FUJITSU AOEG09KATA Air Conditioning User Guide
- May 15, 2024
- FUJITSU
Table of Contents
FUJITSU AOEG09KATA Air Conditioning
Specifications
Model | Type | Max. Pressure (High/Low) | Manufacturing Date | Power Resource |
---|---|---|---|---|
AOEG09KATA | cassette | (4.20) / (2.76) | Refer to the rating label | 1 230V ~ |
50Hz
AUXG09KVLA| duct| (4.20) / (2.76)| Refer to the rating label| 1 230V ~ 50Hz
Product Usage Instructions
Installation
Follow these steps to install the air conditioner:
- Choose a suitable location for the indoor and outdoor units.
- Connect the refrigerant lines between the units.
- Ensure proper electrical connections are made as per the power resource specifications.
operation
To operate the air conditioner:
- Turn on the power using the provided remote control or unit controls.
- Select the desired mode (cooling/heating) and set the temperature.
- Adjust fan speed and airflow direction for comfort.
Maintenance
Regular maintenance is essential for optimal performance:
- Clean or replace air filters as recommended in the user manual.
- Check for any leaks or unusual noises during operation.
- Schedule professional servicing at least once a year.
FAQ
-
Q: What is the recommended operating range for the air conditioner?
A: The indoor temperature range is from 16 to 32 degrees Celsius for cooling/dry mode and 16 to 30 degrees Celsius for heating mode. The outdoor temperature range is -15 to 46 degrees Celsius. -
Q: How do I know when to replace the air filters?
A: It is recommended to check the air filters every month and replace them if they appear dirty or clogged. Regular filter maintenance ensures efficient operation of the air conditioner.
AIR CONDITIONER PRODUCT FICHE
Product fiche according to Commission Delegated Regulation (EU) 626/2011
MODEL
| OUTDOOR UNIT| AOEG09KATA| AOEG12KATA| AOEG14KATA
---|---|---|---|---
INDOOR UNIT| AUXG09KVLA| ARXG09KLLAP| AUXG12KVLA| ARXG12KLLAP| AUXG14KVLA|
ARXG14KLLAP
| COOLING| HEATING| COOLING| HEATING| COOLING| HEATING| COOLING| HEATING|
COOLING| HEATING| COOLING| HEATING
SOUND POWER LEVEL| OUTDOOR UNIT
[dB(A)]| 60| 60| 60| 60| 62| 62| 62| 62| 63| 63| 63| 63
INDOOR UNIT [dB(A)]| 46| 47| 57| 57|
49| 49| 58| 58| 50| 55| 60| 60
REFRIGERANT/GLOBAL WARMING POTENTIAL| R32 / 675 (IPCC AR4) (*1)
SEASONAL ENERGY EFFICIENCY RATIO/ SEASONAL COEFFICIENT OF PERFORMANCE| ****
6.20
| ****
4.00
| ****
5.90
| ****
3.80
| ****
6.10
| ****
4.00
| ****
5.80
| ****
3.80
| ****
6.10
| ****
4.00
| ****
5.60
| ****
3.80
ENERGY EFFICIENCY CLASS| A++| A+| A+| A| A++| A+| A+| A| A++| A+| A+| A
ANNUAL ENERGY CONSUMPTION
[kWh/a] (QCE)(QHE)| ****
141 (*2)
| ****
804 (*3)
| ****
148 (*2)
| ****
847 (*3)
| ****
201 (*2)
| ****
979 (*3)
| ****
211 (*2)
| ****
1031 (*3)
| ****
247 (*2)
| ****
1120 (*3)
| ****
269 (*2)
| ****
1177 (*3)
Pdesign [kW]| 2.5 (35°C)| 2.3
(-10°C)
| 2.5 (35°C)| 2.3
(-10°C)
| 3.5 (35°C)| 2.8
(-10°C)
| 3.5 (35°C)| 2.8
(-10°C)
| 4.3 (35°C)| 3.2
(-10°C)
| 4.3 (35°C)| 3.2
(-10°C)
BACKUP HEATER CAPACITY/ [kW] DECLARED CAPACITY| ****
―
| 0.42/
1.88
| ****
―
| 0.39/
1.91
| ****
―
| 0.49/
2.31
| ****
―
| 0.59/
2.21
| ****
―
| 0.56/
2.64
| ****
―
| 0.55/
2.65
NOTES
- Refrigerant leakage contributes to climate change. Refrigerant with lower global warming potential (GWP) would contribute less to global warming than a refrigerant with higher GWP, if leaked to the atmosphere. This appliance contains a refrigerant fl uid with a GWP equal to [675]. This means that if 1 kg of this refrigerant fl uid would be leaked to the atmosphere, the impact on global warming would be [675] times higher than 1 kg of CO2, over 100 years. Never try to interfere with the refrigerant circuit yourself or disassemble the product yourself and always ask a professional.
- Energy consumption “QCE” kWh per year based on standard test results. Actual energy consumption will depend on how the appliance is used and where it is located.
- Energy consumption “QHE” kWh per year, based on standard test results. Actual energy consumption will depend on how the appliance is used and where it is located
Specifications
MODEL
| OUTDOOR UNIT| AOEG09KATA| AOEG12KATA| AOEG14KATA
---|---|---|---|---
INDOOR UNIT| AUXG09KVLA| ARXG09KLLAP| AUXG12KVLA| ARXG12KLLAP| AUXG14KVLA|
ARXG14KLLAP
TYPE
| CASSETTE| DUCT| CASSETTE| DUCT| CASSETTE| DUCT
SINGLE SPLIT / HEAT PUMP
MAX. PRESSURE| HIGH / DISCHARGE [bar(MPa)]| ― (4.20)
LOW / SUCTION| [bar(MPa)]| ― (2.76)
MANUFACTURING DATE| Refer to the rating label
POWER RESOURCE| 1φ 230 V ~ 50 Hz
| COOLING| HEATING| COOLING| HEATING| COOLING| HEATING| COOLING| HEATING|
COOLING| HEATING| COOLING| HEATING
CAPACITY| [kW]| 2.50| 3.20| 2.50| 3.20| 3.50| 4.10| 3.50| 4.10| 4.30| 5.00|
4.30| 5.00
POWER INPUT| [kW]| 0.680| 0.880| 0.690| 0.880| 1.090| 1.170| 1.090| 1.170|
1.370| 1.420| 1.370| 1.420
CURRENT| [A]| 3.4| 4.4| 3.4| 4.4| 5.2| 5.8| 5.2| 5.8| 6.4| 6.6| 6.4| 6.6
MAX. CURRENT| [A]| 6.9| 7.7| 9.2
ENERGY EFFICIENCY RATIO/ COEFFICIENT OF PERFORMANCE| [kW/kW]| ****
3.68
| ****
3.64
| ****
3.62
| ****
3.64
| ****
3.21
| ****
3.50
| ****
3.21
| ****
3.50
| ****
3.14
| ****
3.52
| ****
3.14
| ****
3.52
DIMENSION (H×W×D)
| OUTDOOR UNIT| [mm]| 541 × 663 × 290| 542 × 799 × 290
INDOOR UNIT (GRILLE)| **** [mm]| 245 × 570 × 570
(49 × 620 × 620)
| 198 × 700 × 620| 245 × 570 × 570
(49 × 620 × 620)
| 198 × 700 × 620| 245 × 570 × 570
(49 × 620 × 620)
| 198 × 700 × 620
WEIGHT
| OUTDOOR UNIT| [kg]| 23| 25| 32
INDOOR UNIT (GRILLE)| [kg]| 15
(2.3)
| 17| 15
(2.3)
| 17| 15
(2.3)
| 17
REFRIGERANT CHARGE
(Tons – CO2 equivalent)
| [kg] (t-CO2eq)| 0.60
(0.405)
| 0.70
(0.473)
| 0.85
(0.574)
- For more information, visit our website at: www.fujitsu-general.com
- For spare parts inquiries, consult the store where you purchased the product.
- Sound pressure level: less than 70 dB(A) by according to IEC 704-1.
OPERATING RANGE | INDOOR | OUTDOOR |
---|---|---|
COOLING/DRY [°C] | 18 | |
to 32 | -10 to 46 |
HEATING
[°C]| 16 to 30| -15 to 24
HUMIDITY [%]|
80 or less| ―
- If the air conditioner is operated under the conditions except the permissible temperature range, the air conditioner may stop because of the automatic protection circuit working.
- Depending on the operating conditions, the heat exchanger may freeze during the Cooling or Dry mode and it may cause water leakage and other damage.
- If the unit is used for long periods under high-humidity conditions, condensation may form on the surface of the indoor unit, and drip onto the floor or other objects underneath.
FUJITSU GENERAL LIMITED
3-3-17, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>