Vent-Axia 447938 Lo Carbon Sentinel Kinetic Plus Owner’s Manual

June 17, 2024
Vent-Axia

Vent-Axia 447938 Lo Carbon Sentinel Kinetic Plus Owner’s Manual
Carbon Sentinel Kinetic Plus

Lo-Carbon Sentinel Kinetic Plus

  • Acoustic Enclosure option for reduced breakout noise
  • Acoustic Top Box option for reduced in-duct noise
  • Recognised in SAP PCDB
  • Horizontal duct option for space-saving installations
  • High airflow, ideal for student accommodation clusters
  • Unique folding filter for removal when access is restricted
  • Integrated digital controller for simple and accurate commissioning
  • Plug and play controls; Humidistat
  • BMS connectivity
  • LS inputs (Light Switch)
  • Volt-free inputs
  • Self diagnosis for simplified fault finding
  • Adjustable delay On/delay Off timer
  • 4 fully adjustable speeds and a purge setting

Increased Performance
The Sentinel Kinetic Plus benefits from the latest high efficiency, backward curved impeller design, ensuring the lowest possible energy consumption, ultra quiet operation and an exceptional performance range covering small one bed apartments to the largest of houses.

For scenarios where noise is a critical issue, an Acoustic Enclosure is available to reduce breakout noise and the Acoustic Top Box will reduce in- duct noise at key frequencies.

Care Homes & Student Accommodation
The Sentinel Kinetic Plus is ideal for larger homes and multiple occupancy units such as care homes and student accommodation. Capable of 400m3 /hr at 150Pa, the unit can extract from up to ten bathrooms and a communal kitchen while still achieving almost 90% heat recovery. The fully automatic capability of the Kinetic range means that adequate ventilation is always achieved.

The Kinetics’ BMS capability is also ideal for those commercial applications where landlords or property managers want to monitor and optimize building performance and maintenance. The Kinetic BMS can provide status information and its self diagnostics can report if any fault is found.

Spigot Options
Spigots may be re-positioned to give horizontal connection or a combination of vertical and horizontal connection

Optional 180mm/200mm spigots can simplify connection in commercial installations where larger diameter duct work has been used.

Quick Change Filter
As many systems are placed within cupboards the unique filter design folds as you remove it to ensure easy access in restricted spaces.

integral Humidity Sensor
The integral humidity sensor increases speed in proportion to relative humidity levels, saving energy and reducing noise. The sensor also reacts to small but rapid increases in humidity, even if the normal trigger threshold is not reached. This unique feature ensures adequate ventilation, even for the smallest wet room. The night time relative humidity setback feature suppresses nuisance tripping as humidity gradually increases with falling temperature.

Models
Model Stock Ref
Sentinel Kinetic Plus BS 447938
Sentinel Kinetic Plus Right 443028
Sentinel Kinetic Plus Right with Acoustic Top Box & Enclosure 479538
Sentinel Kinetic Plus Right with Acoustic Top Box 479537
Sentinel Kinetic Plus Right with Acoustic Enclosure 479536
Sentinel Kinetic Plus Left 443028L
Sentinel Kinetic Plus Left with Acoustic Top Box & Enclosure 479541
Sentinel Kinetic Plus Left with Acoustic Top Box 479540
Sentinel Kinetic Plus Left with Acoustic Enclosure 479539

Accessories
Model Stock Ref
Wired Remote Controller 443283
LED Alarm with 15m cable 448356
Opto-coupler for volt-free BMS connection 447340
ISO 45% Coarse (G3) 2x Filter 403702
ISO ePM10 50% Pollen (M5) 1x Filter 444201
180mm/200mm Spigot Kit (One per pack) 446523
Anti Vibration Mounts 68MP033G
Acoustic Purge Fan 477988
Acoustic Purge Fan XL 479829

SAP PCDB Test Results (Kinetic Plus BS)

K+1 91 0.51 91 0.42
K+2 91 0.40 91 0.44
K+3 90 0.41 90 0.52
K+4 90 0.45 90 0.63
K+5 90 0.53 90 0.76
K+6 90 0.60 91 0.90
K+7 90 0.70 91 1.05

Performance
Fan speeds are fully adjustable within the performance range
Performance

SEC Class

Model SEC Class
Kinetic Plus A+

Dimensions (mm) Unit
Dimensions

A B C D F G
785 635 722 550 150 520 275
Weight: 24kg

Acoustic Solution

A B C D E         F G kg kg Spigot
80 733 501 71 855     583 40 17 33 150

Sound Data (Unit only

   Unit        Testsetting       mode| 63| 125| Octave band, Hz, dB SWL 250 500       lk        2k| 4k| 8k| LwA| SPL dB(A)
at 3m
---|---|---|---|---|---|---|---
‘20%| Supply| 54.4| 60.9| 50.6| 45.9| 34.3| 23.6| 19.1| 24.5| 51.3| 30.8
Extract| 48.4| 56.7| 43.7| 35.9| 21.4| 16| 18.7| 24.5| 42.3| 24.8
Breakout 42.6| 40.2| 39.6| 38| 31.1| 24.3| 19.4| 24.6| 35.1| 176
40%| Supply| 61.6| 64.6| 58.4| 55.5| 45.9| 372| 24.7| 25.1| 58.8| 38.3
Extract| 54.9| 62.2| 51.5| 44.8| 32.1| 24.1| 19.7| 24.6| 48.8| 31.3
Breakout    51.1| 49.3| 48.9| 45.9| 41.3| 35.7| 26.7| 25.6| 44.0| 26.5
60%| Supply| 675| 675| 73.2| 62.4| 53.4| 475| 33.5| 28.3| 69.2| 48.7
Extract| 62.5| 61.7| 601| 51.1| 39.2| 32.1| 23.2| 24.8| 54.0| 36.5
Breakout 54.9| 53| 58.4| 55.1| 49.7| 43.9| 35.4| 31.9| 52.8| 35.3
80%| Supply| 70.5| 71.1| 73.8| 66.5| 58.3| 53.2| 39.7| 33.3| 71.3| 50.8
Extract| 68.4| 65.9| 71.8| 55.6| 43.6| 371| 273| 25.5| 63.8| 46.3
Breakout 59.2| 56.8| 63.6| 57.3| 54.2| 49| 41| 375| 56.8| 39.3
100%| Supply| 72.8| 73.1| 75.2| 70.4| 61.6| 56.6| 44.2| 376| 73.9| 53.4
Extract| 71.7| 69| 71.8| 574| 45.7| 39.9| 30.9| 26.6| 64.1| 46.6
Breakout     61.2| 58.8| 679| 59.6| 56.7| 52.2| 44.4| 41.2| 60.1| 42.6

Sound Data (Unit with Acoustic Solution)

Unitsetting        mode| 63| 125| 250| and, Hz, dB SWL 500         lk 2k| 4k| 8k| LwA| SPL dB(A)
at 3m
---|---|---|---|---|---|---|---|---
20%| Supply| 55.7| 49.2| 36.6| 23.6| 174| 14.9| 178| 23.3| 36.1| 18.6
Extract| 51.4| 42.4| 30.3| 20.9| 16.8| 14.9| 178| 23.3| 30.8| 13.3
Breakout| 374| 39.7| 30.0| 22.7| 15.6| 14.0| 179| 23.3| 28.4| 79
40%| Supply| 59.7| 59.7| 45.5| 32.2| 22.2| 15.2| 179| 23.3| 45.1| 276
Extract| 54.8| 55.0| 38.0| 26.8| 18.1| 14.9| 178| 23.3| 40.2| 22.7
Breakout 45.7| 48.5| 39.9| 32.8| 24.2| 175| 18.0| 23.4| 36.8| 16.3
60%| Supply| 66.1| 61.9| 53.6| 41.0| 29.8| 18.3| 18.0| 23.3| 49.5| 32.0
Extract| 60.6| 55.9| 48.4| 34.9| 23.8| 16.3| 179| 23.3| 43.8| 26.3
Breakout| 51.1| 51.0| 52.4| 40.9| 33.2| 26.1| 19.7| 23.4| 44.5| 24.0
80%| Supply| 70.0| 676| 68.5| 48.1| 379| 25.3| 19.4| 23.6| 60.7| 43.2
Extract| 65.4| 59.7| 572| 41.6| 31.3| 21.8| 19.2| 23.4| 50.4| 32.9
Breakout 55.6| 55.6| 579| 47.9| 40.4| 34.3| 26.1| 23.7| 51.3| 30.8
100%| Supply| 72.1| 70.1| 66.4| 51.6| 41.9| 29.7| 21.7| 24.0| 60.0| 42.5
Extract| 68.2| 62.4| 60.6| 45.5| 36.0| 26.6| 21.7| 23.6| 53.8| 36.3
Breakout| 576| 58.8| 63.3| 51.0| 44.2| 38.5| 31.0| 24.9| 56.3| 35.8

Tested according to BS EN 13141-7:2010. Breakout quoted spherical. Supply and Extract quoted hemispherical. For in-duct data, end reflections are added based on the spigot size of the

Consultant’s Specification

Operation
The supply and extract ventilation unit shall be as Sentinel Kinetic Plus as manufactured by Vent-Axial and shall be sized as indicated on the drawings and shall be in accordance with the particular specification.

Supply air to the room shall be pre-heated by the extract air via the integrated composite plastic counterblow heat recovery cell. The Sentinel Kinetic Plus shall automatically vary the ventilation rate via EC/DC motors, as it receives signals from one of the optional interconnected sensors.

When a signal is received, the fans shall either vary their speed proportionally or on a trickle and boost principle.

The unit shall have the facility to commission the supply and extract fans individually via in-built minimum and maximum speed adjustment, or alternative wired remote control unit. The fans themselves shall have independent, infinitely variable speed control.

Unit Specification
The unit shall be manufactured with an ABS outer case construction, and incorporate a reversible core to allow for left or right hand mounting

The unit shall have a high efficiency composite plastic counterblow heat exchanger, supply and extract filters, automatic summer bypass, integral minimum and maximum infinitely variable speed controls with facia mounted failure indication

The unit shall have low energy, high efficiency EC/DC fan/motor assemblies with sealed for life bearings. The impellers shall be high efficiency backward curved centrifugal type.

The unit shall have a heat exchanger cell with a thermal efficiency of up to 92% when tested to EN 308. This shall be protected by ISO 45% Coarse (G3) grade synthetic filters on supply and extract. Complete with a condensate drip tray and drain connection.

To reduce breakout noise, the MVHR unit shall be provided with an Acoustic Enclosure of steel construction lined with class ‘0’ acoustic foam. To reduce in-duct noise, the top of the MVHR shall be fitted with an Acoustic Top Box to provide attenuation to the 4 ducts of the unit. This Acoustic Top Box shall be of steel construction lined with acoustic class ‘0’ foam with the MVHR spigots linked to the Top Box via 4 separate attenuated ducts. The acoustic enclosure and top box shall each be independently tested for noise to BS EN 13141-7.

The unit shall be constructed with a removable Core allowing full maintenance access. The removable Core shall provide access to the following:

  • Supply and extract filter
  • Heat exchanger
  • Access to the electrical connections

Access shall be provided for wiring termination and setup/commissioning. The backlit LCD user interface therein may be duplicated for remote mounting if required.

Units shall be as manufactured by Vent-Axial Ltd.

The MVHR unit shall incorporate an Expanded Polystyrene (EPS) inner chassis with custom motor and impeller mounting features. The inner chassis will assist in reducing noise and act as a large anti-vibration mount to avoid transmission through to the back mounting plate or the base of the unit.

The MVHR unit shall be tested to ensure it meets the maximum allowable vibration of no more than 1mm/s, measured on the unit wall fixing points.

Sound tested to BS EN 13141-7:2010

Standard Controls
All Sentinel Kinetic units shall incorporate the following functions integrally mounted, pre-wired and factory fitted by the manufacturer:

  • Integral infinitely variable fan speed control on supply and extract
  • Integral min/max ventilation control/set point
  • Integral BMS input/output interfaces – control and status indication
  • Heating interlocks
  • 0-10V proportional speed adjustment
  • Volt free contacts
  • 24V sensor supply
  • Integral on/off or trickle boost function from remote switch, e.g. PIR occupancy detector
  • Fully automatic summer bypass
  • Switched Live input with adjustable ‘delay-on’ feature
  • Fan failure or component failure indicated via individual fault code display
  • Running time counter
  • Control panel PIN number lock
  • Automatic frost protection effective to -20°C
  • The unit shall incorporate an integral humidity sensor with the following features:
    • Ambient Response; Raises the humidity trigger point as dwelling temperature reduces
    • Rapid Response: Monitors the rate of change in humidity and triggers increased airflow even if the humidity trigger threshold is not reached
    • Proportional Response; Incrementally increases the fan speed to reduce noise and reduce energy consumption
  • The unit shall be controlled by the ‘Sentinel’ control devices (enablers and sensors) as detailed in the schedule or on the drawings.
  • Tool free filter access

Mounting Option

Wall

Surface

Airflow Direction

Plan View
Airflow Direction
Front (RH)
Airflow Direction

Electrical Connection
Please note: Electrical connection should be carried out by an appropriately qualified person and in accordance with current wiring regulations
Electrical Connection

Trickle to Boost by two lighting circuits or Trickle/Boost Switch
Electrical Connection