GE APPLIANCES UUC112WC Side Discharge Condensing Unit Instruction Manual
- June 4, 2024
- GE Appliances
Table of Contents
GE APPLIANCES UUC112WC Side Discharge Condensing Unit
RECORD KEEPING
Thank you for purchasing this product from GE appliances, a Haier company. For future reference, record the model and serial number located on the label on the side of your air conditioner, and the date of purchase. Staple your proof of purchase to this manual to aid in obtaining warranty service if needed.
- Model number
- Serial number
- Date of purchase
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING THE SYSTEM
WARNING
For your safety, the information in this manual must be followed to minimize
the risk of fire, electric shock, or personal injury.
- Use this equipment only for its intended purpose as described in this manual.
- This air conditioner must be properly installed in accordance with these instructions before it is used.
- All wiring should be rated for the amperage value listed on the rating plate. Use only copper wiring.
- All electrical work must be completed by a qualified electrician in accordance with local and national building codes.
- Any servicing must be performed by a qualified individual
For any service which requires entry into the refrigerant sealed system, Federal regulations require that the work be performed by a technician having a Class II or Universal certification.
- All air conditioners contain refrigerants, which under federal law must be removed prior to product disposal. If you are disposing of an old product with refrigerants, check with the company handling disposal.
- These R-410A systems require that contractors and technicians use tools, equipment and safety standards approved for use with this refrigerant. DO NOT use equipment certified for R22 refrigerant only.
WARNING
RISK OF ELECTRIC SHOCK. Could cause injury or death.
- An adequate ground is essential before connecting the power supply.
- Disconnect electric power supplies before servicing.
- Repair or replace immediately all electrical wiring that has become frayed or otherwise damaged. Do not use wiring that shows cracks or abrasion damage along its length or at either end.
WARNING RISK OF FIRE. Could cause injury or death.
- Do not store or use combustible materials, gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
WARNING
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge.
Children should be supervised to ensure that they do not play with the unit.
To avoid danger of suffocation, keep the plastic bag or thin film used as the
packaging material away from young children.
Be sure not to allow foreign materials to enter the refrigerant piping. Seal
the ends of refrigerant piping before storage. For installation purposes, be
sure to use the parts supplied by the manufacturer or other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit
falling, water leakage, electric shock, or fire. The rated power supply of 18K
to 48K product are 208/230 VAC/60hz/1PH. Verify the voltage is within 187~253
range before turning the equipment on. The rated power supply of 12K product
is 110 VAC/60hz/1PH. Verify the voltage is within 103~127 range before turning
the equipment on. Supply power should be from a dedicated circuit that meets
branch circuit ampacity requirements. Use a special branch circuit breaker and
receptacle matched to the power circuit capacity of the air conditioner.
Install in accordance with national, state, and local code.
READ ALL INSTRUCTIONS BEFORE USING THE SYSTEM
CAUTION
It is highly recommended that you do not open or close the stop valves when
the outdoor temperature is below -5°F (-21°C), as this may cause refrigerant
leakage. Do not touch the fins of the coil. Touching the coil fins could
result in damage to the fins or personal injury. Ensure the power circuit
capacity is adequate for all loads connected to the electrical service panel.
Increase the conductor and panel capacity if the total electrical loads exceed
the power source capacity. Contact the power utility if the power provided is
below equipment rating plate requirements. Be sure to install a circuit
breaker of the specified capacity. Refer to local requirements regarding type
and kind of circuit breaker, power wiring, and control cable. Regulation of
cables and breaker differs from each locality. Be aware of these regulations
prior to installation. Do not use existing refrigerant lines. Use refrigerant
tubing that is clean and free of any contamination which may cause damage to
the system, including sulfur, copper oxide, dust, metal chips, powder, oil or
water. Avoid coupling lines whenever possible. Use a continuous length of
copper tubing, as oxides formed during improper brazing techniques can damage
the equipment. Do not use copper pipes that have a collapsed, deformed, or
discolored portion (especially on the interior surface). Otherwise, the
expansion valve or capillary tube may become blocked with contaminants.
Improper line sizing will degrade performance. Peak pressure of R410A is much
higher than R22. Use ACR copper tubing with adequate wall thickness. Use a
tubing bender to change piping direction. Make sure the radius of the bend is
no less than 4”. If the pipe is bent repeatedly at the same place, it will
break.
READ AND SAVE THESE INSTRUCTIONS
BEFORE YOU BEGIN CAUTION
READ AND SAVE THESE INSTRUCTIONS BEFORE YOU BEGIN CAUTION
IMPORTANT – Save these instructions for local inspector’s use.
- IMPORTANT – Observe all governing codes and ordinances. Use for future reference.
- Note to Installer – Be sure to leave these instructions with the equipment owner.
- Note to Equipment Owner – Keep these instructions for future reference.
- Skill level – A licensed certified technician (to handle refrigerant R-410A, recovery, etc.) and a qualified electrician are required for installation and service of this equipment.
- Use team lift for installation of this product
- Proper installation is the responsibility of the installer.
- Product failure due to improper installation is not covered under the limited warranty.
- For personal safety, this system must be properly grounded.
- Protective devices (fuses or circuit breakers) acceptable for installation are specified on the nameplate of each unit.
- Piping or wiring within walls must be protected per local code.
CAUTION
- Aluminum electrical wiring may present special problems – consult a qualified electrician.
- When the unit is in the STOP position, there is still voltage to the electrical controls.
INSTALLATION INSTRUCTIONS
General Product Information
Unpacking and Inspection:
This equipment is shipped completely assembled and packaged. All goods are
inspected at the factory and released to the freight company in good
condition. When received at the site, a visual inspection should be made
immediately. Any evidence of rough handling or damage should be photographed
and noted on the delivery receipt in the presence of the carrier. Claims for
damage are to be filed with the freight company.
Indoor Fan Time Delay:
For maximum cooling effect, the furnace or air handler should be equipped with
a time delay. Many popular electronic thermostats have programmable fan
delays, newer furnaces and air handlers include them, and universal delay kits
are readily available on the market.
Model | 12K | 18K | 24K | 30K | 36K | 48K |
---|---|---|---|---|---|---|
Delay | 115s | 90s | 90s | 90s | 100s | 65s |
Thermostat:
Accurate temperature control and unit operation depends on proper
thermostat selection and location. Refer to the thermostat manufacturer’s
installation instructions for specific recommendations. Avoid locating on
outside walls, in direct sunlight, in the air path of a supply register, and
in high traffic areas. Thermostats should be centrally located, close to a
return air grille.
System Protection:
A field-supplied liquid line filter-drier must be installed to remove
particulates or moisture that may collect in the system during field work.
Installations without a filter-drier may void the warranty.
Indoor Unit:
This product is compatible with most major brands of domestic evaporator coils
and air handlers equipped with a thermostatic expansion valve. Consult AHRI’s
directory of products for certified indoor unit matches.
Unit Location and Mounting
- Avoid areas where water, snow, ice, leaves, or other seasonal debris may fall on or accumulate against the unit.
- Do not place the unit in a location where the minimum clearances cannot be maintained.
- For multiple unit installations, the clearance distances shown below must be maintained.
Required Tools for Installation
- Drill
- 2 1/4” hole saw
- Vacuum pump and oil
- Leak solution or tester
- Tubing cutter
- Pipe reamer
- Razor knife
- Measuring tape
- Level
- Micron gauge
- Dry nitrogen and regulator
- Mini-Split AD-87 Adapter (1/4” to 5/16”)
- Customary HVAC hand tools
- Core removal tool with micron gauge port
- Power and control wiring
- Drain hose (Included)
- Refrigerant scale
- Interior and exterior wall sealant
- 18 Gauge Thermostat Wire
- Brazing materials
Model | 12K | 18K | 24K | 30K | 36K | 48K |
---|---|---|---|---|---|---|
Power (outdoor) | PHASE | 1PHASE | 1PHASE | 1PHASE | 1PHASE | 1PHASE |
Volt | 115 V | 208/230V | 208/230V | 208/230V | 208/230V | 208/230V |
CIRCUIT BREAKER/FUSE (A) | 15 | 15 | 15 | 20 | 25 | 40 |
MINIMUM CIRCUIT AMPACITY (A) | 11 | 10 | 12 | 15 | 16 | 26 |
-
The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the installation instruction below.
-
Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage the outdoor unit.
-
If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze. Protection walls
-
A protection wall should be constructed with a solid material to block the sea ODU breeze. The height and the width of the wall should be 1.5 times larger than the Sea breeze
size of the outdoor unit. Also, allow at least 28“ (700mm) between the protection wall and the outdoor unit for air circulation to ventilate.
-
Install the outdoor unit in a place where water can drain freely.
-
If the above conditions cannot be met, contact GE Appliances for assistance.
Clearances
- Minimum clearance around the unit for installation, service, maintenance, and proper operation must be maintained. Anchoring the unit with 3/8 inch (10mm) diameter bolts and nuts is recommended in seaside locations, high wind areas, rooftops, or in regions prone to earthquakes.
The top and two Ide surfaces must be exposed to open space, and barmier on at least one side of the front and back shall be lower than the outdoor unit.
Clearances
Select the Outdoor location:
- Choose a level place solid enough to bear the weight and vibration of the OD unit and where the operation noise will not be amplified.
- Choose a location where the hot air discharge and/or noise will not create a nuisance for neighbors.
- Ensure there is sufficient space to maneuver the OD unit into place.
- Ensure there is sufficient space and no obstructions for the air inlet and outlet.
- Install the unit’s power control wiring at least 10 feet away from television and radio sets to prevent interference.
- Ensure any moisture sensitive items are kept away from the condensate drain path of the OD unit.
- Choose a location not affected by heavy snowfall or wind.
- To prevent wind exposure, install a wind baffle.
Dimensions
Unit Wiring
Electrical Wiring and Supply Voltage:
All wiring must comply with national, state, and local codes. Nameplate data
indicates the operating voltage, phase, ampacity, maximum over current
protection, and minimum voltage.
Install a field-supplied individual branch circuit with current protection for
the unit as required by code. Run power supply wiring through a weatherproof
disconnect box in conduit to the unit connections. Disconnects are required to
be within sight and easy reach of the unit (usually within 3 feet). Always
refer to the unit wiring diagram for the number of conductors required. Route
neatly and protect from sharp edges and damage. Inadequate wiring and improper
power supply will likely result in component failure and will void the
warranty.
NOTE: The supply voltage must be consistent with the rated voltage, not
to exceed +/- 10%. Ensure the unit is properly grounded.
Wiring Connections:
- Remove the electrical control cover from the outdoor unit.
- Connect the cables to the identified terminals on the terminal block. 18 gauge thermostat wire is recommended; however, national and local codes prevail.
- Form a loop in the cable to prevent water from entering the outdoor unit.
- Insulate any unused conductors with electrical tape so that they do not touch exposed electrical or metal parts.
CAUTION
Incorrect wiring connections may cause electrical parts to malfunction. All
wiring must conform to national, state, and local code, and must be installed
by licensed electricians.
Outdoor Unit Wiring
Terminal block of outdoor unit: 12K
Terminal block of outdoor unit: 18K-30K
Terminal block of outdoor unit: 36K and 48K
- *NOTE: For additional wiring instructions, see the installation manual for the 24V thermostat used in conjunction with this unit.
- NOTE: For reference only. Refer to the unit wiring diagram.
Wiring (cont.)
*NOTE: For reference only, the actual wiring diagram shall prevail
Wiring (cont.)
Wiring (cont.)
Refrigerant Piping
The length of refrigerant lines, and the number of bends, determine the
pressure drop which affects capacity, efficiency, and oil return to the
compressor. The outdoor unit connections are braze type. Tube size should
always be the same diameter as the connections provided at the service valves.
Installing tubing sizes other than those shown can result in inadequate oil
return to the compressor and excessive refrigerant charge, and will void the
warranty.
Refrigerant Piping | Model Number |
---|---|
12k | 18k |
Liquid O.D. (inch) | 1/4″ |
Suction O.D. in ( Std ) | 1/2″ |
Suction O.D. in ( Opt) | 3/8″ |
Max. Refrigerant Line Length (inch) | 82 |
Max. Elevation Vertical Lift (inch) | 33 |
*Pipe length must not be less than 10 feet.
** Oil traps are required every 15 ft. when the outdoor unit is installed
above the indoor unit.
Choose a location that places this unit as close to the indoor unit as
possible. Use only clean refrigeration grade tubing. Always keep the tube ends
capped until you are ready to make the final connections. Remove burrs from
cut ends of tubing. Use tube benders to avoid kinking. Insulate the suction
line with a wall thickness of at least 3/8”. Support the tubing adequately to
avoid sags that can trap oil. Isolate the tubing so as not to transmit noise
to the building structure. Avoid sharp edges that could cut the insulation or
piping.
WARNING
It is illegal to discharge refrigerant into the atmosphere. Use proper
recovery methods and equipment when working on parts of the unit containing
refrigerant. Service should be performed by a qualified service agency and
certified technician. Using the appropriate fittings if needed, attach the
line set to the service valve stubs. Apply heat paste to stub next to the
valve and wrap the valve body with a wet cloth. At the outdoor service valves,
remove the valve cores. Introduce a purging flow of dry nitrogen through the
first tube, allowing it to flow out of the flared connection stub. Braze
connections with a brazing alloy. 15% braze rod is recommended. Repeat the
above process for the second tube.
Pairing with A-coils
Manufacture recommend installing AHRI listed matched indoor and outdoor
system. Installing approved matched indoor and outdoor system will provide
optimum efficiency and best overall system reliability. AHRI certification for
approved matched system can be verified in the AHRI site, Residential AC and
AC coil section. https://www.ahridirectory.org/Search/SearchHome Under the
warranty, damage caused by a used or unapproved component is not covered by
the Standard Base Warranty. When installing the Side-discharge Outdoor Unit
with non-AHRI listed 3rd party indoor equipment, manufacture will presume that
any damage to the outdoor unit was not caused by the indoor equipment if the
following installation guidance is followed.
When installers pair 14 SEER Side-discharge outdoor with a pre-existing “A coil + gas furnace indoor” system
- Ensure to change the indoor coil to a new R410a, TXV, tonnage to tonnage matched A-coil
- Ensure to install a bi-flow Filter Drier (Field supplied) in liquid line
- Ensure the linseed size matches 14 SEER Side-discharge outdoor as stated in the outdoor unit installation manual (If existing line set size is different new linseed must be installed).
- Ensure proper airflow
- Ensure existing linseeds are cleaned by flushing if re-used.
When installers pair 14 SEER Side-discharge outdoor with a new 3rd party AHU
- Ensure the 3rd party AHU is a R410a, TXV, tonnage to tonnage matched AHU
- Ensure to install a bi-flow Filter Dryer (Field supplied) in liquid line
- Ensure the linseed size matches 14 SEER Side-discharge outdoor as stated in the outdoor unit installation manual (If existing linseed size is different new linsey must be installed)
- Ensure proper airflow
- Ensure existing linseeds are cleaned by flushing if re-used.
Pairing with A-coils (cont.)
When installers pair 14 SEER Side-discharge outdoor with a pre-existing AHU
- Ensure the 3rd party AHU is a R410a, TXV, tonnage to tonnage matched AHU
- Ensure to install a bi-flow Filter Dryer (Field supplied) in liquid line
- Ensure the linseed size matches 14 SEER Side-discharge outdoor as stated in the outdoor unit installation manual (If existing lineset size is different new lineset must be installed).
- Ensure proper airflow
- Ensure existing linseeds are cleaned by flushing if re-used.
- Ensure to install a bi-flow Filter Dryer (Field supplied) in gas line
- Ensure to triple evacuation the pre-existing coil
If installation guidelines and procedures are followed for each type of application above, the outdoor unit will qualify for a Limited Standard Base Warranty (i.e., 5-year parts and compressor), subject to the other limitations in the standard warranty document.
Model Number| | UUC112WCDA| UUC118WCDA| UUC118WCDBA| UUC124WCDA| UUC124WCDBA|
UUC130WCDA| UUC130WCDBA| UUC136WCDA| UUC136WCDBA| UUC148WCDA
---|---|---|---|---|---|---|---|---|---|---|---
Factory Charge| Oz| 49.4| 75.84| 81.20| 97.00| 100.60| 116.40| 119.90| 123.50|
127.00| 141.10
Liquid O.D. (Std)| Inch| 1/4″| 1/4″| 1/4″| 3/8″| 3/8″| 3/8″| 3/8″| 3/8″| 3/8″|
3/8″
Suction O.D.(Std)| Inch| 1/2″| 1/2″| 1/2″| 5/8″| 5/8″| 5/8″| 3/4″| 3/4″| 3/4″|
3/4″
Max. Refrigerant Line between Indoor and Outdoor| Ft| 82| 82| 82| 82| 82| 82|
82| 82| 82| 98
Max. Refrigerant Line elevation between Indoor and Outdoor| Ft| 33| 33| 33|
33| 33| 33| 33| 33| 33| 49
Additional charge Additional charge if refrigerant line exceeding 25 ft| oz/
FT| 0.16| 0.16| 0.16| 0.32| 0.32| 0.32| 0.32| 0.32| 0.32| 0.32
Memo: Colored columns are paired with ADP A‑coils
Note: Factory charge for UUC124WCDBA is 100.6 oz and UUC130WCDBA is 119.9 oz.
Leak Testing Evacuation, and Charging
The condensing unit is supplied with an R-410A charge sufficient for most
matching evaporator units. Charge must be added for interconnecting tubing.
R=T X (L-25)ft
- R (oz): Additional refrigerant to be charged
- L (ft): The length of the liquid pipe
- T (oz): The quantity of the charged refrigerant per additional foot
Model | 12K | 18K | 24K | 30K | 36K | 48K |
---|---|---|---|---|---|---|
oz/ft | 0.16 | 0.32 |
The service valves are shipped in the closed position and should not be opened until final connections, evacuation, and additional charging are completed.
The recommended procedure for leak test, evacuation, and charging is outlined below:
- Complete the final piping connections to the indoor and outdoor units.
- Remove the service core from both lines, and connect a charging manifold to the service ports on the service valves.
- Pressurize the lines and evaporator with 500 PSI of dry nitrogen. Leak check all connections with either an electronic detector or specialized liquids. Maintain pressure for at least 30 minutes.
- Release the nitrogen and connect a vacuum pump to the manifold center connection. Start the pump and open the manifold valves.
- Evacuate to 350 microns or less. Close the manifold valves and shut off the pump. If the vacuum level does not rise more than 150 microns in one minute, the evacuation is considered complete. Otherwise, the system is indicating either a leak or there is still moisture present.
- If a leak is found, repair as necessary and repeat steps 3, 4, and 5. If there are no leaks, continue with Step 5 until at least 350 microns is attained.
- Close the manifold valves and disconnect the vacuum pump. Reinstall the valve cores and add refrigerant in the amount shown in the charging section of this manual.
- Remove the caps from the services valves. Open the valves to the fully ‘back-seated’ position. Replace service valve caps and tighten securely.
Start-up
Operation of the unit is automatic and will provide cooling depending on the
setting of the thermostat.
IMPORTANT
All panels must be installed, the main power turned on, and the thermostat
properly connected before operating the unit.
- Set thermostat system switch to “Off” position and fan switch to “Auto” position, Turn the power supply breaker on.
- Set the fan switch to “On” and make sure the blower operates.
- Return the fan switch to “Auto” and wait until the blower stops. Set the system switch to “Cool” and lower thermostat set point to coldest setting. The compressor, condenser fan, and evaporator blower will start. Cool air will be supplied after several minutes of run time.
- Proceed to the “Fine Tuning” section of these instructions.
Hard Start Kits for 14-SEER Side
Discharge ODU
When inconsistent compressor starts are found, it is an approved fix to add a
locally sourced “Hard Start” kit. A kit must include a capacitor and a relay.
Replacing the OEM capacitor with one that has a higher micro-fared rating IS
NOT an authorized repair and will void the warranty of the product.
Selecting the Correct Kit
Hard start kits are sized by compressor horsepower (HP). Use the chart below
Model | HP |
---|---|
UUC112WC* | 1 |
UUC118WC* | 1.5 |
UUC124WC* | 2 |
UUC130WC* | 2.5 |
UUC136WC* | 3 |
UUC148WC* | 4 |
Installing Kit
The hard start kit must be installed in parallel with the compressor
capacitor. To do this, connect the leads from the kit to either side of the
compressor capacitor. The kit must also be secured to the chassis of the unit,
and if required, grounded.
Fine Tuning
- Allow the system to operate for at least 20 minutes before checking refrigerant temperature and pressure.
- Perform an air flow calculation to ensure the blower is delivering the correct volume of air at the pressure intended for the distribution system.
- When the above are completed, verify that the operating temperature and pressure comply with the chart.
NOTE: “IDT” = Indoor Temperature “ODT” = Outdoor Temperature
- Remove refrigerant if the pressure is above the chart value.
- Add refrigerant if the pressure is below the chart value.
Perform an inspection of the entire installation and finalize any items needed
for completion. Review the system operation, thermostat functions, and
warranty policy with the owner.
Leave this manual at the jobsite for future reference.
Operating Instructions
This system is designed to provide comfort cooling at outside temperatures
between 50°F (10°C) and 115°F(46°C). Operation outside of this temperature
range may cause unit failure and will void the warranty.
To Operate:
NOTE: Thermostat operation may vary by type and model used. Please
consult the operating manual provided with the thermostat. The instructions
below are generalized for most models.
- Move the switch on the thermostat to the Cool position.
- Set the desired temperature (between 63-86°F or 17-30°C) on the thermostat. If the room is warmer than the setting, the unit will turn on and begin to blow cool air after a few minutes. A hot, humid room or building may take several hours of continuous operation to reach the thermostat setting when starting for the first time or at the beginning of the cooling season.
- Set the Fan switch on the thermostat to Auto if you want the fan to run only when cooling is needed, or to On if you want continuous air circulation.
- If the space will be unoccupied for four or more hours, moving the setting to a higher temperature may save energy. Do not raise the temperature setting by more than 5 degrees. Changing the temperature over 5 degrees, or turning the unit off can actually cost more.
- Be sure that furniture or other objects do not block supply air registers or return air grilles.
IMPORTANT
If the system is turned off, wait at least 3 minutes before restarting it.
This gives the unit time to stabilize. Failure to do so could cause compressor
damage.
Maintenance:
- Change or clean the air filter monthly, or more often if conditions require it. Thoroughly dry a washable filter before re-installing.
- Contact the installer for factory recommended annual maintenance.
Final Check
System Test
Please explain to the customer how to operate the system by using the Owner’s
Manual found with the indoor unit.
Explaining Operation To the End User
- Using the User Manual, explain to the user how to use the air conditioner (thermostat, adding/removing the air filters, cleaning methods, precautions for operation, etc.)
- Review precautions for operation.
- Recommend that the user read the Operating Instructions carefully.
Check Items for Test Run
- No gas leak from linseeds?
- Are the linseeds insulated properly?
- Are the connecting wirings of indoor and outdoor firmly inserted to the terminal block?
- Is the connecting wiring of indoor and outdoor fixed? Is condensate draining correctly?
- Is the ground wire securely connected? Is the indoor unit securely fixed?
- Is power source voltage correct according to local code? Is there any odd noise?
- Does the cooling temperature drop between 20-30°F? Is the room temperature display accurate?
LIMITED WARRANTY
10 YEAR STANDARD REGISTERED LIMITED WARRANTY
All “Indoor and Outdoor Products,” identified in Attachment 1, registered
by the installer or the Original Owner within 60 days of the Date of Purchase
shall receive a Standard Registered Limited Warranty, which shall be identical
to the Standard Base Warranty, except that the Limited Parts Warranty shall be
for a term of 10 Years and the Limited Compressor Warranty shall be for a term
of 10 years. All Product not registered within 60 days of the Date of Purchase
shall be subject to the Standard Base Warranty. Some states and provinces do
not allow warranty terms to be subject to registration; in those states and
provinces the longer terms for Limited Parts Warranty and the Limited
Compressor Warranty apply.
THIS LIMITED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
The remedy provided in this warranty is exclusive and is granted in lieu of
all other remedies. This warranty does not cover incidental or consequential
damages. Some states and provinces do not allow the exclusion of incidental or
consequential damages, so this limitation may not apply to you. Some states
and provinces do not allow limitations on how long an implied warranty lasts,
so this limitation may not apply to you. This warranty gives you specific
legal rights and you may also have other rights which vary by state and
province. This warranty covers units within the 50 United States, the District
of Columbia and Canada. This warranty it provided by GE Appliances a Haier
company, Louisville, KY 40225.
ATTACHMENT 1
The product is defined as product sold by GE Appliances, a Haier Company. The product containers 2 sub-categories of goods, indoor and outdoor products, which are defined as AUH, AHY, UUH**, UUY, UUC, UUH
LIMITED STANDARD BASED WARRANTY **
**
For the product models listed on Attachment 2 (the “Product”), this Standard Limited Warranty is provided to the Original Owner of the Product:
For The Period Of: | GE Appliances Will Replace: |
---|---|
5 year limited parts warranty From the date of the original purchase | This |
limited warranty cover all defects in workmanship or material for the
mechanical and electrical parts contained in the Product (“Defective Parts”)
for a period of 5 years from the Date of Purchase. GE Appliances will provide
new or refurbished parts, or a replacement for all or part of the unit, at its
sole discretion, to your licensed HVAC technician installer. This warranty
also covers all defects in workmanship or material for the unit controller for
a period of 1 year. The system is covered by standard warranty.
7 year compressor warranty from the date of the original purchase| The
compressor contained in this product is warrantied for a period of 7 years
from the Date of Purchase. GE Appliances will provide a new or refurbished
compressor, or a replacement for all or part of the unit, at its sole
discretion, to your licensed HVAC technician installer.
WHAT IS THE DATE OF PURCHASE
The “Date of Purchase” is the date that the original installation is complete
and all product start-up procedures have been properly completed and verified
by the installer’s invoice. If the installation date cannot be verified, then
the Date of Purchase will be sixty (60) days after the manufacture date, as
determined by the Product’s serial number. You should keep and be able to
provide your original sales receipt from the installer as proof of the Date of
Purchase. In new construction, the Date of Purchase will be the date the owner
purchased the residence from the builder.
WHO IS COVERED
Owner occupied: The “Original Owner” of this product, which means the
original owner (and his or her spouse) of the residence where the Product was
originally installed. Subject to the law of the state or province where the
Product is installed, this warranty is not transferable to subsequent owners
or if the product is moved to a different residence after the initial
installation. Non-owner occupied: This limited warranty is provided for
product 1) installed in a) single family or multi-family non-owner occupied
residential buildings, or b) non-industrial commercial applications, (such as
office buildings, retail establishments, hotels/motels) where the product is
not subjected to an atmosphere with corrosives or high levels of particulates
(such as soot, aerosols, fumes, grease), and 2) if the product is maintained
annually by a licensed HVAC technician (proof of annual maintenance is
required). The “Original Owner” of the product, means the original owner of
the building where the product was originally installed. For new construction,
the purchaser of the building from the builder will also be considered an
original owner. This warranty is not transferable to subsequent owners or if
the product is moved to a different location after the initial installation.
HOW CAN YOU GET SERVICE
Contact your licensed HVAC technician installer. All installation and
service must be performed by a licensed HVAC technician. Failure to use a
licensed HVAC technician for installation of this Product voids all warranty
on this Product..
THIS WARRANTY DOES NOT COVER
- Damage from improper installation.
- Damage in shipping.
- Defects other than from manufacturing (i.e., workmanship or materials).
- Damage from misuse, abuse, accident, alteration, lack of proper care and/or regular maintenance, or incorrect electrical voltage or current.
- Damage resulting from floods, fires, wind, lightning, accidents or similar conditions.
- Damage from installation or other services performed by other than a licensed HVAC technician.
- Labor and related services for repair or installation of the Product.
- A Product purchased from an online retailer.
- Damage as a result of subjecting Product to an atmosphere with corrosives or high levels of particulates (such as soot, aerosols, fumes, grease).
- Damage from improper installation.
- Damage in shipping.
- Defects other than from manufacturing (i.e., workmanship or materials).
- Damage from misuse, abuse, accident, alteration, lack of proper care and/or regular maintenance, or incorrect electrical voltage or current.
- Damage resulting from floods, fires, wind, lightning, accidents or similar conditions.
- Damage from installation or other services performed by other than a licensed HVAC technician.
- Labor and related services for repair or installation of the Product.
- A Product purchased from an online retailer.
- Damage as a result of subjecting Product to an atmosphere with corrosives or high levels of particulates (such as soot, aerosols, fumes, grease).
THIS LIMITED STANDARD BASED WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES,
EXPRESS OR IMPLIED, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE.
The remedy provided in this warranty is exclusive and is granted in lieu of
all other remedies. This warranty does not cover incidental or consequential
damages. Some states and provinces do not allow the exclusion of incidental or
consequential damages, so this limitation may not apply to you. Some states
and provinces do not allow limitations on how long an implied warranty lasts,
so this limitation may not apply to you. This warranty gives you specific
legal rights and you may also have other rights which vary by state and
province. This warranty covers units within the 50 United States, the District
of Columbia and Canada. This warranty it provided by GE Appliances a Haier
company, Louisville, KY 40225.
ATTACHMENT 2
The “Product” is defined as GE Appliances and Haier brand Side Discharge
Condensing Units, identified by the following model number prefixes: AUH,
UUC (for outdoor).