LG AUUW36GC0 Air Conditioner Instruction Manual
- June 16, 2024
- LG
Table of Contents
LG AUUW36GC0 Air Conditioner
Please read this installation manual completely before installing the product. Installation work must be performed by the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly. Ɠ This product contains Fluorinated Greenhouse Gases. (R410A)
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
- Excessive cooling may be harmful to your health and may consume more electricity.
- Block sunlight with blinds or curtains while you are operating the air conditioner.
- Keep doors or windows closed while you are operating the air conditioner.
- Adjust the direction of the airflow vertically or horizontally to circulate indoor air.
- Speed up the fan to cool or warm indoor air quickly, in a short period.
- Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
- Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the airflow or weaken the cooling/dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of
purchase or for warranty purposes. Write the model number and the serial
number here:
Model number :
Serial number :
You can find them labeled on the side of each unit.
Dealer’s name :
Date of purchase
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and
ensure peak performance of your product
WARNING
Serious injury or death can result if directions are ignored.
CAUTION
Minor injury or product damage can result if directions are ignored.
WARNING
- Installation or repairs made by unqualified persons can result in hazards to you and others.
- Refrigeration work must be performed by a qualified person who is “F-Gas” registered.
- Installation work must be performed by the National Electric Code by qualified and authorized personnel only.
- The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
- Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
- Do not use a defective or underrated circuit breaker. Use the correctly rated breaker and fuse.
- There is risk of fire or electric shock.
- For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service
- Center. Do not disassemble or repair the product by yourself. There is risk of fire or electric shock.
- Always ground the product as per the wiring diagram. Do not connect the ground wire to gas or water pipes lightening rod or telephone ground wire. There is risk of fire or electric shock.
- Install the panel and the cover of control box securely. There is risk of fire or electric shock due to dust , water etc.
- Use the correctly rated breaker or fuse. There is risk of fire or electric shock.
- Do not modify or extend the power cable. If power cable is damaged or has deteriorated, then it must be replaced. There is risk of fire or electric shock.
- For installation, removal or reinstall , always contact the dealer or an Authorized Service
- Center. There is risk of fire, electric shock, explosion, or injury.
- Do not install the product on a defective installation stand. Be sure that the installation area does not deteriorate with age. It may cause product to fall.
- Never install the outdoor unit on a moving base or a place from where it can fall down.
- The falling outdoor unit can cause damage or injury or even death of a person.
- In outdoor unit the step-up capacitor supplies high voltage electricity to the electrical components. Be sure to discharge the capacitor completely before conducting the repair work.
- A charged capacitor can cause electrical shock.
- When installing the unit, use the installation kit provided with the product. Otherwise the unit may fall and cause severe injury.
- Indoor/outdoor wiring connections must be secured tightly and the cable should be routed properly so that there is no force pulling the cable from the connection terminals.
- Improper or loose connections can cause heat generation or fire.
- Safely dispose off the packing materials. Like screws, nails, batteries, broken things etc after installation or svc and then tear away and throw away the plastic packaging bags. Children may play with them and cause injury.
- Be sure to check the refrigerant to be used. Please read the label on the product. Incorrect refrigerant used can prevent the normal operation of the unit.
- Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it may cause fire, electric shock, explosion or death.
- Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Installation Tools
Operation
- When the product is soaked (flooded or submerged) in water , contact an Authorized Service Center repair before using it again. There is risk of fire or eletric shock.
- Be sure to use only those parts which are listed in the svc parts list. Never attempt to modify the equipment. The use of inappropriate parts can cause an electrical shock, excessive heat generation or fire.
- Do not touch , operate, or repair the product with wet hands. Hold the plug by hand when taking it out. There is risk of electric shock or fire.
- Do not place a heater or other heating appliances near the power cable. There is risk of fire and electric shock.
- Do not allow water to run into electric parts. Install the unit away from water sources. There is risk of fire, failure of the product, or electric shock.
- Do not store or use or even allow flammable gas or combustibles near the product. There is risk of fire.
- Do not use the product in a tightly closed space for a long time. Perform ventilation regularly.
- Oxygen deficiency could occur and hence harm your health.
- Do not open the front grille of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.) There is risk of physical injury, electric shock, or product failure.
- If strange sound, smell or smoke comes from product. Immediately turn the breaker off or disconnect the power supply cable. There is risk of electric shock or fire.
- Ventilate the product room from time to time when operating it together with a stove, or heating element etc. Oxygen deficiency can occur and hence harm your health.
- When the product is not to be used for a long time, disconnect the power supply plug or turn off the breaker. There is risk of product damage or failure, or unintended operation.
- Take care to ensure that nobody especially kids could step on or fall onto the outdoor unit. This could result in personal injury and product damage.
- Take care to ensure that power cable could not be pulled out or damaged during operation. There is risk of fire or electric shock.
- Do not place ANYTHING on the power cable. There is risk of fire or electric shock.
- When flammable gas leaks, turn off the gas and open a window for ventilation before turning on the product. Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
CAUTION
- Two or more people must lift and transport the product. Avoid personal injury.
- Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause corrosion on the product.
- Install the drain hose to ensure that the condensed water is drained away properly. A bad connection may cause water leakage.
- Keep level even when installing the product. To avoid vibration or noise.
- Do not install the product where the noise or hot air from the outdoor unit could damage or disturb the neighborhoods. It may cause a problem for your neighbors and hence dispute.
- Always check for gas (refrigerant) leakage after installation or repair of product. Low refrigerant levels may cause failure of product.
- Please install safely at a place that can sufficiently endure the weight of the product.
- If the strength is not sufficient, the product may fall and cause injury.
- Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system. There is risk of damage or loss of property.
- Do not block the inlet or outlet of air flow. It may cause product failure.
- Use a soft cloth to clean. Do not use harsh detergents, solvents or splashing water etc. There is risk of fire, electric shock, or damage to the plastic parts of the product.
- Do not touch the metal parts of the product when removing the air filter. There is risk of personal injury.
- Do not step on or put anyting on the product. (outdoor units) There is risk of personal injury and failure of product.
- Always insert the filter securely after cleaning. Clean the filter every two weeks or more often if necessary. A dirty filter reduces the efficiency.
- Do not insert hands or other objects through the air inlet or outlet while the product is operating.
- There are sharp and moving parts that could cause personal injury.
- Be cautious when unpacking and installing the product. Sharp edges could cause injury.
- If the refrigerant gas leaks during repair, do not touch the leaking refrigerant gas. The refrigerant gas can cause frostbite (cold burn).
- Do not tilt the unit when removing or uninstalling it. The condensed water inside can spill.
- Do not mix air or gas other than the specified refrigerant used in the system. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage or injury.
- If the refrigerant gas leaks during the installation, ventilate the area immediately. Otherwise it can be harmfull for your health.
- Dismantling the unit, treatment of the refrigerant oil and eventual parts should be done in accordance with local and national standards.
- Replace all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries. There is risk of fire or product failure.
- Do not recharge or disassemble the batteries. Do not dispose off batteries in a fire. They may burn or explode.
- If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
- If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
- Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. Moisture may condense and wet or damage furniture.
- Do not expose your skin or kids or plants to the cool or hot air draft. This could harm to your health.
- Do not drink the water drained from the product. It is not sanitary and could cause serious health issues.
- Use a firm stool or ladder when cleaning, maintaining or repairing the product at height. Be careful and avoid personal injury.
INSTALLATION OF OUTDOOR UNIT
You need to select adequate installation location considering the following conditions, and make sure to acquire the consent of the user.
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit are respected.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
- You need to select adequate installation location considering the following conditions, and make sure to acquire the consent of the user.
- Select a place that can sufficiently endure the weight and vibration of the outdoor unit and where even installation is possible.
- Select a place that has no direct impact of snow or rain
- Select a place with no danger of snowfall or icicle drop
- Select a place without weak floor or base such as decrepit part of the building or with a lot of snow accumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flooded area.
Piping length and the elevation
Model
| Pipe Size mm(inch)| Length A(m)| Elevation B(m)| Additional refrigerant
(g/m)
---|---|---|---|---
Gas| Liquid| Standard| Max.| Standard| Max.
AUUW18GC0| Ø12.7 (1/2)| Ø6.35 (1/4)| 7.5| 30| 5| 30| 20
AUUW24GC0| Ø15.88 (5/8)| Ø9.52 (3/8)| 7.5| 30| 5| 30| 40
AUUW30GC0| Ø15.88 (5/8)| Ø9.52 (3/8)| 7.5| 35| 5| 30| 40
AUUW36GC0| Ø15.88 (5/8)| Ø9.52 (3/8)| 7.5| 40| 5| 30| 40
Single Operation
If installed tube is shorter than 7.5 m, additional charging is not
necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
CONNECTING PIPES
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring
work in the following procedure.
- Cut the pipes and the cable.
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor and the outdoor unit.
- Cut the pipes a little longer than measured distance.
- Cut the cable 1.5m longer than the pipe length.
Burrs removal
- Completely remove all burrs from the cutcross section of pipe/tube.
- Put the end of the copper tube/pipe to do wnward direction as you remove burrs to avoid to let burrs drop in the tubing.
Putting nut on
Remove flare nuts attached to indoor and outdoor units, than put them on
pipe/tube having completed burr removal. (Not possible to put them on after
flaring work)
Flaring work
Carry out flaring work using dedicated flaring tool for R-410A as shown below
Firmly hold copper tube in a bar(or clamp) as an indicated dimension in the
table above.
Outside diameter | “A” |
---|---|
mm | inch |
Ø6.35 | 1/4 |
Ø9.52 | 3/8 |
Ø12.7 | 1/2 |
Ø15.88 | 5/8 |
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the flared section and do flaring work again.
Connection of piping -Outdoor
Outside diameter | Torque |
---|---|
mm | inch |
Ø6.35 | 1/4 |
Ø9.52 | 3/8 |
Ø12.7 | 1/2 |
Ø15.88 | 5/8 |
- Align the center of the piping and sufficiently tighten the flare nut by hand.
- Finally, tighten the flare nut with torque wrench until the wrench clicks.
- When tightening the flare nut with torque wrench ensure the direction for tightening follows the arrow on the wrench.
When tightening the pipe, hold the haxagonal body.
- When connecting in a downward direction, knock out the knock-out hole of the basepan. (refer to figure 2)
- Preventing foreign objects from entering (Figure3)
- Plug the pipe through-holes with putty or insulation material(procured locally)to stop up all gaps,as shown in the figure 3.
Forming the piping
Form the piping by wrapping the connecting portion of the indoor unit with
insulation material and secure it with two kinds of vinyl tape. If you want to
connect an additional drain hose, the end of the drain outlet should be routed
above the ground. Secure the drain hose appropriately. In cases where the
outdoor unit is installed below the indoor unit perform the following. Tape
the piping, drain hose and connecting cable from down to up. Secure the tapped
piping along the exterior wall using saddle or equivalent.
- In cases where the Outdoor unit is installed above the Indoor unit perform the following.
- Tape the piping and connecting cable from down to up.
- Secure the taped piping along the exterior wall. Form a trap to prevent water entering the room.
- Fix the piping onto the wall by saddle or equivalent
WIRING CONNECTION
Model | Phase(Ø) | ELCB |
---|---|---|
AUUW18GC0 | 1 | 15A |
AUUW24GC0 | 1 | 20A |
AUUW30GC0 | 1 | 20A |
AUUW36GC0 | 1 | 25A |
Electrical Wiring
- Perform the electrical wiring work according to the electrical wiring connection.
- All wiring must comply with local requirements.
- Select a power source that is capable of supplying the current required by the air conditioner.
- Use a recognized ELCB(Electric Leakage
- Circuit Breaker) between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted.
- Model of circuit breaker recommended by authorized personnel only
Connecting Cables between Indoor Unit and Outdoor Unit
- Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
- Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
CAUTION
The power cord connected to the outdoor unit should comply to IEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cord set complying with the
national regulation.) The connecting cable connected to the outdoor unit
should comply to IEC 60245 or HD 22.4 S4 (This equipment shall be provided
with a cord set complying with the national regulation.) When the connection
line between the indoor unit and outdoor unit is over 40m, connect the tele
communication line and power line separately. If the supply cord is damaged,
it must be replaced by a special cord or assembly available from the
manufacturer of its service agent.
Model | Phase(Ø) | Area(mm2) |
---|---|---|
AUUW18GC0 | 1 | 2.5 |
AUUW24GC0 | 1 | 2.5 |
AUUW30GC0 | 1 | 2.5 |
AUUW36GC0 | 1 | 2.5 |
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
**When none are available, follow the instructions below
**
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below
WARNING
Make sure that the screws of the terminal are free from looseness.
Connecting the cable to the Outdoor Unit
Remove the side panel for the wiring connection. Use the cord clamp to fix the cord.
Earthing work
- Case 1 : The terminal block of the Outdoor Unit has mark.
- Connect the cable of diameter 1.6mm2 or more to the earthing terminal provided in the control box and do earthing.
- Case 2 : The terminal block of the Outdoor Unit don’t have mark.
- Connect the cable of diameter 1.6mm2 or more, to the panel of the control box, marked as and fasten with earth screw
CAUTION
- The circuit diagram is not subject to change without notice.
- Be sure to connect wires according to the wiring diagram.
- Connect the wires firmly, so that They won’t be pulled out easily.
- Connect the wires according to color codes by referring the wiring diagram.
- The Power cord connected to the unit should be selected according to the specifications on 13 page.
LEAKAGE TEST AND EVACUATION
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
- Pressure in the system rises.
- Operating current rises.
- Cooling (or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze and block capillary tubing.
- Water may lead to corrosion of parts in the refrigeration system.
- Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Preparation
Check that each tube (both liquid and gas side tubes) between the indoor and
outdoor units have been properly connected and all wiring for the test run
have been completed. Remove the service valve caps from both the gas and the
liquid side on the outdoor unit. Check that both the liquid and the gas side
service valves on the outdoor unit are kept closed at this stage.
Leakage test
- Connect the manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.
- Pressurize the system to no more than 3.8 MPa with dry nitrogen gas and close the cylinder valve when the gauge reading reached 3.8 MPa Next, test for leaks with liquid soap.
CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use
a stop valve for this purpose. The “Hi” knob of the manifold valve must always
be kept close.
CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top
of the cylinder must be higher than its bottom when you pressurize the system.
Usually, the cylinder is used in a vertical standing position.
- 1 Do a leakage test of all joints of the tubing (both Indoor unit and outdoor unit) and both gas and liquid side service valves. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
-
After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Required time for evacuation when 11.36 l/h vacuum pump is usedIf tubing length is less than 10 m (33 ft)| If tubing length is longer than 10 m (33 ft)
30 min. or more| 60 min. or more
0.07 kPa or less
Evacuation
- Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the “Lo and Hi” knob of the manifold valve is open.
- Then, run the vacuum pump. The operation time for evacuation varies with tubing length and capacity of the pump. The following table shows the time required for evacuation.
- When the desired vacuum is reached, close the “Lo and Hi” knob of the manifold valve and stop the vacuum pump.
Finishing the job
- With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.
- Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
- Loosen the charge hose connected to the gas side service port slightly to release the pressure, then remove the hose.
- Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut securely with an adjustable wrench. This process is very important to prevent leakage from the system.
- Replace the valve caps at both gas and liquid side service valves and fasten them tight.
- This completes air purging with a vacuum pump.
- The air conditioner is now ready to test run.
TEST RUNNING
Precautions In Test Running
The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
CAUTION
- For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
- Carry out the test run more than 5 minutes without fail. (Test run will be cancelled 18 minutes later automatically)
- The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
- To cancel the test run, press any button.
**CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
**
- After completing work, be sure to measure and record trial run properties, and store measured data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow-out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature, and compressive pressure.
- As to the structure and appearance, check the following items.
- ls the circulation of air adequate?
- ls the remote controller switch operated?
- ls the draining smooth?
- ls there any faulty wiring?
- ls the heat insulation complete
- pare not terminal screws loosened (refrigerant and drain piping)?
- ls there any leakage of refrigerant?
- M4…..118N.cm/12kgf.cm)
- M5…..196N.cm/20kgf.cm)
- M6…..245N.cm/25kgf.cm)
- M8……588N.cm/60kaf.cm)
Connection of power supply
Connect the power supply cord to the independent power supply. A circuit
breaker is required. Operate the unit for fifteen minutes or more.
Evaluation of the performance
- Measure the temperature of the intake and discharge air.
- Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating).
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
- Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover.
- Provide a circuit breaker switch between power source and the unit.
- The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
- Specification of power source
- Confirm that electrical capacity is sufficient.
- Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
- Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
- Never fail to equip a leakage breaker where it is wet or moist.
- The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of fuse breaking, disturbance to the normal function of a overload protection device.
- Proper starting power is not given to the compressor.
- use only 1 remote controller contained in indoor unit, when using a simultaneous operation system as shown below.
- After setting the ESP value in the Ceiling Concealed Duct Type Indoor Unit, the main power turns off and then remove the remote controller. (Only for synchro combination, over 36kBtu/h)
HAND OVER
Teach the customer the operation and maintenance procedures, using the
operation manual (air filter cleaning, temperature control, etc.).
INSTALLATION GUIDE
AT THE SEASIDE
-
Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
-
Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product.
-
Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient
performance. -
If outdoor unit is installed close to the seaside, it should avoid direct exposur to the sea wind. Otherwise, it needs additional anti-corrosion treatment on the heat exchanger.
Selecting the location (Outdoor Unit)
If the outdoor unit is to be installed close to the seaside, direct exposure
to the sea wind should be avoided. Install the outdoor unit on the opposite
side of the sea wind direction. In case, to install the outdoor unit on the
seaside, set up a windbreak not to be exposed to the sea wind.
- It should be strong enough like concrete to prevent the sea wind from the sea.
- The height and width should be more than 150% of the outdoor unit.
- More than 70cm of space should be kept between outdoor unit and the windbreak for easy air flow.
- Place with fluent water draining
- Install at a place with fluent water draining to prevent damage from localized heavy rain and avoid frequent flooded area.
SEASONAL WIND AND CAUTIONS IN WINTER
- Sufficient measures are required in a snow area or severe cold area in winter so that product can operate well.
- Get ready for seasonal wind or snow in winter even in other areas.
- Install a suction and discharge duct not to let in snow or rain.
- Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
- Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average snowfall) if it is installed at the area with much snowfall.
- Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always remove snow for operation.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>