PILZ m EF PDP Link Safety Relay User Manual

June 13, 2024
PILZ

PILZ m EF PDP Link Safety Relay

PILZ-m-EF-PDP-Link-Safety-Relay-product

Product Information

The PNOZ m EF PDP Link is a configurable, safe small controller manufactured by Pilz GmbH & Co. KG. It is designed to provide control and safety functions in various applications. The product comes with an operating manual (1003019-EN-07) that provides detailed instructions on its function, operation, installation, and connection.

Technical Details

  • LED indicators: The PNOZ m EF PDP Link features LED indicators for easy visual monitoring of its status.
  • Fault detection: The product is equipped with fault detection capabilities to ensure safe operation.
  • Safety characteristic data: Detailed safety characteristic data is provided in the operating manual to assist in proper usage and compliance with safety regulations.

Product Usage Instructions

  1. Validity of Documentation: This operating manual is valid for the PNOZ m EF PDP Link until new documentation is published.

  2. Using the Documentation: Before installing and commissioning the product, it is crucial to read and understand the operating manual. Retain the document for future reference.

  3. Definition of Symbols: The operating manual uses specific symbols to highlight important information.

  4. DANGER! – Indicates a hazardous situation that poses an immediate threat of serious injury or death.

  5. WARNING! – Indicates a hazardous situation that could lead to serious injury or death.

  6. CAUTION! – Refers to a hazard that can cause minor injury or material damage.

  7. NOTICE – Describes situations where the product or devices could be damaged.
    Follow the preventive measures mentioned alongside each symbol to ensure safety and prevent damage.

  8. Installation and Connection: The operating manual provides detailed guidelines on how to install and connect the PNOZ m EF PDP Link. Follow these instructions carefully to ensure proper functioning and compliance with safety regulations.
    Note: For any suggestions or comments on improving the documentation, Pilz GmbH & Co. KG welcomes your feedback.

  9. EC Declaration of Conformity: The operating manual includes an EC declaration of conformity, which certifies that the product meets the requirements of applicable European directives and standards.

  10. UKCA-Declaration of Conformity: The operating manual also includes a UKCA-Declaration of Conformity, certifying compliance with relevant UK regulations.
    For further information and specific instructions, refer to the complete operating manual (1003019-EN-07) provided by Pilz GmbH & Co. KG.

Preface
This document is the original document.
Where unavoidable, for reasons of readability, the masculine form has been selected when formulating this document. We do assure you that all persons are regarded without discrim-ination and on an equal basis.
All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user’s internal purposes. Suggestions and comments for improving this documenta-tion will be gratefully received.
Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,
SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.

Introduction

Validity of documentation
This documentation is valid for the product PNOZ m EF PDP Link. It is valid until new docu-mentation is published.
This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.

Using the documentation
This document is intended for instruction. Only install and commission the product if you have read and understood this document. The document should be retained for future ref-erence.

Definition of symbols
Information that is particularly important is identified as follows:

DANGER!
This warning must be heeded! It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken.

WARNING!
This warning must be heeded! It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken.

CAUTION!
This refers to a hazard that can lead to a less serious or minor injury plus material damage, and also provides information on preventive measures that can be taken.

NOTICE
This describes a situation in which the product or devices could be dam-aged and also provides information on preventive measures that can be taken. It also highlights areas within the text that are of particular importance.

INFORMATION
This gives advice on applications and provides information on special features.

Overview

Scope of supply

  • Expansion module PNOZ m EF PDP Link
  • Jumper

Unit features
Application of the product PNOZ m EF PDP Link:
Link module to safely connect decentralized input/output modules to a configurable control system PNO Zmulti 2
The product has the following features:

  • Can be configured in the PNOZmulti Configurator
  • Max. 4 PNOZ m EF PDP Link can be connected to the base unit
  • Max. 4 decentralised modules can be connected to the link module PNOZ m EF PDP Link
  • LEDs for
    • Operating state
    • Error
    • Connection status
  • Plug-in connection terminals:
    Either spring-loaded terminal or screw terminal available as an accessory (see Order ref-erences for accessories).

Front view

Legend:

  • 0 V, 24 V:
    Supply connections

  • CAN+, CAN-, VCC, GND:
    Connection for decentralised modules

  • FE:
    Functional earth

Safety

Intended use
The expansion module is used to connect decentralized input/output modules to a configurable control system PNOZmulti 2 .
The expansion module may only be connected to a base unit from the configurable system PNOZmulti 2 (please refer to the document “PNOZmulti System Expansion” for details of the base units that can be connected).
The configurable small control systems PNOZmulti are used for the safety- related interruption of safety circuits and are designed for use in:

Lifts Directive
The product PNOZ m EF PDP Link can be used as a PESSRAL (programmable electronic system in safety-related applications for lifts) in accordance with the Lifts Directive 2014/33/EU. It meets the requirements for passenger and goods lifts in accordance with EN 81-1/2, EN 81-20, EN 81-22 and EN 81-50, as well as the requirements for escalators and moving walks in accordance with EN 115-1.
The safety controller should be installed in a protected environment that meets at least the requirements of pollution degree 2.
Example: Protected inside space or control cabinet with protection type IP54 and appropri-ate air conditioning.

Use in furnaces
The product PNOZ m EF PDP Link can be used in furnaces in accordance with EN 298.

Improper use
The following is deemed improper use in particular

  • Any component, technical or electrical modification to the product,
  • Use of the product outside the areas described in this operating manual,
  • Use of the product outside the technical details (see Technical details [ 21]).

NOTICE
EMC-compliant electrical installation
The product is designed for use in an industrial environment. The product may cause interference if installed in other environments. If installed in other environments, measures should be taken to comply with the applicable standards and directives for the respective installation site with regard to interference.

System requirements
Please refer to the “Product Modifications PNOZmulti” document in the “Version overview” section for details of which versions of the base unit and PNOZmulti Configurator can be used for this product.

Safety regulations
Use of qualified personnel
The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons.
A competent person is someone who, because of their training, experience and current professional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.
It is the company’s responsibility only to employ personnel who

  • Are familiar with the basic regulations concerning health and safety / accident prevention,
  • Have read and understood the information provided in this description under “Safety”,
  • And have a good knowledge of the generic and specialist standards applicable to the specific application.

Warranty and liability
All claims to warranty and liability will be rendered invalid if

  • The product was used contrary to the purpose for which it is intended,
  • Damage can be attributed to not having followed the guidelines in the manual,
  • Operating personnel are not suitably qualified,
  • Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.).

Disposal

  • When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act).

For your safety
The unit meets all the necessary conditions for safe operation. However, you should always ensure that the following safety requirements are met:

  • This operating manual only describes the basic functions of the unit. The expanded functions are described in the PNOZmulti Configurator’s online help. Only use these functions once you have read and understood the documentations.
  • Do not open the housing or make any unauthorized modifications.
  • Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors).

Function description

Integrated protection mechanisms
The relay meets the following safety requirements:

  • The circuit is redundant with built-in self-monitoring.
  • The safety device remains effective in the case of a component failure.

Functions
The link module PNOZ m EF PDP Link is used to safely transfer the input information from decentralised modules to the control system PNOZmulti 2.
The function of the inputs and outputs on the control system depends on the safety circuit created using the PNOZmulti Configurator. A chip card is used to download the safety cir-cuit to the base unit. The base unit has 2 microcontrollers that monitor each other. They evaluate the input circuits on the base unit and expansion modules and switch the outputs on the base unit and expansion modules accordingly.
The LEDs on the base unit and expansion modules indicate the status of the configurable control system PNOZmulti.
The online help on the PNOZmulti Configurator contains descriptions of the operating modes and all the functions of the control system, plus connection examples.

Data exchange:

  • Communication with the decentralised modules is via a safe data link.
  • The link module PNOZ m EF PDP Link reads the input information from the decentralised modules as part of each cycle and then forwards it to the base unit.
  • At the end of a PNOZmulti cycle, the base unit sends its output data to its link module. This output data is immediately sent to the decentralised modules.

Linking several decentralised modules:

  • A maximum of 4 link modules can be connected to a base unit PNOZmulti 2.
  • A maximum of 4 decentralised modules can be connected to a link module PNOZ m EF PDP Link.
  • If a decentralised module receives data intended for a different decentralised module that is connected, the data is forwarded without being processed.

System reaction time
Calculation of the maximum reaction time between an input switching off and a linked out-put in the system switching off is described in the document “PNOZmulti System Expan-sion”.

Block diagram

Installation

General installation guidelines

  • The unit should be installed in a control cabinet with a protection type of at least IP54.
  • Fit the safety system to a horizontal mounting rail. The venting slots must face upward and downward. Other mounting positions could damage the safety system.
  • Use the locking elements on the rear of the unit to attach it to a mounting rail.
  • In environments exposed to heavy vibration, the unit should be secured using a fixing element (e.g. retaining bracket or end angle).
  • Open the locking slide before lifting the unit from the mounting rail.
  • To comply with EMC requirements, the mounting rail must have a low impedance connection to the control cabinet housing.
  • The ambient temperature of the PNOZmulti units in the control cabinet must not exceed the figure stated in the technical details. Air conditioning may otherwise be required.

NOTICE
Damage due to electrostatic discharge!
Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur-face or by wearing an earthed armband.

Dimensions in mm

Connect the base unit and expansion modules
Connect the base unit and the expansion module as described in the operating instructions for the base units.

  • Connect the black/yellow terminator to the expansion module.
  • Install the expansion module in the position in which it is configured in the PNOZmulti Configurator.

The position of the expansion modules is defined in the PNOZmulti Configurator. The ex-pansion modules are connected to the left or right of the base unit, depending on the type.
Please refer to the document “PNOZmulti System Expansion” for details of the number of modules that can be connected to the base unit and the module types.

Commissioning

Wiring
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.

Please note:

  • Information given in the Technical details [ 21] must be followed.
  • The position of the expansion module is specified in the Hardware configuration of the PNOZmulti Configurator.
  • Use copper wiring with a temperature stability of 75 °C.
  • External measures must be used to connect the FE terminal to the functional earth (e.g. mounting rail).
  • The power supply must meet the regulations for extra low voltages with protective elec-trical separation (SELV, PELV).
  • 2 connection terminals are available for each of the supply connections 24 V and 0 V. This means that the supply voltage can be looped through several connections. The cur-rent at each terminal may not exceed 3 A.
  • Please refer to the technical details for information on the maximum cable length. Please also read the section entitled “Voltage drop”.
  • With a cable length of 30 m or above, or in environments with strong interfaces, shielded cables must be used.
  • If there are signal interferences/EMC problems that are to be expected or present, we re-commend that you use a shielded cable from the beginning. In addition, you can place the braided shield of the cables directly next to the device via a shielded terminal to the functional earth (mounting rail).
  • Pilz pre-assembled cable can be used to connect the decentralised modules (see order reference).
  • The plug-in connection terminals are either designed as cage clamp terminals or screw terminals (see order reference).

CAUTION!
Only connect and disconnect the expansion module when the supply voltage is switched off.

Insulation voltage test
The product PNOZ m EF PDP Link is connected to functional earth via protection ele-ments on the supply voltage. Insulation voltage tests are only possible with voltages up to ca. 42 V.

Connection

PILZ-m-EF-PDP-Link-Safety-Relay- \(4\) PILZ-m-EF-
PDP-Link-Safety-Relay- \(5\)

Download modified project to the PNOZmulti safety system
As soon as an additional expansion module has been connected to the system, the project must be amended in the PNOZmulti Configurator and downloaded back into the base unit. Proceed as described in the operating manual for the base unit.

NOTICE
For the commissioning and after every user program change, you must check whether the safety devices are functioning correctly.

Series connection of 4 decentralised modules
You can connect up to 4 decentralised modules in series to a PNOZmulti link module.
The cable length between every connection must be max. 100 m (see Technical details [ 21]).

PILZ-m-EF-PDP-Link-Safety-Relay- \(6\)

Voltage drop
The max. cable length depends on the voltage drop in the supply voltage cables. The level of voltage drop is determined by the:

  • Cable resistance on the supply voltage cables
  • Operating current of the modules
  • Load on the modules

To increase the max. cable length, the input voltage can be permanently increased by the voltage tolerance (see Technical Details).

Guidelines for various cable types

Cable type Voltage drop per 10 m and per 100 mA
PSS SB BUSCABLE LC 0.1 V
Sensor cable 0.25 mm2 0.15 V
Sensor cable 0.34 mm2 0.11 V
Sensor cable 0.5 mm2 0.07 V

Calculation example

  • The PSS SB BUSCABLE LC is used in accordance with the pin assignment in section 6.2.2.
    Voltage drop per 10 m and per 100 mA: 0.1 V

PILZ-m-EF-PDP-Link-Safety-Relay- \(7\)

Legend:

  • I0: Module’s consumption.
  • I1 … I5: Load current taken from the module
  • U1 … U4: Voltage drop on the respective connection path

Total voltage drop from the link module PNOZ m EF PDP Link to the final PDP67 F 8DI ION:

  • Utotal = U1 + U2 + U3 + U4
  • Utotal = 1.3 V + 0.825 V + 0.5 V + 0.10 V = 2.725 V

Operation

The PNOZmulti safety system is ready for operation when the “POWER” and “RUN” LEDs on the base unit and the “READY” LED on the PNOZ m EF PDP Link are lit continuously.

LED indicators
Legend

LED LED status Meaning
Power
Gree n Supply voltage is present
Ready Gree n
The unit is not ready for operation
Fault Red
Red Internal error
No fault
Traffic Yel- low
Yel- low Connection is not available to all decentralized modules.
No connection to a decentralized module

Fault detection
The base unit contains information about the

  • Link module (in order, defective, no supply voltage)
  • Status of communication with the decentralized modules (data valid, data invalid)

If the connection to a decentralized module is interrupted or there is a major error on the decentralized module, the inputs on the devices connected to the link module are set to zero. The base unit remains in a RUN condition.

Technical details

General

  • Certifications CE, EAC, KOSHA, TÜV, UKCA, cULus Listed
  • Application range Failsafe

Electrical data

Supply voltage for Module supply

  • Voltage 24 V
  • Kind DC
  • Voltage tolerance -15 %/+20 %
  • Output of external power supply (DC) 100 W
  • Output of external power supply (DC) at no load 2,5 W
  • Supply voltage
  • for Module supply
  • internal Via base unit
  • Voltage 3,3 V
  • Kind DC
  • Current consumption 60 mA
  • Power consumption 0,2 W
  • Max. power dissipation of module 4 W
  • Status indicator LED

Inputs

  • Maximum input delay 15 ms

Semiconductor outputs

  • Switch-off delay 5 ms

Test pulse outputs

  • Maximum output current, decentralised module supply 4 A
  • Short circuit protection of decentralised module supply yes

Environmental data
Ambient temperature

  • In accordance with the standard EN 60068-2-14
  • Temperature range 0 – 60 °C

Storage temperature

  • In accordance with the standard EN 60068-2-1/-2
  • Temperature range -25 – 70 °C

Climatic suitability

  • In accordance with the standard EN 60068-2-30, EN 60068-2-78
  • Condensation during operation Not permitted
  • Max. operating height above sea level 2000 m
  • EMC EN 61131-2

Environmental data
Vibration

  • In accordance with the standard EN 60068-2-6
  • Frequency 5 – 55 Hz
  • Acceleration 1g

Shock stress

  • In accordance with the standard EN 60068-2-27
  • Acceleration 15g
  • Duration 11 ms

Airgap creepage

  • In accordance with the standard EN 61131-2
  • Overvoltage category II
  • Pollution degree 2

Protection type

  • In accordance with the standard EN 60529
  • Housing IP20
  • Terminals IP20
  • Mounting area (e.g. control cabinet) IP54

Potential isolation

  • Potential isolation between Module and system voltage
  • Type of potential isolation Functional insulation
  • Rated insulation voltage 30 V
  • Rated surge voltage 2500 V

Mechanical data

  • Mounting position horizontally on mounting rail

DIN rail

  • Top hat rail 35 x 7,5 EN 50022
  • Recess width 27 mm
  • Max. cable length unshielded 30 m
  • Max. cable length shielded 100 m

Material

  • Bottom PC
  • Front PC
  • Top PC
  • Connection type Spring-loaded terminal, screw terminal
  • Mounting type plug-in

Conductor cross section with screw terminals

  • 1 core flexible 0,25 – 2,5 mm², 24 – 12 AWG
  • 2 core with the same cross section, flexible without
  • crimp connectors or with TWIN crimp connectors 0,2 – 1,5 mm², 24 – 16 AWG
  • Torque setting with screw terminals 0,5 Nm
  • Conductor cross section with spring-loaded terminals:
  • Flexible with/without crimp connector 0,2 – 2,5 mm², 24 – 12 AWG
  • Spring-loaded terminals: Terminal points per connection 2
  • Stripping length with spring-loaded terminals 9 mm

Mechanical data
Dimensions

  • Height 101,4 mm
  • Width 22,5 mm
  • Depth 120 mm
  • Weight 96 g

Where standards are undated, the 2013-01 latest editions shall apply.

Safety characteristic data
NOTICE
You must comply with the safety characteristic data in order to achieve the required safety level for your plant/machine.

Operating| EN ISO| EN ISO| EN IEC| EN IEC| EN/IEC| EN/IEC| EN ISO
---|---|---|---|---|---|---|---
mode| 13849-1:| 13849-1:| 62061| 62061| 61511| 61511| 13849-1:
| 2015
PL| 2015
Category| SIL CL/
maximum SIL| PFHD [1/h]| SIL| PFD| 2015
TM [year]
–| PL e| Cat. 4| SIL 3| 5,35E-09| SIL 3| 3,30E-05| 20

Explanatory notes for the safety-related characteristic data:

  • Safety characteristic data in accordance with EN IEC 62061 and EN/IEC 61511 was calculated based on EN/IEC 61508.
  • TM is the maximum mission time in accordance with EN ISO 13849-1. The value also applies as the retest interval in accordance with EN/IEC 61508-6 and EN/IEC 61511 and as the proof test interval and mission time in accordance with EN IEC 62061.

All the units used within a safety function must be considered when calculating the safety characteristic data.

INFORMATION
A safety function’s SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function’s SIL/PL values.

Order reference

Product

Product type Features Order no.
PNOZ m EF PDP Link Configurable safe small controllers PNOZmulti 2, expansion
mod- ule, safe connection decentralised I/O modules. 772121

Accessories

Terminals

Product type Features Order no.
Spring terminals PNOZ mml2p Spring-loaded terminals, PNOZ mml2p, 1 set.

783540
Screw terminals PNOZ mml2p| Plug-in screw terminals, PNOZ mml2p, 1 set.| 793540
Spring terminals PNOZ mml2p 10 pcs.| Spring-loaded terminals, PNOZ mml2p, 10 sets.| 783541
Screw terminals PNOZ mml2p 10 pcs.| Plug-in screw terminals, PNOZ mml2p, 10 sets.| 793541

Connector plug

Product type Features Order no.
PNOZ mm0.xp con- nector left (10 pcs) Connector plug to connect the modules
to the left-hand side of the PNOZmulti base unit, yellow/black (10 pieces).

779260

By the metre

Product type Features Order no.
PSS SB BUSCABLE LC By the metre, bus/power hybrid line, PUR, yellow RAL1003,
2×0.38+2×0.24+1×0.38, colour of the single wires: Red, white, green, brown

311074
PSS67 I/O Cable| By the metre, PUR, yellow RAL1003, 5×0.25, colour of the single wires: Brown, white, blue, black, grey| 380320

Cable

Product type Features Order no.
PSS67 Cable M8sf M12sm, 3m Connection cable, PUR, yellow RAL1003, suitable

for drag chains, 4-pin, socket straight M8, on connector straight M12, A-coded, cable length: 3 m.| 380200
PSS67 Cable M8sf M12sm, 5m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket straight M8, on connector straight M12, A-coded, cable length: 5 m| 380201
PSS67 Cable M8sf M12sm, 10m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket straight M8, on connector straight M12, A-coded, cable length: 10 m| 380202
PSS67 Cable M8sf M12sm, 30m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket straight M8, on connector straight M12, A-coded, cable length: 30 m| 380203
PSS67 Cable M8af M12sm, 3m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket angled M8, on connector straight M12, A-coded, cable length: 3 m| 380204
PSS67 Cable M8af M12sm, 5m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket angled M8, on connector straight M12, A-coded, cable length: 5 m| 380205
PSS67 Cable M8af M12sm, 10m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket angled M8, on connector straight M12, A-coded, cable length: 10 m| 380206
PSS67 Cable M8af M12sm, 30m| Connection cable, PUR, yellow RAL1003, suitable for drag chains, 4-pin, socket angled M8, on connector straight M12, A-coded, cable length: 30 m| 380207
PSS67 Cable M12sf M12sm, 3m| Connection cable, PUR, yellow RAL1003, 5-pin, socket straight, on connector straight M12, A-coded, cable length: 3 m| 380208
PSS67 Cable M12sf M12sm, 5m| Connection cable, PUR, yellow RAL1003, 5-pin, socket straight, on connector straight M12, A-coded, cable length: 5 m| 380209
PSS67 Cable M12sf M12sm, 10m| Connection cable, PUR, yellow RAL1003, 5-pin, socket straight, on connector straight M12, A-coded, cable length: 10 m| 380210
PSS67 cable

M12-5sf, M12-5sm,

20m

| Connection cable, PUR, yellow RAL1003, 5-pin, socket straight, on connector straight M12, A-coded, cable length: 20 m| 380220
PSS67 Cable M12sf M12sm, 30m| Connection cable, PUR, yellow RAL1003, 5-pin, socket straight, on connector straight M12, A-coded, cable length: 30 m| 380211
PSS67 Cable M12af M12am, 3m| Connection cable, PUR, yellow RAL1003, 5-pin, socket angled, on connector angled M12, A-coded, cable length: 3 m| 380212
PSS67 Cable M12af M12am, 5m| Connection cable, PUR, yellow RAL1003, 5-pin, socket angled, on connector angled M12, A-coded, cable length: 5 m| 380213
PSS67 Cable M12af M12am, 10m| Connection cable, PUR, yellow RAL1003, 5-pin, socket angled, on connector angled M12, A-coded, cable length: 10 m| 380214
PSS67 Cable M12af M12am, 30m| Connection cable, PUR, yellow RAL1003, 5-pin, socket angled, on connector angled M12, A-coded, cable length: 30 m| 380215
PSEN op cable axial M12 5-pole 3m| Connection cable, PUR, yellow, RAL1003, 5-pin, socket straight M12, on open line end, A-coded, cable length: 3 m| 630310
Product type| Features| Order no.
---|---|---
PSEN op cable axial M12 5-pole 5m| Connection cable, PUR, yellow, RAL1003, 5-pin, socket straight M12, on open line end, A-coded, cable length: 5 m| 630311
PSEN op cable axial M12 5-pole 10m| Connection cable, PUR, yellow, RAL1003, 5-pin, socket straight M12, on open line end, A-coded, cable length: 10 m| 630312
PSEN cable M12-5sf 20m| Connection cable, PUR, yellow, RAL1003, 5-pin, socket straight M12, on open line end, A-coded, cable length: 20 m| 630298
PSEN op cable axial M12 5-pole 30m| Connection cable, PUR, yellow, RAL1003, 5-pin, socket straight M12, on open line end, A-coded, cable length: 30 m| 630297

Adapter

Product type Features Order no.
PSEN ma adapter Cable, adapter, IP68, M12 female connector, black, straight,

4-pin, A-coded on M12 male connector, black, angled, 5-pin, A-coded, PUR, 0.1 m, 4× 0.34 mm², black, for connecting the sensors PSEN- mag (safety switch)/PIT en1.0 (enabling switch) to PSS67 and PDP67.| 380300
PSEN cs adapter| Cable, adapter, IP68, M12 female connector, black, straight, 8-pin, A-coded on M12 male connector, black, angled, 5-pin, A-coded, PUR, 0.1 m, 5x 0.25 mm², black, with shielding (wire mesh), for connecting a PSENcode sensor (coded safety switch) to PSS67 and PDP67.| 380301
PSEN sl adapter| Cable, adapter, IP68, M12 female connector, black, straight, 8-pin, A-coded on M12 male connector, black, angled, 5-pin, A-coded, PUR, 0.1 m, 5x 0.25 mm², black, with shielding (wire mesh), for connecting a PSENslock sensor (safety gate monitoring) to PSS67 and PDP67.| 380325

Plug-in connector

Product type Features Order no.
PSS67 M12 connector,straight,male,5 pole Plug-in connector, 5-pin, straight

M12 connector, A-coded, screw connection, material ring nut: CuZn nickel- plated, outer cable dia- meter: 4 – 6 mm| 380308
PSS67 M12 con-

nector straight,fe- male,5pin

| Plug-in connector, 5-pin, straight M12 socket, A-coded, screw con- nection, material ring nut: CuZn nickel-plated, outer cable diameter: 4 – 6 mm| 380309
PSS67 M12 con-

nector, angled, male, 5pole

| Plug-in connector, 5-pin, angled M12 connector, A-coded, screw connection, material ring nut: CuZn nickel-plated, outer cable dia- meter: 4 – 6 mm| 380310
PSS67 M12 con-

nector, angled,fe- male,5pole

| Plug-in connector, 5-pin, angled M12 socket, A-coded, screw connection, material ring nut: CuZn nickel-plated, outer cable diameter: 4 – 6 mm| 380311
M12 con., straight, male, 4-pin, D| Plug-in connector, 4-pin, straight M12 connector, D-coded, IDC connection, material ring nut: Die-cast zinc nickel- plated, cable screw connection Pg9, outer cable diameter 6 – 8 mm| 380316

EC declaration of conformity

This product/these products meet the requirements of the directive 2006/42/EC for ma-chinery of the European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads.
Authorised representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel- Str. 2, 73760 Ostfildern, Germany

UKCA-Declaration of Conformity

This product(s) complies with following UK legislation: Supply of Machinery (Safety) Regu-lation 2008.
The complete UKCA Declaration of Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Pilz Automation Technology, Pilz House, Little Colliers Field, Corby, Northamptonshire, NN18 8TJ United Kingdom, eMail: mail@pilz.co.uk

Technical support is available from Pilz round the clock.
Americas
Brazil
+55 11 97569-2804
Canada
+1 888 315 7459
Mexico
+52 55 5572 1300
USA (toll-free)
+1 877-PILZUSA (745-9872)
Asia
China
+86 21 60880878-216
Japan
+81 45 471-2281
South Korea
+82 31 778 3300
Australia and Oceania
Australia
+61 3 95600621
New Zealand
+64 9 6345350
Europe
Austria
+43 1 7986263-0
Belgium, Luxembourg
+32 9 3217570
France
+33 3 88104003
Germany
+49 711 3409-444
Ireland
+353 21 4804983
Italy, Malta
+39 0362 1826711
Scandinavia
+45 74436332
Spain
+34 938497433
Switzerland
+41 62 88979-32
The Netherlands
+31 347 320477
Turkey
+90 216 5775552
United Kingdom
+44 1536 462203

You can reach our international hotline on:
+49 711 3409-222
support@pilz.com

Pilz develops environmentally-friendly products using ecological materials and energy-saving technologies. Offices and production facilities are ecologically designed, environmentally-aware and energy-saving. So Pilz offers sustainability, plus the security of using energy-efficient products and environmentally-friendly solutions.
We are represented internationally. Please refer to our homepage www.pilz.com for further details or contact our headquarters.
Headquarters: Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: info@pilz.com, Internet: www.pilz.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals