The Excel 50 controller has built-in communication capability, allowing it to
be integrated into a Honeywell EXCEL 5000® System or into an open LONWORKS®
network communicating with Excel 10 controllers as room/zone controllers or
with 3 party products. It can also serve as a stand-alone controller. Typical
areas of application include heating systems, district heating systems, and
air conditioning plants for restaurants, shops, offices, and small branch
government buildings.
The Excel 50 supports standard LonMark™ Network Vari- ables according to the
LonMark™ Interoperability Guidelines V.3.0. It can serve 22 integrated I/Os
and supports peer-topeer communication; thus, in the case of larger-scale
applications, several different controllers can be linked and accessed. The
system firmware is stored in Flash EPROM located in the application module (a
separate module plugged into the controller housing.) Flash EPROM allows easy
upgrading of the operating system via download.
The Excel 50 is a freely programmable controller engineered using Honeywell’s
CARE programming tool. For LONWORKS® interoperability, a maximum of 46
LonMark™ NVs are available.
FEATURES
- Various state-of-the-art communication options: Open LONWORKS® bus, Meter-bus, or C-bus communication
- Unique features in open LONWORKS® networks: NVBooster® reduces the number of required NVs and thus also the number of required controllers; NV bindings can be restored after controller reset (and thus need not be redone after exchanging controllers); 46 NVs supported for LONWORKS® integration
- Reduced engineering and start-up costs: Huge variety of pre-tested and fully documented applications
- Easy and flexible installation: Screw terminals; mounting inside cabinet (DIN rail) or in cabinet front door
- Operating options: Integrated operator interface, XI582 Remote Interface, XI882 Remote Touch-Panel Interface, and XL-Online PC-based interface
DESCRIPTION
The Excel 50 controller is available in two housing versions, one with and one
without a Man-Machine-Interface (MMI.) The MMI version allows buswide access
to other controllers. The XI582 operator interface or the PC-based XL-Online
operator and service software can be used in conjunction with either version.
The housing can be mounted inside a cabinet on a DIN-rail or in a cabinet
front door. The Excel 50 has eight analog inputs, four analog outputs, four
digital inputs (three of which can be used as totalizers,) and six digital
outputs. The digital outputs allow the direct drive of 3-position actuators
(up to the max. load.)
The controller can be wired either with screw terminal blocks directly at the
housing.) Pre-wiring is possible in both cases, and a controller can be
replaced without rewiring.
The application modules – all with Flash EPROM – are available in five bus-
wide access versions and one standalone version. They feature a variety of bus
interfaces (see Table 1.) Large RAMs provide for increased trending
capability. All changeable parts or switches are accessible without opening
the housing. Communication capabilities and memory are easily upgraded by
replacing application modules.
SPECIFICATIONS
Versions
Housing
- XL50A-MMI and XL50A-CY (with Man-Machine Interface);
- XL50A (without MMI.)
Versions with MMI
Both the XL50A-MMI and the XL50A-CY feature a keypad (with eight function keys
and four fast-access keys) and an LCD display.
- The LCD display of the XL50A-MMI has four lines, 16 characters per line, adjustable contrast, and backlight.
- The LCD display of the XL50A-CY features 128 X 64 dot graphics, adjustable contrast, and backlight.
Application Modules
The Excel 50 controller can be upgraded by direct firmware download via
serial port or C-Bus. Contact your local Honeywell affiliate for more
information on the available firmware and applications.
Table 1. Module versions
module | description |
---|---|
XD50C-F | Stand-alone; 2 MB Flash EPROM; 256 KB RAM; European and Chinese |
language support
XD50C-FC| Bus-wide access via C-Bus; 2 MB Flash EPROM; 256 KB RAM; European
and Chinese language support
XD50C-FL| Bus-wide access via LONWORKS® Bus; 2 MB Flash EPROM; 256 KB RAM;
European andChinese language support
XD50C-FCL| Bus-wide access via C-Bus / LONWORKS® Bus; 2 MB Flash EPROM; 256 KB
RAM; European and Chinese language support
XD50-FCS| Bus-wide access via C-Bus / Meter-Bus; 1 MB Flash EPROM; 256 KB RAM
XD50-FLS| Bus-wide access via LONWORKS® / Meter-Bus; 2 MB Flash EPROM; 256 KB
RAM
Mounting Options
Front door mounted with sealing ring.
Cabinet mounted on DIN-rail (rail clips shipped with device.)
I/O Terminal Connection
Screw terminal blocks directly attached to housing.
Power Supply
Voltage
24 Vac, ±20 %, 50/60 Hz from external transformer.
Current
3 A (2 A if digital output current 1.5 A.) In case of power failure, the
super gold capacitor saves RAM content and realtime clock for 72 hours (thus,
no battery disposal necessary.)
Power Consumption
Max. 10 VA without load at digital outputs.
Input/Output Specifications
type | characteristics |
---|---|
eight analog inputs (universal) | Voltage: 0…10 V (software-controlled switches |
for high impedance)
Current: 0…20 mA (via external 499 resistor) Resolution: 10-bit
Sensor: NTC 20k, -58…+302 °F (-50…150 °C)
four digital inputs| Voltage: max. 24 Vdc ( 2.5 V = logical status of 0, 5 V
= logical status of 1,) 0…0.4 Hz
(0…15 Hz for three of four inputs when used as totalizer, 4th input only for
static parameter requirements)
four analog outputs (universal)| Voltage: 0…10 V, max. 11 V, ±1 mA
Resolution: 8-bit
Relay: via MCE3 or MCD3
six digital outputs| Voltage: 24 Vac per triac
Current: max. 0.8 A, 2.4 A for all six triacs together
All inputs and outputs protected against overvoltage up to 24 Vac and 35 Vdc.
Digital outputs protected against short circuits via a changeable fuse (built-
in fuse, 5 x 20 mm, 4 A quick-blow.)
Bus and Port Connections
C-Bus Connection
Optional; located on application module. Up to 76.8 Kbaud, switch provided for
selectable termination.
LONWORKS® Bus Connection
Optional; located on application module. 78 Kbaud, FTT-10A Free Topology
Transceiver, using LonTalk® protocol.
Controller Serial Port Connection
9-pin Sub-D connector, RS 232, 9.6 Kbaud for XI582, XL- Online.
Meter-Bus Connection
Optional; located on application module. RS232 serial link with RJ45 connector
(PW3 Meter-Bus adapter also required.)
I/O Connectors
I/O Connector A: 26-pin port, digital outputs and power.
I/O Connector B: 34-pin port, analog and digital inputs, analog outputs.
Environmental Ratings
Operating temperature: | 0…50 °C (+32…+122°F) |
---|---|
Storage temperature: | -20…+70 °C (-4…+158°F) |
Relative humidity: | 5…93% non-condensing |
Purpose: | for home (residential, commer- |
cial, and light-industrial) environments
Construction:| for incorporate mounting in
cabinets
RFI, EMI Pollution degree:| according to CE regulations
Action:| Class II
TySoftware:| Type 1
| Class A
ClImpulse voltage:| 500 V
Protection Standards
IP54 (when front-door mounted with MMI in a cabinet conforming to IP54 and use
of ACC3 mounting clamps and sealing ring.)
IP20 (when wall-mounted: both with and without MMI.) UL94-0: Flame-retardant
class of housing material.
Certifications
- CE
- UL 916 and cUL
- Meets FCC Part 15, Subpart J for Class A equipment.
Application Module
Firmware
The firmware is downloadable via the PC-based XL-Online operator and service
software or C-Bus.
Housing
Plug-in plastic module, wired with screws.
Application Module LEDs and Ports Terminal Blocks
Dimensions
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 01
Fax +49 (0) 7031 637 740
http://ecc.emea.honeywell.com
EN0B-0088GE51 R0215
Subject to change without notice
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>