Connect laptop to controller

Identify the IP address of the controller.
Go to the “Service” menu on the Visotouch display connected to the controller (yellow wrench icon) → Scroll down to “Conf IP & MDB Management” → The IP address is shown in this menu.

EMERSON XC PRO Controller Bios Update 1

The default IP address of the controller is 192.168.0.250.

  • Connect the laptop to the controller with a crossover cable.
  • The laptop can only communicate with the controller if they are in the same network.

i. Disconnect the laptop from your company data network.
ii. In the Windows environment go to “Network & Internet Settings”, then “Change adapter options”.
iii. Select “Ethernet” and “Properties”.

EMERSON XC PRO Controller Bios Update 2

Click on “Internet Protocol Version 4 (TCP/IPv4)” and “Properties”.

EMERSON XC PRO Controller Bios Update 3

In “Properties” set the IP parameters according to the IP address of the controller.

EMERSON XC PRO Controller Bios Update 4

  • Click on “OK” to confirm.
  • Open the webpage of the controller.

i. Go to the browser.
ii. Enter the IP address of the controller.
iii. Enter username “admin” and password “Dixell” to login.

EMERSON XC PRO Controller Bios Update 5

Open “Info” page on the left.

EMERSON XC PRO Controller Bios Update 6

Load empty application

  • Prepare USB stick with following folders and correct isadix file in folder “app”. Contact the Emerson Application Engineering department for the correct isadix file.
  • Connect USB stick to the controller.
  • Session will become invalid (after a few minutes).

EMERSON XC PRO Controller Bios Update 8

  • Reload the page.
  • Application release shows “Restore isadix (Validating)”.
  • When the message “(Validating)” disappears (reloading of the page might be necessary), remove the USB stick.

EMERSON XC PRO Controller Bios Update 9

Load new BIOS

Prepare USB stick with following folders and correct zupdater file in folder “bios” and correct isadix file in folder “app”. Contact the Emerson Application Engineering department for the correct zupdater and isadix files.

  • Connect USB stick to the controller.
  • Session will become invalid (after a few minutes).

EMERSON XC PRO Controller Bios Update 11

  • Reload the page.
  • BIOS and application release show “(Validating)”.

EMERSON XC PRO Controller Bios Update 12

DISCLAIMER

  1. The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability.
  2. Emerson Climate Technologies GmbH and/or its affiliates (collectively “Emerson”), as applicable, reserve the right to modify the design or specifications of such products at any time without notice.
  3. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user.
  4. Emerson does not assume responsibility for possible typographic errors contained in this publication.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Emerson User Manuals

Related Manuals