Kaden KDI Series Ducted Air Conditioner Instruction Manual
- June 16, 2024
- kaden
Table of Contents
- KDI Series Ducted Air Conditioner
- Product Information
- Specifications
- Safety Precautions
- 1. WARNING
- 2. CAUTION
- 1. Accessories
- 2. Indoor Unit Installation
- 3. Outdoor Unit Installation
- 4. Drainpipe Installation
- 5. Refrigerant Piping Connection
- 6. Leak Testing and Evacuation
- 7. Wiring
- 8. Electrical Checks
- 9. Test Run
- 10. Manual Operations
- FAQ (Frequently Asked Questions)
- Q: What should I do if I encounter an error code?
- Q: Can I install the air conditioner by myself?
- Q: What refrigerant does the air conditioner use?
- Q: How should I maintain the air conditioner?
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
KDI Series Ducted Air Conditioner
Product Information
Specifications
- Product: Ducted Air Conditioner
- Model: KDI24
- Refrigerant: R32
Safety Precautions
It is crucial to read and follow the safety precautions outlined
in the user manual before operating or installing the product.
Failure to do so may result in serious damage or injury. The safety
precautions are classified into two categories:
1. WARNING
-
Do not share the electrical outlet with other appliances.
Improper or insufficient power supply can cause fire or electrical
shock. -
When connecting refrigerant piping, do not let substances or
gases other than the specified refrigerant enter the unit. The
presence of other gases or substances will lower the unit’s
capacity and can cause abnormally high pressure in the
refrigeration cycle, leading to explosion and injury. -
Do not allow children to play with the air conditioner.
Children must be supervised around the unit at all times. -
Installation must be performed by an authorized dealer or
specialist. Defective installation can cause water leakage,
electrical shock, or fire.
2. CAUTION
There are no specific cautionary instructions mentioned in the
provided text extract. However, it is essential to read the
complete user manual for any additional cautionary measures.
Installation
1. Accessories
Ensure that all necessary accessories are included in the
package before starting the installation process.
2. Indoor Unit Installation
Indoor Unit Parts
Identify and familiarize yourself with the parts of the indoor
unit.
Safety Precautions
Follow the safety precautions to prevent any accidents during
the installation process.
Indoor Unit Installation Instructions
Refer to the user manual for detailed instructions on installing
the indoor unit.
Installation Place
Select an appropriate location for installing the indoor unit,
considering factors such as airflow, accessibility, and
aesthetics.
Maintenance Space
Ensure there is sufficient space around the indoor unit for
maintenance purposes.
3. Outdoor Unit Installation
Outdoor Unit Installation Instructions
Follow the provided instructions in the user manual for
installing the outdoor unit.
Outdoor Unit Specifications
Refer to the specifications section for details on the outdoor
unit.
Drain Joint Installation
Properly install the drain joint according to the instructions
to ensure efficient drainage.
Notes on Drilling Hole in Wall
Take necessary precautions while drilling a hole in the wall for
outdoor unit installation.
4. Drainpipe Installation
Note on Drainpipe Installation
Follow the provided note on drainpipe installation for proper
functioning of the air conditioner.
5. Refrigerant Piping Connection
Safety Precautions
Adhere to the safety precautions mentioned in the user manual
during refrigerant piping connection.
Note on Pipe Length and Elevation
Follow the guidelines regarding pipe length and elevation for
optimal performance.
Refrigerant Piping Connection Instructions
Refer to the user manual for step-by-step instructions on
connecting the refrigerant piping.
Note on Minimum Bend Radius
Maintain the minimum bend radius while handling the refrigerant
piping to prevent damage.
6. Leak Testing and Evacuation
Perform leak testing and evacuation procedures before operating
the air conditioner.
Leak, Pressure Test, and Evacuation
Follow the provided instructions for conducting leak testing,
pressure testing, and evacuation.
Preparations and Precautions
Take necessary preparations and precautions before performing
the evacuation process.
Opening Outdoor Unit Valves
Follow the instructions for opening the valves of the outdoor
unit during the evacuation process.
Note on Adding Refrigerant
Refer to the note on adding refrigerant if required during the
installation process.
7. Wiring
Safety Precautions
Follow the safety precautions mentioned in the user manual while
performing wiring tasks.
Signal Wiring between Outdoor and Indoor Units
Connect the signal wiring between the outdoor and indoor units
as per the provided instructions.
Indoor Unit Wiring
Ensure proper wiring of the indoor unit following the user
manual guidelines.
8. Electrical Checks
Electrical Safety Checks
Perform electrical safety checks before and during the test run
to ensure safe operation.
9. Test Run
Before Test Run
Make necessary preparations before conducting the test run.
Test Run Instructions
Follow the provided instructions for conducting the test run of
the air conditioner.
10. Manual Operations
Refer to the user manual for details on manual operations and
error codes.
FAQ (Frequently Asked Questions)
Q: What should I do if I encounter an error code?
A: Refer to the manual operations section for information on
error codes and their corresponding actions to be taken.
Q: Can I install the air conditioner by myself?
A: No, installation must be performed by an authorized dealer or
specialist to ensure proper functioning and safety.
Q: What refrigerant does the air conditioner use?
A: The air conditioner uses R32 refrigerant.
Q: How should I maintain the air conditioner?
A: Follow the maintenance instructions provided in the user
manual for regular upkeep of the air conditioner.
DUCTED AIR CONDITIONER
Installation Manual
KDI Series
KDI24
Important note
This appliance must be installed in accordance with: Manufacturer’s
Installation Instructions Current AS/NZS 3000, AS/NZS 5149 Local Regulations
and Municipal Building Codes including local OH&S requirements This appliance
must be installed, maintained, and removed only by an Authorised Person. For
continued safety of this appliance, it must be installed and maintained in
accordance with the manufacturer’s Instructions.
REFRIGERANT
R32
2 | Kaden Installation Manual
Table of contents
1. Safety precautions
Note about fluorinated gases
2. Accessories 3. Installation summary 4. Indoor unit installation
Indoor unit parts Safety precautions Indoor unit installation instructions
Installation place Maintenance space
5. Outdoor unit installation
Outdoor unit installation instructions Outdoor unit specifications Drain joint
installation Notes on drilling hole in wall
6. Drainpipe installation
Note on drainpipe installation
7. Refrigerant piping connection
Safety precautions Note on pipe length and elevation Refrigerant piping
connection instructions Note on minimum bend radius
8. Leak testing and evacuation
Leak, pressure test and evacuation Preparations and precautions Before
performing evacuation Opening outdoor unit valves Note on adding refrigerant
9. Wiring
Safety precautions Signal wiring between outdoor and indoor units Indoor unit
wiring
10. Electrical checks
Electrical safety checks Before test run During test run
11. Test run
Before test run Test run instructions
12. Manual operations
Manual operations Error codes
Important note
Read this manual carefully before installing or operating your new air
conditioning unit. Make sure to save this manual for future reference.
4 5 6 7 8 8 8 9 9 10 15 15 16 17 17 18 18 20 20 20 21 23 24 24 25 25 25 25 26
26 28 28 32 32 32 32 33 33 33 34 34 35
Kaden Installation Manual | 3
1. Safety precautions
Read safety precautions before operation and installation
Incorrect installation due to ignoring instructions can cause serious damage
or injury. The seriousness of potential damage or injuries is classified as
either a WARNING or CAUTION.
This symbol is a WARNING, and indicates that ignoring instructions may cause
death or serious injury.
This symbol is a CAUTION, and indicates that ignoring instructions may cause
moderate injury to your person, or damage to your unit or other property.
This symbol indicates that you must never perform the action indicated.
WARNING
Do not share the electrical outlet with other appliances. Improper or
insufficient power supply can cause fire or electrical shock.
When connecting refrigerant piping, do not let substances or gases other than
the specified refrigerant enter the unit. The presence of other gases or
substances will lower the unit’s capacity, and can cause abnormally high
pressure in the refrigeration cycle. This can cause explosion and injury.
Do not allow children to play with the air conditioner. Children must be
supervised around the unit at all times.
1. Installation must be performed by an authorised dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
2. Installation must be performed according to the installation instructions.
Improper installation can cause water leakage, electrical shock, or fire.
3. Contact an authorised service technician for repair or maintenance of this
unit.
4. Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If
the chosen location cannot support the unit’s weight, or the installation is
not done properly, the unit may drop and cause serious injury and damage.
6. Only fully qualified licensed personnel should install, service or carry
out maintenance to this air conditioning unit. All electrical work is to
follow local and national wiring standards and the Installation Manual.
7. You must use an independent circuit and single outlet to supply power. Do
not connect other appliances to the same outlet. Insufficient electrical
capacity or defects in electrical work can cause electrical shock or fire.
8. For all electrical work, use the specified cables. Connect cables tightly,
and clamp them securely to prevent external forces from damaging the terminal.
Improper electrical connections can overheat and cause fire, and may also
cause shock.
9. All wiring must be properly arranged to ensure that the control board
cover can close properly. If the control board cover is not closed properly,
it can lead to corrosion and cause the connection points on the terminal to
heat up, catch fire, or cause electrical shock.
10. In certain functional environments, such as kitchens, server rooms, etc.,
the use of specially designed airconditioning units is highly recommended.
11. This appliance can be used by children aged from 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards
involved. Children must not play with the appliance. Cleaning and user
maintenance must not be made by children without supervision.
4 | Kaden Installation Manual
CAUTION
Do not install the unit in a location that may be exposed to combustible gas
leaks. If combustible gas accumulates around the unit, it may cause fire. Do
not operate your air conditioner in a wet room such as a bathroom or laundry
room. Too much exposure to water can cause electrical components to short
circuit. 1. The product must be properly grounded at the time of installation,
or electrical shock may occur. 2. Install drainage piping according to the
instructions in this manual. Improper drainage may cause water damage to your
home and property.
Note about fluorinated gases
1. This air-conditioning unit contains fluorinated gases. For specific
information on the type of gas and the amount, please refer to the relevant
label on the unit itself.
2. Installation, decommissioning, service, maintenance and repair of this
unit must be performed by a licensed technician. 3. Product decommissioning
and recycling must be performed by a licensed technician. 4. If the system has
a leak-detection system installed, it must be checked for leaks at least every
12 months. 5. When the unit is checked for leaks, proper record-keeping of all
checks is strongly recommended. 6. Only ARC (Australian Refrigeration Council)
licence holders can install and commission this air conditioner. This air
conditioner must be installed to meet the requirements of the current version
of AS/NZS 5149. 7. It is illegal to vent some types of refrigerant to the
atmosphere.
REFRIGERANT
This appliance uses R32 (difluoromethane) refrigerant, which is a flammable
gas class 2.2 according to AS/NZS 5149 and must be handled by a refrigeration
mechanic with appropriate Australian refrigerant handling licence. · WARNING
risk of fire/flammable material. If the refrigerant is leaked, together with
an external ignition source, there is
possibility of ignition. · Read all the OPERATING INSTRUCTIONS carefully
before operation. · Service personnel are required to carefully read the
OPERATING INSTRUCTIONS and INSTALLATION MANUAL
before operation. · Further information is available in the OPERATING
INSTRUCTIONS, INSTALLATION MANUAL and the like. Certain levels of refrigerant
require minimum room sizes. Please ensure that these minimum room sizes are
adhered to for standard installations (up to 10m pipe length). If larger
refrigerant charges than standard are used then please consult AS/NZS
60335.2.40 to determine the safe minimum floor area for the installation. Make
sure that the area has been made safe by having suitable ventilation and is
free from ignition sources before charging or recovering the charge of R32.
Kaden Installation Manual | 5
2. Accessories
The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.
Name
Shape
Quantity
Tubing and fittings
Soundproof/insulation sheath
2
Drain joint
1
Cooling and heating
Seal ring
1
Owner’s manual
1
Installation manual
1
Others
Display panel (for testing purposes only)
1
Wired controller
1
EMC magnetic ring
Magnetic ring wrap the electric wires
1
S1 & S2 around the magnetic ring twice
6 | Kaden Installation Manual
3. Installation summary
1
2
3
Install the indoor unit (page 8)
Install the outdoor unit (page 15)
Install the drainpipe (page 18)
6
5
4
Connect the wires (page 26)
7
S1
S2
Leak test and evacuation (page 24)
8
Connect the refrigerant pipes (page 20)
Connect the signal wires (page 28)
Perform a test run (page 33)
Kaden Installation Manual | 7
4. Indoor unit installation
Indoor unit parts
Air outlet Supply air
Safety precautions
Air inlet Return air
Fig. 4.1
Electric control cabinet
Air filter
Drain hose Refrigerant connecting pipe
WARNING
Securely install the indoor unit on a structure that can sustain its weight.
If the structure is too weak, the unit may fall, causing personal injury, unit
and property damage, or even death.
CAUTION
Install the indoor and outdoor units, cables and wires at least 1m from
televisions or radios to prevent static or image distortion. Depending on the
appliances, a 1m distance may not be sufficient.
8 | Kaden Installation Manual
Indoor unit installation instructions
Step 1: Select installation location
The indoor unit should be installed in a location that meets the following
requirements: Enough room for installation and maintenance. Enough room for
the connecting pipe and drainpipe. The ceiling is horizontal and its structure
can sustain the
weight of the indoor unit. The air inlet and outlet are not impeded. The
airflow can fill the entire room. There is no direct radiation from heaters.
It is embedded installation.
CAUTION
Do not install unit in the following locations: Where oil drilling or fracking
is taking place. Coastal areas with high salt content in the air. Near
geothermal activity and corrosive gas. Buildings that may experience power
fluctuations. Enclosed spaces. Areas with strong electromagnetic waves. Areas
that store flammable materials or gas. Rooms with high humidity, such as
bathrooms or laundry rooms.
Installation place
Strong and durable ceiling Indoor unit
Left side
Right side
100mm
300mm Fig. 4.2
20mm B > 20mm
300mm
Service access
Ceiling
Floor
2500mm (When no ceiling)
Kaden Installation Manual | 9
Maintenance space
200mm
Air outlet
Supply air
300mm
Air inlet
Return air
Fig. 4.3
600mm x 600mm maintenance clearance
Step 2: Hang indoor unit
1. Please refer to the following diagrams to locate the four positioning screw bolt holes on the ceiling. Be sure to mark the places where you will drill ceiling hook holes.
Air outlet dimensions
Air inlet dimensions
A F
H
Air
filter
Descending ventilation opening and mounted hook
C
D
Air
filter
B E J
G
10 | Kaden Installation Manual
Fig. 4.4
Electric
control
I
box
Table 4.1 (Unit: mm)
Model KDI24
Outline dimension
A
B
C
D
1100
249
774
700
Air outlet opening size
E
F
175
926
Air return opening size
G
H
228
1001
Size of mounted lug
I
J
1140
598
Wood Place the wood mounting across the roof beams, then install the hanging
screw bolts. (See Fig. 4.5)
Wood mounting
Steel roof beam structure Install and use the supporting steel angle. (See
Fig. 4.8)
Hanging screw bolt
Roof beam Ceiling Hanging screw bolts Fig. 4.5 New concrete bricks Inlay or embed the screw bolts. (See Fig. 4.6)
Blade shape insertion
Slide insertion
Fig. 4.6
Original concrete bricks
Use an embedding screw bolt, crock and stick harness. (See Fig. 4.7)
Steel bar
Embedding screw bolt (Pipe hanging and embedding screw bolt)
Fig. 4.7
Hanging bolts
Supporting angle steel
Fig. 4.8
CAUTION
The unit body must be completely aligned with the hole. Ensure that the unit
and the hole are the same size before moving on.
2. Install and fit pipes and wires after you have finished installing the
main body. When choosing where to start, determine the direction of the pipes
to be drawn out. Especially in cases where there is a ceiling involved, align
the refrigerant pipes, drain pipes, and indoor and outdoor lines with their
connection points before mounting the unit.
3. Install hanging screw bolts. · Cut off the roof beam. · Strengthen the
point at which the cut was made. Consolidate the roof beam.
4. Drill 4 holes 10cm deep at the ceiling hook positions in the internal
ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
5. Install the four suspension bolts.
6. Mount the indoor unit with at least two people to lift and secure it.
Insert suspension bolts into the unit’s hanging holes. Fasten them using the
washers and nuts provided. (See Fig. 4.9)
Kaden Installation Manual | 11
Step 3: Duct and accessories installation
1. Install the filter (optional) according to the size of the air inlet.
2. Install the flexible tie-in between the body and the duct. 3. The air
inlet and air outlet duct should be far enough
apart to avoid air passage short-circuit. 4. Connect the duct according to the
following diagram:
Isolation booth Flexible tie-in
Fig. 4.9
7. Mount the indoor unit onto the hanging screw bolts with a block. Position
the indoor unit flat using a level indicator to prevent leaks. (See Fig. 4.10)
Washer
Hanging screw bolt
Screw nut Shockproof cushion Screw nut Overhang part
Fig. 4.10
NOTE: Confirm the minimum drain tilt is 1/100 or more.
Air outlet Checking orifice
Air dust Air inlet filter
Fig. 4.11
5. Refer to the following static pressure guidelines when installing the
indoor unit.
Table 4.2
Model KDI24
Static pressure (Pa)
0~160
Change the fan motor static pressure according to external duct static
pressure.
Note
1. Do not place the connecting duct weight on the indoor unit.
2. When connecting the duct, use a non-flammable canvas tie-in to prevent
vibrating.
3. Insulation foam must be wrapped outside the duct to avoid condensate. An
internal duct under-layer can be added to reduce noise, if the end-user
requires.
12 | Kaden Installation Manual
Step 4: Adjust the air inlet direction (from rear side to under-side)
1. Take off the ventilation panel and flange.
Step 5: Adjust the air inlet direction
Dimension:
Duct joint for fresh air
Air return flange
Ventilation panel Fig. 4.12
2. Change the mounting positions of the ventilation panel and air return
flange.
Model KDI24 Duct joint for fresh air dimensions
Ø125mm
Ventilation panel
Fig. 4.15
Air return flange Fig. 4.13
3. When installing the filter mesh, fit it into the flange as illustrated in
the following figure.
Ø160mm
Fig. 4.14
Note
All the figures in this manual are for demonstration purposes only. The air
conditioner you have purchased may be slightly different in design, though
similar in shape.
Kaden Installation Manual | 13
Step 6: Motor and drain pump maintenance (the rear ventilated panel is used as
an example)
Motor maintenance: 1. Take off the ventilated panel. 2. Take off the blower
housing. 3. Take off the motor.
Motor Blower housing Ventilated panel Fig. 4.16 Pump maintenance: 1. Remove
four screws from the drain pump. 2. Unplug the pump power supply and water
level switch cable. 3. Detach the pump. 4. Replace all components to re-
assemble and complete maintenance.
Pump Fig. 4.17
14 | Kaden Installation Manual
5. Outdoor unit installation
Outdoor unit installation instructions
Step 1: Select installation location
The unit should be installed in a location that meets the following
requirements:
Place the outdoor unit as close to the indoor unit as possible.
Ensure that there is enough room for installation and maintenance.
The air inlet and outlet must not be obstructed or exposed to strong wind.
Ensure the location of the unit will not be subject to snowdrifts,
accumulation of leaves or other seasonal debris. If possible, provide an
awning for the unit. Ensure the awning does not obstruct airflow.
The installation area must be dry and well ventilated.
There must be enough room to install the connecting pipes and cables and to
access them for maintenance.
Strong wind
Fig. 5.2
Strong wind
Step 2: Install outdoor unit
Fix the outdoor unit with anchor bolts (M10).
60cm
Fix with bolts
Strong wind
Fig. 5.1
The area must be free of combustible gases and chemicals.
The pipe length between the outdoor and indoor unit may not exceed the maximum
allowable pipe length.
If possible, do not install the unit where it is exposed to direct sunlight.
If possible, make sure the unit is located far away from your neighbours’
property so that the noise from the unit will not disturb them.
If the location is exposed to strong winds (for example: near a seaside), the
unit must be placed against the wall to shelter it from the wind. If
necessary, use an awning.
Install the indoor and outdoor units, cables and wires at least 1 metre from
televisions or radios to prevent static or image distortion. Depending on the
radio waves, a 1 metre distance may not be enough to eliminate all
interference.
Fig. 5.3
CAUTION
· Be sure to remove any obstacles that may block air circulation.
· Make sure you refer to Length specifications (See Fig. 5.7) to ensure to
ensure there is enough room for installation and maintenance.
Kaden Installation Manual | 15
Outdoor unit specifications
Split type outdoor unit (Refer to Fig. 5.4, Fig. 5.5, Fig. 5.6, Fig. 5.7 and
Table 5.1)
Fig. 5.4 H
Table 5.1 Length specifications of split type outdoor unit
Outdoor unit dimensions W x H x D
890mm x 673mm x 342mm
Mounting dimensions
Distance A Distance B
673mm
403mm
NOTE: The minimum distance between the outdoor unit and walls described in the installation guide does not apply to airtight rooms. Be sure to keep the unit unobstructed in at least two of the three directions (M, N, P). (See Fig. 5.7)
W Fig. 5.5
M
300mm on left
N H
2000mm in front
600mm above
200mm from back wall
Fig. 5.7
P
600mm on right
W A
Fig. 5.6 D
B
16 | Kaden Installation Manual
Rows of series installation
Table 5.2 The relations between H, A and L are as follows.
L H L > H
L
A
L 1/2H
250mm or more
1/2H < L H 300mm or more
Can not be installed
Fig. 5.8
250mm or more
250mm or more
H
L A 3000mm or more
600mm or more 1500mm or more
Drain joint installation
If the drain joint comes with a rubber seal (See Fig. 5.9 A), do the
following: 1. Fit the rubber seal on the end of the drain joint that will
connect to the outdoor unit. 2. Insert the drain joint into the hole in the
base pan of
the unit. 3. Rotate the drain joint 90° until it clicks in place facing the
front of the unit. 4. Connect a drain hose extension (not included) to the
drain
joint to redirect water from the unit during heating mode.
Base pan hole of outdoor unit Seal Seal
If the drain joint doesn’t come with a rubber seal (See Fig. 5.9 B), do the
following:
5. Insert the drain joint into the hole in the base pan of the unit. The
drain joint will click in place.
6. Connect a drain hose extension (not included) to the drain joint to
redirect water from the unit during heating mode.
Notes on drilling hole in wall
You must drill a hole in the wall for the refrigerant piping, and the signal
cable that will connect the indoor and outdoor units. 1. Determine the
location of the wall hole based on the
location of the outdoor unit. 2. Using a 65mm core drill, drill a hole in the
wall. 3. Place the protective wall cuff in the hole. This protects
the edges of the hole and will help seal it when you finish the installation
process.
NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and
other sensitive components.
Drain joint
A
B
Fig. 5.9
Kaden Installation Manual | 17
6. Drainpipe installation
The drainpipe is used to drain water away from the unit. Improper installation
may cause unit and property damage.
CAUTION
· Insulate all piping to prevent condensation, which could lead to water
damage.
· If the drainpipe is bent or installed incorrectly, water may leak and cause
a water-level switch malfunction.
· In HEAT mode, the outdoor unit will discharge water. Ensure that the drain
hose is placed in an appropriate area to avoid water damage and slippage.
· Do not pull the drainpipe forcefully. This could disconnect it.
Indoor drainpipe installation Install the drainpipe as illustrated in Fig.
6.1.
Drain hose
Metal clamp
Drainpipe connecting port
Insulation
Fig. 6.1
1. Cover the drainpipe with heat insulation to prevent condensation and
leakage.
2. Attach the mouth of the drain hose to the unit’s outlet pipe. Sheath the
mouth of the hose and clip it firmly with a pipe clasp. (See Fig. 6.2) 1000mm
1500mm
Ceiling
Note on drainpipe installation
· When using an extended drainpipe, tighten the indoor connection with an
additional protection tube. This prevents it from pulling loose.
· The drainpipe should slope downward at a gradient of at least 1/100 to
prevent water from flowing back into the air conditioner.
· To prevent the pipe from sagging, space hanging wires every 1 1.5m.
· If the outlet of the drainpipe is higher than the body’s pump joint, use a
lift pipe for the indoor unit’s exhaust outlet. The lift pipe must be
installed no higher than 55cm from the ceiling board. The distance between the
unit and the lift pipe must be less than 20cm. Incorrect installation could
cause water to flow back into the unit and flood.
· To prevent air bubbles, keep the drain hose level or slightly tiled up
(<75mm).
Drainpipe installation for units with a pump 200mm 1000mm 1500mm
Ceiling
550mm
Lean over 1/50
0 75mm
Fig. 6.3 NOTE: If the drain pump spigot is not used, the drain pump will still
engage if the drain tray fills and activates the water level sensor. This can
lead to water leakage. Possible actions to avoid water leakage: 1. Disconnect
power to drain pump. 2. Plumb drain pump spigot into gravity fed drain.
Fig. 6.2
Lean over 1/50
18 | Kaden Installation Manual
3. Using a 65mm core drill, drill a hole in the wall. Make sure that the hole
is drilled at a slight downward angle, so that the outdoor end of the hole is
lower than the indoor end by about 12mm. This will ensure proper water
drainage (See Fig. 6.4). Place the protective wall cuff in the hole. This
protects the edges of the hole and will help seal it once you finish
installation.
Wall
Drainage pump test procedure
Check that the drainpipe is unhindered. This test should be performed on newly
built houses before the ceiling is painted.
1. Remove the test cover. Fill the water pan with 2 litres of water.
Outdoor
Indoor
12mm
Fig. 6.4
NOTE: When drilling the hole, make sure to avoid wires, plumbing, and other
sensitive components.
4. Pass the drain hose through the wall hole. Make sure the water drains to a
safe location where it will not cause water damage or a slipping hazard.
NOTE: The drainpipe outlet should be at least 5cm above the ground. If it
touches the ground, the unit may become blocked and malfunction. If you
discharge the water directly into a sewer, make sure that the drain has a U or
S pipe to catch odours that might otherwise come back into the house.
Test cap Fig. 6.6
2. Turn on the unit in COOLING mode. You will hear the drain pump. Check
whether the water is discharged properly (a 1 minute lag is possible,
depending on the length of the drain pipe). Check whether water leaks from the
joints.
3. Turn off the air conditioner and put the cap back on.
NOTE: When connecting multiple drainpipes, install the pipes as shown in Fig.
6.5.
With drain pump 0 530mm
Without drain pump
100mm
Fig. 6.5
Kaden Installation Manual | 19
7. Refrigerant piping connection
Safety precautions
WARNING
· All filed piping must be completed by an ARC licensed technician and must
comply with all local and national regulations including AS/NZS 5149 and
Australian wiring regulations.
· When the air conditioner is installed in a small room, measures must be
taken to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of refrigerant leakage. If the refrigerant leaks and
its concentration exceeds its proper limit, hazards due to lack of oxygen may
result.
· When installing the refrigeration system, ensure that air, dust, moisture or
foreign substances do not enter the refrigerant circuit. Contamination in the
system may cause poor operating capacity, high pressure in the refrigeration
cycle, explosion or injury.
· Ventilate the area immediately if there is refrigerant leakage during the
installation. Leaked refrigerant gas is both toxic and flammable. Ensure there
is no refrigerant leakage after completing the installation work.
Note on pipe length and elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the following table :
Table 7.1 The maximum length and drop height based on models. (Unit: metres)
Type of model KDI24
Length of piping 50
Maximum drop height
25
CAUTION
Oil traps If oil flows back into the outdoor unit’s compressor when the indoor
unit is installed higher than the outdoor unit, this might cause liquid
compression or deterioration of oil return. Oil traps in the rising gas piping
can prevent this. An oil trap should be installed every 10m of vertical gas
piping. (See Fig. 7.1)
Indoor unit
Gas piping
Oil trap Outdoor unit
10m
Liquid 10m piping
The indoor unit is installed higher than the outdoor unit Fig. 7.1
20 | Kaden Installation Manual
CAUTION
If the outdoor unit is installed higher than the indoor unit: It is
recommended that vertical suction risers not be up-sized. Proper oil return to
the compressor should be maintained with suction gas velocity. If velocities
drop below 7.62m/s, oil return will be decreased. An oil trap should be
installed every 6m of vertical gas piping. (See Fig. 7.2)
Outdoor unit
Gas piping
Oil trap 6m
Indoor unit
Liquid 6m piping
Refrigerant piping connection instructions
CAUTION
· Do not install the connecting pipe until both indoor and outdoor units have
been installed. Insulate both the gas and liquid piping to prevent water
leakage.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimise the need for
future maintenance. 1. Measure the distance between the indoor and
outdoor units. 2. Using a pipe cutter, cut the pipe a little longer than the
measured distance.
CAUTION
Do not deform pipe while cutting. Be extra careful not to damage, dent, or
deform the pipe while cutting. This will drastically reduce the heating
efficiency of the unit.
3. Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 7.3
for examples of good and bad cuts.
The outdoor unit is installed higher than the indoor unit Fig. 7.2
Size of joint pipes for indoor unit
Table 7.2 Size of joint pipes for R32 indoor unit
Type of model KDI24
Size of main pipe (mm)
Gas side
Liquid side
15.9mm 5/8″
9.5mm 3/8″
90°
Oblique
Rough
Warped
Fig. 7.3
Kaden Installation Manual | 21
Step 2: Remove burrs
Burrs can affect the airtight seal of the refrigerant piping connection. They
must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the
pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of
the pipe.
Point down
Pipe Deburrer
Fig. 7.4
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent
foreign materials from entering the pipe.
2. Sheath the pipe with insulating material. 3. Place flare nuts on both ends
of pipe. Make sure they are
facing in the right direction, because you can’t put them on or change their
direction after flaring. (See Fig. 7.5)
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.
Flare form
Pipe
Fig. 7.6
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully
flared. Flare the pipe in accordance with the dimensions shown in Table 7.3.
Table 7.3 Piping extension beyond flare form
Pipe gauge Ø 9.5
Ø 15.9
Tightening torque
25 26 N.m (255 265 kgf.cm)
45 47 N.m (459 480 kgf.cm)
Flare dimension (A) (Unit: mm)
Min.
Max.
13.2
13.5
19.2
19.7
Flare nut
Copper pipe Fig. 7.5
4. Remove PVC tape from ends of pipe when ready to perform flaring work.
Fig. 7.7
8. Remove the flaring tool and flare form, then inspect the end of the pipe
for cracks and even flaring.
22 | Kaden Installation Manual
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the
outdoor unit. You should first connect the low pressure pipe, then the high
pressure pipe.
1. When connecting the flare nuts, apply a thin coat of refrigeration oil to
the flared ends of the pipes.
2. Align the centre of the two pipes that you will connect.
Note on minimum bend radius
Carefully bend the tubing in the middle according to the diagram below. Do not
bend the tubing more than 90° or more than 3 times.
Bend the pipe with thumb
Indoor unit tubing
Fig. 7.8
Flare nut Pipe
3. Tighten the flare nut as tightly as possible by hand.
4. Using a spanner, grip the nut on the unit tubing.
5. While firmly gripping the nut, use a torque wrench to tighten the flare
nut according to the torque values in Table 7.3.
NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.
Min radius 10cm
Fig. 7.10
6. After connecting the copper pipes to the indoor unit, wrap the power
cable, signal cable and the piping together with binding tape.
NOTE: Do not intertwine signal cable with other wires. While bundling these
items together, do not intertwine or cross the signal cable with any other
wiring.
7. Thread this pipeline through the wall and connect it to the outdoor unit.
8. Insulate all the piping, including the valves of the outdoor unit.
Fig. 7.9
CAUTION
· Ensure that you wrap insulation around the piping. Direct contact with the
bare piping may result in burns or frostbite.
· Make sure the pipe is properly connected. Over-tightening may damage the
bell mouth and under-tightening may lead to leakage.
CAUTION
Check to make sure there is no refrigerant leak after completing the
installation work. If there is a refrigerant leak, located and repair the leak
before evacuating the system (refer to the Leak testing and evacuation section
of this manual).
Kaden Installation Manual | 23
8. Leak testing and evacuation
MC
MC
Leak, pressure test and evacuation
The interconnecting pipe work and indoor unit must be pressure tested at
1000kpa and leak tested before being evacuated. Before using the manifold
gauge and vacuum pump, read their operation manuals to familiarise yourself
with how to use them properly.
Manifold gauge
Compound gauge -76cmHg
Low pressure valve
Pressure hose/ charge hose
Pressure gauge High pressure valve
Charge hose
1. Connect the charge hose of the manifold gauge to the outdoor unit’s low
pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Monitor test pressure and check with a leak detector and bubble solution.
Safely release the test pressure.
4. Open the Low pressure side of the manifold gauge. Keep the High pressure
side closed.
5. Turn on the vacuum pump to evacuate the system.
6. Evacuate the interconnecting pipes to <=500 microns.
7. Close the low pressure side of the manifold gauge, and turn off the vacuum
pump.
8. Wait for 5 minutes, then check that there has been no change in system
vacuum.
9. If the vacuum does not settle, repeat from Step 1 of Leak, pressure test
and evacuations. If there is no change in system vacuum, unscrew the cap from
the packed valve (high pressure valve).
Low pressure valve
Vacuum pump
Fig. 8.1
24 | Kaden Installation Manual
Preparations and precautions
Note on adding refrigerant
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensible gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
Before performing evacuation
Check to make sure that both high pressure and low pressure pipes between the
indoor and outdoor units are connected properly in accordance with the
Refrigerant piping connection section of this manual.
Pressure test the interconnecting pipes. Check to make sure all wiring is
connected properly.
Opening outdoor unit valves
1. Insert hexagonal wrench into the packed valve (high pressure valve) and
open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen
for gas to exit the system, then close the valve after 5 seconds.
Some systems require additional charging depending on pipe lengths. The additional refrigerant to be charged can be calculated using the below.
Liquid side diameter
Ø 9.52/3/8″
Total pipe length Standard pipe length x
24g/m
Refrigerant type R32
CAUTION
· Refrigerant charging must be performed after wiring, vacuuming, and the leak
testing.
· Do not exceed the maximum allowable quantity of refrigerant or overcharge
the system. Doing so can damage the unit or impact its functioning.
· Charging with unsuitable substances may cause explosions or accidents.
Ensure that the appropriate refrigerant is used.
· Refrigerant containers must be opened slowly. Always use protective gear
when charging the system.
· Do not mix refrigerant types.
Valve body
Flare nut
Cap
Valve stem
Fig. 8.2
2. Watch the pressure gauge for one minute to make sure that there is no
change in pressure. The pressure gauge should read slightly higher than
atmospheric pressure.
3. Remove the charge hose from the service port.
4. Using hexagonal wrench, fully open both the high pressure and low pressure
valves.
5. Tighten valve caps on all three valves (service port, high pressure, low
pressure) by hand. You may tighten it further using a torque wrench if needed.
Kaden Installation Manual | 25
9. Wiring
Safety precautions
WARNING
· Disconnect the power supply before working on the unit.
· All wiring must be performed according to local and national regulations,
and must be installed by a licensed electrician.
· Wiring must be done by a qualified technician. Improper connections may
cause electrical malfunction, injury, or fire.
· All electrical connections must be made according to the electrical
connection diagram located on the panels of the indoor and outdoor units.
· If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client and refuse to install the
unit until the safety issue is properly resolved.
· Power voltage should be within 90-100% of rated voltage. Insufficient power
supply can cause malfunction, electrical shock, or fire.
· If connecting power to fixed wiring, install a surge protector and main
power switch with a capacity of 1.5 times the maximum current of the unit.
· If connecting power to fixed wiring, a switch or circuit breaker that
disconnects all poles and has a contact separation of at least 3mm must be
incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
· Do not let wires touch or rest against refrigerant tubing, the compressor,
or any moving parts within the unit.
· Do not connect another appliance into the same circuit. If the unit cannot
handle the load or there is a defect in the wiring, it can lead to shock,
fire, and property damage.
· Connect the power cable to the terminals and fasten it with a clamp. An
insecure connection may cause fire.
· Make sure that all wiring is done correctly and the control board cover is
properly installed. Failure to do so can cause overheating at the connection
points, fire, and electrical shock.
CAUTION
· Connect the outdoor wires before connecting the indoor wires.
· Make sure you ground the unit. The grounding wire should be located away
from gas pipes, water pipes, lightning rods, telephone wires or other
grounding wires. Improper grounding may cause electrical shock.
· Do not connect the unit to the power source until all wiring and piping is
completed.
· Make sure that you do not cross your electrical wiring with your signal
wiring. This may cause distortion and interference.
Take note of fuse specifications
The air conditioner’s printed circuit board (PCB) is designed with a fuse that
provides overcurrent protection. The specifications of the fuse are printed on
the circuit board; examples of such are T5A/250VAC and T10A/250VAC.
Choose the right cable size
The size of the power supply cable, signal cable, fuse, and switch needed is
determined by the maximum current of the unit. The maximum current is
indicated on the nameplate located on the side panel of the unit. Refer to
this nameplate to choose the right cable, fuse, or switch.
Power specifications
Outdoor power supply specifications:
Power
Model Phase Volt
Circuit breaker/fuse (A)
KDI24 1 phase 220 240V
25
26 | Kaden Installation Manual
Outdoor unit wiring
WARNING
Before performing any electrical or wiring work, turn off the main power to
the system.
Electrical requirement
The indoor unit is powered by the outdoor unit. Do not power indoor unit from separate power source.
Cable
Power cable
Conductor size (mm²)
2.5
Type
Type 60245 IEC 57
Remarks
2 core + Earth (Ground) 1 Ø 230 V
Cable
Interconnect power cable
Conductor size (mm²)
1.5
Type
Type 60245 IEC 57
Remarks
2 core + Earth (Ground) 1 Ø 230 V
Cable
Signal cable
Conductor size (mm²)
1.0
Type
Type 60245 IEC 57
Remarks 2 core Shielded
Cable length: Limit voltage drop to less than 2%. Increase cable gauge if
voltage drop is 2% or more.
If the interconnect cable exceeds 30M in length 2.5mm thick cable should be
used.
The cable specifications are based on the assumption that a metal or plastic
conduit is used with no more than three cables contained in a conduit and a
voltage drop of 2%.
Preparing cable
1. Selecting cable Select the power source cable and connecting cable in
accordance with the specifications mentioned below:
a. Power source cable 3-core 2.5mm² or more, conformed with 60245 IEC57. When
selecting the power source cable length, make sure that voltage drop is less
than 2%. If the voltage drop is more than 2%, increase cable thickness.
b. Connecting cable 3-core 1.5mm², conformed with 60245 IEC57.
2. Arrange each wire length as shown. Make sure that each wire is stripped
10mm from the end.
3. Attach round crimp-type terminal to each wire as shown. Select the size of
round crimp-type terminal after considering the specifications of terminal
block and wire diameter.
Power and interconnect cable 30mm or more
Earth wire
Signal cable 30mm or more
40mm or more
Wire end 10mm
40mm or more
Round crimp type terminal
Sleeve Kaden Installation Manual | 27
4. Remove two fixing screws, then remove front panel.
Magnetic ring (if supplied and packed with the accessories)
2 screws
5. Use a hammer and a flat blade screwdriver to knock out the two metal
electrical knock outs.
Pass the belt through the hole of the magnetic ring to fix it on the cable
6. Connect the u-lugs to the terminals. Match the correct wire with the
correct label on the terminal block. Firmly screw the u-lug of each wire to
its corresponding terminal.
7. Clamp down the cable with the wire clamp.
8. The power cables and interconnect power cables will enter the unit
separately through the two knock out holes on the bottom right side panel and
be fastened with a lock ring adaptor or rubber grommet. Wires should be bound
with cable ties and fixed to the internal side of the right chassis panel as
shown in the figure below.
Signal wiring between outdoor and indoor units
Use 2-core shielded data cable to connections S1, S2 and shield on both
outdoor and indoor units. Do not run this cable next to high amperage loads.
See wiring diagram adhered to the electrical enclosure cover panel.
Indoor unit wiring
1. Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket from both ends of the signal
cable to reveal about 15cm of the wire.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp the u-lugs to the ends of the wires.
28 | Kaden Installation Manual
2. Remove the cover of the electric control box on your indoor unit.
3. Connect the u-lugs to the terminals. Match the wire colours/labels with
the labels on the terminal block and firmly screw the u-lug of each wire to
its corresponding terminal. Refer to the serial number and wiring diagram
located on the cover of the electric control box. Control box
Wiring diagram Connective wiring diagram
CAUTION
· While connecting the wires, please strictly follow the wiring diagram.
· The refrigerant circuit can become very hot. Keep the interconnection cable
away from the copper tube.
4. Clamp down the cable with the cable clamp. The cable must not be loose or
pull on the u-lugs.
5. Reattach the electric box cover.
Kaden Installation Manual | 29
Using the wire controller to set external static pressure
· You can use the unit’s automatic airflow adjustment function to set external
static pressure.
· Automatic airflow adjustment is the volume of blow-off air that has been
automatically adjusted to the quantity rated.
1. Make sure the test run is done with a dry coil. If the coil is not dry,
run the unit for 2 hours in FAN ONLY mode to dry the coil.
2. Check that both power supply wiring and duct installation have been
completed. Check that any closing dampers are open. Check that the air filter
is properly attached to the air suction side passage of the unit.
3. If there is more than one air inlet and outlet, adjust the dampers so that
the airflow rate of each air inlet and outlet conforms with the designed
airflow rate. Make sure the unit is in FAN ONLY mode. Press and set the
airflow adjustment button on the remote control to change the airflow rate
from H or L.
4. Set the parameters for automatic airflow adjustment. When the air
conditioning unit is off, perform the following steps:
Press the COPY button.
Press + or to select the AF.
Press CONFIRM. The air conditioning unit will then start the fan for airflow
automatic adjustment.
ON will flash when the fan is on during automatic airflow adjustment
CAUTION
· If there is no change after airflow adjustment in the ventilation paths, be
sure to reset automatic airflow adjustment.
· If there is no change to ventilation paths after airflow adjustment, contact
your dealer, especially if this occurs after testing the outdoor unit or if
the unit has been moved to a different location.
· Do not use automatic airflow adjustment with remote control, if you are
using booster fans, outdoor air processing unit, or a HRV via duct.
· If the ventilation paths have been changed, reset airflow automatic
adjustment as described from step 3 onwards.
Manual fan setting
The system can be set manually based on four static pressure settings.
Each setting has a low, medium and high speed range.
See fan performance curves on p. 29.
SP No. SP 1 SP 2 SP 3 SP 4
External static pressure parameters 0 40 Pa 40 80 Pa
80 120 Pa 120 200 Pa
When the system is OFF, perform the following steps using the wired controller.
Press the COPY button and hold for 3 seconds.
Press the + or – to select the required SP buttons.
CAUTION
· Do not adjust the dampers when automatic airflow adjustment is active.
After 3 to 6 minutes, the air conditioning unit stops operating once automatic
airflow adjustment has finished.
Press the CONFIRM button.
Press the CONFIRM button. The external static pressure settings are now
complete.
30 | Kaden Installation Manual
KDI24 7.0kW
AIR FLOW (L/S) (WITH FILTER)
672
616
560
504
448
392
336
280
SP4-L SP4-M SP4-H
SP3-L SP3-M SP3-H
224 SP1-L SP1-M SP1-H SP2-L SP2-M SP2-H
168 10 20 25 30 40 50 60 70 80 90 100 110 120 130 140 150 160
SP1
SP2
SP3
SP4
STATIC PRESSURE (pa)
AIR FLOW (L/S) (WITHOUT FILTER)
672
616
560
504 SP2-L SP2-M SP2-H
448
392
336
280
SP4-L SP4-M SP4-H
224 SP1-L SP1-M SP1-H
SP3-L SP3-M SP3-H
168
10 20 25 30 40 50 60 70 80 90 100 110 120 130 140 150 160
SP1
SP2
SP3
SP4
STATIC PRESSURE (pa)
Kaden Installation Manual | 31
10. Electrical checks
Electrical safety checks
After installation, confirm that all electrical wiring is installed in
accordance with local and national requirements, and according to the
Installation Manual.
Before test run
Check grounding work Measure grounding resistance by visual detection and with
grounding resistance tester. Grounding resistance must be less than 4.
During test run
Check for electrical leakage During the test run, use an electroprobe and
multimeter to perform a comprehensive electrical leakage test. If electrical
leakage is detected, turn off the unit immediately and call a licensed
electrician to find and resolve the cause of the leakage.
WARNING Risk of electric shock
All wiring must comply with local and national electrical codes, and must be
installed by a licensed electrician.
32 | Kaden Installation Manual
11. Test run
Before test run
A test run must be performed after the entire system has been completely
installed. Confirm the following points before performing the test: 1. Indoor
and outdoor units are properly installed. 2. Piping and wiring are properly
connected. 3. No obstacles near the inlet and outlet of the unit that might
cause poor performance or product malfunction. 4. Refrigeration system does
not leak. 5. Drainage system is unimpeded and draining to a
safe location. 6. Heating insulation is properly installed. 7. Grounding wires
are properly connected. 8. Length of the piping and additional refrigerant
stow
capacity have been recorded. 9. Power voltage is the correct voltage for the
air conditioner.
CAUTION
Failure to perform the test run may result in unit damage, property damage, or
personal injury.
Test run instructions
5. For the outdoor unit
a. Check to see if the refrigeration system is leaking.
b. Make sure there is no vibration or abnormal noise during operation.
c. Ensure the wind, noise, and water generated by the unit do not disturb your
neighbours or pose a safety hazard.
6. Drainage test
a. Ensure the drainpipe flows smoothly. For installations in new buildings,
you should perform this test before finishing the ceiling.
b. Remove the test cover. Add 2,000ml of water to the tank through the
attached tube.
c. Turn on the main power switch and run the air conditioner in COOL mode.
d. Listen to the sound of the drain pump to see if it makes any unusual
noises.
e. Check to see that the water is discharged. It may take up to one minute
before the unit begins to drain, depending on the drainpipe.
f. Make sure that there are no leaks in any of the piping.
g. Stop the air conditioner. Turn off the main power switch and reinstall the
test cover.
NOTE: If the unit malfunctions or does not operate according to your
expectations, please refer to the Troubleshooting section of the Owner’s
manual before calling customer service.
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to warm up.
3. Set the air conditioner to COOL mode.
4. For the indoor unit
a. Ensure the wired control and its buttons work properly.
b. Double check to see if the room temperature is being registered correctly.
c. Ensure the indicators on the wired control and the display panel on the
indoor unit work properly.
d. Ensure the manual buttons on the indoor unit works properly.
e. Check to see that the drainage system is unimpeded and draining smoothly.
f. Ensure there is no vibration or abnormal noise during operation.
Kaden Installation Manual | 33
12. Manual operations
Manual operations
This display panel on the indoor unit can be used to operate the unit in case
the remote control has been misplaced or is out of batteries.
· MANUAL button: This button selects the mode in the following order: AUTO,
FORCED COOL, OFF.
· FORCED COOL mode: In FORCED COOL mode, the Operation light flashes. The
system will then turn to AUTO after it has cooled with a high wind speed for
30 minutes. The remote control will be disabled during this operation.
· OFF mode: When the panel is turned OFF, the unit turns off and the remote
control is re-enabled.
Manual Timer button indicator
Infrared LED receiver display
Operation indicator
Alarm indicator
PRE-DEF (pre-heating/defrost)
indicator
Fig. 12.1
34 | Kaden Installation Manual
Error codes
Number
Cause
1
Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
2
Indoor and outdoor unit communication malfunction
3
Indoor fan speed malfunction
4
Indoor room temperature sensor error
5
Evaporator coil temperature sensor error
6
Refrigerant leak malfunction
7
Water level alarm malfunction
8
Dual indoor unit (twins model only) communication malfunction
9
Outdoor unit malfunction
10 Communication error between indoor main board chips
11 Outdoor ambient temperature sensor error
12 Outdoor condenser pipe sensor error
13 Compressor discharge temperature sensor error
14 Outdoor IPM Module temperature sensor error
15 Communication error between master and slave unit (twins system)
16 Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error
17 Outdoor fan speed (DC fan motor only) malfunction
18 Inverter module IPM protection
19 High/Low voltage protection
20 Compressor top overheating protection
21 Outdoor high/low pressure protection
22 Compressor drive error
23 Compressor low pressure protection
24 Outdoor IGBT sensor error
The number of
flashes per second
Timer indicator
1
Off
2
Off
4
Off
6
Off
6
Off
8
Off
13
Off
9
Off
14
Off
9
Off
5
Off
5
Off
5
Off
5
Off
11
Off
5
On
12
Off
7
Flash
2
Flash
3
Flash
4
Flash
5
Flash
7
Flash
8
Flash
Error code
EH00 EL01 EH03 EH60 EH61 EL0C EH0E EH12 EC0d EH0b EC53 EC52 EC54 EC55 EL11
EC51 EC07 PC00 PC01 PC02 PC03 PC04 PC03 PC07
Kaden Installation Manual | 35
kadenair.com.au
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>