Honeywell RMA801 HART DE Remote Indicator Installation Guide
- June 17, 2024
- Honeywell
Table of Contents
- Installation and setup
- Explosion-Proof Conduit Seal
- Features and Options
- Mounting Remote indicator
- Mounting Dimensions
- Wiring a Remote Indicator
- Wiring Connections and Power Up
- DEVICE CONFIGURATION
- Appendix A. PRODUCT CERTIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SmartLine RMA801 HART/DE
Remote Indicator Assembly
Quick Start Installation Guide
34-ST-25-63, Revision
8, September 2022
Installation and setup
Site evaluation
Evaluate the site selected for the Remote Indicator installation with respect
to the process system design specifications and Honeywell’s published
performance characteristics for your particular model. Some parameters that
you may want to include in your site evaluation can be found in the RMA801
user manual, #34-ST-25-62
Installation precautions
Temperature extremes can affect display quality. The display can go blank if
the temperature is below -20°C or above +70°C; however, this is only a
temporary condition. The display will again be readable when temperatures
return to within operable limits.
Explosion-Proof Conduit Seal
WARNING
When installed as explosion proof in a Division 1 Hazardous Location, keep
covers tight while the Remote Indicator is energized. Disconnect power to the
Remote Indicator in the non-hazardous area prior to removing end caps for
service.
When installed as non-incendive equipment in a Division 2 hazardous location,
disconnect power to the Remote Indicator in the non-hazardous area, or
determine that the location is non-hazardous before disconnecting or
connecting the Remote Indicator wires.
Features and Options
The RMA801 Remote Indicator provides a means of remote-mounting a indicator
(display) that is associated with a Honeywell Smartline Transmitter or any
transmitter operating in a 4-20 mA current loop.
The RMA801 is a DE/Analog Remote Indicator which can be connected anywhere
along the current loop.
For analog PV, the RMA801 measures the loop current and displays the
equivalent PV value on the display.
The RMA801 will auto configure when connected to Honeywell DE transmitters
except SMV800/3000when a database upload is performed.
This document provides the information for a quick setup. For detailed
information, please efer RMA801 user manual, 34-ST-25-62. CAUTION
Temperature extremes can affect display quality. The display can go blank if
the temperature is below -20°C or above 70°C; however, this is only a
temporary condition. The display will again be readable when temperatures
return to within operable limits.
The device shall be operated by a trained professional. It is the
user/installer’s responsibility to install the indicator in accordance with
national and local code requirements. Conduit entry plugs and adapters shall
be suitable for the environment, shall be certified for the hazardous location
when required and acceptable to the authority having jurisdiction for the
plant
The RMA device is always connected in series with the transmitter. The current
loop will be broken if the RMA801 device is removed from the loop.
Mounting Remote indicator
Summary Remote Indicator models can be attached to a two-inch (50.8 millimeter) vertical or horizontal pipe using Honeywell’s optional pipe mounting bracket. Honeywell’s optional wall mounting bracket is also shown in figures below.
Mounting Dimensions
Refer to Honeywell drawing number 51455045 for detailed electronic housing
dimensions.
Refer to Honeywell drawing numbers 32306827 for detailed pipe mounting
dimensions, 50124813 for Detailed Pipe Angle mounting dimensions and
32306828 for detailed wall mounting dimensions.
THE TRANSMITTER ENCLOSURE CAN BE ROTATED A TOTAL OF 90° FROM THE STANDARD
MOUNTING POSITION
-
Honeywell drawings can be supplied on request.
Bracket Mounting
If you are using an optional bracket, start with Step 1.- Pipe Mount Option -Refer to Figure 2, Figure 3 and Figure 4. Align the two mounting holes at the bottom of the Remote Indicator with the two slots in the mounting bracket and assemble the (2) M8 hex cap screws, (2) lock washers and (2) flat washers provided.
- Rotate the Remote Indicator assembly to the desired position and torque the M8 hex cap screws to 27,0 Nm/20,0 Lb-ft maximum
- Position the bracket on a 2-inch (50.8 mm) horizontal or vertical pipe and install a “U” bolt around the pipe and through the holes in the bracket. Secure the bracket with (2) M10 hex nuts, (2) flat washers and (2) lock washers provided. Refer to Figure 4.
- Wall Mount Option – Refer Figure 5 Position the bracket on the mounting surface at the desired location and secure the bracket to the mounting surface using the appropriate hardware (Wall mounting hardware requirements to be determined and supplied by the end user).
Wiring a Remote Indicator
Overview
The Remote Indicator is designed to operate in normal 4-20mA analog mode with
HART enabled transmitters across SmartLine Devices and DE transmitters except
SMV800/3000.
For improved noise performance, it is recommended to provide earth ground for
both transmitter and RMA housing.
Terminal Block
The RMA801 has 3 terminals. Following table provides the connection details-
Terminal No. | Description |
---|---|
5 | Loop +ve |
6 | Loop -ve |
9 | DE COMM |
Three screw terminals suitable for wirings up to (16AWG)
- Shielded, twisted-pair cable such as Belden 9318 or equivalent must be used for all signal/power wiring.
- The cable shield must be connected at only one end of the cable. Connect it to the power supply side and leave the shield insulated at the transmitter side and RMA side.
Note: If solid core wire is used strip insulation 1/4 in (6 mm). Once
inserted under the square washer the stripped portion should be contained
under the square washer.
If multi-stranded wire is used, a ferrule is to be used and the stripped wire
should be in the insulated portion of the ferrule. The ferrule can be also be
used on the solid core wire.
Loop Terminals 5 & 6 shall be connected in series with the 4-20 ma loop for
both analog and DE modes. Additionally, third wire (Terminal 9) is required
for DE communication in DE mode only.
Loop wiring for analog and DE mode is shown in figure below.
NOTE: After wiring the Transmitter as outline in the next sections,
torque the screws to 1.1 Nm (10 lb-in)
Wiring Connections and Power Up
Make sure that the following power supply constraint is met.
??,??? = 2.3? + ?????,??? +(????? ∗ Im??/1000)
Where
V. win 8 Minimum supply vol tage
V.er.uin 1S Transmitter Minimum supply voltage at terminals
Roop 1S loop resistance in ohms
I max High failSafe/B urnout current in mA
Wiring Options
There are 3 wiring options for connecting Remote Indicator to the loop.
See Figure 8, Figure 9 and Figure 10 for the wiring connections.
DE Devices
In this mode, the Remote Indicator shall be connected as shown in Figure 8.
Once the wiring is complete, power on the loop. The RMA device will take 6s
(approx.) to turn on the display.
Note – The resistor “R” indicates (shown for representation only) the loop
resistor which is needed for HART and DE communication and is typically
provided by the user or control system.
Analog (4-20mA) Devices:
Refer Figure 8 and 9 for the Remote Indicator Connection on the Negative and
positive side of the loop.
- Remote Indicator installed as explosion proof in Class I, Division 1, Group A Hazardous (classified) locations in accordance with ANSI/NFPA 70, the US National Electrical Code, with 1/2 inch conduit do not require an explosion-proof seal for installation. If 3/4 inch conduit is used, a LISTED explosion proof seal must be installed in the conduit, within 18 inches (457.2 mm) of the Remote Indicator.
ATTENTION
For all wiring options, ensure that RMA chassis ground terminal is connected
to earth ground.
Connect the Loop Power shield to earth ground at the power supply end and not
at RMA end. The shield shall be continuous from transmitter through RMA till
the power supply
DEVICE CONFIGURATION
Once the loop is powered, the RMA will be turned ON with a scrolling message
“SmartLine” appearing on the display.
For DE devices, the RMA is autoconfigured. For any DE configuration change in
the transmitter, database upload shall be performed to reflect the changes in
RMA.
To configure the device, open the front cover of the device.
Use the ‘Menu’ and ‘Enter’ key buttons on display to configure the device. See
table below for configuration parameters.
Use the ‘Menu’ button to navigate the configuration parameters. Use the
‘Enter’ button to select and set a parameter value.
Engineering Units
SNO | MENU Parameters | Description |
---|---|---|
1 | SEL PV | Select Process Variable (temperature, pressure, flow and |
Level, loop out, % out)
2| UNIT| Select Engineering Unit
Units are visible as per PV selection
3| ENTLRV| Enter Lower Range Value (Numeric Value)
4| ENTURV| Enter Upper Range Value (Numeric Value)
5| CAL Lo| Input Calibration Low Point. See manual for details of
calibration. (Applicable in Analog Mode only)
6| CAL Hi| Input Calibration High Point. See manual for details of
calibration. (Applicable in Analog Mode only)
7| B UNIT| Select Engineering Base Unit of Transmitter Base Units
visible as per PV selection (Applicable in Analog Mode only)
8| CNTRST| Set LCD Contrast
9| RMA DG| RMA Diagnostic Messages. See manual for details of diagnostic
messages
10| SQRT| Select Square Root (Disable, Enable)
11| SCLLO| Enter Scaling Low Value (Numeric Value)
12| SCLHI| Enter Scaling High Value (Numeric Value)
13| RBoot| Reboot the Remote Indicator Assembly
14| TAG| Displays Tag (Readonly)
15| FW VER| Firmware Version
| EXIT| EXIT Menu
Appendix A. PRODUCT CERTIFICATIONS
A1 European Directive Information (CE Mark)
RMA800 SmartLine Remote Indicator Series EU Declaration of conformity
(Document #32302406), can be downloaded here: EU
Declaration
A2. Hazardous Locations Certifications
C| ATEX| Flame-proof and Dust: SIRA 14ATEX2147X
II 2 G Ex db IIC T6..T5 Gb
II 2 D Ex tb IIIC T 95oC Db| Note 1| T6: -50oC to 65oC T95oC, T5: -50oC to
85oC
---|---|---|---|---
Intrinsically Safe: SIRA 14ATEX2147X/ SIRA 14ATEX4148X
II 1 G Ex ia IIC T4 Ga
II 3 G Ex ic IIC T4 Gc| Note 2| -50oC to 70oC
Increased Safety: SIRA 14ATEX4148X
II 3 G Ex ec IIC T4 Gc| Note 1| -50oC to 85oC
Enclosure: Type IP66/ IP67| ALL| ALL
STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN
60079-31: 2014; EN 60079-7: 2015/ A1: 2018;
C| UKEX| Flame-proof: CSAE 22UKEX1046X
II 2 G Ex db IIC T6..T5 Gb
II 2 D Ex tb IIIC T 95oC Db|
Note 1
| T6: -50oC to 65oC T95oC, T5: -50oC to 85oC
Intrinsically Safe: CSAE 22UKEX1046X/ CSAE 22UKEX1323X
II 1 G Ex ia IIC T4 Ga
II 3 G Ex ic IIC T4 Gc| Note 2| -50oC to 70oC
Increased Safety: CSAE
22UKEX1323X
II 3 G Ex ec IIC T4 Gc| Note 1| -50oC to 85oC
Enclosure: IP66/ IP67| ALL| ALL
STANDARDS: EN IEC 60079-0: 2018; EN 60079-1: 2014; EN 60079-11: 2012; EN
60079-31: 2014; EN 60079-7: 2015/ A1: 2018;
D| IECEx| Flame-proof: IECEx SIR 14.0050X Ex db IIC T6..T5 Gb Ex tb IIIC
T 95oC Db| Note 1| T6: -50oC to 65oC T95oC, T5: -50oC to 85oC
Intrinsically Safe: IECEx SIR 14.0050X Ex ia IIC T4 Ga Ex ic IIC T4 Gc|
Note 2| -50oC to 70oC
Increased Safety: IECEx SIR 14.0050X Ex ec IIC T4 Gc| Note 1| –50oC to
85oC
Enclosure: IP66/ IP67| ALL| ALL
STANDARDS: IEC 60079-0: 2018; IEC 60079-1: 2014; IEC 60079-11: 2011; IEC
60079-7: 2017; IEC 60079-31: 2014
E| SAEx| Flame-proof:
Ex db IIC T6..T5 Gb
Ex tb IIIC T 95oC Db| Note 1| T6: -20oC to 65oC T95oC, T5: -20oC to 85oC
---|---|---|---|---
Intrinsically Safe:
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc| Note 2| -20oC to 70oC
Non-Incendive
Ex ec IIC T4 Gc| Note 1| –20oC to 85oC
Enclosure: IP66/ IP67| ALL| ALL
K| cCSAus| Explosion proof:
Class I, Division 1, Groups A, B,
C, D;T6..T4
Dust Ignition Proof:
Class II, III, Division 1, Groups
E, F, G; T4
Class I Zone 1 Ex db IIC T4 Gb
Ex db IIC T4 Gb
Zone 21 Ex tb IIIC T 95oC Db
Ex tb IIIC T 95oC Db| Note 1| -50 ºC to 70ºC
Intrinsically Safe:
CSA 14.2689056
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G; T4
Class I Zone 0 Ex ia IIC T4 Ga
Ex ia IIC T4 Ga
Class I Zone 2 Ex ic IIC T4 Gc
Ex ic IIC T4 Gc| Note 2| -50oC to 70oC
Non-Incendive
Class I, Division 2, Groups A, B,
C, D; T4
Class I Zone 2 Ex ec IIC T4 Gc
Ex ec IIC T4 Gc| Note 1| -50oC to 70oC
Enclosure: Type 4X/ IP66/IP67| ALL| ALL
Standards: CSA C22.2 No. 0: 2015; CSA C22.2 No. 30: 2016; CSA C22.2 No.
94-M91; CSA C22.2 No. 25: 2017; CSA C22.2
No. 61010-1: 2017; CSA-C22.2No.157: 2016; C22.2 No. 213: 2017; C22.2 No. CSA
60079-0:2015; C22.2 No. 60079-1: 2016; C22.2 No. 60079-11: 2014; C22.2 No.
60079-15: 2016; C22.2
No. 60079-31: 2015;
ANSI/ ISA12.12.01-2017; ANSI/ ISA 61010-1: 2016; ANSI/ UL 60079-0: 2013; ANSI/
UL 60079-1: 2015; ANSI/ UL 60079-11: 2014; ANSI/ UL 60079-15: 2013; ANSI/ UL
60079-31: 2015 ; FM 3600: 2011; FM 3615: 2006; FM Class 3616: 2011; ANSI/ UL
913: 2015; UL 916: 2015; ANSI/ UL 12.27.01: 2017; ANSI/UL 50E: 2015
Notes
-
Operating Parameters:
Voltage= 12 to 42 V Current= 25 mA -
Intrinsically Safe Entity Parameters
For details see Control Drawing, 50089981.
A4. Marking ATEX Directive
a. General
The following information is provided as part of the labeling of the Remote
Indicator:
- Name and Address of the manufacturer
- The serial number of the Remote Indicator is located on the Meter Body data-plate. The first two digits of the serial number identify the year (02) and the second two digits identify the week of the year (23); for example, 0223xxxxxxxx indicates that the product was manufactured in 2002, in the 23rd week.
b. Apparatus Marked with Multiple Types of Protection
The user must determine the type of protection required for installation the
equipment. The user shall then check the box [ ] adjacent to the type of
protection used on the equipment certification nameplate. Once a type of
protection has been checked on the nameplate, the equipment shall not then be
reinstalled using any of the other certification types.
c. WARNINGS and Cautions
Non-Incendive / Non-Sparking (Division 2 and Zone 2 Environments):
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2
Intrinsically Safe (Divisions 1, Zone 1 and Zone 2 Environments):
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC
SAFETY.
WARNING – DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT.
Explosion-Proof (Division 1 and Zone 1 Environments):
WARNING – DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT.
WARNING – DO NOT OPEN WHEN ENERGIZED “OPEN CIRCUIT BEFORE REMOVING COVER”
Flameproof (Division 1 and Zone 1 Environments): WARNING – DO NOT OPEN WHEN
ENERGIZED
General Requirements / Increased Safety (Zone 1): WARNING – DO NOT OPEN WHEN
ENERGIZED
WARNING – OPEN CIRCUIT BEFORE REMOVING COVER
All Protective Measures:
WARNING: FOR CONNECTION IN AMBIENTS ABOVE 60 °C USE WIRE RATED 105 °C
A.5 Conditions of Use” for Ex Equipment”, Hazardous Location
Equipment or “Schedule of Limitations”:
a. Consult the manufacturer for dimensional information on the flameproof
joints for repair.
b. Painted surface of the RMA 800 series may store electrostatic charge and
become a source of ignition in applications with a low relative humidity less
than approximately30% relative humidity where the painted surface is
relatively free of surface contamination such as dirt, dust or oil. Cleaning
of the painted surface should only be done with a damp cloth.
c. The ambient temperature range, maximum process temperature and applicable
temperature class of the equipment is as follows:
RMA801: T4 for -50˚C < Ta < 70˚C
d. The RMA800 series enclosure contains aluminium and is considered to present
a potential risk of ignition by impact or friction. Care must be considered
during installation and use to prevent impact or friction to avoid impact.
e. If a charge-generating mechanism is present, the exposed metallic part on
the enclosure is capable of storing a level of electrostatic charge that could
become incendive for IIC gases. Therefore, the user/installer shall implement
precautions to prevent the buildup of electrostatic charge, e.g. earthing the
metallic part. This is particularly important if the equipment is installed in
a zone 0 location.
f. On installation, the RMA800 series shall be provided with supply transient
protection external to the apparatus such that the voltage at the supply
terminals of the RMA800 series does not exceed 140% of the voltage rating of
the equipment.
COPYRIGHT 2019, HONEYWELL INTERNATIONAL INC. NEITHER THIS DOCUMENT NOR THE INFORMATION CONTAINED HEREIN SHALL BE REPRODUCED. USED OR DISCLOSED TO OTHERS WITHOUT THE WRITTEN AUTHORIZATION OF HONEYWELL USE, DUPLICATION, OR DISCLOSURE OF THIS DOCUMENT IS SUBJECT TO THE RESTRICTIONS SET FORTH IN A WRITTEN AGREEMENT. NOTHING CONTAINED HEREIN SHALL BE CONSTRUED AS CONFERRING BY IMPLICATION, ESTOPPEL, OR OTHERWISE ANY LICENSE TO ANY PATENT, TRADEMARK, COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT OF HONEYWELL OR ANY THIRD PARTY.
RMA 800 Series Remote Meter,
Analog. DE Communications and Foundation Fieldbus
-
intrinsicalty safe mstallation shall be in accordance with
a. FM (USA): ANSI/NFPA 70, NEC’ Arties 504 and 505.
b. CSA (Canada): Canadian Electrica! Code (CEC), part |, section 18.
c. ATEX: Requirements of EN 60079-14, 12.3 (See also 5.2.4).
d. 1ECEx Requirements of IEC 60079-14, 12.3 (See aiso 5.2.4). -
ENTITY approved equipment shall be installed in accordance with the manufacturer’s Intrinsic Safety Control Drawing.
-
The intrinsic Safety ENTITY concept allows the interconnection of two ENTITY Approved intrinsically safe devices with ENTITY parameters not specifically examined in combination as a system when:
Uo, Voc, or Vt < Ui or Vmax; lo, Isc, or tt $ ti or Imax; Ca or Co > Ci + Ccable, La or Lo > Li + Leable, Po < Pi.
Where two separate barrier channels are required, one dual-channel or two single-channel barriers may be used, where in either case, both channels have been Certified for use together with combined entity parameters that meet the above equations. -
System Entity Parameters:
RMA 800 Remote Meter: Vmax Voc or Uo, Imax tsc or bo;
RMA 800 Remote Meter: Ci + Ccable < Control Apparatus Ca,
RMA 800 Remote Meter: Li + Leable < Control Apparatus La. -
When the electrical parameters of the cable are unknowm, the following values may be used:
Capacitance: 197pF/m (60 pF /ft)
inductance: 0.66pH/m (0.020pH/f). -
Control equipment that is connected to Associated Equipment must not use or generate more than 250 V.
-
Associated equipment must be FM, CSA ATEX or IECEx (depending on location) listed. Associated equipment may be installed in a Class |, Division 2 or Zone 2 Hazardous (Classified) location if so approved.
-
Non-Galvanically isolated equipment (grounded Zener Barriers) must be connected to a suitable ground electrode per:
a. FM (USA): NFPA 70, Article 504 and 505. The resistance of the ground path must be less than 1.0 ohm.
b. CSA(Canada): Canadian Electrical Code (CEC), part |, section 10.
c ATEX: Requirements of EN 60079-14, 12.2.4.
d. 1ECEx Requirements of IEC 60079-14, 12.2.4. -
Intrinsically Safe DIVISION 1/ Zone 0 WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS.
-
Division 2/ Zone 2: WARNING: DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT.
-
NO REVISION OF THIS CONTROL DRAWING IS PERMITTED WITHOUT AUTHORIZATION FROM THE AGENCIES listed.
-
For release approvals see ECO-01035538.
This document provides descriptions and procedures
for the Quick Installation of Honeywell’s family of SmartLine Remote
Indicator.
The SmartLine Remote Indicator is a configurable intelligent field device
which functions as an output and status indicator for any HART and DE devices.
For full details refer to the manuals listed below for protocols, user
Interface (HMI) operation, Installation, configuration, calibration,
maintenance, parts, and safety and approvals etc. including options
Copyrights, Notices and
Trademarks.
Copyright 2022 by Honeywell
Revision 8, September 2022
Trademarks
SmartLine, RMA are U.S. registered
trademarks of Honeywell Inc.
HART® is Trademarks of
FieldComm Group™
Documentation
To access complete documentation, including language variants, scan the QR
code below using your smart phone/device or QR code scanner.
Go to the APP store for your free Smartphone QR scanner Or you can follow the
URL to access the online SmartLine HUB page.
The HUB page will contain direct links to open SmartLine product
documentation.
URL QR Code
https://hwll.co/SmartLineHUB
Sales and Service
For application assistance, current specifications, pricing, or name of the
nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC (TAC) hfs-tac-support@honeywell.com
Australia Honeywell Limited, Phone: +(61) 7-3846 1255, FAX: +(61) 7-3840 6481
Toll Free 1300-36-39-36, Toll Free Fax: 1300-36-04-70
China – PRC – Shanghai, Honeywell China Inc. Phone: (86-21) 5257-4568, Fax:
(86-21) 6237-2826
Singapore, Honeywell Pte Ltd. Phone: +(65) 6580 3278. Fax: +(65) 6445-3033
South Korea, Honeywell Korea Co Ltd. Phone:+(822)799 6114. Fax:+(822) 792 9015
EMEA, Phone: + 80012026455 or +44 (0)1202645583. FAX: +44 (0) 1344 655554
Email: (Sales) sc-cp-apps-salespa62@honeywell.com
or (TAC) hfs-tac-support@honeywell.com
AMERICAS, Honeywell Process Solutions, Phone:
1-800-423-9883,
or 1-215/641-3610. (TAC) hfs-tac-support@honeywell.com.
Sales 1-800-343-0228. Email: (Sales)
FP-Sales-Apps@honeywell.com
Knowledge Base search engine http://bit.ly/2N5Vldi
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective
materials and faulty workmanship. Contact your local sales office for warranty
information.
If warranted goods are returned to Honeywell during the period of coverage,
Honeywell will repair or replace without charge those items it finds
defective. The foregoing is Buyer’s sole remedy and is in lieu of all other
warranties, expressed or implied, including those of merchantability and
fitness for a particular purpose.
Specifications may change without notice. The information we supply is
believed to be accurate and reliable as of this printing. However, we assume
no responsibility for its use.
While we provide application assistance personally, through our literature and
the Honeywell web site, it is up to the customer to determine the suitability
of the product in the application.
For more information
To learn more about SmartLine Devices,
visit www.process.honeywell.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell 1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road
Shanghai, China 20061
www.process.honeywell.com
34-ST-25-63, Rev.8
September 2022
©2022 Honeywell International Inc.