TASK LP36HR18NDGSN27 Lighted Power Strip Installation Guide
- June 16, 2024
- TASK
Table of Contents
TASK LP36HR18NDGSN27 Lighted Power Strip Installation
Product Information
Specifications
- Product Name: Lighted Power Strip DV Series
- Installation Type: LPS WITH Built-In Power Supply
- Date: January 2019
- Customer Service: 800-445-6404
- Design Services & Tech Support: 866-848-9094
- Website: www.TaskLighting.com
General Guidelines
The following instructions guide how to install the Lighted Power Strip DV
Series with a built-in power supply.
Bottom of Cabinet Tool
- Turn off the power at the panel before starting the installation.
- Carefully pry open each piece using the provided tool.
- Insert the Romex connector into the knockout hole inside the back frame.
- Pull the wires into the LPS.
Wiring for Combined Light and Receptacle Circuit – Non Dimmable
Factory Wired:
- RED wire is positive (+)
- The BLUE wire is negative (-)
- SWITCH
- DRIVE
- BK (Black)
- WT (White)
- GRN (Green)
- DIVIDER PLATE
- 120V input
Step 1: Secure LPS to Wall
- Screw the LPS into wall studs or use the provided anchors to secure it.
Step 2: Connect the Wiring
- Connect the BLACK Romex wire to the BLACK wire from the receptacles and switch.
- Connect the WHITE Romex wire to the WHITE wire from the receptacles and driver.
- Ground all GREEN wires to PEM studs inside the back frame.
Step 3: Connect Multiple LPS Fixtures
- When connecting two or more LPS fixtures, run Romex from fixture to fixture.
- Ground each section to the next.
Step 4: Terminate Last LPS
- Use wire nuts on the ends of wires to terminate the last LPS fixture.
Step 5: Complete Installation
- Snap the cover in place.
- Turn on the power.
Wiring for Separate Light and Receptacle Circuits
Factory Wired:
- RED wire is positive (+)
- BLUE wire is negative (-)
- SWITCH
- BK (Black)
- DRIVER
- WT (White)
- DIVIDER PLATE
- 120V input for lights
- 120V input for receptacles
Step 1: Secure LPS to Wall
- Screw the LPS into wall studs or use the provided anchors to secure it.
Step 2: Connect the Wiring
- If running two circuits, one for receptacles and one for lighting, connect fixture wires to appropriate Romex wires.
- Connect BLACK to BLACK and WHITE to WHITE.
- Ground all GREEN wires to PEM studs inside the back frame.
Step 3: Connect Multiple LPS Fixtures
- When connecting two or more LPS fixtures, run Romex from fixture to fixture.
- Ground each section to the next.
Step 4: Terminate the Last LPS
- Use wire nuts on the ends of wires to terminate the last LPS fixture.
Step 5: Complete Installation
- Snap the cover in place.
- Turn on the power.
FAQ
-
Q: How do I secure the LPS to the wall?
A: You can either screw the LPS into wall studs or use the provided anchors for installation -
Q: Can I connect multiple LPS fixtures?
A: Yes, you can connect two or more LPS fixtures by running Romex from fixture to fixture and grounding each section to the next. -
Q: What should I do with the last LPS fixture?
A: To terminate the last LPS fixture, use wire nuts on the ends of the wires. -
Q: How do I turn on the power after installation?
A: After completing the installation, snap the cover in place and turn on the power at the panel.
General Guidelines
- The power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI before the connection at LPS.
- All wiring must meet NEC® and local codes.
- Light valance is recommended.
- Firmly insert the plug straight into a receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
Turn the power off at the panel. Carefully pry open each piece with the tool (provided). Insert the Romex connector into the knockout hole inside of the back frame. Pull wires into LPS.
Wiring for Combined Light and Receptacle Circuit – Non-Dimmable
-
Step 1
Secure LPS to the wall by screwing into wall studs or using the anchors provided. Connect BLACK Romex wire to BLACK wire from receptacles and switch. Connect WHITE Romex wire to WHITE wire from receptacles and driver. Ground all GREEN wires to PEM studs inside of the back frame. -
Step 2
When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next. -
Step 3
To terminate the last LPS, use wire nuts on the ends of the wires. -
Step 4
Snap the cover in place and turn the power on.
Wiring for Separate Light and Receptacle Circuits
-
Step 1
Secure LPS to the wall by screwing into wall studs or using the anchors provided. If running two circuits, one for receptacles, and one for lighting, connect fixture wires to appropriate Romex wires. BLACK to BLACK. WHITE to WHITE. Ground all GREEN wires to PEM studs inside of the back frame. -
Step 2
When connecting 2 or more LPS fixtures, run Romex from fixture to fixture. Ground each section to the next. -
Step 3
To terminate the last LPS, use wire nuts on the ends of wires -
Step 4
Snap the cover in place and turn the power On.
Wiring Diagram for Combined Light & Receptacle Circuit – Non-Dimmable
Wiring Diagram for Separate Light & Receptacle Circuits
General Guidelines
- The power source MUST be a 20 amp branch circuit protected by a GFCI at the panel or GFCI before the connection at LPS.
- All wiring must meet NEC and local codes.
- Light valance is recommended.
- Firmly insert the plug straight into a receptacle, applying equal pressure to both blades at the same time. Gently rock plug, if needed.
Turn the power off at the panel. Carefully pry open each piece with a tool (provided). Insert the Romex connector into the knockout hole inside of the back frame. Pull wires into LPS.
Remote Power Supply- 120V Entry
-
Secure LPS to the wall by screwing into wall studs or using the anchors provided. Connect BLACK to BLACK, WHITE to WHITE. Ground all GREEN wires to PEM studs inside of the back frame.
-
When connecting two LPS, run Romex from fixture to fixture. Ground each section to the next.
-
To terminate the last LPS, use wire nuts on the ends of the wires.
Remote Power Supply-Low Voltage Entry -
Using an appropriate knockout hole, pull low voltage wire from the remote power supply into the low voltage space, connect BLACK wire (negative) to BLACK wire from lights and RED wire (positive) to RED wire.
-
Snap the cover in place and turn the power on.
Customer Service: 800.445.6404 • Design Services/Technical Support: 866.848.9094 • TaskLighting.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>