PILZ PNOZ X6 Safety Relays Instruction Manual

June 16, 2024
PILZ

PNOZ X6
Operating Manual-19588-EN-08
– Safety relaysPILZ PNOZ X6 Safety Relays - cover
2 PILZ PNOZ X6 Safety Relays - cover

PNOZ X6 Safety Relays

This document is the original document.
Where unavoidable, for reasons of readability, the masculine form has been selected when formulating this document. We do assure you that all persons are regarded without discrimination and on an equal basis.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user’s internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.
  SD means Secure Digital

Introduction

Validity of documentation
This documentation is valid for the product PNOZ X6. It is valid until new documentation is published.
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.

Using the documentation
This document is intended for instruction. Only install and commission the product if you have read and understood this document. The document should be retained for future reference.

Definition of symbols
Information that is particularly important is identified as follows:

DANGER! This warning must be heeded! It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken.
WARNING! This warning must be heeded! It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken.
CAUTION! This refers to a hazard that can lead to a less serious or minor injury plus material damage, and also provides information on preventive measures that can be taken.
PILZ PNOZ X6 Safety Relays - icon 3NOTICE This describes a situation in which the product or devices could be damaged and also provides information on preventive measures that can be taken. It also highlights areas within the text that are of particular importance.
INFORMATION This gives advice on applications and provides information on special features.

Safety

Intended use
The safety relay PNOZ X6 provides a safety-related interruption of a safety circuit.
The safety relay meets the requirements of EN 60947-5-1 and EN 60204-1 and may be used in applications with:

  • E-STOP pushbuttons
  • Safety gates

Improper use
The following is deemed improper use in particular:

  • Any component, technical or electrical modification to the product,
  • Use of the product outside the areas described in this operating manual,
  • Use of the product outside the technical details (see chapter entitled Technical Details [ 17]).

PILZ PNOZ X6 Safety Relays - icon 3NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product may cause interference if installed in other environments. If installed in other environments, measures should be taken to comply with the applicable standards and directives for the respective installation site with regard to interference.

Safety regulations
Safety assessment
Before using a device, a safety assessment in accordance with the Machinery Directive is required.
The product as an individual component fulfils the functional safety requirements in accordance with EN ISO 13849 and EN 62061. However, this does not guarantee the functional safety of the overall plant/machine. To achieve the relevant safety level of the overall plant/ machine’s required safety functions, each safety function needs to be considered separately.

Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by persons who are competent to do so.
A competent person is a qualified and knowledgeable person who, because of their training, experience and current professional activity, has the specialist knowledge required.
To be able to inspect, assess and operate devices, systems and machines, the person has to be informed of the state of the art and the applicable national, European and international laws, directives and standards.
It is the company’s responsibility only to employ personnel who

  • Are familiar with the basic regulations concerning health and safety / accident prevention,
  • Have read and understood the information provided in the section entitled Safety
  • Have a good knowledge of the generic and specialist standards applicable to the specific application.

Warranty and liability
All claims to warranty and liability will be rendered invalid if

  • The product was used contrary to the purpose for which it is intended,
  • Damage can be attributed to not having followed the guidelines in the manual,
  • Operating personnel are not suitably qualified,
  • Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.).

Disposal

  • In safety-related applications, please comply with the mission time TM in the safety-related characteristic data.
  • When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act).

For your safety
The unit meets all the necessary conditions for safe operation. However, please note the following:

  • Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V.

Unit features

  • Positive-guided relay outputs:
    – 3 safety contacts (N/O), instantaneous

  • Connection options for:
    – E-STOP pushbutton
    – Safety gate limit switch
    – Start button

  • Operation with and without simultaneity monitoring

  • LED display for:
    – Supply voltage
    – Switch status of the safety contacts

  • See order reference for unit types

Safety features
The safety relay meets the following safety requirements:

  • The circuit is redundant with built-in self-monitoring.
  • The safety function remains effective in the case of a component failure.
  • The correct opening and closing of the safety function relays is tested automatically in each on-off cycle.

Block diagram/terminal configuration
Types: AC

  • UB: 42 VAC; Order no. 774721
  • UB: 110 – 120 VAC; Order no. 774725
  • UB: 230 – 240 VAC; Order no. 774726

PILZ PNOZ X6 Safety Relays - Block diagram 1

*Insulation between the non-marked area and the relay contacts: Basic insulation (overvoltage category III), Protective separation (overvoltage category II)

Type: AC/DC

  • UB: 24 VAC/DC; Order no. 774729

PILZ PNOZ X6 Safety Relays - Block diagram 2

*Insulation between the non-marked area and the relay contacts: Basic insulation (overvoltage category III), Protective separation (overvoltage category II)

Function Description
The safety relay PNOZ X6 provides a safety-oriented interruption of a safety circuit. When supply voltage is supplied the “POWER” LED is lit. The unit is ready for operation when the start circuit and feedback loop Y1-Y2 is closed.

  • Input circuit is closed (e.g. safety gate closed):
    – The LEDs “CH.1” and “CH.2” are lit.
    – The safety contacts 13-14, 23-24 and 33-34 are closed. The unit is active.

  • Input circuit is opened (e.g. safety gate opened):
    – The LEDs “CH.1” and “CH.2” go out.
    – Safety contacts 13-14, 23-24 and 33-34 are opened redundantly.

Operating modes

  • Single-channel operation: No redundancy in the input circuit, earth faults in the start and input circuit are detected.

  • Dual-channel operation without detection of shorts across contacts: Redundant input circuit, detects PNOZ X6
    – earth faults in the start and input circuit,
    – short circuits in the input circuit.

  • Automatic start: Unit is active once the input circuit has been closed.

  • Manual start: Unit is active once the input circuit and the start circuit are closed.

  • Monitored start: Unit is active once
    – the input circuit is closed and then the start circuit is closed and opened again.
    – the start circuit is closed and then opened again once the input circuit is closed.

  • Increase in the number of available contacts by connecting contact expandsion modules or external contactors/relays.

Timing diagram

PILZ PNOZ X6 Safety Relays - Block diagram 3

Legend

  • Power: Supply voltage
  • Start: Start circuit
  • Input: Input circuit
  • Output safe: Safety contacts
  • [1]: Automatic start
  • [2]: Manual start
  • [3]: Monitored start
  • a: Input circuit closes before start circuit
  • b: Start circuit closes before input circuit
  • t1: Switch-on delay
  • t2: Delay-on de-energisation

Installation

  • The unit should be installed in a control cabinet with a protection type of at least IP54.
  • Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
  • When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket or end angle).

Wiring

Please note:

  • Information given in the “Technical details [ 17]” must be followed.
  • The output contacts 13-14, 23-24, 33-34 are safety contacts.
  • Do not connect undesignated terminals.
  • To prevent contact welding, a fuse should be connected before the output contacts (see Technical details [ 17]).
  • Calculation of the max. cable length lmax in the input circuit:

Rlmax = max. overall cable resistance (see Technical details [ 17])
Rl / km = cable resistance/km

  • Use copper wiring with a temperature stability of 60/75 °C.
  • To prevent EMC interferences (particularly common-mode interferences) the measures described in EN 60204-1 must be executed. This includes the separate routing of cables of the control circuits (input, start and feedback loop) from other cables for energy transmission or the shielding of cables, for example.
  • Adequate protection must be provided on all output contacts with capacitive and inductive loads.
  • Do not switch low currents using contacts that have been used previously with high currents.
  • With 24 V AC/DC units: The power supply must meet the regulations for extra low voltages with protective electrical separation (SELV, PELV).

Preparing for operation

Supply voltage AC 24 VAC/DC
Input circuit Single-channel Dual-channel
--- --- ---
E-STOP without detection of shorts across contacts
Safety gae without detection of shorts across contacts

PILZ PNOZ X6 Safety Relays - icon 3NOTICE
With single-channel wiring the safety level of your machine/plant may be lower than the safety level of the unit (see Safety characteristic data [ 25]).

Start circuit| E-STOP wiring (single-channel,
dual-channel), safety gate (single-channel)| Safety gate (dual- channel)
---|---|---
Automatic start| |
Manual start| |
Monitored start| |

PILZ PNOZ X6 Safety Relays - icon 3NOTICE
In the event of an automatic start or manual start with bridged start contact (fault):
The unit starts up automatically when the safeguard is reset, e.g. when the E-STOP pushbutton is released. Use external circuit measures to prevent an unexpected restart.

Simultaneity S1 and S2| Simultaneity max. 200 ms| Simultaneity ∞
---|---|---
| |
Feedback loop| Automatic start| Manual start
---|---|---
Contacts from external contactors| |

Legend

  • S1/S2: E-STOP/safety gate switch
  • S3: Reset button
  • : Switch operated
  • : Gate open
  • : Gate closed

Operation

When the relay outputs are switched on, the mechanical contact on the relay cannot be tested automatically. Depending on the operational environment, measures to detect the non-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a check must be carried out to ensure that the safety contacts on the relay outputs open correctly.
Open the safety contacts (switch off output) and start the device again, so that the internal diagnostics can check that the safety contacts open correctly

  • for SIL CL 3/PL e at least 1x per month
  • for SIL CL 2/PL d at least 1x per year

PILZ PNOZ X6 Safety Relays - icon 3NOTICE
The safety functions should be checked after initial commissioning and each time the plant/machine is changed. The safety functions may only be checked by qualified personnel.

Status indicators
LEDs indicate the status and errors during operation:

| LED on
---|---
| POWER
Supply voltage is present.
| CH.1
Safety contacts of channel 1 are closed.
| CH.2
Safety contacts of channel 2 are closed.

Faults – Interference

  • Earth fault: The supply voltage fails and the safety contacts open. Once the cause of the respective fault has been rectified and the supply voltage is switched off for approx. 1 minute, the unit is ready for operation again.
  • Contact malfunctions: If the contacts have welded, reactivation will not be possible after the input circuit has opened.
  • LED “POWER” does not light: Short circuit or no supply voltage.

Dimensions in mm

PILZ PNOZ X6 Safety Relays - Operation 1

Technical details Order no. 774721, 774725

General 774721 774725
Certifications CCC, CE, EAC, TÜV, UKCA, cULus
Listed CCC, CE, EAC, TÜV, UKCA, cULus

Listed
Electrical data| 774721| 774725
Supply voltage
Voltage
Kind
Voltage tolerance
Output of external power supply (AC)
Frequency range AC| 42 V
AC
-15 %/+10 %
6,5 VA
50 – 60 Hz| 110 – 120 V
AC
-15 %/+10 %
6,5 VA
50 – 60 Hz
Duty cycle| 100%| 100%
Inputs| 774721| 774725
Quantity| 2| 2
Voltage at
Input circuit DC
Start circuit DC
Feedback loop DC| 24 V
24 V
24 V| 24 V
24 V
24 V
Current at
Input circuit DC
Start circuit DC
Feedback loop DC| 50 mA
100 mA
100 mA| 50 mA
100 mA
100 mA
Max. overall cable resistance Rlmax
Single-channel at UB AC
Dual-channel without detection
of shorts across contacts at UB AC| 100 Ohm
200 Ohm| 100 Ohm
200 Ohm
Relay outputs| 774721| 774725
Number of output contacts
Safety contacts (N/O), instantaneous| 3| 3
Max. short circuit current IK| 1 kA| 1 kA
Utilisation category in accordance with the standard| EN 60947-4-1| EN 60947-4-1
Relay outputs| 774721| 774725
Utilisation category of safety contacts
AC1 at
Min. current
Max. current
Max. power
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. Power| 400 V
0,01 A
5 A
2000 VA
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W| 400 V
0,01 A
5 A
2000 VA
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
Utilisation category in accordance with the standard| EN 60947-5-1| EN 60947-5-1
Utilisation category of safety contacts
AC15 at
Max. current
DC13 (6 cycles/min) at
Max. Current| 230 V
5 A
24 V
7 A| 230 V
5 A
24 V
7 A
Utilisation category in accordance
with UL
Voltage
with current
Voltage
with current
Pilot Duty| 240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300| 240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300
External contact fuse protection, safety contacts
in accordance with the standard
Max. melting integral
Blow-out fuse, quick
Blow-out fuse, slow
Blow-out fuse, gG
Circuit breaker 24V AC/DC,
characteristic B/C| EN 60947-5-1
240 A²s
10 A
6 A
10 A
6 A| EN 60947-5-1
240 A²s
10 A
6 A
10 A
6 A
Contact material| AgSnO2 + 0,2 µm Au| AgSnO2 + 0,2 µm Au
Conventional thermal current while loading several contacts| 774721| 774725
Ith per contact at UB AC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 contact
Conv. therm. current with 2 contacts
Conv. therm. current with 3 contacts| 8 A
7,3 A
6 A| 8 A
7,3 A
6 A
Times| 774721| 774725
Switch-on delay
with automatic start typ.
with automatic start max.
with automatic start after power on typ.
with automatic start after power on max.| 270 ms
370 ms
260 ms
350 ms| 270 ms
370 ms
260 ms
350 ms
Delay-on de-energisation
with E-STOP typ.
with E-STOP max.
with power failure typ.
with power failure max.| 15 ms
30 ms
150 ms
200 ms| 15 ms
30 ms
150 ms
200 ms
Recovery time at max. switching
frequency 1/s
after E-STOP
after power failure| 50 ms
250 ms| 50 ms
250 ms
Supply interruption before de-energisation| 20 ms| 20 ms
Environmental data| 774721| 774725
Climatic suitability| EN 60068-2-78| EN 60068-2-78
Ambient temperature Temperature range| -10 – 55 °C| -10 – 55 °C
Storage temperature Temperature range| -40 – 85 °C| -40 – 85 °C
Climatic suitability Humidity| 93 % r. h. at 40 °C| 93 % r. h. at 40 °C
Condensation during operation| Not permitted| Not permitted
EMC| EN 60947-5-1, EN 61000-6-2, EN 61326-3-1| EN 60947-5-1, EN 61000-6-2, EN 61326-3-1
Vibration in accordance with the standard
Frequency Amplitude| EN 60068-2-6
10 – 55 Hz 0,35 mm| EN 60068-2-6
10 – 55 Hz 0,35 mm
Environmental data| 774721| 774725
Airgap creepage in accordance with the standard
Overvoltage category Pollution degree| EN 60947-1
III / II
2| EN 60947-1
III / II
2
Rated insulation voltage| 250 V| 250 V
Rated impulse withstand voltage| 4 kV| 4 kV
Protection type
Housing Terminals
Mounting area (e.g. control cabinet)| IP40
IP20
IP54| IP40
IP20
IP54
Mechanical data| 774721| 774725
Mounting position| Any| Any
Mechanical life| 10,000,000 cycles| 10,000,000 cycles
Material
Bottom
Front
Top| PPO UL 94 V1
ABS UL 94 V0
PPO UL 94 V1| PPO UL 94 V1
ABS UL 94 V0
PPO UL 94 V1
Connection type| Screw terminal| Screw terminal
Mounting type| Fixed| Fixed
Conductor cross section with screw terminals 1 core flexible
2 core with the same cross section, flexible with crimp connectors, no plastic sleeve 2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors| 0,2 – 4 mm², 24 – 10 AWG
0,2 – 2,5 mm², 24 – 14 AWG
0,2 – 2,5 mm², 24 – 14 AWG| 0,2 – 4 mm², 24 – 10 AWG
0,2 – 2,5 mm², 24 – 14 AWG
0,2 – 2,5 mm², 24 – 14 AWG
Torque setting with screw terminals| 0,5 Nm| 0,5 Nm
Stripping length with screw terminals| 6 mm| 6 mm
Dimensions
Height
Width
Depth| 87 mm
45 mm
121 mm| 87 mm
45 mm
121 mm
Weight| 390 g| 390 g

Where standards are undated, the 2022-09 latest editions shall apply.

Technical details Order no. 774726, 774729

General 774726 774729
Certifications CCC, CE, EAC, TÜV, UKCA, cULus Listed CCC, CE, EAC, TÜV,

UKCA, cULus Listed
Electrical data| 774726| 774729
Supply voltage
Voltage
Kind
Voltage tolerance
Output of external power supply (AC)
Output of external power supply (DC)
Frequency range AC
Residual ripple DC| 230 – 240 V
AC
-15 %/+10 %
6,5 VA

50 – 60 Hz
–| 24 V
AC/DC
-15 %/+10 %
3 VA
2 W
50 – 60 Hz
160 %
Duty cycle| 100%| 100%
Inputs| 774726| 774729
Quantity| 2| 2
Voltage at
Input circuit DC
Start circuit DC
Feedback loop DC| 24 V
24 V
24 V| 24 V
24 V
24 V
Current at
Input circuit DC
Start circuit DC
Feedback loop DC| 50 mA
100 mA
100 mA| 50 mA
55 mA
55 mA
Max. overall cable resistance Rlmax
Single-channel at UB DC
Single-channel at UB AC
Dual-channel without detection
of shorts across contacts at UB DC
Dual-channel without detection
of shorts across contacts at UB AC| –
100 Ohm

200 Ohm| 100 Ohm
100 Ohm
200 Ohm
200 Ohm
Relay outputs| 774726| 774729
Number of output contacts
Safety contacts (N/O), instantaneous| 3| 3
Max. short circuit current IK| 1 kA| 1 kA
Utilisation category in accordance with the standard| EN 60947-4-1| EN 60947-4-1
Relay outputs| 774726| 774729
Utilisation category of safety contacts
AC1 at
Min. current
Max. current
Max. power
AC1 at
Min. current
Max. current
Max. power
DC1 at
Min. current
Max. current
Max. Power| 400 V
0,01 A
5 A
2000 VA
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W| 400 V
0,01 A
5 A
2000 VA
240 V
0,01 A
8 A
2000 VA
24 V
0,01 A
8 A
200 W
Utilisation category in accordance with the standard| EN 60947-5-1| EN 60947-5-1
Utilisation category of safety contacts AC15 at
Max. current
DC13 (6 cycles/min) at
Max. Current| 230 V
5 A
24 V
7 A| 230 V
5 A
24 V
7 A
Utilisation category in accordance with UL
Voltage
with current
Voltage
with current
Pilot Duty| 240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300| 240 V AC G. P.
8 A
24 V DC Resistive
5 A
B300, R300
External contact fuse protection, safety contacts
in accordance with the standard
Max. melting integral
Blow-out fuse, quick
Blow-out fuse, slow
Blow-out fuse, gG
Circuit breaker 24V AC/DC,
characteristic B/C| EN 60947-5-1
240 A²s
10 A
6 A

10 A| EN 60947-5-1
240 A²s
10 A
6 A

10 A
Contact material| AgSnO2 + 0,2 µm Au| AgSnO2 + 0,2 µm Au
Conventional thermal current while loading several contacts| 774726| 774729
Ith per contact at UB AC; C1: 240 V, DC1: 24 V
Conv. therm. current with 1 contact
Conv. therm. current with 2 contacts
Conv. therm. current with 3 contacts| 8 A
7,3 A
6 A| 8 A
7,3 A
6 A
Ith per contact at UB DC; C1: 240 V, DC1: 24 V
Conv. therm. current with 1 contact
Conv. therm. current with 2 contacts
Conv. therm. current with 3 contacts| –

–| 8 A
8 A
8 A
Times| 774726| 774729
Switch-on delay with automatic start typ.
with automatic start max.
with automatic start after power on typ.
with automatic start after power on max.| 270 ms
370 ms
260 ms
350 ms| 250 ms
350 ms
260 ms
350 ms
Delay-on de-energisation with E-STOP typ.
with E-STOP max.
with power failure typ.
with power failure max.| 15 ms
30 ms
150 ms
200 ms| 15 ms
30 ms
110 ms
160 ms
Recovery time at max. switching
frequency 1/s
after E-STOP
after power failure| 50 ms
250 ms| 50 ms
200 ms
Supply interruption before de-energisation| 20 ms| 20 ms
Environmental data| 774726| 774729
Climatic suitability| EN 60068-2-78| EN 60068-2-78
Ambient temperature
Temperature range| -10 – 55 °C| -10 – 55 °C
Storage temperature
Temperature range| -40 – 85 °C| -40 – 85 °C
Climatic suitability
Humidity| 93 % r. h. at 40 °C| 93 % r. h. at 40 °C
Condensation during operation| Not permitted| Not permitted
EMC| EN 60947-5-1, EN 61000-6-2, EN 61326-3-1| EN 60947-5-1, EN 61000-6-2, EN 61326-3-1
Environmental data| 774726| 774729
Vibration in accordance with the standard
Frequency
Amplitude| EN 60068-2-6
10 – 55 Hz
0,35 mm| EN 60068-2-6
10 – 55 Hz
0,35 mm
Airgap creepage in accordance with the standard
Overvoltage category
Pollution degree| EN 60947-1
III / II
2| EN 60947-1
III / II
2
Rated insulation voltage| 250 V| 250 V
Rated impulse withstand voltage| 4 kV| 4 kV
Protection type
Housing
Terminals
Mounting area (e.g. control cabinet)| IP40
IP20
IP54| IP40
IP20
IP54
Mechanical data| 774726| 774729
Mounting position| Any| Any
Mechanical life| 10,000,000 cycles| 10,000,000 cycles
Material
Bottom
Front
Top| PPO UL 94 V1
ABS UL 94 V0
PPO UL 94 V1| PPO UL 94 V1
ABS UL 94 V0
PPO UL 94 V1
Connection type| Screw terminal| Screw terminal
Mounting type| Fixed| Fixed
Conductor cross section with screw terminals
1 core flexible
2 core with the same cross section, flexible with crimp connectors, no plastic sleeve
2 core with the same cross section, flexible without crimp connectors or with TWIN crimp
connectors| 0,2 – 4 mm², 24 – 10 AWG

0,2 – 2,5 mm², 24 – 14 AWG

0,2 – 2,5 mm², 24 – 14 AWG

| 0,2 – 4 mm², 24 – 10 AWG

0,2 – 2,5 mm², 24 – 14 AWG

0,2 – 2,5 mm², 24 – 14 AWG

Torque setting with screw terminals| 0,5 Nm| 0,5 Nm
Stripping length with screw terminals| 6 mm| 6 mm
Dimensions
Height
Width
Depth| 87 mm
45 mm
121 mm| 87 mm
45 mm
121 mm
Weight| 390 g| 295 g

Where standards are undated, the 2022-09 latest editions shall apply.

Safety characteristic data

PILZ PNOZ X6 Safety Relays - icon 3NOTICE
You must comply with the safety characteristic data in order to achieve the required safety level for your plant/machine.

Operating mode| EN ISO
13849-1:
2015
PL| EN ISO
13849-1:
2015
Category| EN IEC
62061
SIL CL/
maximum
SIL| EN IEC
62061
PFHD [1/h]| EN/IEC
61511
SIL| EN/IEC
61511
PFD| EN ISO
13849-1:
2015
TM [year]
---|---|---|---|---|---|---|---
–| PL e| Cat. 4| SIL 3| 2,31E-09| SIL 3| 2,03E-06| 20

Explanatory notes for the safety-related characteristic data:
► Safety characteristic data in accordance with EN IEC 62061 and EN/IEC 61511 was calculated based on EN/IEC 61508.
► TM is the maximum mission time in accordance with EN ISO 13849-1. The value also applies as the retest interval in accordance with EN/IEC 61508-6 and EN/IEC 61511 and as the proof test interval and mission time in accordance with EN IEC 62061.
All the units used within a safety function must be considered when calculating the safety characteristic data.

INFORMATION
A safety function’s SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function’s SIL/PL values.

Supplementary data

CAUTION!
It is essential to consider the relay’s service life graphs. The relay outputs’ safety-related characteristic data is only valid if the values in the service life graphs are met.
The PFH value depends on the switch frequency and the load of the relay output.
If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switch frequency and the load, as the PFH value already considers the relay’s B10d value as well as the failure rates of the other components.

Service life graph
The service life graphs indicate the number of cycles from which failures due to wear must be expected. The wear is mainly caused by the electrical load; the mechanical load is  negligible.

PILZ PNOZ X6 Safety Relays - Supplementary data 1

Example

► Inductive load: 0.2 A
► Utilisation category: AC15
► Contact service life: 4 000 000 cycles Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With DC contactors, use flywheel diodes for spark suppression.

Order reference

Product type Features Connection type Order no.
PNOZ X6 42 VAC Screw terminals 774721
PNOZ X6 110 – 120 VAC Screw terminals 774725
PNOZ X6 230 – 240 VAC Screw terminals 774726
PNOZ X6 24 VAC/DC Screw terminals 774729

EC declaration of conformity

This product/these products meet the requirements of the directive 2006/42/EC for machinery of the European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads.
Authorised representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel- Str. 2, 73760 Ostfildern, Germany

UKCA-Declaration of Conformity

This product(s) complies with following UK legislation: Supply of Machinery (Safety) Regulation 2008.
The complete UKCA Declaration of Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Pilz Automation Technology, Pilz House, Little Colliers Field, Corby, Northamptonshire, NN18 8TJ United Kingdom, eMail: [email protected]

Support

Technical support is available from Pilz round the clock.

Americas
Brazil +55 11 97569-2804
Canada +1 888 315 7459
Mexico +52 55 5572 1300
USA (toll-free) +1 877-PILZUSA (745-9872)

Asia
China +86 21 60880878-216
Japan +81 45 471-2281
South Korea +82 31 778 3300

Australia and Oceania
Australia +61 3 95600621
New Zealand +64 9 6345350

Europe
Austria +43 1 7986263-0
Belgium, Luxembourg +32 9 3217570
France +33 3 88104003
Germany +49 711 3409-444
Ireland +353 21 4804983
Italy, Malta +39 0362 1826711
Scandinavia +45 74436332
Spain +34 938497433
Switzerland +41 62 88979-32
The Netherlands +31 347 320477
Turkey +90 216 5775552
United Kingdom +44 1536 462203

You can reach our international hotline on:
+49 711 3409-222
[email protected]

Pilz develops environmentally-friendly products using ecological materials and energy-saving technologies.
Offices and production facilities are ecologically designed, environmentally- aware and energy-saving. So Pilz offers sustainability, plus the security of using energy-efficient products and environmentally-friendly solutions.

We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters.
Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected], Internet: www.pilz.com

CECE® , CHRE® , CMSE® , InduraNET p® , Leansafe® , Master of Safety® , Master of Security® , PAS4000® , PAScal® , PASconfig® , Pilz® , PIT® , PLID® , PMCprimo® , PMCprotego® , PMCtendo® ,PMD® , PMI® , PNOZ® , PRBT® , PRCM® , Primo® , PRTM® , PSEN® , PSS® , PVIS® , SafetyBUS p® , SafetyEYE® , SafetyNET p® , THE SPIRIT OF SAFETY® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries. We would point out that product features may vary from the details stated in this document, depending on the status at the time of publication and the scope of the equipment. We accept no responsibility for the validity, accuracy and entirety of the text and graphics presented in this information. Please contact our Technical Support if you have any questions.

19588-EN-08, 2023-05 Printed in Germany
© Pilz GmbH & Co. KG, 2019

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

PILZ User Manuals

Related Manuals