bryant SYSTXBB4ZC01 Evolution Zone Control Instruction Manual
- June 17, 2024
- bryant
Table of Contents
- SYSTXBB4ZC01 Evolution Zone Contro
- SAFETY CONSIDERATIONS
- INTRODUCTION
- INSTALLATION AND START-UP OVERVIEW
- INSTALLATION
- EQUIPMENT WIRING DIAGRAMS:
- QUICK START
- INSTALL / SERVICE MENUS
- EQUIPMENT SUMMARY MENU
- SETUP MENU
- TROUBLESHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SYSTXBB4ZC01 Evolution Zone Contro
A04031
Installation and Start-Up Instructions
Evolution™ Zone Control
SYSTXBBUIZ01
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
SAFETY CONSIDERATIONS
Read and follow manufacturer instructions carefully. Follow all local
electrical codes during installation. All wiring must conform to local and
national electrical codes. Improper wiring or installation may damage the
Evolution™ Zone System. Recognize safety
information. This is the safety-alert symbol . When you see this symbol on the
equipment and in the instruction manual, be alert to the potential for
personal injury. Understand the signal words DANGER, WARNING, and CAUTION.
These words are used
with the safety-alert symbol. DANGER identifies the most serious hazards,
which will result in severe personal injury or death.
WARNING signifies a hazard, which could result in personal injury or
death. CAUTION is used to identify unsafe practices, which may result in minor
personal injury or product and property damage. NOTE is used to highlight
suggestions which may result in enhanced installation, reliability, or
operation.
INTRODUCTION
The Evolution Zone System consists of several intelligent communicating
components which includes the Evolution Zone Control (or User Interface),
Smart Sensors, Damper Control Module, variable- speed furnace or FE fan coil,
2-speed AC or HP, which continually communicate with each other via a four-
wire connection called the ABCD bus. Commands, operating conditions, and other
data are passed continually between components over the ABCD bus. The result
is a new level of comfort, versatility, and simplicity.
All furnaces or fan coils are variable-speed and multi stage for maximum
flexibility, efficiency, and comfort. They support controlled ventilation,
humidification, dehumidification, and air quality control. Either a dual
capacity (communicating), or a standard 24 vac controlled outdoor unit may be
used. When using conventional outdoor units, the variable-speed furnace or fan
coil provides the 24 volt signals needed to control them. Also, the Evolution™
Damper Control Module (P/N SYSTXBB4ZC01) allows connection of a conventional
HRV or ERV without the need for a separate wall control.
All system components are controlled through the wall mounted Evolution™ Zone
Control, which replaces the conventional thermostat and provides the homeowner
with a single wall control for all features of the system.
INSTALLATION AND START-UP OVERVIEW
This instruction covers installation of the Evolution™ Zone Control only.
Physical installation instructions for the indoor and outdoor equipment,
Damper Control Module, and accessories are provided with each unit.
Setup, commissioning, operation, and troubleshooting of the Evolution Zone
System is covered only in this installation instruction.
It is the guide to connecting the system components and commissioning the
system once all physical components are installed. Special screen prompts and
start-up capabilities are provided in the Evolution System to simplify and
automate the initial commissioning of the system.
- Install Evolution™ Zone Control according to this instruction.
- Install indoor unit, outdoor unit, and accessories according to their instructions.
- Wire complete system according to this instruction.
- Setup, commission, and operate system according to this instruction to assure a smooth and trouble free start-up.
INSTALLATION
A. Step 1 — Check Equipment and Job Site
INSPECT EQUIPMENT — File claim with shipping company, prior to
installation, if shipment is damaged or incomplete.
B. Step 2 — Evolution Zone Control™ Location and Wiring Considerations
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or possible
equipment damage.
Disconnect Power before routing control wiring.
All wiring must comply with national, local, and state codes. EVOLUTION™ ZONE
CONTROL LOCATION— The Evolu- tion Zone Control™ User Interface is the command
center for the Evolution Zone System and is typically located in Zone 1 to
sense and control temperature in this zone. It should be located where it is
easily accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following guidelines should be
followed:
The Evolution™ Zone Control and Room Sensors should be mounted:
- Approximately 5 feet (1.5 meters) from the floor.
- Close to or in a frequently used room, preferably on an inside partitioning wall.
- On a section of wall without pipes or ductwork. The Evolution™ Zone Control and Room Sensors should NOT be mounted:
- Close to a window, on an outside wall, or next to a door leading to the outside.
- Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature-radiating objects which could cause a false reading.
- Close to or in direct airflow from supply registers.
- In areas with poor air circulation, such as behind a door or in an alcove.
REMOTE ROOM SENSOR OPTION — A remote room sensor can be used with the
Evolution™ Zone Control to take the place of the User Interface internal
temperature sensor. This allows the Evolution™ Zone Control to be mounted in
areas with less than
optimal airflow (such as near an exterior door, window or in a closet). The
remote sensor can be wired to the terminal block connectors labeled S1 and S2
at the User Interface backplate, or the OS1 and OS1C connection at the Damper
Control Module. In either case, the Evolution Zone Control will automatically
detect the remote room sensor and ignore its internal temperature sensor.
It is also important to note the humidity sensor cannot be remotely located,
so do not locate the Evolution Zone Control in an area where humidity sensing
may not be accurate.
NOTE: S1 & S2 connection on UI backplate is now used for Remote Room
Sensor, NOT for OAT Sensor hookup.
In addition, the Remote Room Sensor is a temperature sensor only, having no
additional user inputs. This sensor is typically connected to the Damper
Control Module and used to sense and control temperature in each zone.
SMART SENSOR — Any zone may use a Smart Sensor. It provides a temperature
display and buttons to adjust the desired temperature in that zone only. It
also displays outdoor temperature and indoor humidity. If a Smart Sensor is
used in a zone, a Remote Room Sensor may also be used in the same zone. The
Remote Room Sensor has priority over the Smart Sensor.
WIRING CONSIDERATIONS — Ordinary thermostat wire is recommended. Use 22
AWG or larger for normal wiring applications. Continuous wire lengths over 100
ft. should use 20 AWG or larger.
NOTE: ABCD bus wiring only requires a four-wire connection; however, it
is good practice to run thermostat cable having more than four wires in the
event of a damaged or broken wire during installation.
Each communicating device in the Evolution Zone System has a four-pin
connector labeled ABCD. It is recommended that the following color code be
used when wiring each device:
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each ABCD connector
in the system MUST be wired consistently.
LOCATING DAMPER CONTROL MODULE — All wiring is run back to the Damper
Control Module. Select a location near the furnace or fan coil where wiring
from the User Interface, each Remote Room Sensor or Smart Sensor, each damper
actuator, and the equipment itself can come together easily.
The Damper Control Module is approved for indoor use only and should never be
installed with any of its components exposed to the elements. The Damper
Control Module (and zone dampers) may be installed in any area where the
temperature remains between -4°F. to 158° F. (-20°Cto70°C), and there is no
condensation. The cover must be installed to prevent damage from other
sources. Do not locate where it will be accessible to children.
It may be mounted in either vertical or horizontal position. Remember that
wiring access is likely the most important consideration.
CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper
operation.
To prevent possible damage to the Damper Control Module, DO NOT mount on
plenum, ductwork, or flush against furnace or fan coil.
MOUNTING EVOLUTION™ ZONE CONTROL — There are two options for mounting the
Evolution Zone Control™ to the wall. First, become familiar with all plastic
assembly pieces shown in Fig. 2 through 9. The User Interface will snap
together with either the Recess Mount or the Surface Mount backplate.
RECESS MOUNT — This provides the thinnest mounting configuration (See
Fig. 3). The backplate containing the recessed terminal block can be mounted
directly to the wall by cutting a hole 1 ½″ wide by 2 1/8″ high. Mark location
and cut hole in wall.
NOTE: Always ensure the Evolution Zone Control™ location is acceptable
before cutting any holes in wall.
SURFACE MOUNT — This provides surface mounting configuration, which
allows use of a small hole in the wall. A surface mount backplate is supplied
(See Fig. 4). Attach backplate as shown in Fig. 7, and the assembly will mount
directly to the wall requiring only a small hole in the wall allowing a four
wire connection to pass through.
NOTE: Once Evolution Zone Control™ is secured to wall with the backplate
assembly (snapped together), care must be taken not to bend or break the
interlocking tabs when removing. Gently remove Evolution Zone Control by
rocking up/down until inter-locking tabs release.
DECORATIVE BACKPLATE — Supplied is a thin decorative backplate (see Fig.
5), to hide any marks/screw holes left from the previous thermostat. This
decorative backplate (or beauty ring) can be used in either the recess or
surface mount installation by snapping it onto back of recessed mount
backplate or surface mount backplate before securing to wall. See Fig. 8 and 9
for a larger decorative backplate P/N SYSTXXOLBP01 (5.75″ wide X 6″ tall),
which can be ordered separately. C. Step 3 — Installing Evolution Zone
Control™
WARNING: ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing Evolution Zone Control™, turn off all power to equipment.
There may be more than one power source to disconnect.
-
Turn off all power to equipment.
-
If an existing User Interface or control is being replaced:
a. Remove existing control from wall.
b. Disconnect wires from existing control.
c. Discard or recycle old control.
NOTE: Mercury is a hazardous waste, if existing control contains any mercury, it MUST be disposed of properly. -
Select Evolution Zone Control™ mounting plastic (recess mount or surface mount and decorative backplate if desired).
-
Route wires through large hole in mounting plastic. Level rear plastic against wall (for aesthetic value only – Evolution Zone Control™ need not be level to operate properly) and mark wall through two mounting holes.
-
Drill two 3/16 inch mounting holes in wall where marked.
-
Secure mounting plastic to wall using two screws and anchors provided.
-
Adjust length and routing of each wire to reach each wire entry on the connector backplate. Strip ¼ inch of insulation from each wire.
-
Match and connect thermostat wires to proper terminals on User Interface backplate. See wiring diagram Fig. 12, 13, and 14.
A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but each ABCD connection in the system MUST be wired consistently.
A separate ABCD Connector comes inside packaging and should be used when connecting to furnace (or fan coil). Ensure connector is inserted properly into circuit board. (See Fig. 10) CAUTION: ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring of the ABCD connector will cause the Evolution Zone System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on power. -
Push any excess wire into the wall. Seal hole in wall to prevent any air leaks. Leaks can affect operation.
-
Attach Evolution Zone Control™ to the mounting plastic by lining up the plastic guides on the back of the control with the opening on the mounting plastic and push on.
-
Perform installation of all other system equipment (i.e. zone sensors, dampers, humidifier, ventilator, UV lights, etc.)
-
Turn on power to equipment.
EQUIPMENT WIRING DIAGRAMS:
See wiring diagrams Fig. 12, 13, and 14 for connecting the Evolution Zone
Control and Smart Sensors to the Damper Control Module. More information
regarding Damper Control set-up and wiring can be found in Damper Control
Module Installation Instructions.
See wiring diagram Fig. 12 which includes a variable-speed indoor
communicating furnace or FE fan coil, with a 2-speed Puron™ communicating
outdoor unit. No additional OAT (outdoor air temperature) sensor is required
because the Evolution Zone Control will use the temperature sensor inside the
2-speed unit.
See wiring diagram Fig. 13 for connecting a variable-speed indoor
communicating furnace or FE fan coil with a 1-speed air conditioning unit
(non-communicating outdoor). An Outdoor Air Temperature (OAT) sensor may be
installed (but is not required) at the indoor furnace or fan coil OAT
terminals. When OAT sensor is applied, the Evolution System will provide
enhanced system features and benefits.
See wiring diagram Fig. 14 for connecting an FE fan coil with a 1-speed heat
pump (non-communicating outdoor unit). When OAT is applied, the Evolution
system will provide enhanced system features and benefits.
NOTE: For other applications not listed, refer to the Network Interface
Module (NIM) Installation Instructions. HUMIDIFIER CONNECTION — A 24vac bypass
or fan powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Evolution™ Zone Control
operate humidifier.
Bypass Humidifiers — A bypass humidifier should be wired directly to the
furnace or fan coil HUM and 24vac COM terminals.
The Evolution Zone Control will automatically energize the HUM output during a
call for humidification.
Fan Powered Humidifiers — Most fan powered humidifiers produce internal
24vac in order to energize upon a switch or contact closure. For this
application, a 24vac N.O. Isolation Relay (DPST) MUST be used to prevent
mixing the internal humidifier power with the indoor equipment transformer.
Applying 24vac isolation relay coil to furnace or fan coil HUM and COM
terminals will allow the Evolution Zone Control to automatically energize the
HUM output during a call for humidification. The N.O. relay contacts will be
used to energize the humidifier. See fan powered
humidifier installation instructions for more details.
WARNING: FIRE OR EQUIPMENT HAZARD
Failure to follow this warning could result in equipment damage or fire.
Do not apply 24vac fan powered humidifier (with internal power supply) direct
to indoor unit HUM and COM terminals.
INITIAL POWER-UP
NOTE: Refer to Functional Overview (Fig. 11) to become familiar with key
function buttons such as ″System On/Off″, ″Zone″, ″Fan″, ″Left-Side″ and
″Right-Side″ buttons, etc. These function buttons will be used frequently
during setup.
A. Section 1 — Power Up Sequence This section addresses initial power up
(or commissioning) of a new Evolution Zone Control™. The User Interface will
communicate and identify all Evolution components in the system. The following
is a typical example for a communicating VariableSpeed Furnace / Fan Coil with
a 2-spd. Air Conditioner / Heat Pump (including Dual Fuel).
The User Interface display will light up and indicate that it is now
″ESTABLISHING COMMUNICATIONS WITH EQUIPMENT PLEASE WAIT″. The User Interface
will automatically continue by ″SEARCHING FOR INDOOR EQUIPMENT″, followed by
″SEARCHING FOR OUTDOOR EQUIPMENT″ (See Fig. 15). Once the indoor and outdoor
equipment has been found, the Installer will be asked to select Accessories.
Proceed to Section 4. Selecting Accessories.
NOTE: If the variable-speed indoor equipment (furnace or fan coil) cannot
be found, the User Interface will display ″CANNOT COMMUNICATE WITH INDOOR
UNIT″. This MUST be corrected before the initial power up sequence can
continue. If indoor unit is found, but outdoor unit is not found, ″OUTDOOR
UNIT NOT IDENTIFIED″ will appear. Proceed to the next section for Outdoor Unit
Identification.
B. Section 2 — Selecting Outdoor Unit If there is no communicating
outdoor unit, the screen, shown in Fig. 16, will appear. Press either Time or
Temp +/- buttons toselect AC (air conditioner), HP (heat pump), or None (no
unit installed). Press right-side button to continue to next screen.
If either AC or HP has been selected as the outdoor unit type, the middle
screen will appear (See Fig. 16). Press either Time or Temp +/- buttons to
select appropriate Btu size of outdoor unit, then press right side button to
continue. If a NIM (Network Interface Module) is applied for non-communicating
two-speed outdoor equipment, select 1 or 2-speed compressor operation , and
press right-side button to continue.
NOTE: Range of outdoor unit Btu selection is limited by model number of
indoor unit installed. The Evolution Zone Control™ will not allow an outdoor
unit size that is not supported by the installed indoor unit.
NOTE: On new system installations, the model and serial number will be
recognized and displayed. On any indoor/outdoor board replacements, the
equipment will be recognized but the exact model/serial number will not be
displayed.
C. Section 3 — Selecting Electric Heater If indoor unit is a fan coil and
the electric heater is not self-identifying, ″ELECTRIC HEATER NOT IDENTIFIED″
will appear (See Fig. 17). Press either Time or Temp +/- buttons to select
appropriate size of electric heater installed, then press right-side button to
continue.
NOTE: Range of electric heaters available is limited by model number of
the fan coil installed. The Evolution Zone Control™ will not allow an electric
heater size that is not supported by the installed fan coil.
D. Section 4 — Selecting Accessories
Once the indoor and outdoor equipment have been found or entered, the
following screens will appear allowing the Installer to select the AIR FILTER
TYPE; HUMIDIFIER INSTALLED; and UV LIGHTS INSTALLED″ (See Fig. 18). Use either
Time or Temp +/- buttons to make appropriate selections in the highlighted
area on the display screen. Press right-side button to continue (or advance)
to the next screen.
AIR FILTER TYPE— This accessory screen will appear first. The installer
will need to enter the type of filter (MEDIA, EAC, or both). See Table 1 and
make a selection using Time or Temp +/button, then press right-side button to
continue.
Table 1 — Filter Selection
INSTALLED FILTER | MENU SELECTION |
---|---|
1 Inch to 4 inch media | MEDIA |
High voltage EAC | EAC |
High voltage EAC+1to4inch media | MEDIA + EAC |
HUMIDIFIER INSTALLED — This will appear after the Air Filter Type screen.
Select whether a humidifier is installed on the system, YES or NO, then press
right-side button to continue.
UV LIGHTS INSTALLED— This screen will appear to select whether UV lights
are installed on the system, select YES or NO, then press right-side button to
continue. E. Section 5 — Zoning SEARCHING FOR ZONE EQUIPMENT will
appear on the screen to identify the number of zones detected. This screen
will show Zone 1, Zone 2, etc. and indicate all zones having either a remote
room sensor, or smart sensors associated with them. If the
system contains smart sensors, they must be assigned a zone number before
continuing. See Smart Sensor Installation Instructions on how to assign Smart
Sensors to their respective zones.
When finished, press right-side button to continue. See Fig. 18a.
F. Section 6 — Equipment Summary The ″EQUIPMENT SUMMARY″ screen will
appear after Accessories and Zoning have been selected. This screen will give
a summary of all equipment automatically found or manually selected. If a
wrong selection was made, press left-side button (BACK selection) to go back
to that particular screen and make changes. When everything is OK, press
right-side button again to continue. (See Fig. 19)
The ″SETUP COMPLETE! SAVE ALL SELECTIONS?″ screen will appear after Equipment
Summary. To Save All Selections press (YES) right-side button. Pressing the
left-side button (NO selection) will return to the Equipment Summary screen
where changes can be performed to any of the equipment selection screens.
After selecting YES, the initial power up sequence of the new Evolution Zone™
Control is complete. The User Interface screen will now display normal
operating mode.
G. Section 7 — Duct Assessment
The following screen will appear after Setup is exited. Press right-side
button to start Duct Assessment. Duct Assessment will measure the relative
size of the ductwork, including damper leakage. These measurements are used to
control the correct amount of airflow in the zoned system. Status messages
will appear on the screen to indicate what the system is doing. The process
will take approximately one minute per zone. At the end of the process, the
display will show the relative size of each zone duct. See Fig. 19a.
QUICK START
For first time installers, Quick Start will allow a quick start up of the
Evolution Zone System before learning all the details of system operation.
However, for the best possible comfort and operation refer to the Evolution
Zone Control™ Owner’s Manual.
A. Set Day, Time & Desired Humidity
- Flip down the door at the base of the Evolution Zone Control™ and press the BASIC button.
- Adjust the highlighted HOUR setting using the TIME (+/−) button.
- Press SCROLL button (down) to highlight MINUTE.
- Adjust the MINUTE setting using the TIME (+/−) button.
- Press SCROLL button (down) to highlight DAY.
- Adjust the current DAY setting using the TIME (+/−) button.
- Press SCROLL button (down) to highlight HUMIDITY.
- Press the red HEAT button to select heating humidity.
- Adjust desired heating humidity level using either (+/−) button.
- Press the blue COOL button to select cooling humidity.
- Adjust the desired cooling humidity level using either(+/−)button.
- To exit press BASIC button or close door.
- If changes are made, you will be asked to ″SAVE CHANGES? YES/NO″.
B. Override Heating Schedule
-
Press the red HEAT button. Heating mode is confirmed when the red LED next to the red HEAT button is lit.
-
Use the TEMP (+/−) button to select your desired heating temperature.
-
The default time for temporarily overriding the temperature schedule is 2:00 HRS as indicated by the text on the lower left.
NOTE: Override time will not appear if programming has been turned off. -
You can change the temporary override time in 15-minute increments by pressing the TIME (+/−) button until the desired override time is selected, or press the HOLD button anytime to override the schedule indefinitely.
C. Override Cooling Schedule
-
Press the blue COOL button. Cooling mode is confirmed when the blue LED next to the COOL button is lit.
-
Use the TEMP (+/−) button to select your desired cooling temperature.
-
The default time for temporarily overriding the temperature schedule is 2:00 HRS as indicated by the text on the lower left.
NOTE: Override time will not appear if programming has been turned off. -
You can change the temporary override time in 15-minute increments by pressing the TIME (+/−) button until the desired override time is selected, or press the HOLD button anytime to override the schedule indefinitely.
D. Quick Program Schedule for All Days
This section will give you a quick program schedule for ALL- DAYS of the week.
For more information on how to create customized schedules for every day, the
entire week, or weekend, refer to the Owner’s Manual.
- Flip down the door at the bottom of the control.
- Press the SCHEDULE button, which allows you to create one schedule for the entire home.
- Press either the LEFT or RIGHT side button repeatedly (if necessary) until ″ALLDAYS″ is displayed. The WAKE time period will be highlighted.
- Using the TIME (+/−) button, set the start time for this time period.
- Press the red HEAT button. Heating temperature will begin flashing.
- Set the heating temperature using the TEMP (+/−) button.
- Press the blue COOL button. Cooling temperature will begin flashing.
- Set the cooling temperature using the TEMP (+/−) button.
- Set the remaining periods by using the SCROLL button to select ″DAY,″″EVENING,″ and ″SLEEP″.
- To copy a zone, use SCROLL button to select ″COPY″. Select YES and copy this zone schedule to other zones using NO or YES
- Exit the scheduling mode by either closing the door or pressing the SCHEDULE button.
- If changes are made, you will be asked to ″SAVE CHANGES YES/NO″
INSTALL / SERVICE MENUS
The ″INSTALL / SERVICE″ menus contain a set of vital information. This
information enables the Installer or Service person to view a summary of what
has been installed, etc. This information is notcovered in the Owner’s Manual.
To enter INSTALL / SERVICE menus, press and hold the ADVANCED button for at
least ten seconds. The following menu will appear (See Fig. 20):
NOTE: The INSTALL / SERVICE menu will automatically exit after 60 minutes
of no push button activity.
EQUIPMENT SUMMARY: Shows all equipment recognized by and attached to the
system.
INSTALL: Used when adding, changing out, or uninstalling equipment.
SETUP: Used to view or modify equipment settings.
CHECKOUT: Allows testing of equipment operation
SERVICE: Used to view operation and fault history of equipment and enter
dealer name/phone number for display.
EQUIPMENT SUMMARY MENU
An example screen is shown in Fig. 21:
This screen shows indoor unit type and model number, outdoor unit type (and
model number if a 2-speed unit), filter type, any accessories that are
installed, and how many zones are recognized.
INSTALL MENU This menu item will perform start-up process in order to
learn all equipment in system. Press right side button to initiate the
process. See Fig. 22.
SETUP MENU
This menu has several layers, allowing modification of equipment settings. No
settings will need to be made at equipment (i.e. DIP switches on a furnace).
All configuration settings made effective from this menu will override
equipment configuration made by dip switches. Fig. 23 shows all the
information that can be found in the SETUP menu. Setup = THERMOSTAT:
AUTO MODE SETUP:
- Enable/Disable Auto Changeover mode (default=Enable).
- Auto Changeover Time may be adjusted 5 to 120 minutes, (default = 30 minutes).
When Auto mode is enabled (factory default) a change from heat to cool (or
vice versa) will not occur until an opposite mode demand has existed for 30
minutes. If the set point is changed, the 30 minute timer is deleted.
HEAT/COOL DEADBAND:
- 0 to 6 degrees, (default = 2°).
A minimum difference of 2° is enforced between heating and cooling desired
temperatures. This will allow one setting to ″push″ the other to maintain this
difference.
OFFSETS: This option allows calibration (or deliberate miscalibration) of
the temperature and humidity sensors. These offsets are added to the actual
temperature/humidity values (defaults = 0).
- Zone 1 Offset: -5 to +5 degrees.
- Outside Temp Offset: -5 to +5 degrees.
- Humidity Offset: -10 to +10 percent.
CYCLES PER HOUR:
- Maximum cycles per hour = 4 (default) or 6.
- Anticipator=1to9(default=3). This adjusts sensitivity to zone temperature changes. 1 = most sensitive, 9 = least sensitive.
PROGRAMMING:
- On or Off (default=On)
- Periods Per Day=2or4(default=4)
- Programmable Fan On/Off (default=Off). If ON is selected, fan can be set to Auto, Low, Med, or High independently in each zone.
SMART RECOVERY:
- On or Off, (default=On)
Applies to programmable operation only. Will start recovery 90 minutes prior
to schedule change in both heating and cooling mode.
ENGLISH/METRIC DISPLAY:
- For°C, (default = °F)
RESET FACTORY DEFAULTS:
Program Schedule:
- Yes/No to reset back to Energy Star default Time and Temp schedules.
User Settings:
- Yes/No to reset the user settings in the Advanced Setup to factory default settings.
Install Settings:
- Yes/No to reset install settings in Install/Service menus to factory default settings.
Last 10 Faults:
- Yes/No to reset last 10 faults under Service Info menu.
Setup = FURNACE:
Upon a first time start-up of the Evolution Zone Control™, the furnace DIP
switch settings will be copied to the furnace setup menu. Any changes can then
be made from the Evolution Zone Control™.
AIRFLOW:
- COMFORT (default)
- EFFICIENCY
Selects the airflow of the furnace when heating. EFFICIENCY is the airflow
used to meet specified ratings, COMFORT is a decreased airflow used to
increase the output air temperature and provide increased comfort.
AC AIRFLOW:
- EFFICIENCY
- COMFORT (default)
- MAXIMUM
Selects the airflow of the furnace when cooling. COMFORT is a decreased
airflow used to improve humidity control. EFFICIENCY is the airflow used to
meet specified ratings. MAXIMUM is a fixed airflow of 400 CFM/ton based on the
outdoor unit size.
DEHUM AIRFLOW:
- NORMAL (default)
- HIGH
NORMAL airflow adjustment is used during dehumidifying. If duct sweating
is an issue, selecting HIGH will increase the dehumidifying airflow and reduce
the sweating.
LOW HEAT RISE:
- ON
- OFF (default)
- Set this to ON if the system contains a bypass humidifier. The ON setting will increase the furnace low heat airflow.
STAGING:
- SYSTEM (default)
- LOW
- HIGH
Controls the staging of the furnace. SYSTEM setting will allow the Evolution
Zone Control™ to determine furnace staging. LOW will only run the low stage of
furnace heat. HIGH will only run the high stage of furnace heat.
OFF DELAY:
- 90 seconds
- 120 seconds (default)
- 150 seconds
- 180 seconds
- Amount of time the blower will continue to run after heating has shut off.
LOCKOUT TEMP:
- NONE (default)
- +5 to 55 deg F
Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.
Setup = FAN COIL:
HP/AC AIRFLOW:
- EFFICIENCY
- COMFORT (default)
- MAXIMUM
Selects the airflow of the fan coil when heating or cooling with a heat pump
(or cooling with an AC unit). COMFORT is a decreased airflow used to improve
humidity control. EFFICIENCY is the airflow used to meet specified ratings.
MAXIMUM is a fixed airflow speed of 400 CFM/ton based on the outdoor unit
size.
DEHUM AIRFLOW:
- NORMAL (default)
- HIGH
Normal airflow adjustment used during dehumidifying. If duct sweating is an
issue, selecting HIGH will increase the dehumidifying airflow speed and reduce
the sweating.
HEATER SIZE:
(choices dependent upon fan coil model)
This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model number of the
fan coil). If the electric heater is self-identifying, this value is not
shown.
Setup = HEAT PUMP / AC:
- COOLING LOCKOUT:
- NONE (default)
- 45° F.
- 50° F.
- 55° F.
Outside temperature below which cooling will not be provided.
ENTERED SIZE:
- (dependent on indoor unit model)
Size of the outdoor unit entered during the start-up process. If the outdoor
unit is a communicating model, this value will not be shown. This size can be
changed here but is limited to sizes that the indoor unit can handle.
DEFROST INTERVAL:
- 30 minutes
- 60 minutes
- 90 minutes
- 120 minutes (default)
Time interval at which defrost cycles can occur on a heat pump.
ELECT HEAT LOCKOUT / LOCKOUT TEMP:
- NONE (default)
- +5 to 55 deg. F
Outside temperature above which the electric heat will not operate. In dual
fuel applications, heat pump will not operate below selected temperature.
HIGH COOL LATCH:
- NONE (default)
- 80 – 110 deg F
Outside temperature above which only the high speed (of a 2-speed outdoor
unit) will run when cooling.
Setup = ZONING
DISABLE ZONING
- No (default)
- Yes
If Yes is selected, zoning is disabled and all dampers open. The system will
run unzoned using the Zone 1 sensor.
ZONE OFFSETS:
- Zone Temperature Offsets (defaults = 0) Range -5° to +5°
This option allows actual temperature offset for each zone, allowing
calibration (or deliberate mis-calibration) of each sensor.
AIRFLOW LIMITS:
- Low
- Medium
- High (default)
- Maximum
Zone airflow limit, which is selectable for each zone. Low, Medium, and High
allows a relative noise/airflow relationship in a zone (i.e. comfort vs.
noise). Maximum allows unlimited noise/airflow (i.e. maximum airflow allowed).
Setup = ACCESSORIES
FILTER TYPE:
- MEDIA (i.e. TrueSense™)
- EAC
- MEDIA+EAC (i.e. TrueSense™)
CLEAN INTERVAL : 30 to 180 days (of actual blower operation).
(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies to EAC
filter selection only.
HUMIDIFIER INSTALLED:
- NO
- YES
If YES, indicates to the system whether a humidifier is installed and enables
humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months of humidifier operation (default=6
months)
Interval at which the Change Humidify Pad notification will be displayed.
HUMIDIFY WITH FAN:
- NO (default)
- YES
If YES, the humidifier will run with Continuous Fan operation if there is a
humidify demand.
VENTILATOR:
NOTE: Only appears if ventilator is installed.
CLEAN INTERVAL:
- 60 to 180 days of actual operation (default=90)
Interval at which the Clean Ventilator Pre-filter notification will turn on.
UV LIGHTS INSTALLED:
- NO
- YES
If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:
- 6 to 48 months operation time (default=12 months)
Interval at which the Change UV Lights notification will be displayed.
Setup = SYSTEM MAINTENANCE
REMIND OWNER OF ROUTINE MAINTENANCE EVERY:
This setup is used to adjust the timer interval in which the normal System
Maintenance notification is turned on for the homeowner.
- Range= OFF, 6 to 24 months, (default=12 months)
CHECKOUT MENUS
The Checkout menu will show the equipment installed in the system. A sample
checkout menu is shown in Fig. 24. Checkout = FURNACE
Make sure the furnace is properly installed before continuing.
- LOW HEAT RUNTIME: 5 min.
- HIGH HEAT RUNTIME: 5 min.
This menu item allows the furnace to be exercised. First, a low heat runtime
and high heat runtime are selected. Range=5-120 min.
If only the low heat is to be exercised:
The furnace will execute its ignition start-up sequence. This sequence will be
displayed on the Evolution Zone Control screen.
After the gas valve and blower motor turn on, the screen will automatically
change to ″FURNACE CHECK″ and show the current operating status of the
furnace.
Checkout = FAN COIL
ELECTRIC HEAT CHECK
- ELECTRIC HEAT RUNTIME: 5 min., Default time = 5 min., Range=0-120min.
If you have a fan coil with electric heaters, this menu item will allow the
heaters to be exercised.
With self-identifying electric heaters, three stages of electric heat are
available to be exercised in any combination. Non-identifying heaters will
only provide one stage of heat.
Enter the run time (in minutes) of each stage of heat to be exercised then
press START (right-side button). The display will change to show the fan
coil’s operating status.
Checkout = HEAT PUMP HEATING
- HIGH HEAT RUNTIME: 5 min.
- LOW HEAT RUNTIME: 5 min.
- DEFROST: NO
The heat pump heating mode can be exercised with this menu option. With a
2-speed heat pump, a low heat runtime and a high heat runtime are
independently selectable to exercise. A defrost cycle is also selectable.
Default time = Fixed 5 min. minimum, range=5-120min.
Checkout = HEAT PUMP COOLING OR AC COOLING
- HIGH COOL RUNTIME: 5 min.
- LOW COOL RUNTIME: 5 min.
The heat pump cooling mode (or AC cooling mode) can be exercised with this
menu option. With a 2-speed heat pump or AC unit, a low cool runtime and a
high cool runtime are independently selectable to exercise. The display will
change to show the heat pump or AC operating status.
Default time = Fixed 5 min.
minimum, range=5-120min.
Checkout = HUMIDIFIER
- OFF
- ON
The humidifier can be exercised On and Off with this menu option.
Checkout = VENTILATOR
SPEED:
- OFF
- LOW
- HIGH
The ventilator can be exercised through all of its operating speeds
with this menu option.
Checkout = ZONING
DUCT ASSESSMENT
This is the same Duct Assessment that runs on first start-up.
Measures duct capacity for each zone. The Duct Assessment will perform an
airflow measurement on each zone and determine the relative size of each zone
along with damper leakage. This assessment will require approximately 1 minute
for each zone in the system.
NOTE: A Duct Assessment will automatically occur every 24 hours at 1:00
p.m. to check system static and calibrate dampers.
SENSOR DAMPER CHECK:
The Sensor/Damper Check allows the installer to check each zone damper for
operation, as well as insure the zone sensor corresponds to that particular
zone.
When first initiated, the Zone 1 damper will fully OPEN, and all other zones
will CLOSE. Using the scroll button, the installer can select each zone and
verify the damper is fully open while all other dampers remain closed.
After proper damper operation has been verified, the installer can now check
and verify that each remote room sensor corresponds to the proper zone damper
in the same zone. Start from the top and highlight zone 1 to open damper.
Temporarily disconnect any
other zone remote room sensor (at sensor location). That zone damper will now
OPEN, while the Zone 1 damper will close.
EXAMPLE: If the Zone 2 remote room sensor is disconnected, the Zone 2
damper will now open as indicated on the User Interface display. The word
″FAIL″ will also be displayed instead of the actual temperature for Zone 2.
Reconnect Zone 2 sensor and try all remaining sensors one at a time in the
system. Smart Sensors may also be checked, see Smart Sensor Installation
Instructions for procedure.
AIRFLOW LIMITS:
- Low
- Medium
- High (default)
- Maximum
Because there is no bypass damper, the Zone Airflow Limit check will allow the
installer to assess the airflow noise generated by the system providing the
maximum amount of airflow to each zone. Select 9 ZONE, then select AIRFLOW
LIMIT: Low, Medium, High (default), or Maximum. When Start is pressed (right
side button), the selected zone’s damper will fully open, all others will
close, and the indoor unit will provide the maximum airflow for that zone (as
selected in Setup = ZONING, Airflow Limits). If the airflow noise is
objectionable, the installer can select a lower airflow noise limit. If the
noise is not objectionable, the installer should leave High selected, or even
Maximum.
NOTE: Selecting a lower airflow noise limit may decrease the homeowner’s
comfort in that zone.
SERVICE MENUS
The Service Info menu will only show the equipment installed in the system.
Below is a sample using a furnace and a heat pump (dual fuel). A sample
service menu is shown in Fig. 25. Service = FURNACE STATUS
The Status screens will show all of the current operating parameters of each
installed piece of equipment.
HEAT STAGE:
- OFF, LOW, HIGH
Displays stage of heat that the furnace is currently delivering.
AIRFLOW CFM:
- (furnace model dependent)
Cubic Feet per Minute of air the blower is currently delivering.
LEAVING AIR TEMP:
This sensor is NOT required. However, if LAT sensor is connected to the Damper
Control Module, the sensor will read leaving air temperature of the furnace.
COIL TEMP:
This sensor is NOT required. However, if HPT sensor is connected to the Damper
Control Module, the sensor will read temperature at that location (i.e. if
placed in return-air, will read return-air temperature).
INDUCER RPM (90% furnaces only):
- Inducer motor RPM value.
BLOWER RPM:
- Blower motor RPM value.
STATIC PRESS:
- Inches of water. Displays static pressure that the furnace is currently experiencing.
LOCKOUT TIMER:
- Seconds
If a lockout timer is active, this will show the current time value. See
furnace manual for details on lockout timers.
Service = FAN COIL STATUS
ELECTRIC HEAT:
- OFF, LOW, MED, HIGH
Displays stages of electric heat that the fan coil is currently delivering.
AIRFLOW CFM:
- (fan coil model number dependent)
Cubic Feet per Minute of air the blower is currently delivering.
LEAVING AIR TEMP:
This sensor is NOT required. However, if LAT sensor is connected to the Damper
Control Module, the sensor will read leaving air temperature of the fan coil.
COIL TEMP:
This sensor is NOT required. However, if HPT sensor is connected to the Damper
Control Module, the sensor will read temperature at that location (i.e. if
placed down stream from evaporator coil, and before electric heat, will read
coil leaving air temperature).
BLOWER RPM:
- Blower motor RPM value
STATIC PRESS:
- Inches of water
Displays static pressure that the fan coil is currently experiencing.
Service = HEAT PUMP / AC STATUS
STAGE: (HEAT / COOL):
- OFF, LOW, HIGH
Displays stage of heating or cooling that the Heat Pump/AC is delivering.
DEFROST:
- NO, YES
Displays status of defrost mode if heat pump.
AIRFLOW CFM:
- Indoor unit CFM measurement.
LEAVING AIR TEMP:
This sensor is NOT required. However, if LAT sensor is connected to the Damper
Control Module, sensor will read leaving air temperature of the indoor unit.
COIL TEMP (outdoor unit):
- Degrees F.
Temperature of the outdoor unit coil (only available on 2-speed communicating
outdoor units).
BLOWER RPM:
- RPM feedback from indoor motor.
STATIC PRESS:
- Static pressure of indoor unit.
Service = ZONING STATUS
ZONE STATUS:
This screen will show each zone in the system with the corresponding damper
position (POS), and CFM being delivered to each zone. Damper position range
from 0 to 15 (0=closed, 15=open).
Service = LAST 10 SYSTEM FAULTS
This screen will show last 10 faults that occurred throughout the system. Each
fault has the time and date incident recorded. Service technician should enter
current date in ″TODAY’S DATE″ menu section BEFORE checking and logging the
last 10 system faults.
Each fault has a two-letter acronym preceding the fault name to identify which
piece of equipment generated the fault. This fault history can be cleared
under Thermostat Setup, Reset Factory Defaults.
- HP = heat pump
- AC = air conditioner
- FN = furnace
- FC = fan coil
- ZO = zoning
Service = RUN / FAULT HISTORY
The indoor unit and outdoor unit (if communicating) have the following
histories:
NOTE: For Critical Fault Screens, see Troubleshooting section in this
document.
Resettable Faults:
- Fault counters for each piece of equipment that can be reset.
Cycle Counters:
- Number of heat/cool/power cycles the unit has performed.
Run Times:
- Lifetime hours of operation in heating, cooling, and how long the unit has been powered.
Service = TODAY’S DATE
- This menu item allows the installer to enter the current date. It is used for time/date stamping of system faults. This should be entered every time prior to viewing ″LAST 10 SYSTEM FAULTS″ section.
Service = MODEL / SERIAL NUMBERS
- This menu item allows the installer to view the model number and serial number (if available) of all communicating pieces of equipment in the system.
Service = SERVICE PHONE NUMBER
This menu item allows the installer to enter a name and phone number that the
homeowner can call for future service of the system. This name and phone
number will appear to the homeowner whenever a service reminder pop-up message
is displayed (i.e. Change Filter, etc.)
To edit:
- Use Temp +/- button to move cursor left and right.
- Use Time +/- button to select numbers and letters.
- Use Scroll button to move up and down between NAME and NUMBER.
OPERATIONAL INFORMATION
Zone Selection:
- Press top left ZONE button to select zones.
Continuous Fan Operation
Pressing FAN button will scroll through the following:
- AUTO = No fan operation except during equipment operation.
- LOW = Approximately 50% of High Speed operation.
- MED = Half way between High and Low speed operation.
- HIGH = Highest of either High Heating or High Cooling CFM.
Five-Minute Compressor Timeguard
This timer prevents compressor from starting unless it has been off for at
least 5 minutes. It can be defeated by simultaneously pressing the Fan and
Temp + buttons.
Emergency Heat (for heat pump applications)
To activate Emergency Heat, you must press and hold the HEAT button for 3
seconds to activate.
Keypad Lockout
Keypad can be locked by pressing ″Fan″ and ″Zone″ buttons at the same time for
3 seconds. When keys are locked, a lock symbol will appear in the upper left
corner of screen. Follow same procedure to unlock keypad.
Heat and Cool LED
The Heat and Cool LEDs will pulsate during actual equipment operation.
Equipment Cycle Timer (adjustable 4-6 cycles per hour)
This timer prevents the start of a heating or cooling cycle until 15 (or 10)
minutes after the last start of the same cycle. Its function is to assure that
the equipment is not cycled more than the selected times per hour. This timer
is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature is manually
changed. It can also be defeated for one cycle by simultaneously pressing the
Fan and Temp + buttons.
Ten-Minute Staging Timer
In multistage heating or cooling, this timer prevents any higher stage from
turning on until the preceding stage has been on for 10 minutes. This timer is
defeated if temperature error is greater than 5°F (usually due to a large
change in desired temperature).
Three-Minute Minimum On Time
In normal operation, when a stage turns on, it will remain on for a minimum of
three minutes. If the set point is changed, this timer is automatically
cancelled, allowing the equipment to turn off immediately when the demand is
removed.
Heat/Cool Set points (Desired Temperatures)
A minimum difference of 2° (default) is enforced between heating and cooling
desired temperatures. This is done by allowing one setting to ″push″ the other
to maintain this difference. This difference is adjustable via the
Install/Service menu under Thermostat
Setup.
Auto Changeover
When Auto mode is enabled (factory default) a change from heat to cool (or
vice versa) will not occur until an opposite mode demand has existed for 30
minutes. If the set point is changed, the 30-minute requirement is defeated.
This Auto Changeover time is adjustable via the Install/Service menu under
Thermostat Setup.
Range=5-120min.
Smart Recovery
With Smart Recovery selected (factory default), transition out of setback
begins 1.5 hours before selected recovery time and gradually adjusts room
temperature so desired temperature will be achieved at selected recovery time.
It operates in both heating and cooling. This only applies to programmable
operation.
Media Filter
If MEDIA or MEDIA+EAC is installed in the indoor unit, the system will perform
a static pressure check of the system every 24 hours at 1:00PM to monitor
filter accumulation (TrueSense™ Dirty Filter Detection) or whenever power is
applied to the system or the system is transitioned from Off to Cool or Heat
modes. The blower will run at a medium airflow for one minute.
Unoccupied
Pressing the HOLD button for 3 sec. will set the selected zone to unoccupied
status.
All Zones
Pressing the zone button for 3 sec. will gray out the entire display and put
the User Interface into All Zones mode (indicated by All Zones in upper left
of the display). Any changes to set temperature, fan, or Hold status will
occur in all zones when the screen is exited. Press the Zone button to exit
All Zones mode.
TROUBLESHOOTING
Evolution Zone Control™ does not power up.
- Recheck wiring to ABCD on all devices.
- Make sure all colors match for every terminal.
- Make sure power is applied to the indoor unit, and the amber LED is lit on indoor control circuit board.
- Check for 24VAC between the C and D terminals at Evolution Zone Control™ terminal connector and Damper Control Module.
- Check fuse on indoor unit’s circuit board.
Display says ″Indoor Unit Not Found″
- Recheck wiring to ABCD on all devices.
- Make sure all colors match for every terminal.
- Press left-side button to try again.
- If display still reads ″Indoor Unit Not Found″, disconnect all devices from ABCD and connect User Interface directly to indoor unit.
Display says ″Outdoor Unit Not Found″, and I have a two-speed communicating outdoor unit:
- Recheck wiring to ABCD connector on outdoor unit.
- Make sure all colors match for every terminal.
- Check for 24VAC between the C and D terminal connector of outdoor unit.
I made a mistake on the start-up screens, and hit the right-side button to get to the run mode. How do I get back to start-up?
- Press the ADVANCED button for at least 10 seconds.
- Install/Service menu will appear.
- Scroll down to the INSTALL selection.
- Press the right-side button; the screen will prompt you to press the right side again to re-install the system.
Control does not see zones 5 through 8.
- Make sure zone module5-8hastheDIPswitches set to the right.
- Recheck wiring to the ABCD connectors.
Control says I have zones5-8butnot1-4.
- Make sure zone module1-4hastheDIPswitches set to the left.
- Recheck wiring to the ABCD connectors.
Some zones in my zoned system do not provide enough comfort. (A noticeable difference exists between the actual room temperature and operating set point, yet the equipment does not turn on).
- The zone airflow limit may be set too low. Perform the Zone Airflow Limit Checkout procedure, raise airflow limit setting, if possible.
Some zones provide too much airflow and are noisy.
- The zone airflow limit may be set too high. Perform the Zone Airflow Limit Checkout procedure, lower airflow limit setting if possible.
CRITICAL MALFUNCTION SCREEN
The following errors will cause a Critical Malfunction screen to pop up. Heat
and Cool LEDs will alternately flash at a 1 second rate. This appears when
system cannot deliver any conditioning at all.
FAN COIL
Code 16 = Communication Fault Code 44 – Blower Communication Fault
Code 41 – Blower Motor Fault
FURNACE
Code 15 – Blower Motor Lockout
Code 22 – Abnormal Flame Proving Signal (not dual fuel)
Code 41 – Blower Motor Fault
USER INTERFACE
No communication with indoor unit
SYSTEM MALFUNCTION SCREEN
This screen appears when system cannot completely deliver conditioning. The
following errors will cause a System Malfunction Screen to pop up: FAN
COIL
Code 37 – Heater output sensed ON when not energized
FURNACE
Code 13 – Limit Circuit Lockout
Code 14 – Ignition Lockout
Code 21 – Gas Heating Lockout
Code 22 – Abnormal Flame Proving Signal (dual fuel only)
Code 23 – Pressure Switch Did Not Open
Code 24 – Secondary Voltage Fuse Open
Code 33 – Limit Circuit Fault AND High Heat Only is active
Code 45 – Control Circuitry Lockout
NOTE: For all the above furnace error codes, the system will use heat
pump heating exclusively if available. When the error code is cleared or
disappears, furnace heating will resume.
TWO-SPEED OUTDOOR UNIT
Code 85 – VC voltage at standby
Code 86 – High capacity compressor lockout
USER INTERFACE
Temp Sensor Failed, ″NO SENSOR DATA″ shown in place of actual temp.
Outdoor Unit communication fault.
Network Interface Module (NIM) communication fault
Defrost Error (defrost signal on for more than 15 minutes)
The user can press the right side button to dismiss the notice. The regular
run mode screen will then appear except ″SYSTEM MALFUNCTION″ will appear in
place of the day/time. If the error has not disappeared within 24 hours, the
above display will return.
If the error code disappears, ″SYSTEM MALFUNCTION″ will disappear and the
day/time will reappear.
© 2004 Bryant Heating & Cooling Systems 7310 W.
Morris St. Indianapolis, IN 46231
Printed in U.S.A. iiuiz01-0-1
Catalog No. 809-60024
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>