Eaton 9E 20000I Double-conversion UPS User Manual
- June 16, 2024
- EATON
Table of Contents
Eaton 9E 20000I Double-conversion UPS
Introduction
Safety instruction
- The UPS must be installed and maintained exclusively by qualified staff. See installation and operation instructions before connecting to the supply.
- The UPS must be installed with an earth connection. It has a high leakage current. The first wire to be connected is the earth wire, which must be connected to the terminal marked PE (yellow/green).
- The UPS generates a leakage current of over 3.5 mA. The leakage current of the load should be added to that of the UPS on the protective earth wire.
- The UPS needs a neutral connection to work properly. Operation without Neutrality may damage the unit.
- A readily accessible disconnect device shall be incorporated in the building installation wiring for permanently connected equipment.
- The UPS generates hazardous electric voltages inside it even when the input and/or battery switches are open. The inside of the UPS is protected by safety guards that are not to be removed by non-qualified staff. All installation and maintenance or other operations that entail gaining access to the inside of the UPS require the use of tools and are to be performed exclusively by qualified staff.
- The UPS contains an energy source: the batteries. All terminals and sockets may be powered even when the UPS is not connected to the mains.
- The total battery voltage is potentially hazardous: it may cause an electric shock. The compartment containing the batteries is protected by safety guards, which are not to be removed by non-qualified staff. All battery installation and maintenance operations entail gaining access to the inside of the UPS and require the use of tools: these operations are to be performed exclusively by qualified staff.
- The batteries replaced are to be considered toxic waste and treated accordingly. Dispose of used batteries according to the instructions. Do not throw the batteries into fire: they could explode. Do not attempt to open the battery casing: no maintenance work can be done on them. In addition, the electrolyte is hazardous for the skin and eyes and may be toxic.
- Risk of explosion if the battery is replaced by an incorrect type.
- Do not turn on the UPS if you see any leaks of liquid or a white powder residue.
- Make sure that no water, liquid in general, and/or other foreign matter gets inside the UPS.
- Under hazardous conditions, turn off the UPS at the “1/0” main power switch and open all the isolators present (see the user manual to locate the “1/0” main power switch and the isolators).
- Do not open the battery fuse holders while the UPS is powering the load from the batteries. An interruption of the battery DC voltage may cause an electric arc and result in breakage of the equipment and/or fire.
- The energy required to power the load is provided by the batteries in the event of a power failure. if the battery protection were open, the load would be powered off.
- Fuses have to be replaced with the same type if necessary.
- To connect external battery cabinets, use the expansion cable suggested by the manufacturer in this manual.
Certification Standards
Safety
IEC 62040-1:2008
IEC 60950-1:2005 (Modified)
EMC
Conducted Emission: IEC 62040-2. Category C3
Radiated Emission: IEC 62040-2. Category C3
ESD:IEC 61000-4-2. Contact: Level 2, Air discharge: Level 3
RS:IEC 61000-4-3. Level 3
EFT:IEC/EN 61000-4-4. Level 4
Surge:IEC/EN 61000-4-5. Level 4
CS:IEC/EN 61000-4-6. Level 3
MS:IEC/EN 61000-4-8. Level 3
Voltage Dips, short interruptions and voltage variations:IEC/EN 61000-4-11
Warning: This is a product for commercial and industrial application, in other
environment installation restrictions or additional measures may be needed to
prevent disturbances. Additional
curbs may be needed while output wiring length is more than 10m or communication wiring length is more than 3m.
Special Symbols
The following are examples of symbols used on the UPS or accessories to show you the important information:
Presentation
9E series UPS uses ON-LINE double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads.
Model List
Model | Power Ratings | PF | Voltage (Output) |
---|---|---|---|
9E6Ki | 6kVA/4.8kW | 0.8 | 230V (220/240) |
9E10Ki | 10kVA/8kW Combo | 0.8 | 230V (220/240) |
9E10KiXL | 10kVA/8kW Combo | 0.8 | 230V (220/240) |
9E15Ki | 15kVA/12kW Combo | 0.8 | 230V (220/240) |
9E20Ki | 20kVA/16kW Combo | 0.8 | 230V (220/240) |
9E20KiXL | 20kVA/16kW Combo | 0.8 | 230V (220/240) |
9EEBM180 | For 9E6Ki | 180V | |
9EEBM240 | For 9E10Ki, 9E10KiXL | 240V |
“XL” Model: Model with internal supercharger, and without internal batteries. Other models with internal batteries
Electrical structure
9E6Ki
9E10Ki, 9E10KiXL
9E15Ki, 9E20Ki, 9E20KiXL
UPS views
UPS FRONT VIEW
- Display
- Multipurpose buttons
- Wheels (front wheels swivel and can be locked, fixed rear wheels)
UPS REAR VIEW
-
9E6Ki With backpanel cover
-
9E6Ki Without backpanel cover
-
9E10Ki/9E10KiXL With backpanel cover
-
9E10Ki/9E10KiXL Without backpanel cover
-
④ USB communication port
-
⑩ Input switch
-
⑤ RS232 communication port and contacts
-
⑪ Cover for terminals
-
⑥ Slot for optional communication card
-
⑫ Fuse
-
⑦ Cooling fan(s)
-
⑬ Terminals for I/O cable connection (refer to related section)
-
⑧ Output switch
-
⑭ Earthing screws
-
⑨ Manual bypass for maintenance
-
⑮ Tie wrap hold-down
9E15Ki/9E15KiXL/9E20Ki/9E20KiXL With backpanel cover
9E15Ki/9E15KiXL/9E20Ki/9E20KiXL Without backpanel cover
- ④ RS232 communication port and contacts
- ⑩ Input switch
- ⑤ USB communication port
- ⑪ Cover for terminals
- ⑥ Slot for optional communication card
- ⑫ Terminals for I/O cable connection (refer to related section)
- ⑦ Cooling fans
- ⑬ Earthing screws
- ⑧ Output switch
- ⑭ Fuse
- ⑨ Manual bypass for maintenance
- ⑮ Tie wrap hold-down
EBM REAR VIEW
- ① Fuse
- ② Cover for terminals
- ③ Tie wrap hold-down
- ④ Wheels (front wheels swivel and can be locked, fixed rear wheels)
- ⑤ Terminals for I/O cable connection (refer to related section)
- ⑥ Earthing screws
Installation
Unpacking
- Cut the straps and carefully remove the cardboard box by sliding it upwards.
- Remove the accessory box, the wooden slide and the top polystyrene foam corner pieces.
- Remove the bottom polyethylene corner pieces by rotating them as shown in the figure.
- Open the protective bag and pull it all the way down.
- Put the previously removed slide on the back part of the pallet (see figure). Make sure that the slide rests firmly against the pallet so it remains in place during unloading operations. Pull the UPS from the front with caution when sliding it off the pallet.
NOTE: All parts of the packaging should be kept for future use.
Package content
After opening the packaging, it is first necessary to check the contents. The package must contain:
Connection
INSTALLATION REQUIREMENTS
Warning:
- Installation must be performed by qualified personnel. The first connection to perform is the protective conductor (earth cable), which must be connected to the screw marketed .
- The UPS, when inserted in an installation, does not alter the existing neutral (system earthing) arrangements.
- A differential switch upstream will also be triggered for a fault occurring downstream of the UPS. In calculating reactivity of this switch, account must be taken of the leakage current of the UPS (approx. 8 mA) plus that of the load which come together on the UPS’s earth conductor.
UPS input | Differential switch |
---|---|
Single-phase | Type B or Type A |
Three-phase | Type B |
- The neutral arrangements are altered only if there is an isolating transformer or when the UPS operates with a neutral that is disconnected upstream.
- In any case avoid connecting the output neutral with the input neutral or to the earth as this could damage the UPS.
- Reminder : The UPS needs a neutral connection to work properly. Operation without Neutral may damage the unit.
- For installation with change in system earthing arrangement or galvanic isolation see below schematic
Notice: It is required to install an external isolating device against current backfeed between Mains input and UPS. After the device is installed, it must add a warning label with the following wording or the equivalent on the external AC contactor: RISK OF VOLTAGE BACKFEED. Isolate the UPS before operating on this circuit, then check for hazardous voltage between all terminals. The current rating of T – AC contactor should be more than 1.3 times of UPS capacity
UPS WIRING CONNECTION
To make the mains power and load connections, follow the instructions below:
- Install a magneto-thermal switch (63A for 6 & 10kVA versions, 125A for 15 and 20kVA versions) with intervention curve D upstream of the machine (4 poles for three-phase versions, 2 poles for single-phase versions).
- The connection terminals to use for the input and output lines are located on the backpanel. Unscrew the 4 screws located on the sides of the cover (one on each side, see figure).
- Remove the backpanel cover (see figure to the side).
- (SINGLE-PHASE CONNECTION 9E6KI): use 3 cables with cross-section 6 mm2 (EARTH, N and L) for the input, and 3 cables with cross-section 6 mm2 for the output (EARTH, N and L).
- Connect the wires to the relative terminals, following exactly the instructions given below:
- Input line
- a – Make sure that the magneto-thermal switch upstream is open.
- b – Connect the earth wire to screw A.
- c – Connect the neutral wire to terminal 2.
- d – Connect the live wire to terminal 1.
- Output line
- a – Connect the earth wire to screw B.
- b – Connect the neutral wire to terminal 3.
- c – Connect the live wire to terminal 4.
- R.E.P.O.
- a – The REPO connection (between terminal 5 and 6) is normally open. For more information please refer to the REPO section of this manual
- Tighten the terminals well, close the backpanel cover and secure it with the screws taken out earlier. The suggested tighten force is 1.2~1.6Nm.
COMBO VERSION
SINGLE-PHASE CONNECTION
- 4. (SINGLE-PHASE CONNECTION 9E10KI, 9E10KIXL): use 3 cables of cross-section 10 mm2 (EARTH, N and L) for the input, and 3 cables of cross-section 10 mm2 for the output(EARTH, N and L).
- (SINGLE-PHASE CONNECTION 9E15KI, 9E15KIXL): use 3 cables of cross-section 16 mm2 (EARTH, N and L) for the input, and 3 cables of cross-section 16 mm2 for the output(EARTH, N and L).
- (SINGLE-PHASE CONNECTION 9E20KI, 9E20KIXL): use 3 cables of cross-section 25 mm2 (EARTH, N and L) for the input, and 3 cables of cross-section 25 mm2 for the output(EARTH, N and L).
- 5. Short-circuit the input terminals (1, 2 and 3) with the jumper provided in the accessories kit. Connect the wires to the respective terminals, following exactly the instructions below:
- Input line
- a – Ensure that the upstream magneto-thermal switch is open.
- b – Connect the earth wire to screw A.
- c – Connect the neutral wire to terminal 4.
- d – Connect the live wire to terminal 1.
- Output line
- a – Connect the earth wire to screw B.
- b – Connect the neutral wire to terminal 5.
- c – Connect the live wire to terminal 6.
- R.E.P.O.
- a – The REPO connection (between terminal 5 and 6) is normally open. For more information please refer to the REPO section of this manual
- 6. Tighten the terminals well, close the backpanel cover and secure it with the screws taken out earlier. For 10 to 15kVA the suggested tighten force is 1.2~1.6Nm. For 20kVA, the suggested tighten force is 2.5~3 Nm.
THREE-PHASE CONNECTION
- (THREE-PHASE CONNECTION 9E10KI, 9E10KIXL): Use 2 cables of cross-section 4 mm2 (L2 and L3) and 3 with cross-section 10 mm2 (EARTH, N, L1) for the input (N.B.: L1 and N are of greater cross-section because in bypass operation they have to carry all of the input current). For the output use 3 cables of cross-section 10 mm2 (EARTH, N and L).
- (THREE-PHASE CONNECTION 9E15KI, 9E15KIXL): Use 2 cables of cross-section 4 mm2 (L2 and L3) and 3 of cross-section 16 mm2 (EARTH, N, L1) for the input (N.B.: L1 and N are of greater cross-section because in bypass operation they have to carry all of the input current). For the output use 3 cables of cross-section 16 mm2 (EARTH, N and L).
- (THREE-PHASE CONNECTION 9E20KI, 9E20KIXL): Use 2 cables of cross-section 6 mm2 (L2 and L3) and 3 of cross-section 25 mm2 (EARTH, N, L1) for the input (N.B.: L1 and N are of greater cross-section because in bypass operation they have to carry all of the input current). For the output use 3 cables of cross-section 25 mm2 (EARTH, N and L).
- Connect the wires to the respective terminals, following exactly the instructions below:
- Input line
- Ensure that the upstream magneto-thermal switch is open.
- Connect the earth wire to screw A.
- Connect the neutral wire to terminal 4.
- Connect the wires of the phases to terminals 1, 2 and 3 (for L1 use red wire).
- Output line
- Connect the earth wire to screw B.
- Connect the neutral wire to terminal 5.
- Connect the live wire to terminal 6.
- R.E.P.O.
- The REPO connection (between terminal 5 and 6) is normally open. For more information please refer to the REPO section of this manual
- 3. Tighten the terminals well, close the backpanel cover and secure it with the screws taken out earlier.
For 10 to 15kVA the suggested tighten force is 1.2~1.6Nm. For 20kVA, the suggested tighten force is 2.5~3 Nm.
R.E.P.O.
- The terminal block on the back of the UPS also implements the R.E.P.O. (Remote Emergency Power Off) function that can be used to shut off the UPS remotely in case of an emergency.
- For installation, connect to the device’s normally open contact .
- In case of an emergency, if the stop device is used, the REPO control is closed and the UPS goes into stand-by mode and the load is completely disconnected.
Attention: before restarting the UPS, reset the stop device.
-
The circuitry of the remote control terminal board is self-powered with SELV circuits. Therefore, an external voltage supply is not required. When a contact is closed, a maximum current of 15mA circulates.
-
All connections with the remote control terminal board are made through a cable which guarantees a double insulation connection.
-
If you would like to bring the R.E.P.O. control outside, unscrew the two screws securing the lower part of the backpanel cover and remove it (as indicated in the section “Connections”). Then, proceed as follows:
- Use a 2×0.75mm2 cable to make the connection with the R.E.P.O. terminals.
- Insert the screw driver in the square hole and press down to make the round hole terminal open. Then insert the wire into the round hole. Then pull out the screw driver. Connect the two wires of the cable to terminals 5 and 6 (for version 9E6Ki), 7 and 8 (for versions 9E10Ki, 9E10KiXL, 9E15Ki, 9E15KiXL, 9E20Ki, 9E20KiXL) to be able to remotely shut off the UPS.
-
Close the backpanel cover and secure it with the screws taken out earlier.
EBM WIRING CONNECTION
It is possible to connect more than one EBM in order to achieve any level of autonomy without mains power. Connect any Battery Boxes in a cascade as shown in the figure below:
-
CONNECTION: Use 3 cables with 10 mm2 section (Earth, +, N and -)
-
Connect the wires to the relative terminals, following exactly the instructions given below:
For 9E6Ki, 9E10Ki, 9E10KiXL- Make sure that the fuse holder of the external battery box is open.
- Connect the earth (PE) wire to EBM’s earth (PE) screw
- Connect the positive (+) branch wire to EBM’s positive (+) terminal.
- Connect the negative (-) branch wire to EBM’s negative (-) terminal.
-
The suggested tighten force is 1.6Nm. (Detailed wiring diagram see fig 3-9~10)
Versions 9E6Ki, 9E10Ki, 9E10KiXL
Fig.3-9 EBM terminal connection for 9E6Ki, 9E10Ki, 9E10KiXL With Single EBM
Fig.3-10 EBM terminal connection for 9E6Ki, 9E10Ki, 9E10KiXL With Multiple EBM
Note: For 9E15Ki, 9E20Ki, 9E20KiXL EBM wiring connection, you should check the 9EEBM manual in EBM package.
OPERATION
Display and Buttons
The following tables shows the buttons, LCD indicator and LED indicator status and description:
Table 4-1 Control Buttons Functions
Table 4-2 LED indicator
LED name | Colour | Description |
---|---|---|
Line | Green | It indicates the utility is normal |
Battery
|
Yellow
| It indicates the input is connected with battery, and the input power is supplied from the battery.
Bypass
|
Yellow
| It indicates the UPS is in bypass mode, the load current is directly supplied from the utility power
Inverter
|
Green
| It indicates that the inverter is OK and the load is supplied from the inverter.
Note: After UPS power on, all LEDs will be lightened for 2 seconds, and then turn to normal status. When UPS is turning on, 4 LEDs will be lightened one by one until the UPS is turned on successfully.
Table 4-3 Buzzer
Priority | UPS condition | Buzzer |
---|---|---|
1 | UPS fault and failure | Continuous |
2 | Normal mode | No beep |
3
| Battery/battery test mode| One beep per 4 sec
(One beep per 1s when battery low)
4| Bypass mode| One beep per 2 minutes
5| Overload| One beep per 500ms
6| Other alarm| One beep per 1s
7| Manual bypass| One beep per 1s
Note: buzzer alarm can be enable/disable by function button, if buzzer alarm is disabled, all present alarm is muted except that the button press still has a tick beep. Buzzer alarm will be enabled automatically once new alarm arises.
Interface
In order to make sure all segments are OK, LCD begins to do self-test after power on. During self-test, all the segments will be lighted for 2 seconds, then the LCD will turn to normal display status.
Fig. 4-2 The default LCD display
Operating UPS
Notice: Please switch off the connected loads first before turning on the UPS, and switch on the loads one by one after the UPS is turned on. Switch off all of the connected loads before turning off the UPS.
Notice: Power on for the first time
- Close the magnetothermic switch located upstream of the UPS.
- Close the input and output switches and insert the battery fuses (if any) located on the back of the UPS’s backpack.
TURNING ON UPS WITH MAINS
- Check that all connections are correct. Check the breaker of external battery pack is in “ON” position.
- Set input breaker in “ON” position. At this time the fan begins to rotate. By pressing button continuously for more than 2 second, the buzzer will beep once, UPS starts to turn on.
- A few seconds later, the UPS turns into Line mode. If the mains power is abnormal, the UPS will transfer to Battery mode without output interruption of the UPS.
TURNING ON UPS WITHOUT MAINS
- Check that all connections are correct. Check the breaker of external battery pack is in “ON” position.
- By pressing button continuously for more than 2s, the buzzer will beep once, UPS starts to turn on.
- A few seconds later, the UPS turns into Battery mode. If the mains power comes back, the UPS will transfer to Line mode without output interruption of the UPS.
TURNING OFF UPS WITH MAINS
- To turn off the inverter of UPS press button continuously for more than 3s and the buzzer beep once. The UPS will turn into standby mode.
- Cut off the mains power supply. A few seconds later, LCD display shuts down.
TURNING OFF UPS WITHOUT MAINS
- To power off the UPS press button continuously for more than 3s, and the buzzer beep once. The UPS will cut off the output.
- A few seconds later, LCD shuts down and no voltage is available from the UPS output.
TRANSFER TO BYPASS
- To transfer the UPS in internal bypass mode, press on/off button and test button at the same time for more than 4 seconds.
- To transfer the UPS back to normal mode, press on/off button and test button at the same time for more than 4 seconds.
TRANSFER TO MAINTENANCE BYPASS
- To transfer the UPS in maintenance bypass mode, switch on the maintenance switch. And then the UPS will transfer to maintenance bypass mode. Switch off the input and output switch before doing maintenance on the UPS.
- To transfer the UPS back to normal mode, switch on the input and output switch and then switch off the maintenance switch. Then turn on the UPS following “Turning on UPS” steps.
Configuration
COMMUNICATION PORTS
- On the back of the UPS (see UPS Views), the following communication ports are present: RS232 connector, USB connector, Slot for optional connectivity cards
RS232 or USB communication ports
-
The RS232 and USB communication ports cannot operate simultaneously.
-
Connect the RS232 or USB communication cable to the serial or USB port on the computer.
-
Connect the other end of the communication cable to the RS232 or USB communication port on the UPS.
The UPS can now communicate with EATON power management software
Connectivity Cards
- The UPS is equipped with an expansion slot for optional Connectivity Cards (see figure on right).
- It is not necessary to shutdown the UPS before installing a communication card.
- Remove the slot cover secured by screws.
- Insert the communication card in the slot.
- Secure the card cover with the 2 screws
Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices.
- Network-MS card – has SNMP and HTTP capabilities as well as monitoring through aWeb browser interface; connects to Ethernet network. In addition, a Environmental Monitoring Probe can be atta- ched to obtain humidity, temperature, smoke alarm, and security information.
- Modbus-MS card – has connection to Modbus protocol in addition to network management.
- Relay-MS card – has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS alarm/OK, or on Bypass.
EATON INTELLIGENT POWER SOFTWARE SUITE
- Each 9E UPS ships with Eaton Intelligent Power Software suite.To begin installing, see the instructions accompanying the Software suite CD.
- Eaton Software suite provides up-to-date graphics of UPS power and system data and power flow.
- It also gives you a complete record of critical power events, and it notifies you of important UPS or power information.
- If there is a power outage and the 9E UPS battery power becomes low, Eaton Software suite can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Trouble shooting
PROBLEM | POSSIBLE CAUSE | SOLUTION |
---|
THE DISPLAY DOES NOT LIGHT UP
| INPUT SWITCH OPEN| Close the input switch located on the back of the UPS.
MAIN CONNECTION CABLE MISSING| Check that the power cable is connected
correctly.
NO MAINS VOLTAGE (BLACKOUT)| ****
Check that the power reaches the UPS
UPSTREAM THERMAL PROTECTION TRIP| Reset the thermal protection.
CAUTION: Check that there is no output overload to the UPS.
THE DISPLAY IS ON BUT THE LOAD IS NOT POWERED| ****
THE UPS IS IN Standby mode
| Press the “ON” button on the front panel to power the loads.
THE UPS IS OPERATING FROM THE BATTERY DESPITE THE PRESENCE OF MAINS VOLTAGE|
THE INPUT VOLTAGE IS OUTSIDE THE PERMITTED TOLERANCE RANGE FOR MAINS OPERATION
| ****
Problem with the mains. Wait until the input mains voltage returns within the tolerance range. The UPS will automatically return to mains operation.
THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES:
A80E, A810, F808
| ****
THE LOAD APPLIED TO THE UPS IS TOO HIGH
| Reduce the load to within the threshold of 100% (or user threshold in the case of code A80E).
If the display shows an Fault:
remove the load and switch the UPS off and back on again.
THE DISPLAY SHOWS THE FOLLOW CODE: A60D| BATTERIES MISSING OR BATTERY BOX
MISSING OR NOT CONNECTED| Check that the Battery Box is inserted and connected
to the UPS correctly.
THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING
CODES:
A004 F004
| ****
THE TEMPERATURE INSIDE THE UPS IS TOO HIGH
| ****
Check that the temperature of the environment in which the UPS is located does not exceed 40°C.
THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES: F805| ****
THERE IS A FAULT ON ONE OR MORE OF THE LOADS POWERED BY THE UPS
| ****
Disconnect all the utilities, switch the UPS off and back on again, reconnect the utilities one at a time to identify which one is faulty.
THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES: F704, F70D,F70C,F302, F303,F305,F300,F301,F3
04, F002
| ****
THE UPS IS MALFUNCTIONING
| ****
If possible, disconnect the power to the load, switch the UPS off and back on again; if the problem occurs again, call the support centre.
THE DISPLAY SHOWS THE CODE: A900| THE MAINTENANCE BYPASS FUNCTION IS ACTIVE| To take the UPS out of the maintenance bypass
function, open the manual bypass switch on the back of the UPS.
Alarm codes
Using a sophisticated self-diagnosis system, the UPS is able to check its own status and any anomalies and/or faults which may occur during normal operation and display them on the display panel. If there is a problem, the UPS signals the event by showing the code and the type of active alarm on the display.
ALARMS
“Minor” problems which reduce performance or prevent certain functions from being used.
CODE | DESCRIPTION |
---|---|
A007 | Fans blocked |
A107 | Cable connection error |
A10A | Unbalanced input voltages (three-phase input) |
A806 | E.P.O control active |
A80E | Overload: load > 105% |
A810 | Load percentage greater than the user threshold set |
A60D | Batteries missing or Battery Box missing or not connected |
A802 | Low battery |
FAULTS
Faults are normally preceded by an alarm signal and their scale leads to the power-off of the inverter and the load being powered by the bypass line.
CODE | DESCRIPTION |
---|---|
F002 | UPS Fault |
F004 | Dissipator over temperature |
F302 F303 | Capacitor bank undervoltage |
F300 F301 | Capacitor bank overvoltage |
F304 | Unbalanced capacitor bank |
F305 | Failed capacitor bank soft start |
F70D | Inverter overvoltage |
F805 | Short circuit |
F704 | Failed inverter soft start |
F70C | Inverter undervoltage |
F808 | Output overload fault |
F811 | Negative output power |
Technical data
UPS MODELS| 9E6Ki| 9E10Ki,
9E10KiXL
| 9E15Ki| 9E20Ki,
9E20KiXL
---|---|---|---|---
INPUT|
Nominal voltage| [Vac]| 220 – 230 – 240| 220 – 230 – 240 / 380 – 400 – 415
Maximum operating voltage| [Vac]| 276| 276 / 478
Nominal frequency| [Hz]| 50 – 60
Nominal current| [A]| 26| 41 / 16
(42 / 20,5 XL)
| 62 / 22| 82 / 28
(83 / 29,5 XL)
BATTERY|
Recharge time (standard versions)| [h]| < 8h for 90% of the charge
Expandability and nominal voltage of the Battery Box| | 180Vdc| 240Vdc| 240 +
240Vdc| 240 + 240Vdc
Charging current
(for XL versions only)
| | Not applicable| 4,4A| 5A| 5A
OUTPUT|
Nominal voltage| [Vac]| Selectable: 220/230/240
Frequency| [Hz]| Selectable: 50, 60 or auto sensing
Nominal power| [VA]| 6000| 10000| 15000| 20000
Nominal power| [W]| 4800| 8000| 12000| 16000
Overload: 105% < load < 110%
| Bypass line available:| activates the bypass after 5 min, then continues to
work
Bypass line not available:| locks after 5 min
Overload: 110% < load < 130%
| Bypass line available:| activates the bypass after 1 min, then locks after 1
min
Bypass line not available:| locks after 1 min
Overload: 130% < load < 150%
| Bypass line available:| activates the bypass after 10 s, then locks after 10
s
Bypass line not available:| locks after 10 s
Overload load > 150%
| Bypass line available:| activates the bypass after 100 ms, then locks after
1 s
Bypass line not available:| locks after 1 s
OTHER|
Leakage current to earth| [mA]| < 8mA
Ambient temperature| [°C]| 0 – 40
Humidity| < 95% without condensation
Protection devices| Batteries deep discharge – overcurrent – short circuit –
overvoltage – undervoltage – circuit breaker
Dimensions W x D x H| [mm]| 262 x 613x 709| 350 x 706 x 818
Weight| [kg]| 65| 85
(34 XL)
| 142| 153
(48 XL)
Operating Temperature| 0 oC to 40 oC
Operating humidity| 0-95% no condensing
Altitude| Up to 1,000 meters above sea level with 10% derating per 1000m
Storage temperature| -15oC to 60oC without batteries 0~35°C with batteries
EBM | 180VDC 9Ah | 240VDC 9Ah |
---|---|---|
Nominal battery voltage | [Vdc] | 180Vdc |
Dimensions W x D x H | [mm] | 262 x 580 x 709 |
Weight | [kg] | 130 |
Frequently Asked Questions
What is the Eaton 9E 20000I Double-conversion UPS, and what does it do?
The Eaton 9E 20000I Double-conversion UPS is a power protection device designed to provide uninterrupted electrical power to critical equipment, ensuring they remain operational during power disturbances.
How much power does the Eaton 9E 20000I UPS deliver?
The Eaton 9E 20000I UPS has a capacity of 20,000 VA (or 20 kVA) to handle a substantial load.
What is double-conversion technology in the Eaton 9E 20000I UPS?
Double-conversion technology means that the UPS constantly converts incoming AC power to DC and then back to AC power, ensuring a clean and stable output even in the presence of irregularities in the input power.
What types of equipment are best protected by the Eaton 9E 20000I UPS?
The Eaton 9E 20000I UPS is ideal for safeguarding sensitive electronics and critical systems such as servers, data centers, networking equipment, and more.
Does the Eaton 9E 20000I UPS come with a warranty?
Typically, Eaton provides a standard warranty for its products. It's important to check the specific warranty details with the seller or manufacturer.
Can the Eaton 9E 20000I UPS be rack-mounted?
Yes, the Eaton 9E 20000I UPS is designed to be rack-mounted, making it suitable for data center environments.
How long can the Eaton 9E 20000I UPS provide backup power during an outage?
The backup runtime of the UPS depends on the load it is supporting. You can typically find this information in the product's specifications.
Is it possible to extend the runtime of the Eaton 9E 20000I UPS with additional battery packs?
Some UPS models allow you to extend the runtime by adding external battery packs. Check if this option is available for the Eaton 9E 20000I.
Does the Eaton 9E 20000I UPS have a built-in monitoring and management system?
Eaton UPS systems often come with monitoring and management capabilities, including remote monitoring and alerts. Confirm the specific features of this model.
Can the Eaton 9E 20000I UPS protect against power surges and spikes?
Yes, the Eaton 9E 20000I UPS provides protection against power surges, spikes, and other electrical disturbances.
How is the Eaton 9E 20000I UPS different from other UPS models in the market?
The differences may include capacity, features, form factor, and efficiency. It's essential to compare specifications to determine which UPS best suits your needs.
What is the efficiency rating of the Eaton 9E 20000I UPS?
Eaton UPS systems are known for their high efficiency. Look for the efficiency rating in the product specifications for precise details.
Reference:Eaton 9E 20000I Double-conversion UPS User Manual- device.report
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>