SARGENT KP Series Keypad Mortise Lock Instruction Manual

June 16, 2024
SARGENT

SARGENT-LOGO

SARGENT KP Series Keypad Mortise Lock

Specifications

  • Product Name : KP Series Keypad Mortise Lock
  • Model: KP8276/KP8277/KP8278/KP8279
  • Power Source : Four (4) C alkaline batteries
  • User Codes : Holds a total of 100 different user codes

General Description

  • The SARGENT KP Series Mortise Lock is designed for areas which require stand alone authorized entry. It is a self-contained microprocessor-controlled keypad with non-volatile memory.
  • The keypad holds a total of 100 different user codes. User codes 01, 02 and 03 are utilized for Master Code, Emergency Code and Supervisory Code, respectively.
  • This motorized 8200 mortise lock is operated by four (4) C alkaline batteries.
  • SARGENT mortise locks are designed with quality components to provide high security, performance and durability.

Features
PHR-prefix locks will not allow Emergency or Master Code users entry when deadbolt is thrown. Entry is through key cylinder override only.

Parts Breakdown

KP Series Parts List

Item Part # Description
1 01-0803 Battery Alkaline (C cell)
2 01-1119 #8-32 x 1-1/2 Flat Head Screw
3 01-0297 Security Socket Screw Key (1/8)
4 01-1157 #8-32 x 1-1/4 Phillips Pan Head Screw
5 01-0440 Flat Washer
6 81-0467 Inside Lever (L.H.) A Design

Product Usage Instructions

Installation

  1. Ensure that the door is properly prepared for installation according to the provided template.
  2. Install the mortise lock body into the prepared door, following the manufacturer’s instructions.
  3. Attach the inside lever and outside lever to the mortise lock body using the provided screws and washers.
  4. Insert four (4) C alkaline batteries into the battery compartment located on the inside lever.
  5. Close the battery compartment cover securely.
  6. The keypad lock is now ready for programming.

Programming

  1. Press the Master Code button followed by the Master Code to enter programming mode.
  2. Follow the programming instructions provided in the user manual to add or delete user codes, change the Master Code, and set other programming options.
  3. Exit programming mode by pressing the Exit button.

Operation

  1. Enter a valid user code on the keypad to unlock the door.
  2. Rotate the inside lever to open the door.
  3. To lock the door, press the Lock button on the keypad or rotate
    the inside lever to the locked position.

FAQ

  1. Q: Can I use rechargeable batteries with the KP Series Keypad Mortise Lock?
    A: No, the lock requires four (4) C alkaline batteries for proper operation. Do not use rechargeable batteries.

  2. Q: How many user codes can be programmed into the lock?
    A: The lock can hold a total of 100 different user codes.

  3. Q: What are the default user codes?
    A: User code 01 is the Master Code, user code 02 is the Emergency Code, and user code 03 is the Supervisory Code.

Copyright 2014, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.

Warning
Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation.

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that the interference will not occur in a particular installation.

  • If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
    • Reorient or relocate the receiving antenna
    • Increase the separation between the equipment and receiver
    • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
    • Consult the dealer or an experienced TV technician for help

This Class B digital apparatus complies with Canadian ICES-003. Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening, and SARGENT makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings

  • To comply with “Fire Listed” doors, the batteries must be replaced with alkaline batteries only. Do not install batteries if controller is powered by external power supply.
  • Warning SARGENT Mfg. Co. locksets utilizing a door position switch (DPS) are not rated for, or intended for use in life safety applications.

General Description

  • The SARGENT KP Series Mortise Lock is designed for areas which require stand alone authorized entry. It is a self-contained microprocessor-controlled keypad with non-volatile memory.
  • The keypad holds a total of 100 different user codes. User codes 01, 02 and 03 are utilized for Master Code, Emergency Code and Supervisory Code, respectively.
  • This motorized 8200 mortise lock is operated by four (4) “C” alkaline batteries.
  • SARGENT mortise locks are designed with quality components to provide high security, performance and durability.

Specifications

  •  Latchbolt – Stainless Steel
  • Deadbolt – Stainless Steel
  • Buardbolt – Stainless Steel, non handed
  •  Handed – Easily field reversible without disassembling the lock body
  • Case – 12 gauge heavy duty wrought steel
  • Outside lever controlled by keypad
  • Inside lever retracts latchbolt and deadbolt
  • Locks furnished for 1 3/4” doors. Can be furnished for other door sizes upon request. (Consult factory)
  • UL Listed (3 hr.)
  • Accepts size 41(standard) and 42 (removable core) SARGENT mortise cylinders (KP8276 and KP8278)
  • Key retracts latchbolt (KP8276 and KP8278)

Features

  • Non-volatile memory
  • Motor driven, battery operated mortise lock
  • Battery operated with 4 (each) “C” Alkaline
  • Low battery alert – 4 chirps after code entry
  • Option Code available to sound horn every time keypad is pressed
  • External remote “request to enter” connector requires wire harness (52-2071)
  • External battery input connector included to power unit in event of battery failure
  • All programming done at keypad
  • Deadbolt switch inside mortise lock allows Emergency Code and Master Code users to gain entry when deadbolt is thrown*
  • Operates utilizing any two to six digits per code. Digits may be repeated and codes may start with zero
  • Adjustable unlock time
  • Entry of three wrong User Codes disables all codes for ten seconds. Green LED flashes.
  • Piezo horn can be heard with each keystroke or turned off by Master or Supervisory Code
  • Last 15 transactions can be output to printer via Data Transfer Device (DTD)
  • 100 users total: one Master Code, one Emergency Code, one Supervisory Code, with the rest being standard codes, passage codes, or one time only codes

PHR-prefix locks will not allow Emergency or Master Code users entry when deadbolt is thrown. Entry is through key cylinder override only.

  • KP8276
    • Deadbolt function
    • Cylinder override provided
  • KP8277
    • Cylinder override provided
    • No deadbolt function
  • KP8278
    • Deadbolt function
    •  No cylinder override
  • KP8279
    • No cylinder override
    • No deadbolt function
  • Keypad
    • Tactile keypad made of Ultraviolet stable material
    • LED’s indicate valid or invalid entries
    • Green LED indicates unlocked.Yellow LED indicates unit is in programming mode
    • Flashing green and yellow LED’s indicate deadbolt thrown or lock set in passage mode
    • Infrared LED for transaction output. Provides last 15 valid codes.

Items included in your KP8276/KP8278 Keypad Mortise Lock:

  • Outside Escutcheon with Keypad
  • Outside Lever Handle Assembly
  • Inside Lever Handle
  • Mortise cylinder
  • Inside Escutcheon with Circuit Board and Battery Pack
  • Batteries (4 “C”)
  • Tool (security socket screw key 1/8”)

Items included in your KP8277/KP8279 Keypad Mortise Lock:

  • Outside Escutcheon with Keypad
  • Outside Lever Handle Assembly
  • Inside Lever Handle
  • Inside Escutcheon with Circuit Board and Battery Pack
  • Batteries (4 “C”)
  • Tool (security socket screw key 1/8”)

 Parts Breakdown

KP Series Parts List

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-1

Item Part # Description Req.
1 01-0803 Battery Alkaline (“C” cell) 4
2 01-1119 #8-32 x 1-1/2 Flat Head Screw 1
3 01-0297 Security Socket Screw Key (1/8) 1
4 01-1157 #8-32 x 1-1/4 Phillips Pan Head Screw 1
5 01-0440 Flat Washer 1
6 81-0467 Inside Lever (L.H.) A” Design 1
81-0468 Inside Lever (R.H.) A” Design 1
81-0490 Inside Lever B” Design 1
81-0470 Inside Lever E” Design 1
81-0471 Inside Lever F” Design 1
81-4648 Inside Lever H” Design 1
81-0447 Inside Lever J” Design 1
81-0489 Inside Lever L” Design 1
81-0513 Inside Lever P” Design 1
81-0445 Inside Lever W” Design 1
7 01-1472 Lever Handle Screw A, E, F & H (Lever) 1
01-1174 Lever Handle Screw B, J, L, P & W (Lever) 1
8 82-0347 Handle Spring 1
9 82-0368 Spindle 1
10 81-0093 LN” Rose 1
11 01-4388 #8 x 1 Phillips Flat Head Screw 1
12 01-1495 #8-32 x 5/8 Machine Screw 2
13 82-3088 Inside Lever Adapter & Plate Assembly 1
14 52-0033 Fire Stop Plate 1
15 01-1500 #8 x 1/2 Pan Head Self Tapping Screw 2
16 52-2340 Outside Escutcheon & Keypad Assembly 1
17 77-0566 Cylinder Rosette (Size 41 Cylinder) 1
13-0596 Cylinder Rosette (Size 42 Cylinder) 1
18 13-0489 Cylinder Ring (Size 41 Cylinder) 1
13-0490 Cylinder Ring (Size 42 Cylinder) 1
19 13-0140 Compression Spring 1
20 OS-8276 x LNA Outside Lever (R.H.) A” Design 1
(L.H.) A” Design “ 1
OS-8276 x LNB Outside Lever B” Design “ 1
OS-8276 x LNE Outside Lever E” Design “ 1
OS-8276 x LNF Outside Lever F” Design “ 1
OS-8276 x LNH Outside Lever H” Design 1
OS-8276 x LNJ Outside Lever J” Design 1
OS-8276 x LNL Outside Lever L” Design 1
OS-8276 x LNP Outside Lever P” Design 1
OS-8276 x LNW Outside Lever W” Design “ 1
OS-8276 x LA Outside Lever (R.H.) A” Design “ 1
(L.H.) A” Design “
OS-8276 x LB Outside Lever B” Design “ 1
OS-8276 x LE Outside Lever E” Design “ 1
OS-8276 x LF Outside Lever F” Design “ 1
OS-8276 x LH Outside Lever H” Design “ 1
OS-8276 x LJ Outside Lever J” Design “ 1
OS-8276 x LL Outside Lever L” Design 1
OS-8276 x LP Outside Lever P” Design “ 1
OS-8276 x LW Outside Lever W” Design 1
21 01-1028 Outside Front #8-32×1/4 FL HD Screw 2
01-2299 Lockbody Screws for Wood #12×1-1/4 FL HD (not shown) 2
01-1019 Lockbody Screws for Metal #12-24×1/2 FL HD (not shown) 2
22 82-0084 Outside Front (KP8276 & KP8277) 1
82-0081 Outside Front (KP8278 & KP8279) 1
23 KP-8276-hand-finish Lockbody Assembly with deadbolt & cylinder 1
KP-8277-hand-finish Lockbody Assembly with deadbolt only (no cylinder)
KP-8278-hand-finish Lockbody Assembly with cylinder only (no deadbolt)
KP-8279-hand-finish Lockbody Assembly without deadbolt & without cylinder

24

25

| 82-3730| Inside Escutcheon Assembly (Turn Lever-KP8276/KP8777)| 1

1

82-3729| Inside Escutcheon Assembly (Hole Plug-KP8278/KP8779)
26| 52-4758| Inside Escutcheon Assembly (Turn Lever-KP8276 **only*** )| 1

Installation Instructions

Step #1 – Verify Hand and Bevel of Door
A. Verify Hand and Bevel of Door
Stand on outside/locked side of door when determining the door handSARGENT-
KP-Series-Keypad-Mortise-Lock-IMAGE-2

B. Prepare Door
Prep door according to Instruction Sheet A7454 and appropriate template: Manufacturer Door Template: 4632
Documents are available at www.sargentlock.com

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-3

Step #2 – Verify Hand and Bevel of Door

A. Reverse Lock Hand
Red surface of locking piece must face the outside/locked side of door. To rotate locking piece (Fig. 2A):

  1. Position lock body with red surface of locking piece visible.
  2. Insert blade type screwdriver into locking piece slot to rotate locking piece toward back of lock body.
  3. Rotate the locking piece 180° until RED surface is on opposite side.
    Note: Red indicates locked side (outside).

B. Reverse Latch Hand

Beveled surface of latchbolt must face strike (Fig. 2B). The dead latch is self adjusting.
To change the hand of the latchbolt:

  1. Insert the blade of a slotted screwdriver (>1/4”) into the spade shape slot behind latch.
  2. Rotate the screwdriver 90° to push latchbolt out until back of bolt clears lock case front.
  3. Rotate latchbolt 180° until the latchbolt drops back into the lock body.
    Note: Latch cannot be unscrewed.SARGENT-KP-Series-Keypad-Mortise-Lock-
IMAGE-5

Step #3 – Install Lock Body

  1. Insert lock body into mortised cutout (Fig. 3A).
  2. Hold lock body loosely in place with (2) lock  body screws.
    Note: Do not completely tighten screws at this time.

Step #4 – Exterior Door Options

A. Fire Stop Plate (P/N 53-0033)
Fire-rated doors require a fire stop plate on the outside of the door (Fig. 4A).

  1. Drill (2) 1/8” x 1-1/4” deep holes in the door if not already present. Refer to template for fire-stop prep locations.
  2. Attach with flap up and out using (2) #8 x 1/2” self-tapping screws for wood and metal doors.SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-8

Step #5 – Install Weather seal Gasket (Exterior Doors)

  1. Carefully remove adhesive backing from the gasket (Fig. 5A).
  2. Apply gasket to escutcheon:
    • Starting in one place, press the adhesive side of the gasket firmly against the escutcheon.
    • Work around the escutcheon, pressing the sticky side of the gasket firmly against the escutcheon edge.
    • The gasket should be aligned so that all edges of the escutcheon are covered.
  3. Attach escutcheon to the door.
    Note: The 43 cylinder may be used with or without a gasket.

Step #6 – Install Outside Escutcheon and Lever Assembly

  • A. From the outside , of the door, feed wires and connector through fire stop plate
  • From the inside of the door, use the #8-32 x 1 1/4″ Round Head Screw with the Flat Washer to attach the Escutcheon using the lower lug
  • C. Straighten Escutcheon and tighten the #8-32 X Round Head Screw

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-10 SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-11

Install Outside Lever Assembly

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-12

  • A. Back off retaining nut slightly until star pattern lines up with square lever assembly corners
  • B. Insert spindle into outside lever assembly.
  • With outside lever horizontal. Carefully insert the mounting posts through the door and lock body. Make sure the spindle is properly engaged in the lock.
  • D. Insert Spindle into square hole on inside of door
  • E. To secure the adapter and plate assembly to the inside of the door, thread the screws mounting posts of the outside lever assembly

Step #7 – Install Inside Escutcheon

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-13 SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-14

Step #8 – Inside Lever Installation

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-15 SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-16SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-17

  • Slide lever handle onto spindle until fully seated. Be sure handle is horizontal and facing to the rear of door.
  • E. Tighten set screw securely with 1/8″ hex wrench

Step #9 – KP8276 and KP8278 Only – Install Cylinder

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-28

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-29Step #10 – Application of Front Plate

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-30

Step #11 – Battery Installation

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-31

 Operational Check

  • Place key into cylinder and rotate key.
  • The key will retract the latchbolt.
  • If the deadbolt is thrown, the key will retract both the deadbolt and the latchbolt.
  • Inside handle lever retracts latchbolt and (if provided).
  • Enter 1234* to unlock outside lever handle and retract latchbolt and deadbolt (if provided).

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-23

  • Key should rotate freely. There should be no friction against lock case, wire harness or any other obstructions.
  • Refer to Step 7 if harness friction exists.
  • Rotate cylinder further into lock case to eliminate lockbody obstruction.

Programming Instructions

The KP Keypad Lock can support 100 users. Each user is assigned a User Number in addition to the code used for entry.

Example:

USER TYPE USER NUMBER USER CODE (2-6 DIGITS)

Master Emergency

Supervisor

|

  • 01
  • 02
  • 03

|

  • 1 2 3 4
  • 2 2 2 2 2
  • 3 0 3 0 3 0

Standard| 04-97| 2 6 5
Special Factory 10 Sec. Time Preset| 98

99

| 1 3 6 8

This Keypad Mortise Lock has 99 User Codes available for programming purposes.

  • The Master Code is always User “01”. The Master Code assigns the Emergency and Supervisory Codes. It is also used for programming and will override the deadbolt*. Users are deleted through the Master Programming Code only.
  • The Emergency Code is always User “02”. The Emergency Code will override the deadbolt* in the mortise lock and has an unlock time of 10 seconds.
  • The Supervisory Code is always User “03”. The Supervisory Code allows temporary lockout of selected users, changes duration of unlock time, requests infrared interrogation output, and may add additional User Codes.
  • The first User Code will be User “04” or higher. User numbers do not have to be used or entered sequentially.
  • User codes “98” and “99” have a factory-set unlock time of ten seconds. This allows a handicapped person extra time which would not be required by other users.

NOTE: PHR-prefix locks will not allow Emergency or Master Code users entry when deadbolt is thrown.

Entry (with deadbolt thrown) is through key cylinder override only.
To Begin Programming:
The Keypad Mortise Lock is preset at the factory with Master Code “1234”. Entering “1234*” will unlock the lock allowing the lever handle to retract the latchbolt.
Initial Set-Up Procedures:

  • The following are typical procedures to follow when setting up your KP Series Keypad.
  • If a mistake is made during any of procedures, depress the “*” several times until the yellow LED goes out.
  • If no keystroke is made in a 30-sec time frame the programming up to that point will default and you will have to start over.

All of the following procedures start with 99#.
If after the last “ ” is depressed, the yellow LED does not go out, depress “ ” once more. Change Master Code:

  • 1234* (Yellow LED Begins to Blink Slowly) This example uses the Factory Default Master Code
  • 50# 1# 01# New Master Code* (Yellow LED Blinks Quickly)
  • New Master Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

To Enter the Emergency Code: (Unlock Duration is Factory Set at 10 Sec)

  • Master Code* (Yellow LED Begins to Blink Slowly)
  • 50# 1# 02# Emergency Code* (Yellow LED Blinks Quickly)
  • Emergency Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

To Enter the Supervisory Code:

  • Master Code* (Yellow LED Begins to Blink Slowly)
  • 50# 1# 03# Supervisory Code* (Yellow LED Blinks Quickly)
  • Supervisory Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

To Enter a User Code:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 50# 1# User Number (04-97)# User Code* (Yellow LED Blinks Quickly)
  • User Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

If after the last “” is depressed, the yellow LED does not go out, depress “” once more.
To Enter a Passage (Maintained Mode) Code: When Passage Mode is used, the same User Code must be used to re-lock the lock.

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 50# 2# User Number (04-97)# User Code* (Yellow LED Blinks Quickly)
  • User Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

To Enter a One Time User Code:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 50# 3# User Number# User Code* (Yellow LED Blinks Quickly)
  • User Code (Yellow LED Blinks Slowly) (Yellow LED Goes Out)

To Deactivate “Beep” With the Depression of Each Key:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 30# 0# 0# (Yellow LED Continues to Blink Slowly)
  • (Yellow LED Blinks Quickly)
  • (No Beep on Depression and Yellow LED Blinks Slowly)
  • (No Beep on Depression and Yellow LED Goes Out)

To Reactivate “Beep” With the Depression of Each Key:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 30# 0# 1# (Yellow LED Continues to Blink Slowly)
  • (Yellow LED Blinks Quickly)
  • (Beep on Depression and Yellow LED Blinks Slowly)
  • (Beep on Depression and Yellow LED Goes Out)

To Clear the Entire Memory:

  • Master Code* (Yellow LED Begins to Blink Slowly)

  • 46# 00000# 00000# (Yellow LED Continues to Blink Slowly)

  •  (Yellow LED Blinks Quickly)

  • (No Beep on Depression and Yellow LED Goes Out)

  • PAUSE, Yellow LED Begins to Blink Again

  • (Yellow LED Goes Out)

NOTE This Deletes ALL Codes, including Master, Emergency and Supervisory. The Master Code is set back  to 1234, Door Number to 0001 and Unlock time to 5 Sec. If the Master Code is not known, Factory Assistance will be required to clear the memory. 1-800-810-WIRE.

To Program Door Numbers into Keypad:

  • Master Code* (Yellow LED Begins to Blink Slowly)
  • 43# 0# Door Number# (must be four digits) (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  • (Yellow LED Blink Slowly)
  • (Yellow LED Goes Out)

All of the following procedures start with 99# (continued).
If after the last “” is depressed, the yellow LED does not go out, depress “” once more.
To Interrogate Transaction Log:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 70# 0# 0# (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  • (Yellow LED Goes Out)

SARGENT-KP-Series-Keypad-Mortise-Lock-IMAGE-24

Note: Seq. # 1 is the programming request to output the entries. Sequence numbers 2-6 are the actual entries.
To Reset / Clear Transaction Log

  • Master Code* (Yellow LED Begins to Blink Slowly)
  • 76# 00000# 00000# (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  •  (Yellow LED Goes Out)

To Delete a User Number:

  • Master Code* (Yellow LED Begins to Blink Slowly)
  • User Number# (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  • (Yellow LED Blinks Slowly)
  • (Yellow LED Goes Out)

To Disable / Enable a User Number:

  • Supervisory or Master Code* (Yellow LED Begins to Blink Slowly)
  • 56# 0# = Enable, 1# = Disable User Number# (04-99) (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  • (Yellow LED Blinks Slowly)
  • (Yellow LED Goes Out)

To Set Unlock Time:

  •  Master Code* (Yellow LED Begins to Blink Slowly)
  • 85# Time Duration# (01-99 Sec) 0# (Yellow LED Blinks Slowly)
  • (Yellow LED Begins to Blink Quickly)
  • (Yellow LED Blinks Slowly)
  • (Yellow LED Goes Out)

Note: The Unlock Time is Adjustable for Momentary Operation. A 5 second unlock time is recommended to extend battery life. Once the unlock time is entered, it is the same for ALL users except 02, 98 and 99 which are factory set for 10 seconds.

Transaction Log
To output the last 15 entries, enter 99 # Supervisory or Master Code * 70 # 0

0 # **.

  • Door Number

    • 4 Digits
    • Up to 9999 different doors, assigned by user
  • Transaction Number

    • Single digit – 1-6
    • Latest transaction – 1
    • Oldest transaction – 6
  • User Number

    • Three digits – 001 through 099
    • User numbers assigned at time of programming
      Note: Seq. # 1 is the programming request to output the entries. Sequence numbers 2-6 are the actual entries.
  • Transaction Types

    • 001 = Access granted
    • 002 = Access denied (Deadbolt thrown and code entered did not have proper access level.)
    • 003 = Log printed
  • Optional Equipment

    • Printer Paper (6 Rolls) – 52-0034 used for infrared printers
    • Auxiliary Power Unit (APU) 52-2065 – used to unlock unit if batteries are too weak and cylinder is not used.
    • Data Transfer Device (DTD) – used to download the user and transaction type.
    • Remote Unlocking – 52-2071 – used for remote unlocking of keypad mortise lock. When the deadbolt is thrown and the remote unlocking feature is used, both the latchbolt and deadbolt can be retracted by turning the lever handle.
      Hold an infrared printer up to the red infrared LED (as shown). A Data Transfer Device (DTD) can be used to download information from the keypad to a printout.

SARGENT Manufacturing Company 100 Sargent Drive

  • New Haven, CT 06511 USA
  • 800-810-WIRE (9473) 
  • Founded in the early 1800s, SARGENT® is a market leader in locksets, cylinders, door closers, exit devices, electro-mechanical products and access control systems for new construction, renovation, and replacement applications. The company’s customer base includes commercial  construction, institutional, and industrial markets.
  • Copyright © 2014, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved.
  • Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.