Honeywell WEB-300E Controllers with Two Ethernet Ports Instruction Manual
- June 17, 2024
- Honeywell
Table of Contents
- Honeywell WEB-300E Controllers with Two Ethernet Ports
- Product Information
- Product Usage Instructions
- FAQs
- APPLICATION
- INSTALLATION INSTRUCTIONS
- MOUNTING
- EXPANSION OPTIONS
- INSTALLATION
- MAINTAINING THE CONTROLLER
- Battery maintenance
- CERTIFICATIONS
- TAB MOUNTING DIMENSIONS
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- 2 phillips screwdriver: used to install and remove any option card.
Honeywell WEB-300E Controllers with Two Ethernet Ports
Product Information
- Specifications
- The WEB-300E, WEB-600E/U, CP-300E, CP-600E/U Series Controllers have the following specifications:
- Model: WEB-300E, WEB-600E/U, CP-300E, CP-600E/U
- Description: The controllers include two Ethernet ports, one RS-232 port, and one RS-485 port. They come with Web User Interface and Niagara Connectivity. Standard drivers include oBIX Client/Server and Niagara Network (Fox) Client/Server.
- Mounting: The WEB-600E/U, WEB-600E-O/U, WEB-600E-US/U, WEB-600E-US-O/U, and CP-600E/U are designed for batteryless operation and DIN rail mounting.
- Features: Standard features include WEBs-AX station and Web User Interface.
- Made in the USA: The WEB-600E-US/U and WEB-600E-US-O/U models are made in the USA.
- Software Requirement: The WEB-300E-AX-DEMO and CP-300E-DEMO models require AX release 3.7.106 or higher.
Product Usage Instructions
- Installation Instructions
- To install the WEB-300E, WEB-600E/U, CP-300E, CP-600E/U Series Controllers, follow these steps:
- Ensure you have the necessary tools and equipment for installation.
- Read the related documentation provided (95-7753) for detailed instructions.
- Mount the controller using DIN rail mounting.
- Connect the necessary cables to the Ethernet ports, RS-232 port, and RS-485 port.
- If using expansion options, refer to the separate documents for mounting and wiring instructions.
- WEB-300E, WEB-600E/U, CP-300E, CP-600E/U Series Controllers
- The WEB-300E, WEB-600E/U, CP-300E, and CP-600E/U Series Controllers are versatile devices that offer various control options. Here’s how to use them:
- Step 1: Power On
- Ensure that the controller is connected to a power source.
- Step 2: Access Web User Interface
- Open a web browser on a device connected to the same network as the controller.
- Type the IP address of the controller in the browser’s address bar and press Enter.
- The Web User Interface should load, allowing you to access and configure the controller’s settings.
- Step 3: Configure Settings
- Use the Web User Interface to configure various settings such as network configurations, control parameters, and system options. Refer to the user manual for detailed instructions on each setting.
- Step 4: Monitor and Control
- Once the settings are configured, you can monitor and control the connected devices through the Web User Interface. Use the provided drivers (oBIX Client/Server and Niagara Network (Fox) Client/Server) for seamless integration with other systems.
FAQs
- Q: What is the difference between the WEB-300E and WEB-300E-O models?
- A: The WEB-300E-O model includes an Open License, which provides additional software capabilities compared to the WEB-300E model.
- Q: Can the WEB-600E/U controllers be used without batteries?
- A: Yes, the WEB-600E/U controllers are designed for batteryless operation.
- Q: What software version is required for the WEB-300E-AX-DEMO and CP-300E-DEMO models?
- A: The WEB-300E-AX-DEMO and CP-300E-DEMO models require AX release 3.7.106 or higher.
APPLICATION
The Honeywell WEB-300E, CP-300E, WEB-600E/U, WEB-600E-O/U, and CP-600E/U
controllers are compact, embedded controller/server platforms that allow
integrated control and management of external devices over the Internet. The
300E uses a PowerPC 405 400Mhz processor; the 600E uses a PowerPC 440 524Mhz
processor. Each controller supports two optional communications cards as well
as optional I/O expansion modules. Onboard static RAM (SRAM) provides WEBs-AX
station backup capability without any battery installed. An optional backup
battery is also available.
IMPORTANT
- This document covers the mounting and wiring of the Honeywell WEB-300E, WEB-300E-O, CP-300E, WEB-600E/U, CP-600E/U, and WEB-600E-O/U controllers. It assumes that you are an engineer, technician, or service person who is performing control system installation.
- Instructions in this document apply to the products listed in Table 1.
- Not covered in this document is the WEBs-AX software installation and configuration required for a fully functioning unit.
- In addition, the mounting and wiring of JACE expansion options are covered in separate documents. See “Related Documentation” on this page, and “Expansion Options” on page 5.
INSTALLATION INSTRUCTIONS
Related Documentation
- For more information on configuring and using the WEB-300E or WEB-600E/U controller, refer to the following documents:
- JACE WEBs-AX Install and Startup Guide
- JACE Data Recovery Service (SRAM Support) – Engineering Notes
- IO-16-H Input/Output Module Installation Instructions (95-7756)
- IO-34-H Input/Output Module Installation Instructions (95-7753)
- Various optional card installation documents, such as:
- NPB-LON Installation Instructions (62-0263)
- NPB-2X-RS485 Option Card Installation Instructions (95-7778)
- NPB-RS232 Option Installation Instructions (95-7779)
- WEBs-AX NPB-GPRS Modem Installation Instructions (62-0301)
- NPB-ZWAVE Option Card Installation Instructions (62-0349)
- WEBs-AX Ndio Guide
- WEBs-AX User Guide
Table 1.
Model | Description |
---|---|
WEB-300E | WEB-300E, includes two Ethernet ports, one RS-232 port, and one |
RS-485 port. Web User Interface and Niagara Connectivity included. oBIX
Client/Server driver included.
WEB-300E-O| WEB-300E with Open License, includes two Ethernet ports, one
RS-232 port, and one RS-485 port. Web User Interface and Niagara Connectivity
included. oBIX Client/Server driver included.
CP-300E| Comfort Point 300E, includes two Ethernet ports, one RS-232 port, and
one RS-485 port. Web User Interface and Niagara Connectivity included. oBIX
Client/Server driver included.
WEB-600E/U| The WEB-600E/U is designed for Battery-less operation and DIN rail
mounting. Standard features include WEBs-AX station and Web User Interface.
Standard drivers include oBIX Client / Server and Niagara Network (Fox) Client
/ Server.
WEB-600E-O/U| The WEB-600E-O/U with Open License is designed for Battery-less
operation and DIN rail mounting. Standard features include WEBs-AX station and
Web User Interface. Standard drivers include oBIX Client / Server and Niagara
Network (Fox) Client / Server.
WEB-600E-US/U| The WEB-600E-US/U is designed for Battery-less operation and
DIN rail mounting. Standard features include WEBs-AX station and Web User
Interface. Standard drivers include oBIX Client / Server and Niagara Network
(Fox) Client / Server. Made in USA controller.
WEB-600E-US-O/U| The WEB-600E-US-O/U with Open License is designed for
Battery-less operation and DIN rail mounting. Standard features include WEBs-
AX station and Web User Interface. Standard drivers include oBIX Client /
Server and Niagara Network (Fox) Client / Server. Made in USA controller.
CP-600E/U| The CP-600E/U is designed for Battery-less operation and DIN rail
mounting. Standard features include a CP-AX station and Web User Interface.
Standard drivers include oBIX Client / Server and Niagara Network (Fox) Client
/ Server.
WEB-300E-AX-DEMO| Base Unit includes two Ethernet ports, one RS-232 port, and
one RS-485 port. Web User Interface and Niagara Connectivity included. oBIX
Client/Server driver included. Includes NPB- WPM-US/U, NPB-LON/U, NPB-2X-
RS485/U, IO-16-REM-H/U, NPB-BATTERY/U, NPB-RS232/U.
Requires AX release 3.7.106 or higher.
CP-300E-DEMO| Base Unit includes two Ethernet ports, one RS-232 port, and one RS-485 port. Web User Interface and Niagara Connectivity included. oBIX Client/Server driver included. Includes NPB- WPM-US/U, NPB-LON/U, NPB-2X- RS485/U, IO-16-REM-H/U, NPB-BATTERY/U, NPB-RS232/U.
Requires AX release 3.7.106 or higher.
W-600E-AX-DEMO/U| Office Demo WEB 600E Controller
CP-600E-AX-DEMO/U| Comfort Point 600E Demo Controller
NPB-PWR-H/U| 24Vac/DC input/15V DC output power supply module, DIN mountable.
NPB-PWR-UN-H/U| 120–240Vac universal input/15Vdc output power supply module,
DIN mountable.
NPB-WPM-US/U| Wall Adaptor (US)
PREPARATION
- Unpack the controller and inspect the package contents for damaged or missing components.
- If damaged, notify the appropriate carrier at once and return any damaged components for immediate repair or replacement. See “Returning a Defective Unit” on page 17.
Included in this Package
Included in this package you should find the following items:
- A WEB-300E, WEB-300E-O, CP-300E, WEB-600E/U, WEB-600E-O/U, or a CP-600E/U controller.
- WEB-300E, WEB-600E/U, CP-300E, CP-600E/U Series Controllers Installation Instructions (31-00010).
- a hardware bag containing the following items:
One (1) grounding wire, with quick-disconnect 0.187″ female connector.
Material and Tools Required
The following supplies and tools are typically required for installation:
- A suitable power module, is one of the following types:
- NPB-PWR-H/U: 24Vac or 24Vdc, in-line, DIN mount capable, with grounding wire.
- NPB-PWR-UN-H/U: 120–240Vac, in-line, DIN mount capable, with grounding wire.
- NPB-WPM-US/U: External wall-mount power adapter.
- NOTE: Using an NPB-PWR-H/U power module provides the widest operating temperature range. See “Environmental Requirements” on page 3.
- If using a NPB-PWR-H/U (24V) power module, either one of the following:
- UL listed, Class 2, 24Vac transformer, rated at a minimum of 7.5VA to 20VA (approximate range of controller alone, to the fully-expanded unit with four additional IO-16-H/U modules and other option boards). Note that a dedicated transformer is required (cannot also power additional equipment).
- 24Vdc power supply, capable of supplying at least 1A (24W).
- DIN rail, type NS35/7.5 (35mm x 7.5mm) and DIN rail end-clips (stop clips), recommended for any installation that includes NPB-PWR-H/U or NPB-PWR-UN-H/U power module and/or optional I/O modules.
- Suitable tools and fasteners for mounting units and accessories.
-
2 phillips screwdriver: used to install and remove any option card.
- Small flat-blade screwdriver: used for making wiring connections to removable screw terminal plugs, also for mounting and removing modules from DIN rail.
This document uses the following warning and caution conventions:
CAUTION
- Cautions remind the reader to be careful. They alert readers to situations where there is a chance that the reader might perform an action that cannot be undone, might receiveunexpected results, or might lose data. Cautions contain an explanation of why the action is potentially problematic.
WARNING
- Warnings alert the reader to proceed with extreme care in situations where there is a chance that the reader might do something that can result in personal injury or equipment damage. Warnings contain an explanation of why the action is potentially dangerous.
Safety Precautions
- The following are warnings relating to the installation and start-up of the controller. Be sure to heed these warnings to prevent personal injury or equipment damage.
WARNING
Depending on the power module used, the circuit powering the controller is 120–240Vac at 50/60 Hz (if an NPB-PWR-UN-H/U), 24Vac at 50/60 Hz or 24Vdc (if an NPB-PWR-H/U), or from 100– 240Vac at 50/60 Hz (if an NPB-WPM-US/U). Disconnect power before installation or servicing to prevent electrical shock or equipment damage.
- Make all connections by national and local electrical codes. Use copper conductors only.
- To reduce the risk of fire or electrical shock, install in a controlled environment relatively free of contaminants.
- This device is only intended for use as a monitoring and control device. To prevent data loss or equipment damage, do not use it for any other purpose.
- Static Discharge Precautions
- Static charges produce voltages high enough to damage electronic components. The controller’s microprocessors and associated circuitry are sensitive to static discharge. Follow these precautions when installing, servicing, or operating the system:
CAUTION
- Work in a static-free area.
- Discharge any static electricity you may have accumulated. Discharge static electricity by touching a known, securely grounded object.
- Do not handle printed circuit boards (PCBs) without proper protection against static discharge.
- Use a wrist strap when handling PCBs. The wrist strap clamp must be secured to the earth’s ground.
Battery Precautions
CAUTION
- The optional NiMH battery used in this device may present a risk of fire or chemical burn if mistreated. Do not disassemble, heat above 122ºF (50ºC), or incinerate. Replace the battery pack with type NPB-BATTERY/U only.
- The use of another battery may present a risk of fire or explosion.
- Dispose of the used battery promptly. Keep away from children. Do not disassemble and do not dispose of in fire.
- Replace the external backup battery with the Listed Power Source Battery Only.
MOUNTING
- Before mounting the controller, install any option card(s).
- See “About Option Cards” on page 5. Also, see “RS-485 Biasing” on page 11. Then mount the controller in a location that allows clearance for wiring, servicing, and module removal.
- NOTE: This product is for indoor use only, altitude to 2,000m (6,562 ft.) maximum.
- Depending on installed options, the allowable temperature range varies. See “Environmental Requirements” below.
- Avoid mounting the controller in a manner that would make it difficult to operate the disconnect device. See “Physical Mounting” for more details.
Environmental Requirements
- Do not expose the unit to ambient operating temperatures outside the range:
- 0°C (32°F) to 60°C (140°F), providing the unit:
- Is not powered by the AC line input NPB-PWRUN- H/U module, and
- The optional NiMH battery pack is not installed. Otherwise, 0°C (32°F) to 50 (122°F) is the ambient operating temperature range.
- The relative humidity range is 5% to 95% non-condensing.
- Pollution Degree III.
- Supply (mains) voltage requirements are as follows:
- Allowable voltage fluctuation to -15%, +10%,
- Temporary overvoltages +/- 15%.
- Transient overvoltages: Overvoltage Category II.
- a Powering the controller with the wall mount adapter (NPB-WPM-US/U) at 60°C (140°F) is supported, however, at 60°C its output is derated 50%, i.e. 15V at 0.5A (7.5W). No IO modules are supported.
- If mounting inside an enclosure, that enclosure should be designed to keep the unit within its required operating range considering a 20-watt dissipation by the controller, plus dissipation from any other devices installed in the same enclosure. This is especially important if the controller is mounted inside an enclosure with other heat-producing equipment.
- Do not mount the unit:
- in an area with excessive moisture, corrosive fumes, or explosive vapours.
- where vibration or shock is likely to occur.
- in a location subject to electrical noise. This includes the proximity of large electrical contractors, electrical machinery, welding equipment, spark igniters, and variable frequency drives.
Physical Mounting
The following information applies to physically mounting the unit.
- You can mount the controller in any orientation. It is not necessary to remove the cover before mounting.
- Mounting on a 35mm wide DIN rail is recommended. The controller’s unit base has a moulded DIN rail slot and locking clip, as do the power supply modules and both types of I/O expansion modules. Mounting on a DIN rail ensures accurate alignment of connectors between all modules.
- If DIN rail mounting is impractical, you can use screws in mounting tabs on the controller, as well as any end connected accessory (NPB-PWR-H/U, etc.). Tab mounting dimensions are on the last page of this document.
To mount on DIN rail
- Securely install the DIN rail with at least two screws, near the two rail ends.
- Position the controller on the rail, tilting to hook DIN rail tabs over one edge of the DIN rail (Fig. 1).
- Use a screwdriver to pry down the plastic locking clip, and push down and in on the unit, forcing the locking clip to snap over the other DIN rail edge.
- Mount any accessory module (I/O module, NPBPWR- H/U) onto the DIN rail in the same manner.
- lide the accessory module along the DIN rail to connect its 20-position plug to the controller.
- Repeat this for all accessories, until all are mounted on the DIN rail and firmly connected.
- To keep the final assembly together, secure at both ends with DIN rail end-clips provided by the DIN rail vendor. This also prevents the assembly from sliding on the DIN rail. See Fig. 1.
Removing and Replacing the Cover
- You must remove the controller’s cover to install any option cards, or to install (or replace) the optional NiMH backup battery.
- The cover snaps onto the base with four plastic end tabs—two on each end.
- NOTE: If accessory modules are plugged into the controller, you may need to slide them away from the unit to get to the end cover tabs.
- To remove the cover, press in the tabs on both ends of the unit, and carefully lift it off.
- To replace the cover, orient it so the cutout area for comm ports is correct, then push inwards to snap in place.
Board Layout
Fig. 3 shows the location of LEDs, option slots, and other features of the 300E or 600E controller with the removed. For a side view of communications ports and other features, see Fig. 6 on page 10.
The controller ships with onboard static RAM (SRAM) that can provide station backup during power loss and also has two (2) open option card slots for a variety of available option cards. For details, see “About Expansion Options” below, and also “About Backup Configurations” on page 13.
EXPANSION OPTIONS
The controller provides for field-installable expansion using these types of options:
- Option cards — Install connectors on the controller’s baseboard. See “About Option Cards” on page 5.
- Accessory modules — To “chain” on the controller’s 20-pin connector. See “About Accessory Modules” on page 6.
About Option Cards
- The controller has two (2) available option slots for option cards designed for use with controllers. Each slot has a 30-pin connector. Installing an option card is recommended before mounting the unit. See “Installing an Option Card” on page 6.
WARNING
- Power to the controller must be OFF when installing or removing option cards, or damage will occur!
- Also, you must be very careful to plug an option card into its connector properly (pins aligned).
- Option cards typically provide additional communications features, with the following available models (with others still in development) listed in Table 2.
Table 2.
Option | Description | Notes |
---|---|---|
NPB-2X-RS485/U | Dual, optically-isolated, RS-485 adapter with two 3- position | |
removable screw-terminal connector plugs. | If installed in Option slot 1, |
ports operate as COM3 and COM4. If two 485 option cards, ports are COM3, COM4
for Option slot 1, and COM5, COM6 for Option slot 2.
NPB-LON/U| FTT-10A LON (LonWorks) adapter with a 2-position removable screw-
terminal connector plug.| Port operates as LON1 if only one LON option, or
LON2 in slot 2 if two LON cards.
NPB-RS232/U| Single port RS-232 adapter, with a DB-9M connector. Supports baud
rates up to 115200.| If installed in option slot 1, the port operates as COM3.
If two 232 option cards, ports are COM3 for Option Slot 1 and COM4 for Option Slot 2.
NPB-GPRS-W-H/U| GSM cellular modem card using GPRS (General Packet Radio Service), with an onboard socket for a SIM card, and a Wyless SIM.| Includes SMA coax tilt-and-swivel antenna.
The NPB-GPRS-W-H/U model is bundled with a Wyless-provisioned SIM card.
NPB-ZWAVE/U| A Z-Wave wireless serial gateway between the JACE’s WEBs-AX station and an RF wireless Z-Wave domain. Includes RP-SMA coax tilt-and-swivel antenna.| US model is 908.42 MHz for U.S. usage.
If installed in option slot 1, the card operates as COM3.
INSTALLATION
Installing an Option Card
For option-specific details, see the Installation Instructions document that
accompanies the particular option card. The following procedure provides a
basic set of steps. Mounting an option card in a WEB/CP300E or 600E
controller.
1. If a station is running, stop it using the platform Application Director
view.
-
Remove power from the controller—see the previous Warning.
-
Remove the cover. See “Removing and Replacing the Cover” on page 4.
-
If the optional NiMH battery/bracket assembly is installed, remove it by taking out the four screws holding it in place, setting them aside for later. Two of these screws will also secure the option card, once installed.
- a. Unplug the battery from the connector on the controller’s baseboard.
- b. Remove the blanking plate from the option slot to be used.
-
If no optional NiMH battery/bracket assembly is installed, remove the blanking plate for the option slot to be used, retaining the two screws.
- NOTE: If you are also installing the optional NiMH battery/bracket assembly now, remove and retain the other two screws, that is for the other option slot.
-
Carefully insert the pins of the option card into the socket headers of the option card slot. The mounting holes on the option board should line up with the standoffs on the baseboard. If they do not, the connector is not properly aligned. Press until the option card is completely seated.
-
Place the custom end plate for the option card over the connector(s) of the option card. With some option cards, the card’s end plate is pre-fastened.
-
If installing (or replacing) the optional NiMH battery/ bracket assembly:
- a. Plug the battery connector plug into the battery connector on the controller’s baseboard.
- b. Set the battery and bracket assembly over the option card slots, with the mounting holes aligned with the standoffs.
- c. Place the four screws through the bracket, end plates, and into the standoffs on the controller baseboard. With a screwdriver, hand tighten the screws. For more details, see “NiMH Battery Installation and Maintenance” on page 14.
Otherwise, place the two screws through the option card end plate and into the standoffs on the baseboard. With a screwdriver, hand tighten the screws.
-
Replace the cover on the controller.
-
Restore power to the controller and verify normal operation.
About Accessory Modules
- The controller has a 20-pin, right-angle, Euro-DIN connector that accepts custom-built accessory modules.
- The connector provides power and signal lines to any connected modules.
WARNING
- Power to the controller must be OFF when inserting or unplugging accessory modules.
- Wait for all LED activity to stop (all LEDs off). Also, do not connect live voltages to the inputs or outputs of an I/O module while it is “unpowered” before plugging the module into the controller.
- Otherwise, damage to the I/O module and/or controller may result!
- Each accessory module has a DIN-mount base and typically provides two (2) 20-pin connectors that allow you to “chain” multiple accessories. Table 3 lists the currently available modules.
Table 3. Accessory modules compatible with the WEB/CP 300E and WEB/CP 600E/U Series controller
Option | Description | Notes |
---|---|---|
NPB-PWR-H/U | DIN-mountable, 24V isolated power module, used to power the |
controller from a dedicated, external, Class-2, 24Vac transformer or a 24Vdc power supply.| Only one NPB-PWR-H/U per controller.
• Do not install if using NPB-WPM-US/U or NPB-PWR-UN-H/U.
• For wiring, see “NPB-PWR-H/U” on page 8.
NPB-PWR-UN-H/U| DIN-mountable, Universal 120–240Vac input, 15Vdc output, 30W power supply to power the controller.| Only one NPB-PWR-UN-H/U per controller.
• Do not install if using NPB-WPM-US/U or NPB-PWR-H/U.
• For wiring, see “NPB-PWR-UN-H/U” on page 8.
IO-16-H/U| DIN-mountable, 16 points I/O module, used to provide I/O points as noted.| Up to four (maximum) IO-16-H/U modules are supported. Each provides these I/O points:
• 8 – Universal Inputs (UIs).
• 4 – Digital Outputs (DOs), SPST-relay type.
• 4 – Analog Outputs (AOs), 0–10Vdc type.
Wiring is covered in the IO-16-H/U Installation Instructions.
IO-34-H/U| DIN-mountable, combined 34 points I/O with 24V isolated power module, used to provide
I/O points as well as power the controller from a dedicated, external, Class-2, 24Vac transformer or a 24Vdc power supply.
| Only one IO-34-H/U module per controller. This module provides these I/O points:
• 16 – Universal Inputs (UIs).
• 10 – Digital Outputs (DOs), SPST-relay type.
• 8 – Analog Outputs (AOs), 0–10Vdc type.
Wiring is covered in the IO-34-H/U Installation Instructions.
- a. A wall-mount AC adapter (NPB-WPM-US/U) is also available; however, it is not an accessory module that mounts on the 20-pin connector of the controller.
WIRING
See Fig. 3 on page 5 to locate connectors and components on the controller.
Make connections to the controller in the following order.
- Install any option card (LON, RS-485, RS-232, etc.) in the available option slots. See “Installing an Option Card” on page 6 for a procedure. For complete details, refer to the document that shipped with the option card. If installing the optional NiMH battery, do that after inserting option card(s). See “NiMH Battery Installation and Maintenance” on page 14.
- Connect the supplied grounding wire from the earth ground lug on the controller, as well ground wire for each accessory module, to a nearby earth grounding point. See “Grounding” on page 7.
- Prepare power wiring (leave the unit powered off). See “Power Wiring” on page 7.
- Connect communications cables. See “Communications Wiring” on page 9 for ports on the controller. For ports on any installed option card (485-PWR, LON, RS-485, modem) see the option’s specific mounting and wiring guide for details.
- If I/O accessory modules are installed, connect I/O wiring. Refer to the appropriate mounting and wiring guide for details.
- Apply power to the unit. See “Initial power up and check out.” on page 12.
Grounding
- An earth ground spade lug (0.187″) is provided on the controller base for connection to earth ground.
- For maximum protection from electrostatic discharge or other forms of EMI, connect the supplied earth grounding wire to this lug and nearby earth ground. Keep this wire as short as possible, see Fig. 4 on page 8.
- Wire the earth-ground spade lug of accessory modules in the same manner.
Power Wiring
The controller must be powered by an approved 15 Vdc power source.
This can be either a DIN-mountable module: the NPB-PWR-H/U, a 24Vac/dc-
powered module, or the NPB-PWR-UN-H/U, a line-powered 120–240Vac module. Or,
an external Class 2 wall mount AC adapter (NPBWPM- US/U) can be used for
controller power.
NOTE: See “Environmental Requirements” on page 3 for mains supply
requirements.
The controller does not include an on/off switch. To apply power, you
either:
- if NPB-PWR-H/U, plug in its 2-position power connector.
- if NPB-PWR-UN-H/U, energize the AC circuit (120– 240 Vac) wired to that module.
- if NPB-WPM-US/U, plug in the power connector to the controller.
CAUTION
Do not connect both the NPB-WPM-US/U and NPB-PWR-H/U / NPB-PWR-UN-H/U supplies
at the same time, or equipment damage may result.
Power consumption depends mainly on installed I/O modules, and may vary
from:
- Controller alone (with or without installed option cards): approximately 7.5 VA (AC) or 7.5 W (DC).
- Controller (with or without installed option cards), plus four (4) IO-16-H/U modules: up to 20 VA (AC) or 20 W (DC).
- a. A fourth power option is available: an IO-34-H/U accessory module, which is a combination of the NPB-PWRH/ U module and two IO-16-H/U modules (plus two extra relays). Refer to its mounting and wiring document for more details. For a listing of modules, see “About Accessory Modules” on page 6.
If desired, you can use the wall mount NPB-WPM-US/U in your office (to initially commission the controller), and then install the controller at the job using either an NPB-PWR-H/ U or NPB-PWR-UN-H/U module. The following sections provide more details:
- “NPB-PWR-H/U” on page 8 (24 Vac/dc-powered in-line module)
- “NPB-PWR-UN-H/U” on page 8 (Universal 120V– 240Vac-powered in-line module)
- “NPB-WPM-US/U (Wall Mount AC Adapter)” on page 9
NPB-PWR-H/U
Use the NPB-PWR-H/U module to power the controller (and if installed,
IO-16-H/U modules) from a dedicated Class 2, 24Vac transformer, or from a
24Vdc power supply.
- NOTE: If there is no optional NiMH backup battery, using the NPB-PWR-H/U allows a higher operating temperature. See “Environmental Requirements” on page 3.
- NOTE: If powering from a 24V transformer, do not power any other equipment with it. Otherwise, conducted noise problems may result. Also, do not ground either side of the transformer’s 24V secondary.
- Located at the bottom of the NPB-PWR-H/U module is a 2-position power connector, and an earth ground spade lug, as shown in Fig. 4.
- Connect the supplied earth ground wire to a nearby earth ground point. Unplug the power connector plug from the module and make connections to it as shown.
CAUTION
- Do not plug 24V power into the NPB-PWR-H/U(reinsert connector plug) until all other mounting and wiring is completed. See “Initial power up and check out.” on page 12.
NPB-PWR-UN-H/U
- The NPB-PWR-UN-H/U module lets you power the controller (and if installed, connected I/O modules) from AC line power, with a universal input range from 120– 240Vac. If installing IO-16-H/U modules, the NPB-PWRUN- H/U module mounts as the last (end) module in the chain. (See Fig. 1 on page 4).
WARNING
- A 120Vac or 240Vac circuit powers the NPBPWR- UN-H/U. Disconnect power to this circuit before installation to prevent electrical shock or equipment damage.
- Make all connections per national and local electrical codes. Use copper conductors only.
- Do not exceed the 30W capacity of NPBPWR- UN-H/U by the powered devices.
Wiring NPB-PWR-UN-H/U input power and earth ground.
- Remove power from the AC circuit being wired to the NPB-PWR-UN-H/U. See the previous Warning.
- Remove the NPB-PWR-UN-H/U cover. To do this, press in the four tabs on both ends of the unit, and lift the cover off. If the controller or an IO-16-H/U accessory module is plugged into the unit, you may need to slide it away to get to the cover tabs.
- Connect the supplied earth grounding wire to a nearby grounding point. See Fig. 5.
- Make AC circuit connections line (mains) and neutral to the terminals labelled “INPUT PWR.”
- Replace the cover on the NPB-PWR-UN-H/U module. Make sure all modules in the mounted assembly are firmly connected and secured.
- CAUTION
- Do not energize the AC circuit wired to the NPB-PWR-UN-H/U until all other controller mounting and wiring is completed. See “Power Up and Initial Checkout” on page 12.
- NPB-WPM-US/U (Wall Mount AC Adapter)
- The NPB-WPM-US/U is a self-contained, isolated, Class 2, switching power supply designed to plug into a standard building power receptacle of appropriate voltage.
- To supply power to the controller, you simply plug the barrel connector plug from the NPB-WPM-US/U into the barrel power connector on the controller’s baseboard (see Fig. 3 on page 5).
- NOTE: The adapter’s 15W output rating is derated 50% at the 60°C (140°F) maximum ambient temperature (for a controller without a NiMH battery), such that no I/O modules are supported at 60°C. See “Environmental Requirements” on page 3.
CAUTION
- Do not plug the barrel connect plug from the NPB-WPM-US/U into the controller until all other mounting and wiring are completed. See “Initial power up and check out.” on page 12.
Communications Wiring
- Communication ports are on the controller’s bottom side, which includes:
- Ethernet
- Serial
NOTE: Before connecting cables, provide strain relief for them to prevent damage to the controller.
Ethernet
- Two, female 10/100-Mbit Ethernet connections are provided on the controller. These RJ-45 connectors are labelled LAN1 (PRI) and LAN2 (SEC). Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch.
- The factory-default IP address for LAN1 is 192.168.1.12n, where the last numeral n in the address matches the last digit in the controller’s serial number, and the subnet mask is 255.255.255.0. By default, LAN2 is disabled.
- NOTE: Typically, you only use LAN1 (primary port), unless you have a specific application for the other LAN2 port. For example, isolating a driver’s network traffic, using LAN2. Do not use LAN2 as the primary port.
- If enabling LAN2, note that LAN1 and LAN2 must be connected to different subnets. Further, a controller does not provide IP routing or bridging operation between the two LAN ports.
- Refer to the JACE WEBs-AX Install and Startup Guide for details on changing IP addresses using the platform Commissioning Wizard (TCP/IP configuration step).
Serial
- There are two “RS” serial ports on the controller’s baseboard. Each has a UART capable of operating up to 115,200 baud. At the bottom of the board (see Fig. 6) is an RS-232 port using a DB-9 plug (male) connector.
- To the right of this is a two-wire plus shield RS-485 port, using a 3-position screw-terminal connector plug.
- NOTE: A green “receive” LED and a yellow “transmit” LED are provided for both serial ports. These LEDs are on the controller’s bottom board, on the side opposite the serial connectors (see Fig. 3 on page 5). These LEDs are labeled on the board (COM1, COM2) and are not visible with the cover on.
RS-232
- An RS-232 serial port using a male DB-9 connector always operates as COM1. You can use standard DB-9 serial cables with this port.
- The controller is a serial DTE device, such that another DTE device (PC, for example) requires a “null modem” cable. If connecting to a DCE device such as a modem, use a straight-through cable. Table 4 provides standard serial DB-9 pinouts.
- NOTE: If rebooted with the mode jumper in the “Serial Shell” position (see Fig. 3 on page 5), the RS-232 port provides “system shell” access. See the JACE WEBs-AX Install and Startup Guide for related details.
Table 4. Base serial port (RS-232 and RS-485) pinouts.
RS-485
- An RS-485 port uses a 3-position, screw terminal connector, and always operates as COM2.
- As shown in the Table 4 pinouts, from left to right the screw terminals are shield (S), plus (+), and minus (–).
- Wire in a continuous multidrop fashion to other RS-485 devices, meaning “minus to minus”, “plus to plus,” and “shield to shield.”
- Connect the shield to the earth’s ground at one end only, such as at the controller.
RS-485 Biasing
- The RS-485 port on the controller’s baseboard has a pair of two-pin jumpers that can be shorted with jumper blocks to provide “biasing”. As shipped from the factory, these pins are not shorted, thus the RS-485 port is unbiased.
- NOTE: See “Need for RS-485 Bias” before following the “Adding RS-485 Bias” procedure. In many cases, the default unbiased RS-485 port is preferred.
Need for RS-485 Bias
- NOTE: A full discussion of communication line termination is beyond the scope of this document.
- Biasing sometimes improves RS-485 communications by eliminating “indeterminate” idle states. When you install two, 2-pin shorting blocks on the controller’s RS-485 bias jumper pins, this adds two onboard 3.3K ohm resistors into the controller’s RS-485 circuit, as follows:
- from RS-485 “+” to 5V.
- from RS-485 “-” to Ground.
- NOTES: In general, only one device on an RS-485 trunk should be biased. Otherwise, undue loading of the circuit may result, with fewer devices supported.
- RS-485 bias resistors are different than “termination resistors”, externally installed at the two physical ends of a daisy-chained RS-485 trunk, across the “+” and “–” terminals. Termination resistors are typically 100 or 120-ohm value resistors.
- Whenever termination resistors are used, RS-485 biasing is typically required.
Adding RS-485 Bias
- To add biasing, you must power off the controller and remove a few assemblies (such as metal shield and NPM3E or NPM6E processor module) to access the baseboard jumper pins, located behind the RS-485 port. Then you must reposition the two shorting blocks on these jumper pins.
- Then you reassemble the unit by remounting the processor module, hex standoffs, metal shield, and shield screws.
WARNING
- Remove all power from the controller before working on the unit.
- Observe static discharge precautions. See the “Static Discharge Precautions” section.
- If the controller is already installed or mounted, it is recommended that you remove it first. Then work on a flat, stable, well-lit work surface.
Disassembling the controller.
- Remove all power from the controller. (See previousWarning).
- Remove the plastic cover. See “Removing and Replacing the Cover” on page 4.
- Remove the four Phillips head screws that secure the metal shield, and set them aside.
- Remove the metal shield and set it aside. To do this, carefully pry up from the top (hole-vented side) first, then push out the other side to slip the port holes past the port edges. Then lift the shield up and away.
- NOTE: Be mindful of the “side clips” on the controller’s two Ethernet ports.
- Use a 1/4 in. (7 mm) nut driver to unscrew the four metal standoffs, and set them aside.
- Carefully pry up the NPM3E or NPM6E processor module board, noting that the two-row, 50-pin connector is on the option card side. Keep the board level as you work it loose from this connector.
- Set the processor module board aside. Note the jumper block on the baseboard behind the RS-485 port (see bottom of Fig. 7).
Installing shorting blocks to add RS-485 biasing.
- Locate the four jumper pins behind the RS-485 port, with 2-pin shorting blocks installed on one pin each. See Fig. 8.
- To add biasing, remove and replace both shorting blocks back onto the jumper pins, as shown in Fig. 8.
Reassembling the controller.
- Carefully replace the processor module board with the 50-pin connector, with its corner mounting holes aligned on the four lower standoffs. Press down on the connector to fully seat the board. See Fig. 7 on page 11.
- Refasten the four metal hex standoffs, hand tightening with a 1/4 in. (7 mm) nut driver.
- Replace the shield onto the unit. To do this, carefully ease it over the port side first, then spring it down over the other side. Make sure that its corner holes align with the metal standoffs below.
- Refasten the four Phillips head screws that secure the shield to the standoffs.
- Replace the plastic cover on the unit.
POWER UP AND INITIAL CHECKOUT
- Ensure power wiring to the controller is ready—see “Power Wiring” on page 7. See Fig. 3 page 4 for the location of status LEDs and connectors. See Fig. 4 on page 8 for the location of the NPB-PWR-H/U module’s power connector. After completing all mounting and wiring, do the following:
Initial power-up and checkout.
- Apply Power.
- Check the Status LED. Also, see the section “About Backup Configurations” on page 13.
Apply Power
- To apply power, insert the power plug into either the NPBPWR- H/U module, or if using a NPB-WPM-US/U wall adapter, the controller.
- If using the line-voltage input NPBPWR- UN-H/U power supply module, energize the 120– 240Vac circuit wired to the module.
CAUTION
- Do not connect both the NPB-WPM-US/U and NPB-PWR-H/U / NPB-PWR-UN-H/U supplies at the same time, or equipment damage may result.
Check the Status LED
- When power is applied, the green LED labelled “STATUS” will light.
- This indicates that the system is OK, with power applied. When the controller finishes booting, the yellow “BEAT” LED should be blinking steady at a 50% duty cycle, typically at a 1Hz rate.
- In most cases, this blink pattern starts about 30 seconds after power is applied.
- If after applying power, the STATUS LED goes out, or if the BEAT LED comes on (steady) and stays lit for over 2 minutes, seek technical assistance. See the section “LED Status Indicators” on page 13, especially “Heartbeat”.
ABOUT BACKUP CONFIGURATIONS
- A 300E or 600E series controller allows two separate and configurable methods to preserve unsaved station data when “power quality events” occur, including loss of primary power or low-voltage dips (brownout):
- Using the integral static RAM (SRAM) on the controller’s NPM3E or NPM6E processor module. This default method can allow the unit to operate “batteryless”, that is, without installing the optional NiMH battery pack. Note in this configuration a controller reboot is likely to occur whenever a power outage or voltage dip is sustained for more than one AC line cycle (1/50th or 1/60th of a second) or several line cycles, depending on the load and power supply. Critical station data will already be saved before any power quality event, but the NiMH battery option is available to prevent nuisance controller reboots/station restarts during extended or frequent power outages.
- An optional on-board NiMH battery pack. Installing this battery allows the controller to continue operation (without rebooting) over short power outages or brownouts lasting several seconds (or if also using SRAM, up to 10 minutes). For longer-duration outages, the battery allows the controller to perform a“controlled shutdown”, safely backing up the station before shutting down.
- Starting in the WEBs-AX 3.6.47 maintenance build, the controller can use both the NiMH backup battery and available SRAM for backup protection (before this, SRAM support required removing backup batteries).
- Configuring for both backup battery and SRAM support provides the most comprehensive backup protection.
- This allows the controller to “ride out” brief power outages, while also protecting against a scenario of a battery too weak (or aged) to perform a controlled shutdown.
SRAM
- The controller’s NPM3E or NPM6E processor module includes on-board SRAM and associated circuitry, allowing “battery-less” operation.
- This is the same circuitry as provided by the “SRAM option card” for earlier QNX-based controller models, available since the initial release of WEBs-AX 3.6.47.
- Therefore, an SRAM option card is not needed (or supported) in a 300E or 600E series controller.
- The default configuration is to use SRAM for station backup, via the platform “DataRecoveryService” that is automatically created in the controller’s running station.
- However, in some cases, a station may be a poor candidate for SRAM support, requiring too many resources by this associated platform service.
- An example is a station with many rapidly changing values all captured as histories, on COV. In this case, you may wish to disable SRAM support and install and use only the optional NiMH battery pack.
- For an overview, see “About Backup Configurations” on page 13. Complete WEBs-AX details on the operation of the controller’s integral SRAM are in the JACE Data Recovery Service (SRAM support) – Engineering Notes document.
NiMH battery pack
- A custom 10-cell NiMH (nickel metal hydride) battery assembly is available as a separately orderable option for a 300E or 600E series controller. This battery assembly includes a metal bracket with a tie-wrapped NiMH battery pack. It is the same battery assembly installed in the previous 201 and 600 series controllers.
- This battery allows the controller to continue station operation through short power bumps, ranging from a few seconds to a minute or more in duration (up to 10 minutes, if also using SRAM). If a longer outage, the NiMH battery provides enough run time for the unit to backup data and then shutdown. Shutdown occurs automatically after data is backed up to on-board flash memory.
- The controller charges the battery during normal operation, until fully charged. Typically, the charge operation is completed within 18 hours. Following a power outage, the battery is charged again, as necessary.
- The power and battery circuitry is monitored by a station running on the JACE (via its PowerMonitorService).
- Station alarms are generated whenever primary power is lost, or if the battery is uncharged or unable to hold a sufficient charge.
NOTE:
- A NiMH battery characteristic is to lose charge if not left in charge mode (trickle charge).
- Leaving the battery unconnected, or in the unit powered off will cause the battery to fully discharge in a matter of weeks. Note that a new NiMH battery may be partially discharged.
- Therefore, allow at least 18 hours for a new battery to charge if it has not been in a powered unit.
- The NiMH battery assembly should be replaced approximately every three years, or more often if the unit is in a high-temperature environment. For more details, see “NiMH Battery Installation and Maintenance” on page 14.
LED STATUS INDICATORS
The controller includes several LEDs that can help determine the status of the
unit. They are located in two places: the top of the controller, visible
through the cover, and for serial ports, on the bottom board (only with the
cover removed).
From left to right these LEDs include:
- Visible on the cover:
- Ethernet Ports
- Heartbeat
- Status
- Bottom board only:
- Serial Ports
Ethernet Ports
Each Ethernet port has a green LED, labelled on the top cover “LAN2” (or
“SEC”), and “LAN1” (or “PRI”). The LED indicates activity on that LAN2
(secondary) port or LAN1 (primary) port as follows:
- Off — No Ethernet link is made.
- On — Ethernet link is present, but no activity on the LAN.
- Blinking — Ethernet link is present with data activity on the LAN.
Heartbeat
- A yellow heartbeat “BEAT” LED is next to the Ethernet LEDs, also visible on the cover. In normal operation, this LED blinks at 1 Hz, at 50%/50% on/off duty cycle. During controller bootup, this LED blinks at 1 Hz with a 90%/10% on/off duty cycle on any controller running WEBs-AX-3.7 update 1 (build 3.7.106) or later.
- When bootup completes, the platform daemon is started, and the normal (50%/50%) duty cycle heartbeat flash pattern returns.
CAUTION
- This same 90%/10% on/off “BEAT” flash occurs during critical operations, such as any firmware upgrade (in progress) to the controller and/or any attached I/O modules. To be safe, do not remove power from the controller while its “BEAT” LED flashes with a 90%/10% on/off duty cycle. Wait for the normal (50%/50%) flash to return before removing power.
- If the “BEAT” LED stays on constantly, does not light, or blinks very fast—more than 1Hz (once per second), seek technical support.
Status
- The green “STATUS” LED is next to the heartbeat LED and is visible on the cover. This LED provides a CPU machine status check and should remain lit whenever the controller is powered. If the status LED does not light while power is applied, seek technical support.
Serial Ports
- LEDs for the two serial ports are located on the controller’s bottom board, on the opposite side of the RS-232 and RS-485 ports. Labels “COM1” and “COM2” correspond to the software configuration of the COM ports. LEDs show the transmit and receive activity for the serial ports and optional modem.
NOTE: You must remove the cover to see these LEDs. See “Removing and Replacing the Cover” on page 4.
- The yellow transmit LED indicates that the controller is sending data out of the serial port over a communications line to a connected device.
- The green receive LED indicates that the controller is receiving data from a connected device.
- Serial port LEDs provide a fixed on-time when data is detected on the port. If the receive LED is on constantly, this indicates a problem with the communications channel, such as a shorted wire or reversed wiring.
MAINTAINING THE CONTROLLER
This section provides information on the following topics:
- Cleaning
- NiMH Battery Installation and Maintenance (optional)
- Replacement Parts
- Replacing the Controller Base Assembly
- Returning a Defective Unit
Cleaning
- If dust or metal filings are present inside the unit, clean with vacuum or compressed air. Otherwise, no cleaning inside the unit is required. Optionally, if the cover becomes dirty, you can wipe it with a damp cloth and mild detergent.
NiMH Battery Installation and Maintenance
- Installing or replacing the optional NiMH battery
- Battery maintenance
- Battery disposal
INSTALLING OR REPLACING THE OPTIONAL NIMH BATTERY
- The optional NiMH battery pack is sold as an assembly, that is a custom battery pack with an attached cable and connector plug, mounted on a bracket.
- To install (or replace) the battery, you must remove power to the controller and remove its cover.
- Then you mount the battery assembly on top of the option card area (Fig. 9).
CAUTION
Use only NiMH battery packs approved for use with the controller.
Installing/replacing WEB/CP-300E or WEB/CP-600E/U series controller NiMH battery assembly.
- If replacing an existing battery in a controller not currently configured for SRAM usage, backup the controller’s configuration to your PC using the appropriate WEBs-AX software tool (for example, Workbench).
- If a station is running, stop it using the platform Application Director view.
- Remove all power from the controller. Wait for all LED activity to stop (if a battery is already installed, this may take a minute or two).
- Remove the cover. See “Removing and Replacing the Cover” on page 4. Note the Option Slot area where the NiMH battery assembly mounts.
- If a battery assembly is already mounted, unplug the battery from the connector on the controller board (see Fig. 9).
- Remove the four screws that secure both option slot end plates (and if installed, the existing battery assembly bracket). Set the screws aside. Remove any existing battery assembly (if applicable).
- Plug the battery connector plug of the new battery assembly into the battery connector on the controller (see Fig. 9).
- Set the new NiMH battery assembly on top of the option card slots, over the option card end plates. Ensure the bracket mounting holes are aligned with the standoffs.
- Place the four screws through the battery bracket, option card end plates, and into the standoffs on the controller’s baseboard. Using a screwdriver, hand tighten these screws.
- Replace the cover.
- Restore power to the controller and verify normal operation.
Battery maintenance
- Battery life expectancy is a function of its discharge cycles (the number of discharges and their depth) and the ambient temperature of the battery during normal operation. In most applications, the NiMH battery should see relatively few discharges.
- Therefore, ambient temperature has more to do with the life expectancy of the battery than any other factor. If the controller is installed in a conditioned space, this battery should provide dependable service for approximately three years (average).
- In an environment where the operating temperature reaches the highest range (50 ºC or 122 ºF), you should only expect the battery to last around one year.
- A new NiMH battery is typically only partially charged when shipped. Additionally, NiMH batteries lose charge over time if not kept trickle-charged (for more details, see “NiMH battery pack” on page 13).
- Therefore, even a new or replacement battery will require up to 18 hours of powered operation before it can provide reliable backup power (is at full charge).
- The controller monitors the NiMH battery and periodically loads the battery to test its ability to maintain battery-backed functions. Investigate any battery trouble messages, and check the battery connections to the unit.
- Replace the battery as required. To order a new battery, see “Standard Replacement Parts” on page 16.
Battery disposal
- Please dispose of the used NiMH battery following local, state, and federal regulations.
WARNING
- Do not incinerate or mutilate the battery, as this may cause it to burst or release toxic materials.
- If regulations specify returning the old battery to a recycling centre, but no acceptable recycling centre can be found, please return the old NiMH battery pack to Tridium for proper disposal.
REPLACEMENT PARTS
- Servicing the controller may call for replacement parts.
There are three categories of parts:
- Non-replaceable Parts
- Standard Replacement Parts
- New Replacement Unit
Non-replaceable Parts
- Other than the parts listed in the replacement parts sections, there are no serviceable components on the base assembly.
MEMORY
- Any addition, modification, or replacement of memory components requires software configuration and is not a field upgrade.
FUSE
- The controller contains a non-user replaceable fuse, soldered on the circuit board. This fuse protects from internal shorts or connection to incorrect power supplies. If the fuse circuitry is suspect, seek technical support. See “Returning a Defective Unit” on page 17.
Standard Replacement Parts
- Standard replacement parts are listed in Table 5 and can be ordered from stock without restriction. Standard replacement parts cannot be returned for credit and should be disposed of properly.
Table 5. Standard replacement parts for a WEB/CP 300E or WEB/CP 600E controller.
Part Number | Description |
---|---|
NPB-BATTERY/U | Optional NiMH Battery Pack—see “NiMH Battery Installation and |
Maintenance” on page 14
H10027/U| RS-485 connector plug, 3-position.
New Replacement Unit
- To replace an entire unit, order and install a new WEB/ CP-300E or WEB/CP-600E/U controller. If the faulty controller is still under warranty, you can receive credit by returning it. Be sure to contact the vendor for a return authorization (RA) number before shipping an item for return credit. See “Returning a Defective Unit” on page 17, for more details.
- NOTE: Before ordering a new controller, it is strongly recommended that you contact your normal technical support resource to eliminate the possibility of a software issue or misconfiguration problem.
Replacing the Controller Base Assembly
- NOTE: Before handling circuit boards, discharge any accumulated static by touching a nearby earth ground. For details, see the “Static Discharge Precautions” section on page 6.
- To replace a controller with a new replacement unit, proceed as follows:
REPLACING A WEB/CP-300E OR WEB/CP-600E/U CONTROLLER.
- If possible, use the appropriate WEBs-AX software tool to back up the controller’s configuration to your PC.
- Remove power to the controller. The unit should power down automatically. Wait for all LEDs to remain off.
- NOTE: If IO accessory modules are installed, and any I/O points have voltage, turn the devices off or disconnect power to them.
- Note the positions of all communications and other wiring cables going to the controller, as well as installed accessory modules (if they must be removed). If necessary, label connectors and accessory modules to avoid mis-connection later, after the controller is replaced.
- Unplug all Ethernet, serial, LON, modem, and I/O connectors from the controller.
- If IO accessory modules are installed:
- a. If DIN rail mounting with DIN end clips was used, you may be able to remove the DIN rail end clip that secures the 600E controller end of the assembly, and then slide the controller away from the rest of the assembly. Then you can remove the controller from the DIN rail (see Fig. 1 on page 4), leaving the mounting and wiring of IO modules untouched. In this case, after removing the controller from the DIN rail, go to Step 6.
- b. If tab (screw) mounting was used instead of DIN rail mounting, or if a combination of DIN mounting and tab screws was used (into the controller’s “accessory side” tab holes, see last page), you will need to remove accessory modules first, before removing the controller. In this case:
- Making a careful note of all wiring terminations, unplug the I/O connector plugs and earth ground wires from the installed IO modules.
- Remove the installed accessory modules, starting with the end module.
- Remove any screws fastening the controller, and remove it (see Fig. 1).
- Remove the cover of the old unit. See See “Removing and Replacing the Cover” on page 4. Note the position of installed option cards, if any. You must transfer them to the replacement controller.
- Remove any option cards from the old controller and install them into the replacement controller, if applicable. See See “Installing an Option Card” on page 6. for more details.
- Check the RS-485 biasing jumpers on the existing unit, and duplicate on the replacement unit (See “Disassembling the controller.” on page 11.)
- Mount the replacement controller as it was previously, using the same DIN rail location and/or screws.
- Reconnect/remount any removed accessory modules, being careful to replace in the same order, using the same DIN rail location and/or screws. Secure all modules as done previously.
- Reconnect the earth-ground wire to the controller’s grounding lug and any installed accessory modules.
- Reconnect any Ethernet, serial, modem, and I/O connectors.
- If using IO modules, and any of your I/O points have voltage, turn the devices back on, or reconnect power to them.
- Replace the cover. See “Removing and Replacing the Cover” on page 4.
- Restore power to the unit. It should boot up as a new unit (See “Check the Status LED” on page 12.).
- Using the WEBs-AX platform tools, re-commission the controller, and install the saved station database. For more details, see the JACE WEBs-AX Install and Startup Guide.
Returning a Defective Unit
- For proper credit on an in-warranty unit, ship the defective unit per the vendor’s return material procedures.
- NOTE: If the defective unit is under warranty, please follow the return instructions provided in this section.
- If the unit is out of warranty, please discard any replaced parts. Do not return an out-of-warranty controller.
- Before returning the unit, contact your vendor to obtain a return materials authorization (RMA) number and other instructions.
Please provide:
- Product model
- Serial number
- Nature of the defect
- PO number to secure the RMA
CERTIFICATIONS
The WEB/CP-300E and WEB/CP-600E/U controller each has the following agency listings, compliances, and certifications:
- UL 916 – Underwriters Laboratories, Energy Management Device, CAN/CSA C22.2 Canadian
Safety Standards
- FCC Part 15, Class B – Federal Communications
Commission
- ICES-003, Class B – Industry Canada Interference-
Causing Equipment Standard
- EU 202/95/EC RoHS (Restriction of Hazardous Substances)
- CE Declaration of Conformity (Council Directive 004- 108-EC)
- For complete details on listings and compliances for these controllers, refer to the document Agency Listings and Approvals for Tridium Hardware Products.
TAB MOUNTING DIMENSIONS
Measurements are in inches and (mm). Note that DIN mounting is recommended over tab mounting. See Fig. 1 on page 4.
CONTACT
- Automation and Control Solutions
- Honeywell International Inc.
- 1985 Douglas Drive North
- Golden Valley, MN 55422
- customer.honeywell.com
- ® U.S. Registered Trademark
- © 2013 Honeywell International Inc.
- 31-00010—01 M.S. 09-13
- Printed in the United States
- WEB-300E, WEB-600E/U, CP-300E, CP-600E/U SERIES CONTROLLERS