Mircom MIX-4040 Dual Input Module Instruction Manual
- June 16, 2024
- Mircom
Table of Contents
25 Interchange way, Vaughan Ontario. L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113
Web: www.mircom.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MIX-4040 DUAL INPUT MODULE
ABOUT THIS MANUAL
This manual is included as a quick reference for installation. For further information on the use of this device with a FACP, please refer to the panel’s manual.
Note: This manual should be left with the owner/operator of this equipment.
MODULE DESCRIPTION
The MIX-4040 Dual Input module is designed to operate with a listed compatible intelligent fire system control panel. The module can support one Class A or 2 Class B inputs. When configured for Class A operation, the module provides an internal EOL resistor. When configured for Class B operation, the module can monitor two independent input circuits while using only one module address. The address of each module is set using the MIX-4090 programmer tool and up to 240 units may be installed on a single loop. The module has a panel controlled LED indicator.
FIGURE 1 MODULE FRONT:
- LED
- PROGRAMMER INTERFACE
SPECIFICATIONS
Normal Operating Voltage: | 15 to 30VDC |
---|---|
Alarm Current: | 3.3mA |
Standby Current: | 2mA with two 22k EOL |
EOL Resistance: | 22k Ohms |
Maximum Input Wiring Resistance: | 150 Ohms total |
Temperature Range: | 32F to 120F (0c to 49C) |
Humidity: | 10% to 93% Non-condensing |
Dimensions: | 4 5/8”H x 4 1/4” W x 1 1/8” D |
Mounting: | 4” square by 2 1/8” deep box |
Accessories: | MIX-4090 Programmer |
BB-400 Electrical Box
MP-302 EOL on mounting plate
Wiring range on all terminals:| 22 to 12 AWG
MOUNTING
Notice: You must disconnect power from the system before installing the module. If this unit is being installed in a system that is currently operational, it is necessary to inform the operator and the local authority that the system will be temporarily out of service.
The MIX-4040 module is intended to be mounted in a standard 4″ square back-box (see Figure 2). The box must have a minimium depth of 2 1/8 inches. Surface mounted electrical boxes (BB-400) are available from Mircom.
FIGURE 2 MODULE MOUNTING:
WIRING:
Note: This device should be installed as per applicable requirements of the authorities having jurisdiction. This device shall be connected to power limited circuits only.
- Install the module wiring as indicated by the job drawings and appropriate wiring diagrams (see Figure 3 for an example of wring for a Class A connected device and Figure 4 for an example of Class B)
- Use the programmer tool to set the address on the module as indicated on the job drawings.
- Mount the module in the electrical box as shown in figure 2.
FIGURE 3 SAMPLE CLASS A WIRING:
- TO PANEL OR NEXT DEVICE
- FROM PANEL OR PREVIOUS DEVICE
- E.O.L RESISTOR INSDE THE MODULE
FIGURE 4 SAMPLE CLASS B WIRING:
- TO PANEL OR NEXT DEVICE
- FROM PANEL OR PREVIOUS DEVICE
LT-6139 rev 1.2 7/18/19