MITSUBISHI ELECTRIC PLA-A36EA8 36,000 BTU Commercial Ceiling Cassette Single Zone Heat Pum User Manual

June 17, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC PLA-A36EA8 36,000 BTU Commercial Ceiling Cassette

Single Zone Heat Pum

Product Information

Specifications

  • Job Name: System Reference: PLA-A36EA8 & PUZ-HA36NKA
  • Indoor Unit: PLA-A36EA8
  • Outdoor Unit: PUZ-HA36NKA
  • BTU/H: 36,000
  • Cooling Capacity (Indoor // Outdoor): 36,000 BTU/H
  • Heating Capacity (Indoor // Outdoor): 14,800 BTU/H
  • Operating Temperature Range (Indoor Unit): 33-1/16″ x 33-1/16″ x 11-3/4″ [840 x 840 x 298]
  • Operating Temperature Range (Outdoor Unit): 41-5/16″ x 14-3/16″ x 52-11/16″ [1050 x 360 x 1338]
  • Electrical: 208/230V AC, 1 phase, 60Hz
  • Refrigerant: R410A

Product Usage Instructions

Installation

  1. Select a suitable location for the indoor unit and outdoor unit.
  2. Ensure proper electrical connections are made.
  3. Connect the refrigerant piping between the indoor and outdoor units.
  4. Install any necessary accessories such as the air outlet guide, drain pan, control/service tool, etc.
  5. Mount the units securely using the designated mounting pads or brackets.
  6. Ensure proper spacing in the ceiling for the indoor unit.
  7. Make sure to slack the electrical wire a little bit for easy installation of optional parts.
  8. Properly position the indoor unit in relation to the ceiling slab.

Operation

  1. Turn on the power supply for the system.
  2. Use the wired remote controller or remote sensor to control the system.
  3. Adjust the desired temperature and fan speed settings.
  4. Ensure proper airflow by adjusting the air outlet guide and wind baffle if necessary.
  5. Maintain the system by regularly cleaning and replacing filters as needed.

Maintenance

To properly maintain the system, follow these steps:

  1. Regularly clean or replace filters to ensure optimal air quality.
  2. Clean the indoor and outdoor units to remove dust and debris.
  3. Inspect refrigerant piping for leaks and damage.
  4. Check electrical connections and wiring for any issues.
  5. Perform routine maintenance checks as recommended by the manufacturer.

Frequently Asked Questions

  • Q: What is the cooling capacity of the system?
    • A: The cooling capacity of the system is 36,000 BTU/H.
  • Q: What is the operating temperature range for the indoorunit?
    • A: The operating temperature range for the indoor unit is 33-1/16″ x 33-1/16″ x 11-3/4″ [840 x 840 x 298].
  • Q: How do I control the system?
    • A: You can control the system using the wired remote controller or remote sensor.
  • Q: How often should I clean or replace the filters?
    • A: It is recommended to clean or replace the filters regularly to ensure optimal air quality. The frequency may vary depending on usage and environmental conditions.
  • Q: What maintenance checks should I perform?
    • A: Regular maintenance checks include cleaning the units, inspecting refrigerant piping, checking electrical connections, and following the manufacturer’s recommended maintenance schedule.

INDOOR UNIT FEATURES

  • Space-efficient ductless installation
  • Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency
  • Airflow settings for high and low ceiling applications
  • Individual vane settings for direct/indirect airflow control or variable airflow patterns
  • Knockouts for outside-air intake and branch-duct run
  • Filter indicator signal
  • Easy-to-clean, washable filter (optional high-efficiency filter available – requires multi-function casement)
  • Built-in condensate lift mechanism
  • Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more
  • Multiple control options available:
    • Kumo cloud® smart device app for remote access
    • Third-party interface options
    • Wired or wireless controllers

OUTDOOR UNIT FEATURES

  • Variable speed INVERTER-driven compressor
  • High heating capacity: flash injection circuit maintains 100% heating capacity at 5°F outdoor temperature
  • Wide heating range: heating performance down to -13°F (average of 80% heating capacity)
  • High-speed heating at start up: Hyper-Heating INVERTER® reduces the time for heating at start up by about half compared to standard models
  • Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft.
  • High pressure/temperature protection
  • Built-in base pan heater
  • Flash injection circuit provides efficient high heating capacities at low ambient temperatures

SPECIFICATIONS

SPECIFICATIONS: PLA-A36EA8 & PUZ-HA36NKA

Cooling at 95°F1

| Maximum Capacity| BTU/H| 36,000
---|---|---|---
Rated Capacity| BTU/H| 36,000
Minimum Capacity| BTU/H| 14,800
Maximum Power Input| W| 2,750
Rated Power Input| W| 2,750
Moisture Removal| Pints/h| 5.5
Sensible Heat Factor| 0.83
Power Factor [208V / 230V]| %| 98.0 / 98.0

Heating at 47°F2

| Maximum Capacity| BTU/H| 40,000
Rated Capacity| BTU/H| 38,000
Minimum Capacity| BTU/H| 16,700
Maximum Power Input| W| 2,880
Rated Power Input| W| 2,650
Power Factor [208V / 230V]| %| 98.0 / 98.0

Heating at 17°F3

| Maximum Capacity| BTU/H| 38,000
Rated Capacity| BTU/H| 24,200
Maximum Power Input| W| 4,785
Rated Power Input| W| 2,715

Heating at 5°F4

| Maximum Capacity| BTU/H| 38,000
Maximum Power Input| W| 5,465
Heating at -13°F7| Maximum Capacity| BTU/H| 30,400

Efficiency

| SEER2| 20.0
EER21| 13.0
HSPF2 [IV]| 9.0
COP at 47°F2| 4.2
COP at 17°F at Maximum Capacity3| 2.3
COP at 5°F at Maximum Capacity4| 2.0

Electrical

| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 198 – 253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating [SCCR]| kA| 5
Recommended Fuse/Breaker Size (Oudoor)| A| 35
Recommended Wire Size [Indoor – Outdoor]| AWG| 14
Power Supply| Indoor unit is powered by the outdoor unit

Indoor Unit

| MCA| A| 2.0
Fan Motor Full Load Amperage| A| 0.56
Fan Motor Type| DC Motor
Airflow Rate at Cooling, Dry| CFM| 670–850–1,020–1,200
Airflow Rate at Cooling, Wet| CFM| 630–810–980–1,160
Airflow Rate at Heating, Dry| CFM| 670–850–1,020–1,200
Sound Pressure Level [Cooling]| dB[A]| 32–37–41–44
Sound Pressure Level [Heating]| dB[A]| 32–37–41–44
Drain Pipe Size| In. [mm]| 1-1/4 [32]
Condensate Lift Mechanism, Maximum Distance| In. [mm]| 33-7/16 [850]
Coating on Heat Exchanger| —
External Finish Color| White Munsell 6.4Y 8.9/0.4
Unit Dimensions| W x D x H: In. [mm]| 33-1/16 x 33-1/16 x 11-3/4 [840 x 840 x 298]
Package Dimensions| W x D x H: In. [mm]| 34-19/64 x 35-35/64 x 16-37/64 [871 x 903 x 421]
Unit Weight| Lbs. [kg]| 57 [26]
Package Weight| Lbs. [kg]| 89 [40]
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum / Minimum]*| °F| 90 DB, 72 WB / 66 DB, 61 WB
Heating Intake Air Temp [Maximum / Minimum]| °F| 77 DB / 59 DB

NOTES:

  • AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
  • (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
  • Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB 7Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB

Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Wind baffles required to operate below 23°F DB in cooling mode.
  • Refer to wind baffle documentation for further information.

Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out /Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

SPECIFICATIONS: PLA-A36EA8 & PUZ-HA36NKA

Outdoor Unit

| MCA| A| 24.0
---|---|---|---
MOCP| A| 42
Fan Motor Output| W| 74
Airflow Rate [Cooling / Heating]| CFM| 3880 / 3880
Refrigerant Control| LEV
Defrost Method| Reverse Cycle
Sound Pressure Level, Cooling1| dB(A)| 52
Sound Pressure Level, Heating2| dB(A)| 53
Compressor Type| Scroll
Compressor Model| ANB33FJMMT
Compressor Rated Load Amps| A| 18
Compressor Locked Rotor Amps| A| 27.5
Compressor Oil [Type // Charge]| oz.| FV50S // 1.4,47
External Finish Color| Ivory Munsell 3Y 7.8/1.1
Base Pan Heater| Built-in
Unit Dimensions| W x D x H: In. [mm]| 41-5/16 x 14-3/16 x 52-11/16 [1050 x 360 x 1338]
Package Dimensions| W x D x H: In. [mm]| 43 x 18 x 57 [1110 x 480 x 1440]
Unit Weight| Lbs. [kg]| 261 [118]
Package Weight| Lbs. [kg]| 285 [129]

Outdoor Unit Operating Temperature Range

| Cooling Air Temp [Maximum / Minimum]*| °F| 115 DB / 0 DB
Heating Air Temp [Maximum / Minimum]| °F| 70 DB, 59 WB / -13 DB, -13 WB
Heating Thermal Lock-out / Re-start Temperatures**| °F| -22 / -13

Refrigerant

| Type| R410A
Pre-Charged Refrigerant Amount| Lbs, oz| 11.0, 7.0
Maximum Pre-Charged Piping Length| Ft. [m]| 100.0 [30.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| .7 [56]

Piping

| Gas Pipe Size O.D. [Flared]| In.[mm]| 5/8 [15.88]
Liquid Pipe Size O.D. [Flared]| In.[mm]| 3/8 [9.52]
Maximum Piping Length| Ft. [m]| 245 [75]
Maximum Height Difference| Ft. [m]| 100 [30]
Maximum Number of Bends| 15

NOTES:

  • AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
  • 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
  • Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB 7Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB

Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):

  • Wind baffles are required to operate below 23°F DB in cooling mode.
  • Refer to wind baffle documentation for further information.

Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):

  • The system cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

INDOOR UNIT ACCESSORIES: PLA-A36EA8

Control Interface

| 3-Pin Connector| □ PAC-715AD
---|---|---
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEFACECB
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEZEROCB
Airzone ZBS Wired Lite Controller White| □ AZZBSLITECB
Airzone ZBS Wireless Lite Controller White| □ AZZBSLITERB
Airzone ZBS Wireless Think Controller White| □ AZZBSTHINKRB
CN24 Relay Kit| □ CN24RELAY-KIT-CM3
IT Extender| □ PAC-WHS01IE-E
kumo station® for kumo cloud®| □ PAC-WHS01HC-E
Procon BACnet® and Modbus® Interface| □ PAC-UKPRC001-CN-1
Remote Operation Adapter‡| □ PAC-SF40RM-E
Thermostat Interface| □ PAC-US445CN-1
USNAP Adapter| □ PAC-WHS01UP-E
Wireless Interface for kumo cloud®| □ PAC-USWHS002-WF-2

Remote Sensor

| Flush Mount Remote Temperature Sensor| □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor| □ PAC-USSEN001-FM-1
Remote Temperature Sensor| □ PAC-SE41TS-E
Wireless temperature and humidity sensor for kumo cloud®| □ PAC-USWHS003-TH-1

Wired Remote Controller

| Deluxe Wired MA Remote Controller†| □ PAR-40MAAU
Simple Ductless Wired Remote Controller| □ PAC-SDW01RC-1
Simple MA Remote Controller†| □ PAC-YT53CRAU-J
Touch MA Controller†| □ PAR-CT01MAU-SB

Wireless Remote Controller

| kumo touch™ RedLINK™ Wireless Controller| □ MHK2
Lockdown bracket for remote controller| □ RCMKP1CB
Wireless MA Receiver| □ PAR-FA32MA-W
Wireless MA Remote Controller| □ PAR-FL32MA-E
Wireless Remote Contoller| □ PAR-SL101A-E
Wireless Signal Receiver Panel| □ PAR-SR4LU-E
Casement| Multi-function Casement| □ PAC-SJ41TM-E

Condensate

| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended]| □ X87-721
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor| □ X87-835
Blue Diamond Sensor Extension Cable — 15 Ft.| □ C13-103
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI

Disconnect Switch

| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ-MS303
(30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ-MS303W
Filter| High Efficiency Filter Element**| □ PAC-SH59KF-E
i-see Sensor® Panel| Grille with 3D i-see Sensor® (required)| □ PLP-41EAEU

Lineset

| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-65
Shutter Plate| Shutter Plate| □ PAC-SJ37SP-E
Space Panel| Space Panel| □ PAC-SJ38AS-E

OUTDOOR UNIT ACCESSORIES: PUZ-HA36NKA

Air Outlet Guide| Air Outlet Guide (1 Piece)| □ PAC-SH96SG-E (two pieces are required)
---|---|---
Centralized Drain Pan| Central Drain Pan| □ PAC-SH97DP-E
Control/Service Tool| Control/Service Tool| □ PAC-SK52ST
Hail Guards| Hail Guard| □ HG-A2

M-NET Converter

| M-NET Converter| □ PAC-SJ85MA-E
M-NET Converter| □ PAC-SJ95MA-E
Mounting Pad| Condensing Unit Mounting Pad: 24” x 42” x 3”| □ ULTRILITE2
Optional Defrost Heater| Optional Defrost Heater| □ PAC-SJ20BH-E

Stand

| 18” Dual Fan Stand| □ QSMS1802M
24” Dual Fan Stand| □ QSMS2402M
Condenser Wall Bracket| □ QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish| □ QSWBSS
Outdoor Unit Stand — 12” High| □ QSMS1202M
Wind Baffle| Front Wind Baffle| □ WB-PA3 (two pieces are required)

DIMENSIONS

INDOOR UNIT DIMENSIONS: PLA-A36EA8MITSUBISHI ELECTRIC-PLA-A36EA8-36,000
-BTU-Commercial-Ceiling-Cassette-Single-Zone-Heat-Pum-
fig-1 MITSUBISHI ELECTRIC-PLA-A36EA8-36,000-BTU-Commercial-Ceiling-
Cassette-Single-Zone-Heat-Pum-fig-2

MODELS     A B C D E F
12/18

FLARED CONNECTION 1/4F

| REFRIGERANT PIPE{ FLARED CONNECTION 1/2F|

(241)

| 10-3/16 (258)| 3(76)|  | 10-7/16(265) OR MORE| 137-13/16(3500) OR LESS
24/30/36/42|

FLARED CONNECTION 3/8F

| REFRIGERANT PIPE{ FLARED CONNECTION 5/8F| 11-1/16 (281)| 11-3/4| 3-1/8| 12(305) OR MORE| 177-3/16(4500 ) OR LESS

  1. NOTE1.CHOOSE THE GRILLE AMONG THE DEDICATED GRILLES.
  2. REINFORCE THE SUSPENSION BOLT FOR EARTHQUAKE RESISTANCE AS NEEDED.
  3. FOR THE SUSPENSION BOLT, USE M10 OR W3/8. (PROCURED AT THE LOCAL SITE.)
  4. FOR DRAIN PIPE, USE VP-25(O.D. n1-1/4″ ({ 32) PVC TUBE). DRAIN PUMP INCLUSION. RAISE IS MAX 33-7/16 (850mm) FROM THE CEILING.
  5. ELECTRICAL BOX MAY BE REMOVED FOR THE SERVICE PURPOSE. MAKE SURE TO SLACK THE ELECTRICAL WIRE LITTLE BIT FOR THE CONTROL/POWER WIRES CONNECTION
  6. THE HEIGHT OF THE INDOOR UNIT IS ABLE TO BE ADJUSTED WITH THE GRILLE ATTACHED.
  7. REQUIRES “E” OR MORE SPACE BETWEEN THE TRANSOM AND CEILING FOR THE INSTALLATION.
  8. WHEN INSTALLING THE BRANCH DUCTS, BE SURE TO INSULATE ADEQUATELY. OTHERWISE CONDENSATION AND DRIPPING MAY OCCUR. (IT BECOMES THE CAUSE OF DROPLET OR DROPLET DRIPPING.)
  9. AS FOR NECESSARY INSTALLATION/SERVICE SPACE, PLEASE REFER TO THE RIGHT AT FIGURE.
  10. FOR THE INSTALLATION OF THE OPTIONAL HIGH-EFFICIENCY FILTER OR MULTI-FUNCTIONAL CASEMENT, REFER TO SPECIAL DRAWING.

OUTDOOR UNIT DIMENSIONS: PUZ-HA36NKAMITSUBISHI ELECTRIC-PLA-A36EA8-36,000
-BTU-Commercial-Ceiling-Cassette-Single-Zone-Heat-Pum-
fig-3 MITSUBISHI ELECTRIC-PLA-A36EA8-36,000-BTU-Commercial-Ceiling-
Cassette-Single-Zone-Heat-Pum-fig-4

1340 Satellite Boulevard Suwanee, GA 30024

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)