will help conserve natural resources. For more detailed information about recycling this product, please contact your Local Council, household waste disposal service or the shop where you purchased the product.
& Recycling: PAPER. Check the regulations of your municipality

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals