TOSHIBA TCB-SFMCA1V-E Multi Function Sensor User Manual
- June 16, 2024
- Toshiba
Table of Contents
TOSHIBA TCB-SFMCA1V-E Multi Function Sensor
Thank you for purchasing the “Multi-function sensor” for TOSHIBA Air
Conditioner.
Before starting the installation work, please read this manual carefully and
install the product properly.
Model name: TCB-SFMCA1V-E
This product is used in combination with a heat recovery ventilation unit. Do
not use the multi-function sensor on its own or in combination with other
companies’ products.
Product Information
Thank you for purchasing the Multi-function sensor for TOSHIBA Air Conditioner. This product is used in combination with a heat recovery ventilation unit. Please note that it should not be used on its own or in combination with other companies’ products.
Specifications
- Model Name: TCB-SFMCA1V-E
- Product Type: Multi-function sensor (CO2 / PM)
CO2 / PM2.5 Sensor DN Code Setting List
Refer to the table below for the DN code settings and their descriptions:
DN Code | Description | SET DATA and Description |
---|---|---|
560 | CO2 concentration control | 0000: Uncontrolled |
0001: Controlled
561| CO2 concentration remote controller display| 0000: Hide
0001: Display
562| CO2 concentration remote controller display correction| 0000: No
correction
-0010 – 0010: Remote controller display value (no correction)
0000: No correction (altitude 0 m)
563| CO2 sensor altitude correction|
564| CO2 sensor calibration function| 0000: Autocalibration enabled, Force
calibration disabled
0001: Autocalibration disabled, Force calibration disabled
0002: Autocalibration disabled, Force calibration enabled
565| CO2 sensor force calibration|
566| PM2.5 concentration control|
567| PM2.5 Concentration remote controller display|
568| PM2.5 Concentration remote controller display correction|
790| CO2 target concentration| 0000: Uncontrolled
0001: Controlled
793| PM2.5 target concentration|
796| Ventilation fan speed [AUTO] fixed operation|
79A| Fixed ventilation fan speed setting|
79B| Concentration-controlled minimum ventilation fan speed|
Product Usage Instructions
How to Set Each Setting
To configure the settings, follow these steps:
- Stop the heat recovery ventilation unit.
- Refer to the installation manual of the heat recovery ventilation unit (7 Installation method for each system configuration) or the installation manual of the remote controller (9. DN setting in the 7 Field setting menu) for details on how to set the DN code.
Sensor Connection Settings
To perform automatic fan speed control using the CO2 / PM2.5 sensor, change
the following setting:
DN Code | SET DATA |
---|---|
Multi function sensor (CO2 / PM) | 0001: With connection |
FAQ
-
Q: Can I use the multi function sensor on its own?
A: No, this product is designed to be used in combination with a heat recovery ventilation unit. Using it on its own may result in improper functionality. -
Q: Can I use the multi function sensor with other companies’ products?
A: No, this product should only be used with TOSHIBA Air Conditioner and its specified heat recovery ventilation unit. -
Q: How do I calibrate the CO2 sensor?
A: Refer to the DN code settings for CO2 sensor calibration. The manual provides options for autocalibration and force calibration.
CO2 / PM2.5 sensor DN code setting list
Refer to How to set each setting for the details of each item. Refer to the installation manual of the heat recovery ventilation unit for other DN codes.
DN code | Description | SET DATA and description | Factory default |
---|---|---|---|
560 | CO2 concentration control | 0000: Uncontrolled |
0001: Controlled
| 0001: Controlled
561| CO2 concentration remote controller display| 0000: Hide
0001: Display
| 0001: Display
562| CO2 concentration remote controller display correction| 0000: No
correction
-0010 – 0010: Remote controller display value (no correction)
+ setting data × 50 ppm
| 0000: No correction
563| CO2 sensor altitude correction| 0000: No correction (altitude 0 m)
0000 – 0040: Setting data ×100 m altitude correction
| 0000: No correction (altitude 0 m)
564| CO2 sensor calibration function| 0000: Autocalibration enabled, Force
calibration disabled 0001: Autocalibration disabled, Force calibration
disabled 0002: Autocalibration disabled, Force calibration enabled| 0000:
Autocalibration enabled, Force calibration disabled
565| CO2 sensor force calibration| 0000: No calibrate
0001 – 0100: Calibrate with setting data × 20 ppm concentration
| 0000: No calibrate
566| PM2.5 concentration control| 0000: Uncontrolled
0001: Controlled
| 0001: Controlled
567| PM2.5 concentration remote controller display| 0000: Hide
0001: Display
|
0001: Display
568| PM2.5 concentration remote controller display correction| 0000: No correction
-0020 – 0020: Remote controller display value (no correction)
+ setting data × 10 μg/m3
| 0000: No correction
5F6| Multi function sensor (CO2 / PM)
connection
| 0000: Without connection
0001: With connection
| 0000: Without connection
790| CO2 target concentration| 0000: 1000 ppm
0001: 1400 ppm
0002: 800 ppm
| 0000: 1000 ppm
793| PM2.5 target concentration| 0000: 70 μg/m3
0001: 100 μg/m3
0002: 40 μg/m3
| 0000: 70 μg/m3
796| Ventilation fan speed [AUTO] fixed operation| 0000: Invalid (according to
fan speed in remote controller settings) 0001: Valid (fixed at Fan speed
[AUTO])| 0000: Invalid (according to fan speed in remote controller settings)
79A| Fixed ventilation fan speed setting| 0000: High
0001: Medium
0002: Low
| 0000: High
79B| Concentration-controlled minimum ventilation fan speed| 0000: Low
0001: Medium
| 0000: Low
How to set each setting
Configure the settings when the heat recovery ventilation unit is stopped (Be sure to stop the heat recovery ventilation unit). Refer to the installation manual of the heat recovery ventilation unit (“7 Installation method for each system configuration”) or the installation manual of the remote controller (“9. DN setting” in the “7 Field setting menu”) for details on how to set the DN code.
Sensor connection settings (be sure to implement)
To perform automatic fan speed control using the CO2 / PM2.5 sensor, change
the following setting (0001: With connection).
DN code | SET DATA | 0000 | 0001 |
---|---|---|---|
5F6 | Multi function sensor (CO2 / PM) connection | Without connection (factory | |
default) | With connection |
CO2 / PM2.5 target concentration setting
Target concentration is the concentration at which the fan speed is the
highest. The fan speed is changed automatically in 7 stages according to the
CO2 concentration and PM2.5 concentration. The CO2 target concentration and
PM2.5 target concentration can be changed in the settings below.
DN code | SET DATA | 0000 | 0001 | 0002 |
---|---|---|---|---|
790 | CO2 target concentration | 1000 ppm (factory default) | 1400 ppm | 800 ppm |
793 | PM2.5 target concentration | 70 μg/m3 (factory default) | 100 μg/m3 | 40 |
μg/m3
- Although the fan speed is switched automatically using the set CO2 concentration or PM2.5 concentration as a target, the detection concentration differs depending on the operating environment and product installation conditions etc., so the concentration may go above the target concentration depending on the operating environment.
- As a general guideline, the CO2 concentration should be 1000 ppm or less. (REHVA (Federation of European Heating Ventilation and Air Conditioning Associations))
- As a general guideline, the PM2.5 concentration (daily average) should be 70 μg/m3 or less. (Ministry of Environment of China)
- The concentration at which the fan speed is the lowest will not change even if the settings above are configured, with the CO2 concentration being 400 ppm, and the PM2.5 concentration being 5 μg/m3.
Remote controller display settings
The display of the CO2 concentration and PM2.5 concentration on the remote
controller can be hidden with the following settings.
DN code | SET DATA | 0000 | 0001 |
---|---|---|---|
561 | CO2 concentration remote controller display | Hide | Display (factory |
default)
567| PM2.5 concentration remote controller display| Hide| Display (factory
default)
- Even if the concentration is hidden in the remote controller display, when DN code “560” and “566” control is enabled, automatic fan speed control is performed. Refer to section 5 for DN code “560” and “566”.
- If the concentration is hidden, in the event of a sensor failure, the CO2 concentration “- – ppm”, PM2.5 concentration “- – μg/m3” will also notbe displayed.
- The display range of the concentration is as follows: CO2: 300 – 5000 ppm, PM2.5: 0 – 999 μg/m3.
- Refer to section 6 for details on the remote controller display in a group connection system.
Remote controller concentration display correction
Detection of the CO2 concentration and PM2.5 concentration is performed at the
RA air path of the heat recovery ventilation unit main body. As unevenness
will also occur in the indoor concentration, a difference between the
concentration displayed in the remote controller and the environmental
measurement etc. may result. In such a situation, the concentration value
displayed by the remote controller can be corrected.
DN code | SET DATA | -0010 – 0010 |
---|---|---|
562 | CO2 concentration remote controller display correction | Remote controller |
display value (no correction) + setting data × 50 ppm (factory default: 0000
(no correction))
DN code| SET DATA| -0020 – 0020
---|---|---
568| PM2.5 concentration remote controller display correction| Remote
controller display value (no correction) + setting data × 10 μg/m3
(factory default: 0000 (no correction))
- The CO2 concentration will appear as “- – ppm” if the corrected value is too low.
- If the corrected PM2.5 concentration is negative, it will appear as “0 μg/m3”.
- Correct only the concentration display value displayed by the remote controller.
- Refer to section 6 for details on the remote controller display in a group connection system.
Concentration control setting
Automatic fan speed control according to the CO2 concentration or PM2.5
concentration can be selected individually. When both controls are enabled,
the unit will run at a fan speed close to the target concentration (higher of
the concentrations).
DN code | SET DATA | 0000 | 0001 |
---|---|---|---|
560 | CO2 concentration control | Uncontrolled | Controlled (factory default) |
566 | PM2.5 concentration control | Uncontrolled | Controlled (factory default) |
- Both CO2 concentration control and PM2.5 concentration control are enabled in the factory default settings, so be extra careful when either control is disabled as the following faults may occur.
- If CO2 concentration control is disabled and the PM2.5 concentration is maintained at a low level, the fan speed will drop, so the indoor CO2 concentration may rise.
- If PM2.5 concentration control is disabled and the CO2 concentration is maintained at a low level, the fan speed will drop, so the indoor PM2.5 concentration may rise.
- Refer to section 6 for details on the concentration control in a group connection system.
Remote controller display and concentration control according to system configuration
-
Heat recovery ventilation unit only system
(when multiple heat recovery ventilation units are connected in a group) The CO2 / PM2.5 concentration displayed on the remote controller (RBC-ASU5) is the concentration detected by the sensor connected to the header unit. Automatic fan speed control by sensor is only applicable to heat recovery ventilation units connected to a sensor. Heat recovery ventilation units not connected to sensors will run at a fixed ventilation fan speed setting when Fan speed [AUTO] is selected. (Refer to section 8) -
When system is linked with air conditioners
The CO2 / PM2.5 concentration displayed on the remote controller (RBC-ASU5) is the concentration detected by the sensor connected to the heat recovery ventilation unit with the smallest indoor address. Automatic fan speed control by sensor is only applicable to heat recovery ventilation units connected to a sensor. Heat recovery ventilation units not connected to sensors will run at a fixed ventilation fan speed setting when Fan speed [AUTO] is selected. (Refer to section 8)
Minimum ventilation fan speed setting
When running under automatic fan speed control, the minimum ventilation fan
speed is set as [Low] but this can be changed to [Medium]. (In this case, the
fan speed is controlled at 5 levels)
DN code | SET DATA | 0000 | 0001 |
---|---|---|---|
79B | Concentration-controlled minimum ventilation fan speed | Low (factory | |
default) | Medium |
Fixed fan speed setting with no sensor equipped when there is a sensor
failure
In the system configuration in section 6 above, heat recovery ventilation
units with no sensor equipped will run at a fixed ventilation fan speed
setting when Fan speed [AUTO] is selected with the remote controller. In
addition, for heat recovery ventilation units equipped with a sensor, the unit
will also run at a fixed ventilation fan speed setting when the sensor
performing concentration control fails (*1). This fixed ventilation fan speed
setting can be set.
DN code | SET DATA | 0000 | 0001 | 0002 |
---|---|---|---|---|
79A | Fixed ventilation fan speed setting | High (factory default) | Medium | Low |
When this DN code is set to [High], the unit will run in the [High] mode even if the DN code “5D” is set to [Extra High]. If the fan speed needs to be set to [Extra High], see the installation manual of the heat recovery ventilation unit (5. Power setting for applied control) and set the DN code “750” and “754’ to 100%.
- 1 If both CO2 and PM2.5 concentration control are enabled and either sensor fails, the unit will run at automatic fan speed control with the functioning sensor.
CO2 sensor calibration function settings
The CO2 sensor uses the lowest CO2 concentration in the past 1 week as a
reference value (equivalent to the general atmospheric CO2 concentration) to
perform automatic calibration. When the unit is used in a location where the
atmospheric CO2 concentration is always higher than the general reference
value (along main roads etc.), or in an environment where the indoor CO2
concentration is always higher, the detected concentration may deviate greatly
from the actual concentration due to the autocalibration effect, so either
disable the automatic calibration function, or perform force calibration where
necessary.
DN code | SET DATA | 0000 | 0001 | 0002 |
---|---|---|---|---|
564 | CO2 sensor automatic calibration function | Autocalibration enabled Force |
calibration disabled
(factory default)
| Autocalibration disabled Force calibration disabled| Autocalibration
disabled Force calibration enabled
DN code| SET DATA| 0000| 0001 – 0100
---|---|---|---
565| CO2 sensor force calibration| No calibrate (factory default)| Calibrate
with setting data × 20 ppm concentration
For force calibration, after setting the DN code “564” to 0002, set DN code “565” to a numeric value. To perform force calibration, a measuring instrument that can measure the CO2 concentration is required separately. Run the heat recovery ventilation unit at a time period during which the CO2 concentration is stable, and quickly set the CO2 concentration value measured at the air inlet (RA) with the remote controller using the prescribed method. Force calibration is performed once only after configuration ends. Not implemented periodically.
CO2 sensor altitude correction
Correction of the CO2 concentration will be performed according to the
altitude at which the heat recovery ventilation unit is installed.
DN code | SET DATA | 0000 | 0000 – 0040 |
---|---|---|---|
563 | CO2 sensor altitude correction | No correction (altitude 0 m) (factory | |
default) | Setting data × 100 m altitude correction |
Ventilation fan speed [AUTO] fixed operation setting
For a system that is connected to an air conditioner, Fan speed [AUTO] cannot
be selected from the remote controller. By changing the DN code “796” setting,
it is possible to run the heat recovery ventilation unit at Fan speed [AUTO]
regardless of the fan speed set by the remote controller. In this case, take
note that the fan speed will be fixed as [AUTO].
DN code | SET DATA | 0000 | 0001 |
---|---|---|---|
796 | Ventilation fan speed [AUTO] fixed operation | Invalid (according to fan | |
speed in remote controller settings) (factory default) | Valid (fixed at Fan |
speed [AUTO])
List of check codes for CO2 PM2.5 sensor
Refer to the installation manual of the heat recovery ventilation unit for other check codes.
Check code| Typical cause of trouble| Judging
device
| Check points and description
---|---|---|---
E30| Indoor unit – sensor board communication trouble| Indoor| When
communication between the Indoor unit and sensor boards is not possible
(operation continues)
J04| CO2 sensor trouble| Indoor| When a CO2 sensor trouble is detected
(operation continues)
J05| PM sensor trouble| Indoor| When a PM2.5 sensor trouble is detected
(operation continues)
- “Indoor” in “Judging device” refers to the heat recovery ventilation unit or the air conditioner.