MITSUBISHI ELECTRIC PLA-A36EA8 36,000 BTU Commercial Ceiling Cassette Single Zone Heat Pum User Manual
- June 17, 2024
- Mitsubishi Electric
Table of Contents
MITSUBISHI ELECTRIC PLA-A36EA8 36,000 BTU Commercial Ceiling Cassette
Single Zone Heat Pum
Product Information
Specifications
- Job Name: System Reference: PLA-A36EA8 & PUZ-HA36NKA
- Indoor Unit: PLA-A36EA8
- Outdoor Unit: PUZ-HA36NKA
- BTU/H: 36,000
- Cooling Capacity (Indoor // Outdoor): 36,000 BTU/H
- Heating Capacity (Indoor // Outdoor): 14,800 BTU/H
- Operating Temperature Range (Indoor Unit): 33-1/16″ x 33-1/16″ x 11-3/4″ [840 x 840 x 298]
- Operating Temperature Range (Outdoor Unit): 41-5/16″ x 14-3/16″ x 52-11/16″ [1050 x 360 x 1338]
- Electrical: 208/230V AC, 1 phase, 60Hz
- Refrigerant: R410A
Product Usage Instructions
Installation
- Select a suitable location for the indoor unit and outdoor unit.
- Ensure proper electrical connections are made.
- Connect the refrigerant piping between the indoor and outdoor units.
- Install any necessary accessories such as the air outlet guide, drain pan, control/service tool, etc.
- Mount the units securely using the designated mounting pads or brackets.
- Ensure proper spacing in the ceiling for the indoor unit.
- Make sure to slack the electrical wire a little bit for easy installation of optional parts.
- Properly position the indoor unit in relation to the ceiling slab.
Operation
- Turn on the power supply for the system.
- Use the wired remote controller or remote sensor to control the system.
- Adjust the desired temperature and fan speed settings.
- Ensure proper airflow by adjusting the air outlet guide and wind baffle if necessary.
- Maintain the system by regularly cleaning and replacing filters as needed.
Maintenance
To properly maintain the system, follow these steps:
- Regularly clean or replace filters to ensure optimal air quality.
- Clean the indoor and outdoor units to remove dust and debris.
- Inspect refrigerant piping for leaks and damage.
- Check electrical connections and wiring for any issues.
- Perform routine maintenance checks as recommended by the manufacturer.
Frequently Asked Questions
- Q: What is the cooling capacity of the system?
- A: The cooling capacity of the system is 36,000 BTU/H.
- Q: What is the operating temperature range for the indoorunit?
- A: The operating temperature range for the indoor unit is 33-1/16″ x 33-1/16″ x 11-3/4″ [840 x 840 x 298].
- Q: How do I control the system?
- A: You can control the system using the wired remote controller or remote sensor.
- Q: How often should I clean or replace the filters?
- A: It is recommended to clean or replace the filters regularly to ensure optimal air quality. The frequency may vary depending on usage and environmental conditions.
- Q: What maintenance checks should I perform?
- A: Regular maintenance checks include cleaning the units, inspecting refrigerant piping, checking electrical connections, and following the manufacturer’s recommended maintenance schedule.
INDOOR UNIT FEATURES
- Space-efficient ductless installation
- Equipped with 3D i-see Sensor® for enhanced comfort and energy efficiency
- Airflow settings for high and low ceiling applications
- Individual vane settings for direct/indirect airflow control or variable airflow patterns
- Knockouts for outside-air intake and branch-duct run
- Filter indicator signal
- Easy-to-clean, washable filter (optional high-efficiency filter available – requires multi-function casement)
- Built-in condensate lift mechanism
- Ideal for retail shops, classrooms, office spaces, conference centers, building lobbies, and more
- Multiple control options available:
- Kumo cloud® smart device app for remote access
- Third-party interface options
- Wired or wireless controllers
OUTDOOR UNIT FEATURES
- Variable speed INVERTER-driven compressor
- High heating capacity: flash injection circuit maintains 100% heating capacity at 5°F outdoor temperature
- Wide heating range: heating performance down to -13°F (average of 80% heating capacity)
- High-speed heating at start up: Hyper-Heating INVERTER® reduces the time for heating at start up by about half compared to standard models
- Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft.
- High pressure/temperature protection
- Built-in base pan heater
- Flash injection circuit provides efficient high heating capacities at low ambient temperatures
SPECIFICATIONS
SPECIFICATIONS: PLA-A36EA8 & PUZ-HA36NKA
Cooling at 95°F1
| Maximum Capacity| BTU/H| 36,000
---|---|---|---
Rated Capacity| BTU/H| 36,000
Minimum Capacity| BTU/H| 14,800
Maximum Power Input| W| 2,750
Rated Power Input| W| 2,750
Moisture Removal| Pints/h| 5.5
Sensible Heat Factor| 0.83
Power Factor [208V / 230V]| %| 98.0 / 98.0
Heating at 47°F2
| Maximum Capacity| BTU/H| 40,000
Rated Capacity| BTU/H| 38,000
Minimum Capacity| BTU/H| 16,700
Maximum Power Input| W| 2,880
Rated Power Input| W| 2,650
Power Factor [208V / 230V]| %| 98.0 / 98.0
Heating at 17°F3
| Maximum Capacity| BTU/H| 38,000
Rated Capacity| BTU/H| 24,200
Maximum Power Input| W| 4,785
Rated Power Input| W| 2,715
Heating at 5°F4
| Maximum Capacity| BTU/H| 38,000
Maximum Power Input| W| 5,465
Heating at -13°F7| Maximum Capacity| BTU/H| 30,400
Efficiency
| SEER2| 20.0
EER21| 13.0
HSPF2 [IV]| 9.0
COP at 47°F2| 4.2
COP at 17°F at Maximum Capacity3| 2.3
COP at 5°F at Maximum Capacity4| 2.0
Electrical
| Voltage, Phase, Frequency| 208/230, 1, 60
Guaranteed Voltage Range| V AC| 198 – 253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208/230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating [SCCR]| kA| 5
Recommended Fuse/Breaker Size (Oudoor)| A| 35
Recommended Wire Size [Indoor – Outdoor]| AWG| 14
Power Supply| Indoor unit is powered by the outdoor unit
Indoor Unit
| MCA| A| 2.0
Fan Motor Full Load Amperage| A| 0.56
Fan Motor Type| DC Motor
Airflow Rate at Cooling, Dry| CFM| 670–850–1,020–1,200
Airflow Rate at Cooling, Wet| CFM| 630–810–980–1,160
Airflow Rate at Heating, Dry| CFM| 670–850–1,020–1,200
Sound Pressure Level [Cooling]| dB[A]| 32–37–41–44
Sound Pressure Level [Heating]| dB[A]| 32–37–41–44
Drain Pipe Size| In. [mm]| 1-1/4 [32]
Condensate Lift Mechanism, Maximum Distance| In. [mm]| 33-7/16 [850]
Coating on Heat Exchanger| —
External Finish Color| White Munsell 6.4Y 8.9/0.4
Unit Dimensions| W x D x H: In. [mm]| 33-1/16 x 33-1/16 x 11-3/4 [840 x 840 x
298]
Package Dimensions| W x D x H: In. [mm]| 34-19/64 x 35-35/64 x 16-37/64 [871 x
903 x 421]
Unit Weight| Lbs. [kg]| 57 [26]
Package Weight| Lbs. [kg]| 89 [40]
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp [Maximum /
Minimum]*| °F| 90 DB, 72 WB / 66 DB, 61 WB
Heating Intake Air Temp [Maximum / Minimum]| °F| 77 DB / 59 DB
NOTES:
- AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
- (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
- Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB 7Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB
Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
- Wind baffles required to operate below 23°F DB in cooling mode.
- Refer to wind baffle documentation for further information.
Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out /Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
- System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
SPECIFICATIONS: PLA-A36EA8 & PUZ-HA36NKA
Outdoor Unit
| MCA| A| 24.0
---|---|---|---
MOCP| A| 42
Fan Motor Output| W| 74
Airflow Rate [Cooling / Heating]| CFM| 3880 / 3880
Refrigerant Control| LEV
Defrost Method| Reverse Cycle
Sound Pressure Level, Cooling1| dB(A)| 52
Sound Pressure Level, Heating2| dB(A)| 53
Compressor Type| Scroll
Compressor Model| ANB33FJMMT
Compressor Rated Load Amps| A| 18
Compressor Locked Rotor Amps| A| 27.5
Compressor Oil [Type // Charge]| oz.| FV50S // 1.4,47
External Finish Color| Ivory Munsell 3Y 7.8/1.1
Base Pan Heater| Built-in
Unit Dimensions| W x D x H: In. [mm]| 41-5/16 x 14-3/16 x 52-11/16 [1050 x 360
x 1338]
Package Dimensions| W x D x H: In. [mm]| 43 x 18 x 57 [1110 x 480 x 1440]
Unit Weight| Lbs. [kg]| 261 [118]
Package Weight| Lbs. [kg]| 285 [129]
Outdoor Unit Operating Temperature Range
| Cooling Air Temp [Maximum / Minimum]*| °F| 115 DB / 0 DB
Heating Air Temp [Maximum / Minimum]| °F| 70 DB, 59 WB / -13 DB, -13 WB
Heating Thermal Lock-out / Re-start Temperatures**| °F| -22 / -13
Refrigerant
| Type| R410A
Pre-Charged Refrigerant Amount| Lbs, oz| 11.0, 7.0
Maximum Pre-Charged Piping Length| Ft. [m]| 100.0 [30.0]
Additional Refrigerant Charge Per Additional Piping Length| oz./Ft. [g/m]| .7
[56]
Piping
| Gas Pipe Size O.D. [Flared]| In.[mm]| 5/8 [15.88]
Liquid Pipe Size O.D. [Flared]| In.[mm]| 3/8 [9.52]
Maximum Piping Length| Ft. [m]| 245 [75]
Maximum Height Difference| Ft. [m]| 100 [30]
Maximum Number of Bends| 15
NOTES:
- AHRI Rated Conditions 1Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB (Rated data is determined at a fixed compressor speed) 2Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
- 3Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
- Conditions 4Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB 7Heating at -13°F (Indoor // Outdoor) °F 70 DB, 60 WB // -13 DB, -14 WB
Indoor/Outdoor Unit Operating Temperature Range (Cooling Air Temp [Maximum / Minimum]):
- Wind baffles are required to operate below 23°F DB in cooling mode.
- Refer to wind baffle documentation for further information.
Outdoor Unit Operating Temperature Range (Cooling Thermal Lock-out / Re-start Temperatures; Heating Thermal Lock-out / Re-start Temperatures):
- The system cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
INDOOR UNIT ACCESSORIES: PLA-A36EA8
Control Interface
| 3-Pin Connector| □ PAC-715AD
---|---|---
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEFACECB
Airzone ZBS Wired Blueface Principal Controller White| □ AZZBSBLUEZEROCB
Airzone ZBS Wired Lite Controller White| □ AZZBSLITECB
Airzone ZBS Wireless Lite Controller White| □ AZZBSLITERB
Airzone ZBS Wireless Think Controller White| □ AZZBSTHINKRB
CN24 Relay Kit| □ CN24RELAY-KIT-CM3
IT Extender| □ PAC-WHS01IE-E
kumo station® for kumo cloud®| □ PAC-WHS01HC-E
Procon BACnet® and Modbus® Interface| □ PAC-UKPRC001-CN-1
Remote Operation Adapter‡| □ PAC-SF40RM-E
Thermostat Interface| □ PAC-US445CN-1
USNAP Adapter| □ PAC-WHS01UP-E
Wireless Interface for kumo cloud®| □ PAC-USWHS002-WF-2
Remote Sensor
| Flush Mount Remote Temperature Sensor| □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor| □ PAC-USSEN001-FM-1
Remote Temperature Sensor| □ PAC-SE41TS-E
Wireless temperature and humidity sensor for kumo cloud®| □ PAC-USWHS003-TH-1
Wired Remote Controller
| Deluxe Wired MA Remote Controller†| □ PAR-40MAAU
Simple Ductless Wired Remote Controller| □ PAC-SDW01RC-1
Simple MA Remote Controller†| □ PAC-YT53CRAU-J
Touch MA Controller†| □ PAR-CT01MAU-SB
Wireless Remote Controller
| kumo touch™ RedLINK™ Wireless Controller| □ MHK2
Lockdown bracket for remote controller| □ RCMKP1CB
Wireless MA Receiver| □ PAR-FA32MA-W
Wireless MA Remote Controller| □ PAR-FL32MA-E
Wireless Remote Contoller| □ PAR-SL101A-E
Wireless Signal Receiver Panel| □ PAR-SR4LU-E
Casement| Multi-function Casement| □ PAC-SJ41TM-E
Condensate
| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor
(208/230V) [recommended]| □ X87-721
Blue Diamond (MegaBlue Advanced) Condensate Pump w/ Reservoir & Sensor| □
X87-835
Blue Diamond Sensor Extension Cable — 15 Ft.| □ C13-103
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI
Disconnect Switch
| (30A/600V/UL) [fits 2” X 4” utility box] – Black| □ TAZ-MS303
(30A/600V/UL) [fits 2” X 4” utility box] – White| □ TAZ-MS303W
Filter| High Efficiency Filter Element**| □ PAC-SH59KF-E
i-see Sensor® Panel| Grille with 3D i-see Sensor® (required)| □ PLP-41EAEU
Lineset
| 10’ x 3/8” x 10’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-10
100’ x 3/8” x 100’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-100
15’ x 3/8” x 15’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-15
30’ x 3/8” x 30’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-30
50’ x 3/8” x 50’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-50
65’ x 3/8” x 65’ x 5/8” Lineset (Twin-Tube Insulation)| □ MPLS385812T-65
Shutter Plate| Shutter Plate| □ PAC-SJ37SP-E
Space Panel| Space Panel| □ PAC-SJ38AS-E
OUTDOOR UNIT ACCESSORIES: PUZ-HA36NKA
Air Outlet Guide| Air Outlet Guide (1 Piece)| □ PAC-SH96SG-E (two pieces are
required)
---|---|---
Centralized Drain Pan| Central Drain Pan| □ PAC-SH97DP-E
Control/Service Tool| Control/Service Tool| □ PAC-SK52ST
Hail Guards| Hail Guard| □ HG-A2
M-NET Converter
| M-NET Converter| □ PAC-SJ85MA-E
M-NET Converter| □ PAC-SJ95MA-E
Mounting Pad| Condensing Unit Mounting Pad: 24” x 42” x 3”| □ ULTRILITE2
Optional Defrost Heater| Optional Defrost Heater| □ PAC-SJ20BH-E
Stand
| 18” Dual Fan Stand| □ QSMS1802M
24” Dual Fan Stand| □ QSMS2402M
Condenser Wall Bracket| □ QSWB2000M-1
Condenser Wall Bracket – Stainless Steel Finish| □ QSWBSS
Outdoor Unit Stand — 12” High| □ QSMS1202M
Wind Baffle| Front Wind Baffle| □ WB-PA3 (two pieces are required)
DIMENSIONS
INDOOR UNIT DIMENSIONS: PLA-A36EA8
MODELS | A | B | C | D | E | F | ||
---|---|---|---|---|---|---|---|---|
12/18 |
FLARED CONNECTION 1/4F
| REFRIGERANT PIPE{ FLARED CONNECTION 1/2F|
(241)
| 10-3/16 (258)| 3(76)| | 10-7/16(265) OR MORE| 137-13/16(3500) OR LESS
24/30/36/42|
FLARED CONNECTION 3/8F
| REFRIGERANT PIPE{ FLARED CONNECTION 5/8F| 11-1/16 (281)| 11-3/4| 3-1/8| 12(305) OR MORE| 177-3/16(4500 ) OR LESS
- NOTE1.CHOOSE THE GRILLE AMONG THE DEDICATED GRILLES.
- REINFORCE THE SUSPENSION BOLT FOR EARTHQUAKE RESISTANCE AS NEEDED.
- FOR THE SUSPENSION BOLT, USE M10 OR W3/8. (PROCURED AT THE LOCAL SITE.)
- FOR DRAIN PIPE, USE VP-25(O.D. n1-1/4″ ({ 32) PVC TUBE). DRAIN PUMP INCLUSION. RAISE IS MAX 33-7/16 (850mm) FROM THE CEILING.
- ELECTRICAL BOX MAY BE REMOVED FOR THE SERVICE PURPOSE. MAKE SURE TO SLACK THE ELECTRICAL WIRE LITTLE BIT FOR THE CONTROL/POWER WIRES CONNECTION
- THE HEIGHT OF THE INDOOR UNIT IS ABLE TO BE ADJUSTED WITH THE GRILLE ATTACHED.
- REQUIRES “E” OR MORE SPACE BETWEEN THE TRANSOM AND CEILING FOR THE INSTALLATION.
- WHEN INSTALLING THE BRANCH DUCTS, BE SURE TO INSULATE ADEQUATELY. OTHERWISE CONDENSATION AND DRIPPING MAY OCCUR. (IT BECOMES THE CAUSE OF DROPLET OR DROPLET DRIPPING.)
- AS FOR NECESSARY INSTALLATION/SERVICE SPACE, PLEASE REFER TO THE RIGHT AT FIGURE.
- FOR THE INSTALLATION OF THE OPTIONAL HIGH-EFFICIENCY FILTER OR MULTI-FUNCTIONAL CASEMENT, REFER TO SPECIAL DRAWING.
OUTDOOR UNIT DIMENSIONS: PUZ-HA36NKA
1340 Satellite Boulevard Suwanee, GA 30024
- Toll-Free: 800-433-4822
- www.mehvac.com