Vent-Axia 438342 Lo Carbon Sentinel Kinetic BH User Guide
- June 17, 2024
- Vent-Axia
Table of Contents
Lo-Carbon Sentinel Kinetic BH
- Recognised in SAP PCDB
- Lightweight for easier installation
- Horizontal duct option for space-saving installations
- Fits within a 290mm deep kitchen cupboard
- Integrated digital controller for simple and accurate commissioning
- Plug and play controls; Humidistat, Wireless Remote
- BMS connectivity
- LS inputs (Light Switch)
- Horizontal duct options
- Acoustic Enclosure option for reduced breakout noise
- Acoustic Top Box option for reduced in-duct noise
Easy Installation
The Sentinel Kinetic models can be mounted vertically in a roof space, hallway cupboard or kitchen or within a kitchen cupboard. When mounted in an unheated area ducting and MVHR unit should be insulated. Ducting can be attached to the unit horizontally, vertically or both. Minimum internal depth of kitchen cupboard 290mm.
For scenarios where noise is a critical issue, an Acoustic Enclosure is available to reduce breakout noise and the Acoustic Top Box will reduce in- duct noise at key frequencies.
Left (L) or right (R) hand installation. The unit is supplied with duct spigots to outside on the right hand side. These can be reversed on site by simply removing the control panel, rotating the unit 180 degrees and re- attaching the control panel.
Spigot Options
The combination of spigot options allows installation in confined locations. If vertical and horizontal connection is required on the same outlet/inlet, additional spigots can be supplied.
The condensate drain can be taken out through the back, side or bottom of the unit. Using the fittings supplied, the final condensate connection is made outside the unit and can be completed after installation.
Integral Humidity Sensor (BH Models)
The integral humidity sensor increases speed in proportion to relative humidity levels, saving energy and reducing noise. The sensor also reacts to small but rapid increases in humidity, even if the normal trigger threshold is not reached. This unique feature ensures adequate ventilation, even for the smallest wet room. The night time relative humidity setback feature suppresses nuisance tripping as humidity gradually increases with falling temperature.
Models
Model|
Stock Ref
---|---
Kinetic VS Right|
438342
Kinetic BH Right|
443319
Kinetic BH Right with Acoustic Enclosure & Top Box|
479526
Kinetic BH Right with Acoustic Top Box|
479525
Kinetic BH Right with Acoustic Enclosure|
479524
Kinetic BH Left|
443319L
Kinetic BH Left with Acoustic Enclosure & Top Box|
479529
Kinetic BH Left with Acoustic Top Box|
479528
Kinetic BH Left with Acoustic Enclosure|
479527
(BH with summer bypass & humidity sensor)
Accessories
Model|
Stock Ref
---|---
Wired Remote Controller|
443283
LED alarm with 15m cable|
448356
Acoustic Purge Fan|
477988
Acoustic Purge Fan XL|
479829
ISO 45% Coarse (G3) 2x Filter|
442356
ISO ePM10 50% Pollen (M5) 1x Filter|
444199
Anti Vibration Mounts|
68MP033G
SAP PCDB performance (Kinetic VS)
|
SAP 2009
| SAP 2012
---|---|---
Thermal Efficiency %| SFP (W/l/s)| Thermal Efficiency %|
SFP (W/l/s)
K+1
| 90| 0.60| 90| 0.61
K+2| 90| 0.59| 90|
0.74
K+3
| 90| 0.68| 90| 0.95
K+4| 89| 0.79| 90|
1.19
K+5
| 90| 0.97| –|
–
SEC Class
Model
| SEC Class
---|---
Kinetic VS & BH|
A
Dimensions (mm)
Unit
A
| B| C| D| EØ| F| G
---|---|---|---|---|---|---
550| 550| 285| 140| 125| 360|
90
Weight: 15kg
Acoustic Solution
Top
Front Side
- Acoustic Top Box
- Acoustic Enclosure
A
| B| C| D| E| F| G| Acoustic
Top Box
kg| Acoustic
Enclosure
kg| Spigot
---|---|---|---|---|---|---|---|---|---
80| 633| 501| 75| 626| 447| 45| 11| 19|
125
Performance
Fan speeds are fully adjustable within the performance range.
Vertical Spigots
Horizontal Spigots
figure relates to Wattage (both motors)
Sound Data (Kinetic VS & BH)
|
Octave band, Hz, dB SWL
| SPL dB(A)
---|---|---
Speed| Test mode| 63| 125| 250| 500| 1k| 2k| 4k| 8k| LwA|
@ 3m
20%
| Supply| 52.9| 52.9| 46.5| 41.7| 39.3| 29.3| 19.3| 22.8| 44.4| 26.9
Extract| 50.7| 41.9| 37.4| 34.5| 29.8| 17.7| 17.4| 22.7| 35.7|
18.2
Breakout
| 36| 34.5| 33.6| 34.3| 33.8| 27.2| 22.2| 25.3| 37.2| 16.7
40%| Supply| 57.1| 64.1| 56.8| 50.6| 49.7| 41.1| 32.8| 26.4| 54.7|
37.2
Extract
| 55.2| 50.3| 44.9| 43| 38.3| 27.7| 19.8| 22.9| 43.8| 26.3
Breakout| 43.5| 41.7| 40.4| 41.3| 41.7| 36.1| 27.8| 26.2| 44.7|
24.2
60%
| Supply| 71.3| 72.5| 68.5| 57.6| 56.4| 51.1| 42.7| 38.1| 63.6| 46.1
Extract| 60.2| 56.3| 52| 48.8| 44.8| 35.5| 26.9| 24.4| 50.2|
32.7
Breakout
| 50.7| 47.8| 47.7| 47.7| 48.3| 44.9| 36.7| 30| 51.8| 31.3
80%| Supply| 66.3| 74.8| 71.2| 62.8| 61| 56.3| 49.8| 46.7| 67.3|
49.8
Extract
| 63.8| 59.4| 57.6| 53.8| 49.2| 41.2| 33.5| 29| 55.0| 37.5
Breakout| 54.4| 52.7| 54| 52.7| 53.5| 50.3| 43.6| 37.7| 57.2|
36.7
100%
| Supply| 70.3| 75.7| 73.9| 66.3| 63.5| 59.7| 53.2| 50.6| 70.0| 52.5
Extract| 66.6| 63.9| 60.9| 56.5| 51.2| 44.2| 36.8| 32.6| 57.9|
40.4
Breakout
| 59.1| 55.2| 56.8| 55.6| 56.1| 53.5| 47.1| 41.6| 60.1|
39.6
Sound Data (Kinetic VS & BH with Acoustic Solution)
|
Octave band, Hz, dB SWL
| SPL dB(A)
---|---|---
Speed| Test mode| 63| 125| 250| 500| 1k| 2k| 4k| 8k| LwA|
@ 3m
20%
| Supply| 57.1| 44.6| 36.4| 27.9| 20.6| 14.8| 18.1| 23.8| 35.2| 17.7
Extract| 54.4| 40.1| 29.6| 22.2| 17.5| 14.5| 17.8| 23.5| 31.1|
13.6
Breakout
| 37.5| 33.8| 29.1| 22.9| 17.0| 14.0| 17.8| 23.6| 27.7| 7.2
40%| Supply| 64.9| 56.3| 46.4| 36.1| 28.2| 15.4| 18.1| 23.8| 44.6|
27.1
Extract
| 60.2| 46.8| 35.7| 28.2| 21.9| 14.8| 18.1| 23.7| 36.6| 19.1
Breakout| 46.0| 43.6| 36.3| 30.4| 23.9| 15.9| 18.1| 23.6| 33.5|
13.0
60%
| Supply| 72.3| 63.0| 55.6| 43.1| 34.1| 19.5| 18.6| 24.0| 51.9| 34.4
Extract| 61.4| 53.3| 43.4| 34.7| 27.2| 15.5| 18.1| 23.8| 41.4|
23.9
Breakout
| 52.2| 50.5| 44.4| 38.2| 33.5| 23.8| 19.3| 23.8| 41.0| 20.5
80%| Supply| 73.8| 67.9| 61.6| 50.0| 38.6| 23.4| 20.2| 25.2| 56.8|
39.3
Extract
| 68.6| 58.2| 50.5| 40.5| 31.1| 17.2| 18.2| 23.9| 47.5| 30.0
Breakout| 65.6| 55.5| 50.5| 43.8| 39.7| 32.7| 24.9| 24.0| 47.4|
26.9
100%
| Supply| 77.3| 70.8| 64.9| 53.8| 41.4| 26.3| 21.9| 26.8| 60.1| 42.6
Extract
| 71.5| 60.6| 53.5| 43.9| 33.4| 19.1| 18.5| 24.0| 50.5|
33.0
Breakout| 69.0| 58.4| 53.4| 47.1| 43.0| 37.5| 29.9| 24.9| 51.1|
30.6
Tested according to BS EN 13141-7:2010. Breakout quoted spherical. Supply and Extract quoted hemispherical. For in-duct data, end reflections are added based on the spigot size of the unit.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>