Vent-Axia 428049 900mm (36) Ceiling Sweep Fan Installation Guide

June 17, 2024
Vent-Axia

428049 900mm (36) Ceiling Sweep Fan

Ceiling Sweep Fan
Fitting & wiring InstructionsVent-Axia 428049 900mm \(36\) Ceiling Sweep
Fan 900mm (36”)
1200mm (48”)
1400mm (56”)

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE COMMENCING INSTALLATION
This instruction leaflet covers the following sized fans
All sizes are supplied with 2 downrod lengths 400mm Downrod fitted giving 610mm overall drop (From ceiling to base of motor body)
150mm Downrod supplied loose giving 360mm overall drop (From ceiling to base of motor body)

IMPORTANT

THE FAN MUST BE SITED AND CONNECTED IN ACCORDANCE WITH CURRENT IEE REGULATIONS (UK) OR THE APPROPRIATE STANDARDS IN YOUR COUNTRY.
THIS APPLIANCE MUST BE EARTHED
THE APPLIANCE IS NOT INTENDED FOR USE BY YOUNG CHILDREN OR INFIRM PERSONS WITHOUT SUPERVISION.
YOUNG CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE APPLIANCE.
CHECK THAT THE VOLTAGE AND FREQUENCY ON BOTH THE FAN MOTOR AND CONTROLLER (IF FITTED) RATING LABELS CORRESPOND WITH YOUR ELECTRICITY SUPPLY.
THE INSTALLATION MUST BE PROVIDED WITH A DOUBLE POLE ISOLATOR SWITCH HAVING A CONTACT SEPARATION OF NOT LESS THAN 3MM AND PROTECTED WITH A 5 AMP FUSE (UK).
ENSURE THAT THE SAFETY WIRE IS CONNECTED TO THE J-HOOK BRACKET BEFORE OPERATING FAN.
ALL INSTALLATION AND ELECTRICAL CONNECTION WORK MUST BE CARRIED OUT BY A SUITABLY QUALIFIED PROFESSIONAL PERSON.
THE SHORTER (150mm) DOWN ROD LENGTH SHOULD ONLY BE USED WHERE FANS ARE TO BE MOUNTED TO BEAMS BELOW THE CEILING OR ROOF.

INSTALLING THE CEILING FAN

(Ensure that the mains supply is isolated before proceeding with the wiring)

  1. Decide on the position the fan is to be sited; it must be a minimum of 2.3m from the floor to the lowest point on the fan. (A shorter 150mm long downrod is supplied with the fan if required. Refer to the section on installing the shorter downrod).
  2. Fix the ceiling J-hook (supplied) firmly to a timber joist or concrete ceiling with the coach screws supplied (Or similar). Ensure that the fixing bracket in the ceiling is able to support a hanging weight of 15kg minimum. (Fig A)
  3. Fit the three blades to the fan body (see Diagram Fig B)
  4. Hang the fan on the hook with the safety wire, then hook up the fan on the black rubber roller making sure that all wires are clear.
  5. Connect supply wires to the fan using the terminal block at the top of the downrod. (See wiring Diagram Fig C)
  6. The size of supply wires is 0.5 and 0.75mm² for flexible cord, 1 to 2.5mm² cable for fixed wiringVent-Axia 428049 900mm \(36\) Ceiling Sweep Fan - CEILING JOIST
  7. Secure upper canopy with the screws fitted to cover the wiring connections.
  8. Tighten all screws including the earth connections.
  9. Switch on supply and check fan function.Vent-Axia 428049 900mm \(36\) Ceiling Sweep Fan - screws fittedVent-Axia 428049 900mm \(36\) Ceiling Sweep Fan - PHASE SUPPLY

INSTRUCTIONS FOR CHANGING TO SHORTER 150mm DOWNROD
Ensure that the mains supply is isolated before proceeding

Vent-Axia 428049 900mm \(36\) Ceiling Sweep Fan -
DOWNROD

  1. Loosen the lower canopy screws and slide canopy up the downrod.
  2. Disconnect the Brown (LF) Red (LR) and Blue (N), which run up the downrod from the lower terminal block located just above fan motor body.
  3. Disconnect the Earth (Green/Yellow) wire from the lower mounting bracket which also runs up inside of downrod.
  4. Carefully remove split pin and downrod securing bolt.
  5. Loosen the upper canopy screws and slide canopy down the downrod.
  6. Carefully remove the split pin and downrod securing bolt and then disconnect the Earth wire.
  7. Carefully remove existing downrod passing the disconnected feed wires through the rod along with the safety wire.
  8. Replace with the 150mm long downrod supplied.
  9. Pass the feed wires through the new Rod along with the safety wire.
  10. Replace the upper and lower downrod securing bolts and split pins.
  11. The feed wires will need to be cut and stripped to suit the shorter rod. And re-connected as follows to the lower terminal block Brown (LF) Red (LR) and Blue (N).12. Re-connect all Earth (Green/Yellow) wires.
  12. Because the shorter downrod has been required for your particular installation, It is important that the safety wire is reduced in length to protrude 75mm above the

Height of the 150mm downrod. The loop for the safety wire will need re-making by using a wire rope grip or crimp. (Supplied by others) It is essential that the new safety wire loop will withstand the weight of the fan in the event of it falling.

IMPORTANT
ALL FIXINGS MUST BE TIGHT BEFORE OPERATING THE FAN IT IS ADVISABLE TO CHECK/INSPECT ALL THE FIXINGS ANNUALLY, AND RE-TIGHTEN AS NECESSARY.
This Fan is guaranteed for one year from date of purchase against Faulty material or workmanship. In the event of any part being found To be defective please contact your local supplier stating the nature of the fault and providing evidence of date and source of purchase.