Eubank 7AA1024A-1060A Wall Mount Air Conditioner
IMPORTANT
This manual may include information for options and features which may not be
included on the unit being installed. Refer to the unit data label or Model
Identification to determine which features and options this unit is equipped
with.
INSTALLER: Affix the instructions on the inside of the building adjacent
to the thermostat.
END USER: Retain this manual for future reference.
Manufactured By:
Eubank, An AirX Climate Solutions Brand
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia
31015 229-273-3636 • Fax
229-273-5154
E-mail: eubanksales@airxcs.com
Internet: www.EubankWallMount.com
The most current version of this manual can be found at
www.EubankWallMount.com.
How To Use This Manual
This manual is intended to be a guide to the Eubank Wall Mount family of
vertical air conditioners. It contains installation, troubleshooting,
maintenance, warranty, and application information. The information contained
in this manual is to be used by the installer as a guide only. This manual
does not supersede or circumvent any applicable national or local codes. If
you are installing the Eubank unit, first read Chapter 1 and scan the entire
manual before beginning the installation as described in Chapter 2. Chapter 1
contains general, descriptive information and provides an overview which can
speed up the installation process and simplify troubleshooting.
If a malfunction occurs, follow this troubleshooting sequence:
- Make sure you understand how the Eubank unit works (Chapters 1 & 3).
- Identify and correct installation errors (Chapter 2).
- Refer to the troubleshooting information in Chapter 4.
If you are still unable to correct the problem, contact the Factory at 1-800-841-7854 for additional assistance. Please read the following “Important Safety Precautions” before beginning any work.
Product Information
Specifications
- Product: Vertical Wall-Mount Air Conditioners with Front Control Box Panel
- Installation & Operation Manual: Included
- EER (Energy Efficiency Ratio): 11
- Models: 7AA1024A-7AA1060A (Single Stage), 7AA2036A-7AA2060A (2-Stage)
- Manufacturer: Eubank, An AirX Climate Solutions Brand
- Manual Version: 05/2023 Rev.5
Product Usage Instructions
Important Safety Precautions
- USE CARE when LIFTING or TRANSPORTING equipment.
- TRANSPORT the UNIT UPRIGHT. Laying it down on its side may cause oil to leave the compressor and breakage or damage to other components.
- TURN ELECTRICAL POWER OFF AT THE breaker or fuse box BEFORE installing or working on the equipment. LINE VOLTAGES ARE HAZARDOUS or LETHAL.
- OBSERVE and COMPLY with ALL applicable PLUMBING, ELECTRICAL, and BUILDING CODES and ordinances.
- SERVICE may be performed ONLY by QUALIFIED and EXPERIENCED PERSONS.
- Wear safety goggles when servicing the refrigeration circuit.
- Beware of hot surfaces on refrigerant circuit components.
- Beware of sharp edges on sheet metal components.
- Use care when recovering or adding refrigerant.
- Use COMMON SENSE – BE SAFETY-CONSCIOUS.
This is the safety alert symbol . When you see this symbol on the Eubank unit and in the instruction manuals be alert to the potential for personal injury. Understand the signal word DANGER, WARNING, CAUTION and IMPORTANT. These words are used to identify levels of the seriousness of the hazard.
Signal Words
The following signal words are used to identify the seriousness of the
hazard:
- DANGER: Failure to comply will result in death or severe personal injury and/or property damage.
- WARNING: Failure to comply could result in death or severe personal injury and/or property damage.
- CAUTION: Failure to comply could result in minor personal injury and/or property damage.
- IMPORTANT: Used to point out helpful suggestions that will result in improved installation, reliability, or operation.
AS PART OF THE EUBANK CONTINUOUS IMPROVEMENT PROGRAM, SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE. © 05/2023 Eubank, An AirX Climate Solutions Brand
WARNING
- If the information in these instructions are not followed exactly, a fire may result causing property damage, personal injury or loss of life.
- Read all instructions carefully prior to beginning the installation. Do not begin installation if you do not understand any of the instructions.
- Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life.
- Installation and service must be performed by a qualified installer or service agency in accordance with these instructions and in compliance with all codes and requirements of authorities having jurisdiction.
INSTALLER: Affix the instructions on the inside of the building adjacent
to the thermostat.
END USER: Retain these instructions for future reference.
Description & Specifications
General Description
The Eubank 7AA are a series of vertical wall-mounted air conditioning
systems that provide heating, cooling, and ventilation for electronic
equipment shelters, process control centers, and other applications with high
internal heat gains. The series includes multiple sizes and nominal cooling
capacities from 24,000 to 60,000 BTUH. Resistance heating elements are
available in various wattages. 7AA modes are available with cooling capacities
of 24,000 to 60,000 BTUH and EER’s of 11.00 to 11.75. 7AA2036A-2060A models
have a 2-stage compressor. The Eubank Product Data Sheets have detailed
information on the capacities and efficiencies for each model. See Appendix A
for instructions on field installation of electric heat. Eubank air
conditioners feature an exclusive electronic control board. The control board
consolidates several of the electrical components and improves the air
conditioner’s reliability. The control board replaces the blower relay, the
lockout relay, the compressor time delay and the timed low pressure bypass. In
addition, the control board has LED’s to indicate operating status and fault
conditions to assist the service technician. A complete description of
functions of the control board is in Section 1.6. All models are designed for
easy installation and service. Major components are accessible for service
beneath external panels. All units have internal disconnects (optional on 380V
and 575V). Follow local codes for external disconnect requirements. Eubank
wall mount air conditioners have a 0-15% manual outside air damper as standard
equipment. All models are available with an optional factory installed
economizer for 100% free cooling with outside air.
Serial Number Date Code
20 = 2020 01 = January 05 = May 09 = September
21 = 2021 02 = February 06 = June 10= October
22 = 2022 03= March 07 = July 11 = November
23 = 2023 04 = April 08 = August 12 = December
Air Flow, Weights and Filter Sizes
Complete electrical and performance specifications and dimensional drawings
are in the Eubank Wall Mount Air Conditioner Product Data Sheets.
Note: Follow local codes and standards when designing duct runs to
deliver the required airflow. Minimize noise and excessive pressure drops
caused by duct aspect ratio changes, bends, dampers and outlet grilles in duct
runs.
MODEL| INCHES| MILLIMETERS| PART NUMBER| FILTERS
PER UNIT| MERV RATING
---|---|---|---|---|---
7AA1024A| 30 x 16 x 2| 762 x 406 x 52| 80138| 1| 8
7AA1030A/1036A/1042A & 7AA2030A/2036A/2042A| 36½ x 22 x 2| 927 x 559 x
52| 80162| 1| 8
7AA1048A/1060A & 7AA2048A/2060A| 18 x 24 x 2| 457 x 610 x 52| 81257| 2| 8
Return Air Filter Sizes
MODEL| 7AA1024A| 7AA1030A| 7AA1036A| 7AA1042A|
7AA1048A| 7AA1060A| 7AA2036A| 7AA2042A| 7AA2048A|
7AA2060A
---|---|---|---|---|---|---|---|---|---|---
Ounces| 68| 130| 110| 120| 153| 149| 110| 120| 165| 165
Refrigerant Charge (Ounces)
MODEL|
---|---
7AA1024A|
7AA1030A|
7AA1036A|
7AA1042A|
7AA1048A|
7AA1060A|
7AA2036A|
7AA2042A|
7AA2048A|
7AA2060A|
Values in bold are the minimum air flow.
Air flow ratings of 208-230 volt units are at 230v. Air flow ratings of 460
volt units are at 460 volts. Operation of units at a voltage different from
the rating point will affect air flow .
CFM @ External Static Pressure (Wet Coil) (IWG)
MODEL | LBS | KG |
---|
Non-Economizer
7AA1024A| 395| 179
7AA1030A/1036A & 7AA2036A/2042A| 451| 205
7AA1048A/1060A & 7AA2048A/2060A| 599| 272
With Economizer
7AA1024A| 415| 188
7AA1030A/1036A & 7AA2036A/2042A| 471| 214
7AA1048A/1060A & 7AA2048A/2060A| 619| 281
Shipping Weights for Eubank Wall Mount AC Units
Model Identification
Example| 7| A| A| 1| 0| 3| 6| A|
D| 0| 5| 0| C| +| +| +| +| 1|
E| A| +| A| 2| 1| +| +| +| +|
+| +
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Position| 1| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12| 13| 14| 15| 16| 17| 18|
19| 20| 21| 22| 23| 24| 25| 26| 27| 28| 29| 30
1| Unit Designation/Family| **| 7 = Eubank Wall Mount
---|---|---|---
2| Energy Efficiency Ratio (EER)| **| A = 11
3| Refrigerant Type| **| A = R-410a
4| Compressor Type/Quantity| **| 1 = Fixed Speed/Single
2 = 2-Stage/Single
5| Unit Capacity/Nominal Cooling (BTUH)| | 024| =
24,000| 042| = 42,000
6| **| 030| =
30,000| 048| = 48,000
7| **| 036| =
36,000| 060| = 60,000
8| System Type| **| A = Air Conditioner
****9| Power Supply (Volts-Phase-Hz)| **| A| = 208/230-1-60| |
D| = 460-3-60
**| C| = 208/230-3-60| | Z = 575-3-60
10| ** Heat Designation @ Rated Voltage| **| 000| = No Heat| |
080| = 8KW
**| 022| =
2.2KW| | 090| = 9KW
11|
**| 036| = 3.6KW| | 100| = 10KW
****12| **| 040| = 4KW| | 120| = 12KW
**| 050| = 5KW| | 150| = 15KW
**| 060| = 6KW| | |
13| Ventilation Configuration| | A = Solid Front Door
C = Economizer
D = Motorized Damper w/Pressure Relief
E = Motorized Damper w/Pressure Relief & Independent Motorized Damper
Control
F = No Free Cooling, 100% Emergency Ventilation Only w/Independent
Control
N = Barometric Damper w/15% OSA
V = Economizer VZW Spec
Y = Manual Damper w/No Pressure Relief
Z = Manual Damper w/Pressure Relief
+ = None
$ = Special
**14**
| ****
**** Dehumidification
| **| G = Hot Gas Reheat
R = Electric Reheat
T = Electric Reheat w/Humidity Control
+ = None
$ = Special
****15| ** Controls| **| A = Power Fail Alarm w/Additional
Lockouts
C = 24V EMS Relay Kit
D = 24V EMS Relay Kit w/Factory Installed T-Stat
E = Factory Installed T-Stat
+ = None
$ = Special
****16| ** Operating Condition| **| A = Evaporator Freeze
Sensor (EFS)
C = EFS w/Hot Gas Bypass
D = Desert Duty
F = Desert Duty w/Hard Start
G = Desert Duty w/EFS
H = Desert Duty w/Hard Start & EFS
N = Hard Start
P = Hard Start w/Low Ambient & CCH
Q = Hard Start w/Low Ambient & Fan Cycle Control (FCC)
R = Crank Case Heater (CCH)
T = Hard Start w/EFS
U = Hard Start w/Hot Gas Bypass
V = Hard Start w/Low Ambient & CCH & EFS
W = Low Ambient w/CCH
X = Hot Gas Bypass
Y = Low Ambient w/CCH & FCC
Z = Low Ambient w/CCH & EFS
1 = Low Ambient w/FCC
2 = Low Ambient w/FCC & EFS
3 = CCH w/Hot Gas Bypass
+ = None
$ = Special
17| ** Indoor Air Quality Features| D = Dry Bulb Sensor
E = Dry Bulb Sensor w/Dirty Filter
G = Dirty Filter Sensor
+ = None
$ = Special
---|---|---
**18| ** Air Flow| 1 = Top Supply/Bottom Return
2 = Center Supply (Reverse)
3 = Bottom Supply/Top Return (Counter)
4 = Top Panel Discharge
5 = Centrifugal Blowers
6 = 3T3
7 = 3T5
8 = 4T2
9 = 4T3
A = 3T2
$ = Special
**19| ** Compressor Location| C = Center – All 6 ton
units and above
D = Left Hand – All 31/2 to 5 ton units
E = Right Hand – All 2 to 3 ton units
**20| ** Filter Option| A = 2” Pleated (MERV 8, AC/HP-C)
C = 2” Charcoal
D = MERV 11 High Filtration Package
E = MERV 13 High Filtration Package
F = Filter Access Through Return Air Grille
W = Aluminum Washable
+ = None
$ = Special
**21| ** Corrosion Protection| A = Condenser Coil Only
C = Evaporator Coil Only
D = Both Coils Condenser & Evaporator
E = All Coils Cond/Evap/Reheat
F = Coat All
G = Coastal Package & Evaporator Coil
K = Coastal Package
+ = None
$ = Special
22| Engineering Revision Level| A2 C2
23
**24| ** Cabinet Color| 1 = Marvair Beige
2 = Gray
3 = Carlsbad Canyon
4 = White
5 = Stainless Steel Exterior
6 = Dark Bronze
7 = .050 Aluminum Stucco
8 = Mesa Tan
9 = Pebble Gray
A = Stainless Steel – Unit
$ = Custom Color (Powder Coat)
25| Sound Attenuation| 2 = Compressor Blanket
+ = None
**26| ** Security Option| A = Lockable Access Plate/Tamper
Proof
C = Tamper Proof Screws
D = Lockable Access Plate w/Tamper Proof
+ = None
$ = Special
**27| ** Fastener/Drain Pan Option| A = Stainless Steel
Fasteners
C = Stainless Steel Drain Pan
D = Stainless Steel Fasteners & Drain Pan
+ = None
$ = Special
28| Unused| + = None
$ = Special
29| Unused| + = None
$ = Special
**30| ** Special Variation| + = None
$ = Special Configuration Not Covered by Model Nomenclature
Note: Not all options are available with all configurations. Contact your Eubank sales representative for configuration details and feature compatibility.
General Operation
Model | Ventilation Configuration | Temperature Range |
---|---|---|
Non-Economizer | Standard (“N”), Desert Duty (“ND”) | 0ºF – 131ºF (-18ºC – |
55ºC)
With Economizer| Standard (“CE”), Desert Duty (“CD”)| -40ºF – 131ºF
(-40ºC – 55ºC)
Ambient Temperature Operating Range
Refrigerant Cycle (Cooling Mode)
Eubank air conditioners use R-410A refrigerant in a conventional vapor-
compression refrigeration cycle to transfer heat from air in an enclosed space
to the outside. A double blower assembly blows indoor air across the
evaporator. Cold liquid refrigerant passing through the evaporator is boiled
into gas by heat removed from the air. The warmed refrigerant gas enters the
compressor where its temperature and pressure are increased. The hot
refrigerant gas condenses to liquid as heat is transferred to outdoor air
drawn across the condenser by the condenser fan. Liquid refrigerant is metered
into the evaporator to repeat the cycle.
Heating Mode
A wall-mounted thermostat controls the heating cycle of models which
incorporate resistance heating elements. On a call for heat, the thermostat
closes the heat relay to energize the indoor fan and the resistance elements.
Except on units with the optional dehumidification kit, the compressor is
locked out during the heating cycle. Please see Appendix A for instructions on
field installing electric heaters.
Economizer Operation
The economizer is a regulated damper system with controls. The damper
regulates the circulation of outside air into the enclosure (when the outdoor
air conditions are suitable) to reduce the need for mechanical cooling, save
energy, and extend compressor life. Depending upon the options selected, the
damper responds to the enthalpy of the outdoor air.
On a call for cooling from a space thermostat, it operates as follows:
When the enthalpy of the outdoor air is below the set point, the outdoor air
damper is proportionally open (and return air damper is proportionally closed)
to maintain between 50°F and 56°F (10°C to 13°C) at the mixed/discharge air
sensor. Integral pressure relief allows the indoor air to exit the shelter
through the air conditioner. When the enthalpy of the outdoor air is above the
set point, the outdoor air damper closes to its minimum position. A call for
cooling from the space thermostat brings on mechanical cooling. A built-in
adjustable minimum position potentiometer controls the amount of outdoor air
admitted to meet minimum ventilation requirements.
Optional Controls & Packages
Hard Start Kit
Used on single phase equipment to give the compressor higher starting torque
under low voltage conditions. Generally not recommended on units with scroll
compressors.
Protective Coating Packages
Typically only the non-economizer units are used in corrosive environments,
but the air conditioners with an economizer is also available with corrosion
protection. Two corrosion protection packages are offered- one for the
condenser section (the Coastal Environmental package) and the other for the
entire unit (the Coat-All Package).
The Coastal Environmental Package includes:
- Corrosion resistant fasteners
- Sealed or partially sealed condenser fan motor
- Protective coating applied to all exposed internal copper and metal in the condenser section
- Protective coating on the condenser coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment) technology.
The Coat all Package includes all of the above, plus:
- Protective coating on the evaporator coil (Luvata Insitu®) contains ES2 (embedded stainless steel pigment) technology
- Protective coating on exterior and interior components and sheet metal. (Note: the internal sheet metal which is insulated, bottom outside panel, and the internal control box are not coated)
Hot Gas Bypass (Non-Economizer Models Only)
Used in specialty applications; i.e., Magnetic Resonance Imaging (MRI)
buildings, to prevent magnetic voltage disturbance caused by compressor
cycling. Two hot gas bypass option packages are available to allow operation
to 20°F (-7°C) or minus 20°F (-29°C). Please refer to Hot Gas Bypass
Application Bulletin for details.
Electric Reheat Dehumidification
A humidity controller allows electric heat and cooling to operate
simultaneously. Eubank® air conditioners equipped with the dehumidification
option allow the indoor humidity of the controlled environment to be
maintained at or below a certain humidity set point. These units do not have
the ability to add humidity to the building.
IMPORTANT
The electrical wire and breaker or fuses must be sized for simultaneous
operation of the electric heater and the air conditioner. Refer to the data
sticker on the unit or the appropriate Air Conditioner Product Data Sheet for
the sizing information. Dehumidification is achieved by operating mechanical
cooling in conjunction with electric reheat. The strip heat is sized
approximately to the sensible capacity of the total tonnage of the machine
(i.e., on a 24,000 BTU unit the strip heat is sized at approximately 20,000
BTU). Because the strip heat is sized to the approximate sensible cooling
capacity, only selected models are available.
Operation:
When the humidity rises above the set point on the humidity controller both
mechanical cooling and electric reheat operate to temper the air and lower the
humidity. If the temperature in the controlled environment rises above the set
point of the thermostat and the unit is operating in the dehumidification
mode, the call for cooling will override the call for dehumidification and the
strip heat is disengaged until the thermostat is satisfied. This assures the
environment temperature is maintained as first priority and humidity control
is second. In applications where a shelter has redundant air conditioning
units and is controlled by a lead lag controller (CommStat Touch, CommStat 4,
CommStat 3 HVAC Controller), most times the dehumidification option is only
necessary on one of the two units. It is possible for one unit to be operating
in the cooling mode while the unit with dehumidification is operating at the
same time. If the cooling unit does not maintain the shelter temperature set
point, the unit with dehumidification will go into the cooling mode. It does
not matter whether the unit with dehumidification is the lead or lag unit.
Three Phase Voltage Monitor
Continuously measures the voltage of each of the three phases. The monitor
separately senses low and high voltage, voltage unbalance including phase loss
and phase reversal. An LED indicator glows when all voltages are acceptable.
Automatically resets when voltages and phases are within operating tolerances.
Not required on 1ø units.
Dirty Filter Indicator
A diaphragm type of indicator measures the air pressure on either side of the
filter and when the pressure drops below the set point, a red LED is
illuminated. The set point is adjustable.
Protective Coil Coatings
Either the condenser or evaporator coil can be coated, however, coating of the
evaporator coil is not common. For harsh conditions, e.g., power plants, paper
mills or sites were the unit will be exposed to salt water, the condenser coil
should be coated. Note: Cooling capacity may be reduced by up to 5% on units
with coated coils.
Thermal Expansion Valve
Available on all Eubank air conditioners. Improves performance in hot ambient
temperatures.
High Filtration
Selected units are built with larger blowers/motors for use with higher
efficiency filters with MERV ratings of 11, 13 and 14 when tested to ASHRAE
52.2. Units with economizers have a pre-filter on the outside air.
Lockable Disconnect Access Cover Plate
The access plate to the service disconnect switch can be equipped with a
lockable cover.
Cold Climate Kit
Controls and components which allow the units to operate in extremely cold
temperatures. The kit includes a suction line accumulator, thermal expansion
valve (TXV), crankcase heater, hard start kit, and an outdoor thermostat and
fan cycle switch. The fan cycle control is standard on all Eubank air
conditioners and operates based upon the liquid line pressure. The outside
thermostat opens whenever the outside temperature is below 50°F (10°C) and
closes when the outside temperature is 50°F (10°C) or higher. Whenever the
temperature is below 50°F (10°C), the fan cycle switch is in the circuit; when
temperatures are 50°F (10°C) or higher, the fan cycle switch is not in the
circuit. The outdoor thermostat is used with a TXV to prevent excessive
cycling or “hunting” of the TXV.
Desert Duty
Controls and components which allow the units to operate in very hot ambients
(131°F/55°C). Includes a thermal expansion valve, a sealed condenser fan motor
and a sealed control box. A closed loop design on non-economizer units insures
that no outside air is introduced into the shelter.
Cabinet Color and Material
Eubank air conditioners are available in three different cabinet colors -the
standard Marvair beige, white and gray. The standard cabinet’s sides, top and
front panels are constructed of 20 gauge painted steel. Contact your Eubank
representative for color chips. The cabinet can also be constructed of type
316 stainless steel. Two stainless steel cabinet constructions are available-
the complete cabinet, including most internal sheet metal or only the exterior
sheet metal
Electrical Operation
The compressor and condenser fan are energized with a contactor controlled by
a 24 VAC pilot signal. Some compressors incorporate an internal PTC crankcase
heater that functions as long as primary power is available. The heater drives
liquid refrigerant from the crankcase and prevents loss of lubrication caused
by oil dilution. Power must be applied to the unit for 24 hours before
starting the compressor. The condenser (outside fan) motor is energized by the
same contactor. However, the motor is cycled on and off by the low ambient
control (see low ambient control 1.6). The indoor evaporator fan motor is
controlled by the fan purge on the electronic control board.
Typical Electrical Schematic – Non-Economizer)
Typical Electrical Schematic – w/Economizer
Typical Electrical Schematic – w/Economizer (Alternate Construction)
Typical Electrical Schematic – w/Economizer (Alternate Construction)
Typical Electrical Schematic – w/Economizer (Alternate Construction)
Electronic Control Board
Introduction
WARNING
Failure to observe the instructions contained in this document may result in
personal injury and/or property damage and may void the warranty. Read this
manual before installing, replacing or using this product.
Eubank’s proprietary Printed Circuit Board (PCB) sets the standard for the
industry in flexibility, reliability and performance. This UL certified
component is engineered to optimize Heating, Cooling and Dehumidification
operation while communicating valuable information to the end user. Special
features include 2-Stage operation with varying speed control to optimize
latent and sensible capacity, built in remote communication (Modbus) for
monitoring and/or control, optimized head pressure control and configurable
menu options for various operations and control. The Eubank PCB comes equipped
with seven segment display to annunciate faults, which drastically reduces
troubleshooting time and system downtime. Lockout contacts are also provided
along with the alarms being transferred via Modbus. This chapter provides the
necessary information for installing and operating the Eubank PCB. The diagram
below identifies the inputs, outputs and connections for the Eubank PCB. See
I/O table.
Item | Description |
---|---|
1 | Economizer Actuator Output 2-10 VDC |
2 | Outdoor Motor Control Output 0-10 VDC or PWM |
3 | Indoor Motor Control Output 0-10 VDC or PWM |
4 | Enthalpy Sensor Signal Input 4-20mA |
5 | Outdoor Sensor Signal 10K NTC (Heat Pumps) / Dry Bulb Sensor Signal |
Input 10K NTC (Systems Equipped with Dry Bulb Economizer)
6| Supply Air Sensor Signal Input 10K NTC (Systems Equipped with
Economizer)
7| Defrost Sensor Signal Input 10k NTC (Heat Pumps Only)
8| Head Pressure Control Sensor Signal 10k NTC (ECM Motors)
9| Control Board Menu/Fault Display
10| Menu/Up/Down Selection Buttons
11| Modbus RJ11 Communications Ports
12| Low Pressure / Freeze Sensor Signal Input 10k NTC
13| High Pressure Switch Input (Normally Closed)
14| Thermostat Inputs/Alarm And Status Terminals
15| 24 VAC To Power Board (18 VAC To 30 VAC)
16| Indoor Blower Output 24 VAC (PSC Motors)
17| Reheat Output 24 VAC (Hot Gas Or Electric Reheat Dehumidification)
18| Reversing Valve Output 24 VAC (Heat Pumps Only)
19| Electric Heat Output 24 VAC
20| Outdoor Fan Output 24 VAC (PSC Motors)
21| Compressor 1/1st Stage Output 24 VAC (Single Stage Compressor)
22| Compressor 2/2nd Stage Output 24 VAC (Dual Compressor System 2nd
Compressor) (Single Compressor 2nd Stage)
23| Control Board Power Indicator LED
Installation and Replacement
The PCB is factory installed. To install a replacement PCB, use the six
mounting holes along with the appropriate screw size to firmly secure the
board to the control box. After this is achieved, follow the wiring diagram
and menu configuration for the respective system for appropriate operation.
Ensure that the terminals used do not make any unwanted electrical connection
(via strands etc.) with any other terminals. Please allow a 1” creepage
distance between the board and all other adjacent electrical components.
PCB Details and Information
The PCB is equipped with an on board seven-segment display (Item #9) for
configuring various settings and displaying faults. During normal operation
the display remains off unless the configuration menu is accessed or a fault
has occurred. Faults will be annunciated on the display as shown below:
Display | Displayed Faults |
---|---|
AS- F | Supply Air Sensor Fault (Sensor Disconnected Or Faulty) If |
Equipped
DB- F| Dry Bulb / Outdoor Sensor Fault (Sensor Disconnected Or
Faulty) If Equipped
DS- F| Defrost Sensor Fault (Sensor Disconnected Or Faulty) Heat
Pumps Only
ES-F| Enthalpy Sensor Fault (Sensor Disconnected Or Faulty) If Equipped
LP-1| Low Pressure Lockout Compressor Circuit 1
LP-2| Low Pressure Lockout Compressor Circuit 2
HP- 1| High Pressure Lockout Compressor Circuit 1
HP- 2| High Pressure Lockout Compressor Circuit 2
03| Low Voltage “Brownout” 16VAC or Less for 10 Minutes
Programming Menu Configuration
- To Enter Programming Mode:
- Press and hold the Menu button for 5 seconds until P-01 is displayed.
- While in Programming Mode main menu:
- Press the Menu button to enter the displayed parameter menu.
- Press the Up/Down buttons to adjust the current parameter number.
- The current parameter number will be displayed seven segments alternating showing “P-” and the number every 0.5s.
- While in parameter menu:
- The current parameter selection will be displayed seven segments.
- Press the Menu button to save the current parameter selection return to the programming main menu.
- Press the Up/Down buttons to adjust the current parameter selection.
- To exit programming mode, press and hold the Mode and Up buttons while in the programming main menu.
- Press and hold the Menu button for 5 seconds.
- Note: The control will automatically exit the programming mode after 2 minutes with no activity.
Note: 100 will be displayed by alternating between “1” and “00” every 0.5s.
Configuration Menu
Menu Setting| Name| Default| Selections| General
Description
1| AC/HP Select| AC| AC, HP| HP = Heat Pump Unit, AC = AC Unit
2| IBM Select| P| P, dC| P = PWM, dC = 0-10V
3| FAN PURGE| 90| N, 10-90| Indoor Blower off delay in seconds
4| IBM Y1 Set| 80| 40-100| “G” Fan only and “Y1” 1st Stage Cooling
Indoor Blower Speed Setting
5| IBM Y2 Set| 100| 40-100| “Y2” 2nd Stage Cooling Indoor Blower Speed
Setting
6| OFM Select| P| P, dC| P = PWM, dC = 0-10V
7| OFM Set| 80| 65-100| Outdoor Fan Motor Max Speed setting
8| Defrost Timer| 30| 30, 60, 90| Defrost cycle timer in minutes
9| EHDD select| Y| Y, n| CAN ONLY BE “Y” IF SCKT IS “N”
10| SCKT select| n| Y, n| SCKT= Y OVERRIDES EHDD
11| ODS set| 50| 0-70| Outdoor Sensor for HP or Econo. Dry Bulb Setpoint
12| ECONO select| n| Y, n| n = Disabled (No Econo.), Y = Enabled
(W/Econo.)
13| Sensor Type| EN| EN or DB| Economizer sensor type selection EN=
Enthalpy, DB = Dry Bulb
14| ECONO set| d| A-E| Selections A=73F, B=70F, C= 67F, D =63F E= 55F
all @ 50%RH (Only available if EN sensor type is selected)
15| MIN POS| 20| 20-100| Sets the damper position for Minimum Open
16| W2 speed| 100| 70-100| Sets the Indoor Blower Speed for Electric
Heat
17| Dehum speed| 80| 60-100| Sets the Indoor Blower Speed for
Dehumidification
18| DS calibration| 0| -18| Defrost Sensor Calibration
19| SAS calibration| 0| -18| Supply Air Sensor Calibration
20| T’STAT Select| H| H, C| H = hardwired 24V Tstat, C = communicating
Tstat
21| Modbus ID| 1| 36161| Sets the Modbus ID for the unit
22| Modbus BAUD rate| 19| 9.6, 19| Available Baud Rates 9.6 = 9600, 19 =
19200
23| Modbus timeout| 25| 21916| Communications Timeout in minutes
24| Test| n| Y, n| When set to “Y” all timers are reduced for testing
25| SW version number| N/A| N/A| Displays the current version software
Configuration Menu Details
-
AC/HP Select: This setting allows the PCB to be configured for AC (air-conditioner) or HP (heat-pump). The system type is configured at the factory during production testing for the appropriate system type. The default system type is AC.
-
IBM Select: This setting allows the IBM (Indoor Blower) control signal to be configured for PWM or 0-10vdc control. The default control output signal is PWM.
-
Fan Purge: This setting allows the delay off time of the indoor blower once the call for the indoor blower has been removed. The selections are N (no delay) or 10-90 seconds. After the default time of 90 seconds the indoor blower will shut off. Selecting the N (no delay) will allow the Indoor blower to shut off immediately after any request has been removed.
-
IBM Y1 Set: This is an independent setting for the speed at which the Indoor blower will operate upon a request for Y1 (1st stage cooling) via Digital Input or Modbus. The default setting for the IBM Y1 Set is 80% of maximum speed. The speed may be adjusted from 40-100% in 1%increments to meet desired airflow requirements.
Note: Adjusting the speed too low will result in coil freezing. -
IBM Y2 Set: This is an independent setting for the speed at which the Indoor blower will operate upon a request for Y2 (2nd stage cooling) via Digital Input or Modbus. The default setting for the IBM Y1 Set is 100% of maximum speed. The speed may be adjusted from 40-100% in 1%increments to meet desired airflow requirements.
Note: Adjusting the speed too low will result in coil freezing, low- pressure or high-pressure lockout. -
OFM Select: This setting allows the IBM (Indoor Blower) control signal to be configured for PWM or 0-10vdc control. The default control output signal is PWM.
-
OFM Set: This is an independent setting for the max speed at which the Outdoor fan will operate. The default setting for the OFM Set is 80% of maximum speed. The speed may be adjusted from 65- 100% in 1% increments to meet desired airflow requirements.
Note: Adjusting the speed too low will result in coil freezing, low- pressure or high-pressure lockout. -
Defrost Timer: The defrost timer only applies to Heat-pump systems (when setting 1 is set to HP). This is the accumulation timer used to monitor for heat-pump defrost control. The selections for defrost timing is 30, 60 and 90 minutes. The defrost timer accumulates the compressor runtime in the heat-pump mode and monitors the defrost sensor for freezing conditions to initiate a defrost cycle at the selected defrost timing interval. The default defrost time is 30 minutes.
-
EHDD Set: The Electric heat during defrost setting allows the electric heat to operate when a defrost cycle is being performed in heat-pump mode. The selections for the EHDD Set are Y (yes) or N (no). When set to N (no) the electric heat will not operate automatically during a defrost cycle in heat-pump mode. When the EHDD Set is set to Y (yes, Default) the electric heat will operate upon each defrost cycle in the heat-pump mode.
Note: EHDD and SCKT cannot both be set to the Y (yes) selection at the same time. SCKT takes priority over EHDD. -
SCKT Set: The SCKT setting is used to prevent simultaneous operation of the electric heat and compressor. The selections for the SCKT Set are Y (yes) or N (no). When set to N (no, Default) the electric heat will be allowed to operate with the compressor in heat-pump mode upon a call for W2 (auxiliary / emergency heat). When the SCKT Set is set to Y (yes) the electric heat will not be allowed to operate with the compressor in the heat-pump mode. When set to Y (yes) and upon a request for W2 (auxiliary / emergency heat) the compressor will shut off and the electric heat will operate.
Note: SCKT and EHDD cannot both be set to the Y (yes) selection at the same time. SCKT takes priority over EHDD. -
ODS Set: The ODS Set is used to set the Outdoor Sensor temperature for Heat-pump systems. When the system type is configured for Heat-pump (when setting 1 is set to HP), the ODS Set allows the outdoor sensor to be used to govern when electric heat is allowed to operate. When the outdoor temperature is below the ODS setpoint, the electric heat will be allowed to operate. The adjustable range is 0F-70F in 1F increments with a default setpoint of 50F.
-
ECONO Select: The ECONO Select is used to select whether the system has an economizer system installed or not. When set to the Y (yes) selection the system will include the economizer cooling algorithm within its sequence of operation and utilize the economizer package when conditions are favorable for economizer cooling. When set to the N (no) selection the system will only utilize the compressor for cooling operation. This setting is configured at the factory during production testing for the appropriate system type.
Note: When ECONO Set is set to Y (yes) the system must have an Enthalpy or Dry Bulb and Supply Air sensor connected and properly selected in setting 13 in order to operate in economizer cooling. The system will default to compressor cooling if any sensor becomes disconnected or faulty. Changing the ECONO Select to N (no) will disable economizer operation and the economizer function will be ignored. -
Sensor Type: This setting is used for selecting the type of economizer sensor used EN (Enthalpy) or DB (Dry Bulb). The appropriate sensor must be connected and selected for economizer operation. This setting is configured at the factory during production testing for the appropriate sensor type.
-
ECONO Set: This setting is used to set the economizer setpoint at which the economizer is allowed to operate for cooling. When setting 13 is set for EN (Enthalpy), the selections are A= 73F, B=70F, C=67F, D=63F and E=55F all at 50% relative humidity. The A – E selections will only be available when setting 13 is set to EN (Enthalpy). When setting 13 is set for DB (Dry Bulb), the selection is from 20F to 105F in 1F increments. The 20F-105F range will only be available when setting 13 is set to DB (Dry Bulb).
-
MIN POS: The MIN POS setting is for setting the minimum position of the economizer or motorized damper. When set above 20 (2vdc) the damper will remain open to the selected position at all times, hence minimum position. The adjustable range is from 20 (2vdc) to 100 (10vdc) in 1vdc increments.
-
W2 Speed: This is an independent setting for the speed at which the Indoor blower will operate upon a request for W2 (Electric heat) via Digital Input or Modbus. The default setting for the W2 speed is 100% of maximum speed. The speed may be adjusted from 70-100% in 1% increments to meet desired airflow requirements.
Note: Adjusting the speed too low will result in increased supply air temperatures in electric heat mode. -
Dehum Speed: This is an independent setting for the speed at which the Indoor blower will operate upon a request for HUM (Dehumidification) via Digital Input or Modbus. The default setting for the Dehum speed is 80% of maximum speed. The speed may be adjusted from 60-100% in 1% increments to meet desired airflow requirements.
-
DS Calibration: This setting is used to calibrate the defrost sensor from 0 to -18F.
-
SAS Calibration: This setting is used to calibrate the supply air sensor from 0 to -18F.
-
T’STAT Select: The thermostat type can be selected with this setting for an option of H= Hardwired 24vac Thermostat or C = Communicating Thermostat via Modbus. The default setting is H= Hardwired 24vac Thermostat.
-
Modbus ID: This setting allows the Modbus ID to be entered for Modbus communications for the unit. The range for the Modbus ID is 1 – 36161 the default Modbus ID is 1.
-
Modbus Baud Rate : This setting allows the Modbus Baud Rate to be entered for Modbus communications. The available Baud Rates are 9.6= 9600 and 19= 19200. The default Modbus Baud Rate is 19 = 19200.
-
Modbus Timeout: This is the setting for the Modbus communications timeout in minutes. The range of communications timeout is from 25 minutes to 21916 minutes. The default communications timeout is 25 minutes.
-
Test: The Test feature has two options Y= Yes or N= No. When this setting is set to Y=Yes, all circuit timers are reduced to expedite testing for various system operations. When set to N=No, all circuit timers are used in their default configuration and normal operation.
-
Software Version Number: The software version of the 92589-control board will be displayed on the seven-segment display. This is for informational purposes only.
Operation
Power
The Eubank PCB requires 24 VAC to operate. When the board is sufficiently
powered, the “PWR” status light on the PCB illuminates “Green.” When the power
supply voltage is 16vac or less for 10 seconds the control board will de-
energize all outputs. This is considered a voltage brownout (low voltage)
condition and the display of the control board will show “03” as an indicator
of brownout (low voltage). When the voltage rises back to 17 VAC, the control
board will allow the system to operate.
Note: The nominal power supply for the control board is 24 VAC and this
voltage should be confirmed during startup to assure normal operation.
Communication
The Eubank PCB comes equipped the Modbus communications standard. There are 2
adjacent RJ11 Modbus communication ports connected in parallel. That is, both
ports transmit the same information. The board allows you to set the Baud Rate
at 9600 bits per second or 19200 bits per second. The board also allows the
Modbus ID to be selected in the configuration menu with the available range
from 1 to 36161. The default Modbus ID is 1. See section 2.1 for reference.
Sequence of Operation **
**
IMPORTANT
All equipment should go through the recommended commissioning/start up
sequence to ensure safety and system reliability. This document is only valid
if the system is used as intended.
This section defines the manner and method of control of the HVAC system. It
will cover the following operations and protections.
Indoor Blower Operation
- G – Indoor Blower Only
- Y1 – Indoor Blower Operation
- Y2 – Indoor Blower Operation
- W2 – Indoor Blower Operation
- HUM – Indoor Blower Operation
Cooling Operation AC / HP
- Mechanical Cooling (AC systems)
- Partial Capacity
- Full Capacity
- Mechanical Cooling (HP systems)
- Partial Capacity
- Full Capacity
Economizer Operation
- Enthalpy Sensor and Operation
- Dry Bulb Sensor and Operation
- Supply Air Sensor
- Minimum Position
Heating Operation AC / HP
- Electric Heat (AC systems)
- Heat Pump Heating Operation
- Defrost Operation (Heat Pumps)
- Electric Heat / Outdoor Sensor / SCKT / EHDD (Heat Pumps)
Dehumidification Operation AC / HP
- Hot Gas Reheat 5.2 Electric Reheat
Refrigeration Protection
- High Pressure lockout
- Low Pressure Lockout / Freeze Protection
- Anti Short Cycle
Additional Features
- Modulating Head pressure Control (ECM Outdoor Motors)
- Emergency Ventilation
- Forced Cooling
- Modbus Communications
- Low Voltage (Brownout)
Smoke / Fire Shutdown
- System Shutdown Contact Wiring
Note: Equipment, devices and necessary system components are specified in
the respective section.
Note:
- All inputs on the control board go through a 5 seconds Time-On Delay to prevent nuisance request. Compressor Outputs go through 5 seconds staggered Time On delay to prevent nuisance tripping of breaker due to the inrush associated with these large inductive loads.
- Normal Operating Mode describes a mode in which there are no active faults which would interrupt the operation of the system.
Indoor Blower Operation
The speed at which the indoor blower will operate is based on the discrete
operational inputs that have 24vac applied. These inputs are listed below.
- G Input – A request for Fan Only (independent G-signal via Digital input or Modbus), results in the indoor motor turning “ON” and operating at the “Y2” (BY DEFAULT) motor speed (Only Applicable for EC motors).
- Y1 Input – A request for Y1 (independent Y1-signal via Digital input or Modbus), results in the indoor motor turning “ON” and operating at the “Y1” motor speed (Only Applicable for EC motors).
- Y2 Input – A request for Y2 (independent Y2-signal via Digital input or Modbus), results in the indoor motor turning “ON” and operating at the “Y2” motor speed (Only Applicable for EC motors).
- W2 Input – A request for W2 (independent W2-signal via Digital input or Modbus), results in the indoor motor turning “ON” and operating at the “W2” motor speed (Only Applicable for EC motors).
- HUM Input – A request for HUM (independent HUM-signal via Digital input or Modbus), results in the indoor motor turning “ON” and operating at the “HUM” motor speed (Only Applicable for EC motors).
When there is a request for Indoor Fan (G-input High) along with a request for cooling, heating or dehumidification, the G-Input becomes lowest priority. This means that in any combination involving the G-input, the speed associated to Fan Only will never take precedence.
The priority list from Highest to Lowest goes as follows:
- Y2 – Request
- Y1 – Request
- W2 – Request
- HUM – Request
- G – Request
Note: The priority list above also describes the operation that takes
precedence in the event that there is a request for all operations or a
combination of operations. The controller will NOT energize the compressor
outputs and the heater output simultaneously if configured for AC. The
controller WILL energize the compressor outputs and the heater output
simultaneously if configured for HP.
The speed at which the Indoor Fan Operates during Stage 1 (Y1) and Stage 2
(Y2) Cooling Request can be set directly at the board using the configuration
menu settings 4 and 5. All requests are interlocked with the Indoor Fan and
will run the Fan at the respective speed associated with the operation. This
means that a lone call for Stage 1 (Y1) Cooling will automatically run the
Indoor Fan at Stage 1 (Y1) Cooling Speed even without a request for Indoor
Fan. This holds true for all request.
Cooling Operation
AC Systems Request | Active Input | Active Output |
---|---|---|
Stage 1 Cooling (Fixed Compressor) | Y1 | CC1 (Partial Capacity) |
Stage 1 Cooling (2 Fixed Compressors) | Y1 or Y2 | CC1 or CC2 Respectively |
(Partial Capacity)
Stage 1 Cooling (1 Staged Compressor)| Y1| CC1 (Partial Capacity)
Stage 2 Cooling (2 Fixed Compressors)| Y1 + Y2| CC1 + CC2 (Full Capacity)
Stage 2 Cooling (2 Staged Compressors)| Y1 + Y2| CC1 + CC2 (Full Capacity)
Mechanical Cooling (AC systems) – This section will describe the sequence
of operation which takes place during Direct Expansion (DX) cooling from a
control standpoint.
Note: The system type must be configured for “AC” operation in setting 1
of the configuration menu of the control board for proper AC system operation.
This system type is selected at the factory and there’s no need to change this
setting.
Y1 Cooling (Partial Capacity 1st Stage) – In normal operating mode, a
request for “Stage1 Cooling” Y1-signal via Digital input or Modbus),
energizes Compressor 1 Relay Output (CC1) on the PCB. The controller provides
a continuous control signal associated to the Indoor Fan Motor, that is
proportional to the “Y1” speed setting on the board or via Modbus. It also
outputs a request dependent (based on FCC IN) control signal for the Outdoor
Fan Motor (Only applicable to ECM motors). In Stage 1 Cooling operation, the
compressor operates at partial capacity and the indoor fan remains on
continuously but the outdoor fan modulates based on liquid line temperature.
The Fan Cycle Control Sensor (Low Ambient Control Sensor) monitors the liquid
line to maintain a 90F liquid line temperature. When the liquid line
temperature is below 80F the outdoor fan will shut off. A liquid line
temperature above 115F will force the outdoor fan to operate at the maximum
speed set on the control board for setting 7 in the configuration menu. The
outdoor fan will speed up and slow down between liquid line temperature of 80F
and 115F. Systems with (PSC Outdoor Motors) utilizes a Fan Cycle Switch which
closes at 400 PSIG to energize the OFR (outdoor fan relay) to start the
outdoor fan which runs until the switch reopens (at 290 PSIG). These outputs
function as described until the Cooling setpoint is satisfied. This is
considered as ON/OFF fan cycle control and the PSC motor will not modulate.
Note: Single Stage compressors operate at full capacity upon a request
for Y1.
Y1 and Y2 Cooling (Full Capacity 2nd Stage) – If the space temperature
continues to increase pass the defined differential, Stage 2 Cooling
(Y2-input) is energized. Under normal operation, this energizes the Compressor
2 Output (CC2). The Indoor Fan motor, will operate at “Y2” speed instead of
“Y1” speed since Y2 has higher priority. These outputs remain energized until
the cooling setpoint is satisfied. Once the setpoint is satisfied, the
Compressor and the Outdoor fan outputs are de-energized. The Indoor motor
continues to run based on the fan purge timer setpoint (default 90 seconds)
selected in setting 3 of the configuration menu of the control board.
Note: 2 Stage compressors require a request for Y2 to operate at full
capacity in Cooling operation. All Air-conditioners and Heat Pump systems with
2 stage compressors are allowed 2 stage cooling operation.
Mechanical Cooling (HP systems) – This section will describe the sequence
of operation which takes place during Direct Expansion (DX) cooling from a
control standpoint. The reversing valve (O Input) must be energized for
Cooling operation on Heat Pump systems.
Note: The system type must be configured for “HP” operation in setting 1
of the configuration menu of the control board for proper HP system operation.
This system type is selected at the factory and there’s no need to change this
setting.
Y1+ O Cooling (Partial Capacity 1st Stage) – In normal operating mode, a
request for “Stage1 Cooling” Y1 + O signal via Digital input or Modbus),
energizes the Reversing Valve Output (RV) and Compressor 1 Relay Output (CC1)
on the PCB. The controller provides a continuous control signal associated to
the Indoor Fan Motor, that is proportional to the “Y1” speed setting on the
board or via Modbus. It also outputs a request dependent (based on FCC IN)
control signal for the Outdoor Fan Motor (Only applicable to ECM motors). In
Stage 1 Cooling operation, the compressor operates at partial capacity and the
indoor fan remains on continuously but the outdoor fan modulates based on
liquid line temperature. The Fan Cycle Control Sensor (Low Ambient Control
Sensor) monitors the liquid line to maintain a 90F liquid line temperature.
When the liquid line temperature is below 80F the outdoor fan will shut off. A
liquid line temperature above 115F will force the outdoor fan to operate at
the maximum speed set on the control board for setting 7 in the configuration
menu. The outdoor fan will speed up and slow down between liquid line
temperature of 80F and 115F. Systems with (PSC Outdoor Motors) utilizes a Fan
Cycle Switch which closes at 400 PSIG to energize the OFR (outdoor fan relay)
to start the outdoor fan which runs until the switch reopens (at 290 PSIG).
These outputs function as described until the Cooling setpoint is satisfied.
This is considered as ON/OFF fan cycle control and the PSC motor will not
modulate.
Note: Single Stage compressors operate at full capacity upon a request
for Y1.
Y1 + Y2 + O Cooling (Full Capacity 2nd Stage) – If the space temperature
continues to increase pass the defined differential, Stage 2 Cooling (Y1+Y2+O
input) is energized. Under normal operation, this energizes the Compressor 2
Output (CC2). The Indoor Fan motor, will operate at “Y2” speed instead of “Y1”
speed since Y2 has higher priority. These outputs remain energized until the
cooling setpoint is satisfied. Once the setpoint is satisfied, the Compressor
and the Outdoor fan outputs are de-energized. The Indoor motor continues to
run based on the fan purge timer setpoint (default 90 seconds) selected in
setting 3 of the configuration menu of the control board.
Note: 2 Stage compressors require a request for Y2 to operate at full
capacity in Cooling operation. All Air-conditioners and Heat Pump systems with
2 stage compressors are allowed 2 stage cooling operation.
- With staged compressors, a CC2 output without a CC1 output will neither result in partial capacity nor full capacity. Only CC1 output can achieve partial capacity. Both CC1 and CC2 outputs are required to achieve full capacity.
Economizer Operation (If Equipped)
Damper Actuator
The damper actuator is a 24V motor that modulates the position of the damper
blade. It is capable of driving a full 90 degrees within 90 seconds. The
assembly has a spring return to close the damper during power outage.
Enthalpy Sensor and Operation – The enthalpy sensor responds to the total
heat content of the outdoor air to provide the changeover to outside air for
free cooling. The control board must be configured for proper operation of the
economizer by selecting Y= Yes in the configuration menu setting 12. The
sensor type must be selected in setting 13 for EN=Enthalpy. The desired
changeover setpoint must be selected in setting 14 (default D=63F@50% rh).
Example of Enthalpy Sensor and Enthalpy curve is shown below.
Note: Selecting N=No in configuration setting 12 will disable economizer
operation.
DANGER
Sever hazard. The economizer contains moving parts capable of causing serious
injury or death. Disconnect power before removing the covering panel.
Enthalpy Setpoint is Setting 14 in control board configuration menu.
Options
A= 73ºF
B= 70ºF
C= 67ºF
D= 63ºF
E= 55ºF
All settings are @ 50%Rh
Enthalpy Sensor & Temperature Control Points
Enthalpy Operation
On a call for cooling from the wall-mounted thermostat, if outdoor conditions
are suitable, the sensor will open the damper and admit outside air (i.e.,
economizer free cooling). If the outdoor ambient is too hot or humid (enthalpy
sensor only), the sensor will place the actuator in the closed or minimum open
position and activate mechanical cooling. The compressor is locked-out during
the economizer cooling mode. The Supply Air sensor monitors the supply air of
the system in economizer mode to modulate the economizer damper to maintain a
55F supply air temperature. During the testing of the air conditioner at the
factory, the control board has been configured for the sensor type used in the
system. There should be no need to change the sensor configuration. If an
enthalpy sensor is being used, setting 13 of the control board configuration
menu will be set for EN= Enthalpy. A disconnected or faulty enthalpy sensor is
annunciated on the control board display as “ES-F”. Economizer operation is
only allowed in Cooling Mode.
Note: A call for Y2 or FC Inputs or a faulty or disconnected enthalpy
sensor will override the economizer operation and force the compressor to
operate.
Dry Bulb Sensor and Operation – The dry bulb sensor only responds to the
dry bulb temperature of the outside air and ignores the humidity. The sensor
is a 10K NTC sensor probe. The factory setting is 63°F. This setpoint can be
adjusted in 1F increments from 20F to 105F in the control board configuration
menu setting 14. Example of the dry bulb sensor is shown below.
Note: Selecting N=No in configuration setting 12 will disable economizer
operation.
Dry Bulb Sensor
On a call for cooling from the wall-mounted thermostat, if outdoor conditions
are suitable, the sensor will open the damper and admit outside air (i.e.,
economizer free cooling). If the outdoor ambient is too hot (dry bulb sensor
only), the sensor will place the actuator in the closed or minimum open
position and activate mechanical cooling. The compressor is locked-out during
the economizer cooling mode. The Supply Air sensor monitors the supply air of
the system in economizer mode to modulate the economizer damper to maintain a
55F supply air temperature. During the testing of the air conditioner at the
factory, the control board has been configured for the sensor type used in the
system. There should be no need to change the sensor configuration. If a dry
bulb sensor is being used, setting 13 of the control board configuration menu
will be set for DB=Dry Bulb. A disconnected or faulty dry bulb sensor is
annunciated on the control board display as “db-F”. Economizer operation is
only allowed in Cooling Mode.
Note: A call for Y2 or FC Inputs or a faulty or disconnected dry bulb
sensor will override the economizer operation and force the compressor to
operate.
Supply Air Sensor – The supply air sensor is a 10K NTC sensor probe
mounted on a bracket in the supply air opening of the system. The probe senses
the air temperature entering the structure, and provides a signal to the
economizer controller for modulating the position of the damper. The default
supply air temperature is 55F in economizer cooling and is not adjustable. A
disconnected or faulty supply air sensor is annunciated on the control board
display as “AS-F”.
Note: A faulty or disconnected supply air sensor will override the
economizer operation and force the compressor to operate.
Minimum Position – The minimum position controls the amount of outside
air introduced in the building when not in economizer operation or to meet a
minimum outside air requirement to keep the damper open. This feature is only
applicable to systems with economizer or ventilation damper options. The
minimum position can be adjusted in the control board configuration menu with
setting 15. The setpoint adjustments are from 20 (2vdc) to 100 (10vdc) in 1vdc
increments. This is an independent adjustment and can be set to drive the
ventilation damper open to any position from closed to fully opened. A
selection of 20 (2vdc) is the same as being set to OFF or fully closed.
Heating Operation
Electric Heat (AC Systems with Electric Heat) – When there is a request for
“Electric Heat” (W2-signal via Digital input or Modbus), the system will run
the Indoor Motor for 10 seconds prior to energizing the Heater Output. The
Indoor Motor will operate at the “W2” speed setting on the board or via
Modbus. Once the Heater output is energized, the Heater comes on at full
capacity (no staging). The Heater will remain on until the Heating setpoint is
satisfied and the request is dropped. Once the heating setpoint is satisfied,
the Indoor motor continues to run based on the fan purge timer setpoint
(default 90 seconds) selected in setting 3 of the configuration menu of the
control board.
Note: A request for Cooling and Heating at the same time is not allowed
and control board will not allow the electric heat to operate.
Heat Pump Heating Operation – This section will describe the sequence of
operation which takes place during Direct Expansion (DX) heating from a
control standpoint. The reversing valve (O Input) must NOT be energized for
Heating operation on Heat Pump systems.
Note: The system type must be configured for “HP” operation in setting 1
of the configuration menu of the control board for proper HP system operation.
This system type is selected at the factory and there’s no need to change this
setting.
In normal operating mode, a request for “Heat Pump Heating” Y1 signal via
Digital input or Modbus), energizes the Compressor 1 and 2 Relay Output
(CC1+CC2) on the PCB. The controller provides a continuous control signal
associated to the Indoor Fan Motor, that is proportional to the “Y2” speed
setting on the board or via Modbus. The system is defaulted to operate at Full
capacity in heat pump heating mode. It also outputs a request for the Outdoor
Fan to operate at the max speed. In heat pump Heating operation, the
compressor operates at Full capacity and the indoor and outdoor fans remain on
continuously. The outdoor fan does not modulate in heat pump heat mode.
Defrost Operation (Heat Pump Systems Only) – The board has an integral
accumulation run timer that runs on every request for heat pump heating. The
system has a Defrost Sensor (DS) that monitors the outdoor coil circuit for
freezing conditions. If the defrost sensor registers a temperature of 32°F
while in the heat pump heating mode, it will initiate a defrost cycle based on
the time selected in the control board configuration menu setting 8. The
defrost time intervals selections are 30, 60 and 90 minutes and the factory
default setting is 30 minutes. If the defrost sensor is still calling for
defrost at the end of this delay, it will de-energize the outdoor fan,
energize the reversing valve through the RV terminal, and keep the compressor
energized. The defrost cycle will terminate on time or temperature. It will
have a maximum defrost run time of 10 minutes, however, if the defrost sensor
registers a temperature of 70°F or higher before the 10-minute maximum run
time, the defrost cycle will terminate. If the defrost cycle has not completed
(DS sensor above 70F) due the heating call being satisfied, the defrost cycle
will continue upon the next call for heat pump heating to complete the defrost
cycle. If freezing conditions are not present at the end of the defrost
interval timer, the system will not perform a defrost cycle.
Note: If the DS sensor is disconnected or faulty, the compressor will not
operate in heat pump heating mode and the control board display will
annunciate the fault as “DS-F”.
- If “Yes” has been selected for Electric Heat During Defrost (EHDD) and “No” selected for the SCKT, the electric heat (EH) output will be energized during a defrost cycle to supply heat while the coil defrosts. If the ODS is used, the electric heat will operate only if the outdoor temperature is below the ODS setpoint.
Electric Heat / Outdoor Sensor / SCKT / EHDD (Heat Pumps) – Electric Heat (HP systems with electric heat)– When there is a request for “Electric Heat” (W2-signal via Digital input or Modbus), the system will run the Indoor Motor for 10 seconds prior to energizing the Heater Output. The Indoor Motor will operate at the “W2” speed setting on the board or via Modbus. Once the Heater output is energized, the Heater comes on at full capacity (no staging). The Heater will remain on until the Heating setpoint is satisfied and the request is dropped. Once the heating setpoint is satisfied, the Indoor motor continues to run based on the fan purge timer setpoint (default 90 seconds) selected in setting 3 of the configuration menu of the control board. When the system is operating in Heap Pump mode the electric heat is considered as supplemental heat and will only be allowed under certain conditions due to additional features that may be used. These features include the Outdoor Sensor and SCKT (safety circuit). See ODS and SCKT for more details.
ODS – Outdoor Sensor (Heat-Pumps Only)
The outdoor sensor only responds to the temperature of the outside air. The
sensor is a 10K NTC sensor probe. The factory setting is 50°F. This setpoint
can be adjusted in 1F increments from 0F to 70F in the control board
configuration menu setting 11. If the optional Outdoor Sensor is used (Heat-
pump systems only). The electric heat will not operate upon a request for “W2”
unless the outdoor temperature is below the setpoint for the ODS setpoint. If
the sensor is not connected or faulty the electric heat will be allowed to
operate anytime a request for W2 is present.
Note: A request for Cooling and Electric Heat at the same time is not
allowed and the control board will not allow the electric heat to operate.
SCKT – Safety Circuit (Heat-Pumps Only)
The SCKT is a selectable menu option in the control board configuration menu
setting 10. The options for this feature are Y=Yes or N=No. When set to Y=Yes,
control board will prevent the compressor and electric heat from operating
simultaneously. In this case the compressor will shut off upon a request for
“W2” (Electric Heat). The compressor will remain off as long as the request
for W2 is active. Once the request for W2 satisfies the compressor will be
allowed to operate. The default setting for SCKT is N=No, the electric heat
and compressor will be allowed simultaneous operation in the heat pump heating
mode.
Note: If the ODS is used the electric heat will not operate unless the
outdoor temperature is below the ODS setpoint.
EHDD – Electric Heat During Defrost (Heat-Pumps Only)
The EHDD is a selectable menu option in the control board configuration menu
setting 9. The options for this feature are Y=Yes or N=No. When set to Y=Yes,
control board will force the electric heat to operate during a defrost cycle
unless SCKT is set to Y=Yes or the outdoor temperature is not below ODS (if
equipped) setpoint. The default setting for EHDD is Y=Yes.
Note: SCKT takes priority over ODS and EHDD.
Dehumidification Operation AC / HP
Hot Gas Reheat (if equipped) – When there is a request for
“Dehumidification” (HUM-signal via Digital input or Modbus), this will result
in the control board energizing the Indoor Fan (IBR), Compressor 1 (CC1),
Compressor 2 (CC2), Reversing Valve (RV) “heat pumps only” and the Reheat (RH)
relay outputs on the board. This forces the system to operate in the full
capacity cooling mode while energizing the reheat solenoid valve to allow hot
gas to be introduced into the supply air stream of the system for
dehumidification operation. The indoor fan motor will operate at the “Dehum”
speed setting on the board or via Modbus. The indoor fan remains on
continuously but the outdoor fan modulates based on liquid line temperature.
The Fan Cycle Control Sensor (Low Ambient Control Sensor) monitors the liquid
line to maintain a 90F liquid line temperature. When the liquid line
temperature is below 80F the outdoor fan will shut off. A liquid line
temperature above 115F will force the outdoor fan to operate at the maximum
speed set on the control board for setting 7 in the configuration menu. The
outdoor fan will speed up and slow down between liquid line temperature of 80F
and 115F. Systems with (PSC Outdoor Motors) utilizes a Fan Cycle Switch which
closes at 400 PSIG to energize the OFR (outdoor fan relay) to start the
outdoor fan which runs until the switch reopens (at 290 PSIG). These outputs
function as described until the Dehumidification setpoint is satisfied. This
is considered as ON/OFF fan cycle control and the PSC motor will not modulate.
Note: A request for Y1 or Y2 vis digital input or Modbus takes priority
over dehumidification operation and the hot gas reheat valve will de-energize.
Electric Reheat (if equipped) – When there is a request for
“Dehumidification” (HUM-signal via Digital input or Modbus), this will result
in the control board energizing the Indoor Fan (IBR), Compressor 1 (CC1),
Compressor 2 (CC2), Reversing Valve (RV) “heat pumps only” and the Reheat (RH)
relay outputs on the board. This forces the system to operate in the full
capacity cooling mode while energizing the electric heat to allow heat to be
introduced into the supply air stream of the system for dehumidification
operation. The indoor fan motor will operate at the “Dehum” speed setting on
the board or via Modbus. The indoor fan remains on continuously but the
outdoor fan modulates based on liquid line temperature. The Fan Cycle Control
Sensor (Low Ambient Control Sensor) monitors the liquid line to maintain a 90F
liquid line temperature. When the liquid line temperature is below 80F the
outdoor fan will shut off. A liquid line temperature above 115F will force the
outdoor fan to operate at the maximum speed set on the control board for
setting 7 in the configuration menu. The outdoor fan will speed up and slow
down between liquid line temperature of 80F and 115F. Systems with (PSC
Outdoor Motors) utilizes a Fan Cycle Switch which closes at 400 PSIG to
energize the OFR (outdoor fan relay) to start the outdoor fan which runs until
the switch reopens (at 290 PSIG). These outputs function as described until
the Dehumidification setpoint is satisfied. This is considered as ON/OFF fan
cycle control and the PSC motor will not modulate.
Note: A request for Y1 or Y2 vis digital input or Modbus takes priority
over dehumidification operation and the electric heat will de-energize.
Refrigeration Protection
-
High Pressure Lockout – This condition describes the abnormal rise in Head Pressure within system with an acceptable limit of 660 PSI (+/-20PSI). The fault will only be active when the High-Pressure Switch (Normally Closed) opens during a request for Cooling or Heat Pump Heating. The first time this fault condition occurs, the system cuts the compressor off WITHOUT locking out. Once the pressure normalizes (drops below 450 PSI), the system will resume operation if the cooling or heat pump heating call still exist. If this fault occurs a second time on the same Cooling or Heat pump heating request, the system locks out. Lockouts can be monitored using the control board display for the current fault. The fault for a high-pressure lockout will displayed as “HP-1” or “HP-2” followed by “F”. The faults can also be monitored via Modbus by reading the respective value based on the Modbus map that is provided. After this lockout condition is reached, the cooling/heat pump heating call must be cycled (on/off of respective request) or the system must be power cycled to clear the fault. For a 2-compressor system, each lockout is isolated to the respective circuit and will not interfere with the operation of the other circuit providing that the circuits operate independently. The system will continue to lockout until the problem is rectified.
-
Low Pressure Lockout / Freeze Protection – A10K Nominal NTC Thermistor is connected to the “LPS 1” and “LPS2” inputs of the control board for circuit 1 and circuit 2 respectively. The sensor is secured to the common suction line of the system to monitor the suction line temperature.
This condition describes the abnormal fall in Suction Line Temperature below 9ºF. This fault will only be active when the Low-Pressure Sensor detects suction line temperatures below 9ºF during a request for Cooling / Heat pump heating. The Low-Pressure Sensor is bypassed on the initial call for cooling for 3 minutes to allow low ambient start-up of the system. Once these 3 minutes have elapsed plus a 2-minute validation timer (5 minutes total), if the sensor remains below 9ºF, the system cuts the compressor off. The system will remain off for the defaulted 3-minute anti-short cycle time and then the system will restart the cooling / heat pump heating operation and the 3-minute bypass timer begins. Once these 3 minutes have elapsed plus a 2-minute validation timer (5 minutes total), if the sensor remains below 9ºF the system locks out. Lockouts can be monitored using the control board display for the current fault. The fault for a low-pressure lockout will displayed as “LP-1” or “LP-2” followed by “F”. The faults can also be monitored via Modbus by reading the respective value based on the Modbus map that is provided. After this lockout condition is reached, the cooling/heat pump heating call must be cycled (on/off of respective request) or the system must be power cycled to clear the fault. For a 2-compressor system, each lockout is isolated to the respective circuit and will not interfere with the operation of the other circuit providing that the circuits operate independently. The system will continue to lockout until the problem is rectified. -
Anti-Short Cycle – This is a built-in protection mechanism that increases the reliability of the compressor by protecting it from excessive short cycling. When the compressor goes off, due to any fault, emergency or if the cooling / heat pump heating setpoint is satisfied, a built-in 3-minute timer locks the compressor for that respective circuit out. This can be monitored and adjusted via Modbus by referencing the appropriate register. However, it can only be monitored at the board level by waiting for the 3 minutes to elapse.
Additional Features
Modulating Head Pressure Control (ECM Outdoor Motors) – A10K Nominal NTC
Thermistor is connected to the “FCC1” and “FCC2” inputs for circuit 1 and
circuit 2 respectively. The sensor is secured to the liquid line of the system
to monitor the liquid line temperature. When this sensor is connected, the
thermistor value is used as the process variable when controlling the head
pressure. The controller modulates the Outdoor Fan Motor to maintain a 90ºF
temperature setpoint. The controller will always use the greater value of FCC1
and FCC2 input as the reference point. In the event that the Thermistor is
disconnected, the controller reverts to the outdoor fan operating at the max
speed setting selected on the control board configuration menu setting 7.
Note: Systems with PSC outdoor motors utilize a fan cycle switch in the
refrigeration circuit for on/off fan cycle head pressure control.
PSC Motor Head Pressure Control
The onboard outdoor fan relay (OFR) is used to control the Fan Cycle Switch
based on CC output to the Compressor. Once the compressor out (CC1) is
energized the OFR output will also be energized and the fan cycle switch will
cycle on and off at 290psi and 400psi. This will turn the Outdoor Fan Motor on
and off to maintain the head-pressure of the system, the OFR output is only
used on systems with PSC out door motor and Fan Cycle Switch (FCC) only.
Emergency Ventilation (Motorized Damper or Economizer Equipped Systems) –
When there is a request for “Emergency Ventilation” (EV-signal via Digital
input or Modbus), the system will run the Indoor Motor at the “Y2” speed
setting on the board or via Modbus and provide a 10vdc signal from the ECO
output of the control board to drive the motorized damper fully open.
Note: The compressor and electric heat WILL NOT operate while in the
emergency ventilation mode.
Forced Cooling (economizer equipped systems) – During economizer cooling,
if a request for “Forced Cooling” (FC-signal via Digital input or Modbus) is
present. The control board will force the economizer to close and start the
compressor to operate at full capacity cooling. This is considered an override
of the economizer in the event economizer cooling can’t keep up with the
cooling demand in economizer mode. The Indoor Motor at the “Y2” speed setting
on the board or via Modbus and the system will operate in normal cooling mode
until the request for FC is satisfied. Once satisfied the system will be
allowed to return to economizer operation if conditions are favorable.
Low Voltage (Brownout) – The control board monitors the 24 VAC power
supply for low voltage protection. When the power supply voltage is 16 VAC or
less for 10 seconds the control board will de-energize all outputs. This is
considered a voltage brownout (low voltage) condition and the display of the
control board will show “03” as an indicator of brownout (low voltage). When
the voltage rises back to 17 VAC, the control board will allow the system to
operate.
Note: The nominal power supply for the control board is 24VAC and this
voltage should be confirmed during startup to assure normal operation.
Smoke / Fire Shutdown
System Shutdown Contact Wiring – Add Normally Closed Dry contacts as
shown for immediate shutdown of HVAC upon contacts opening.
Installation
WARNING
Failure to observe and follow Warnings and Cautions and these Instructions
could result in death, bodily injury or property damage. Read this manual and
follow its instructions and adhere to all Cautions and Warnings in the manual
and on the A/C unit.
Equipment Inspection
Concealed Damage
Inspect all cartons and packages upon receipt for damage in transit Remove
cartons and check for concealed damage. Important: keep the unit upright at
all times. Remove access panels and examine component parts. (Note: the
“L”-shaped bottom bracket is screwed to the shipping pallet, against the air
conditioner. Remove it before replacing the side screen). Inspect refrigerant
circuit for fractures or breaks. The presence of refrigerant oil usually
indicates a rupture. If damage is apparent, immediately file a claim with the
freight carrier.
Units that have been turned on their sides or tops may have concealed damage
to compressor motor mounts or to the oil system.
If the unit is not upright, immediately file a claim for concealed damages and follow these steps:
- Set unit upright and allow to stand for 24 hours with primary power turned on.
- Attempt to start the compressor after 24 hours.
- If the compressor will not start, makes excessive noise, or will not pump, return the unit to the freight carrier.
Installation Requirements
General
- Inspect unit for completeness. Check for missing parts (e.g. hardware). Refer to the installation kit information in section 2.3.
- Remove access panels and check for loose wires. Tighten screw connections.
- Complete and mail the warranty registration card.
You must consider all of the following when choosing the installation site:
-
Noise. Install the unit so that the least amount of noise will be transmitted to inhabited spaces.
-
Condensate Drainage. Condensate produced during operation must be discharged to a suitable drain.
-
Placement.
- Place the unit in a shaded area, if possible.
- Install it above ground for protection against flooding.
- The unit exhausts air. Be sure that the airflow is not impeded by shrubbery or other obstructions.
- When installing multiple units, please note the recommended clearances noted in Table 4.
-
Airflow Requirements:
Note the maximum static pressure (Table 6). Keep duct lengths as short as possible. Do not obstruct airflow through the unit. Duct work should be designed and installed in accordance with all applicable safety codes and standards. Eubank® strongly recommends referring to the current edition of the National Fire Protection Association Standards 90A and 90B before designing and installing duct work. The duct system must be engineered to insure sufficient air flow through the unit to prevent over-heating of the heater element. This includes proper supply duct sizing, sufficient quantity of supply registers, and adequate return and filter areas. Duct work must be of correct material and must be properly insulated. Duct work must be constructed of galvanized steel with a minimum thickness of .019 inches. Duct work must be firmly attached, secured, and sealed to prevent air leakage. See section 2.4 for additional duct work requirements. -
Clearances: Note the minimum clearances required for proper operation and service.
MODEL| MIN. CLEARANCE AROUND SIDES (SINGLE UNIT)| MIN. CLEARANCE BETWEEN UNITS (TWO UNITS)| MIN. SPACE ABOVE UNIT| MIN. SPACE BELOW UNIT
---|---|---|---|---
A| B| C| D
1024A| 30 inches (76 cm)| 18 inches (46 cm)| 24 inches (61 cm)| 6 inches (15 cm)
1030A/1036A &2030A/2036A| 30 inches (76 cm)| 18 inches (46 cm)| 24 inches (61 cm)| 6 inches (15 cm)
1042A/1048A/1060A & 2042A/2048A/2060A| 30 inches (76 cm)| 30 inches (76 cm)| 24 inches (61 cm)| 6 inches (15 cm)
Minimum Clearances
-
Codes:
Make sure your installation conforms to all applicable electrical, plumbing, building, and municipal codes. Some codes may limit installation to single story structures. -
Electrical Supply:
The power supply must have the appropriate voltage, phase, and ampacity for the model selected. Voltage must be maintained above minimum specified values listed below. Refer to the data sticker on the unit for ampacity requirements. **Electrical Rating Designations*| A| C| D**
---|---|---|---
Nominal Voltage| 208/230| 208/230| 460
Phase| 1| 3| 3
Minimum Voltage| 197| 197| 414
Maximum Voltage| 253| 253| 506
Letters refer to model number code designations. Refer to page 5.
Voltage Limitations
Installation Materials
Installation Kits
Eubank air conditioners are shipped with one 12 Ga. “L” shaped bottom
bracket. If you have not yet unpacked the unit, follow the instructions in
section 2.1. All units have built-in full length mounting flanges. Therefore,
use of mounting brackets is not required.
Kit Components:
- One 12 Ga. “L”-shaped bottom bracket.
Accessories
The package may include other factory-supplied items (optional) as follows
on the next page:
Controllers/Thermostats
CommStat 4 HVAC Controller, Solid State Lead/Lag Controller………………………………… P/N
S/07846
CommStat 3 HVAC Controller, Solid State Lead/Lag Controller………………………………… P/N
S/04581
Digital thermostat. 1 stage heat, 1 stage cool. 7 day programmable. Fan
switch:
Auto & On. Auto-change over. Keypad lockout. Non-volatile program memory………………
P/N 50123
Digital thermostat. 2 stage heat, 2 stage cool. 7 day programmable. Fan
switch:
Auto & On. Auto-change over. Status LED’s. Backlit display.
Programmable fan. Non-volatile program memory………………………………………………………. P/N 50107
Grilles/Wall Sleeves
Supply Grilles
- For 7AA1024A…………………………………………………………………………………………………………P/N 80675
- 28” x 8” (711 mm x 203 mm)
- For 7AA1030A, 1036A, 1042A, 1048A, 1060A…………………………………………………………….P/N 80676
- 30” x 10” (762 mm x 254 mm)
- For 7AA1060A Reverse Flow…………………………………………………………………………………….P/N 93197
- 30” x 16” (762 mm x 406 mm)
Return Grilles
- For 7AA1024A…………………………………………………………………………………………………………P/N 80678
- 28” x 14” (711 mm x 356 mm)
- For 7AA1030A, 1036A, 1042A, 1048A, 1060A…………………………………………………………….P/N 80679
- 30” x 16” (762 mm x 406 mm)
- For 7AA1060A Reverse Flow…………………………………………………………………………………….P/N 93198
- 30” x 10” (762 mm x 254 mm)
Return Filter Grilles
Used when filter must be changed from the interior. Not recommended for air
conditioners with an economizer.
Note: Filter used in Return Filter Grille is 1” (25 mm) thick.
- For 7AA1024A…………………………………………………………………………………………………………P/N 80672
- 28” x 14” (711 mm x 356 mm)
- For 7AA1030A, 1036A, 1042A, 1048A, 1060A…………………………………………………………….P/N 80673
- 30” x 16” (762 mm x 406 mm)
Additional Items Needed:
Additional hardware and miscellaneous supplies (not furnished by Eubank®)
are needed for installation. For example, the list below contains approximate
quantities of items typically needed for mounting a unit on a wood frame wall
structure. Concrete or fiberglass structures have different requirements.
(10) 3/8″ carriage head mounting bolts for unit mounting flanges. The length
needed is typically the wall thickness plus one inch.
(20) 3/8″ washers
(10) 3/8″ hex nuts
(6) 3/8″ x 2-1/2″ lag screws for bottom bracket
- Silicone Sealer to seal around cracks and openings
- Minimum 5 conductor low voltage multicolored wire cable (i.e. thermostat wire)
- Appropriate electrical supplies such as conduit, electrical boxes, fittings, wire connectors, etc.
- High voltage wire, sized to handle the MCA (minimum circuit ampacity) listed on the data plate.
- Over-Current Protection Device sized in accordance with the MFS (maximum fuse size) listed on the unit data plate.
WARNING – FIRE HAZARD
Improper adjustment, alteration, service, maintenance or installation could
cause serious injury, death and/or property damage. Installation or repairs
made by unqualified persons could result in hazards to you and others.
Installation MUST conform with local codes or, in the absence of local codes,
with codes of all governmental authorities have jurisdiction. The information
contained in this manual is intended for use by a qualified service agency
that is experienced in such work, is familiar with all precautions and safety
procedures required in such work, and is equipped with the proper tools and
test instruments.
Porting and Duct Work
General Information
Note: The following instructions are for general guidance only. Due to the
wide variety of installation possibilities, specific instructions will not be
given. When in doubt, follow standard and accepted installation practices, or
contact Technical Support for additional assistance.
Wall Openings (All Eubank 7AA air conditioners)
Measure the dimensions of the supply and return ports on the unit. Cut the
openings in the exterior wall for the supply and return. IMPORTANT: All units
with electric heat must have 1″ (25.4mm) clearance on all four sides of the
supply outlet duct flange on the unit. The 1″ (25.4mm) clearance must extend
on all sides of the supply duct for the first 3 feet (1 meter) from the unit.
IMPORTANT: Eubank® requires a minimum of 1″ (25.4mm) from the surface of
any supply ducts to combustible material for the first 3 feet (1 meter) of the
duct.
For all air conditioners with electric heat, the wall sleeve MUST have 1”
(25.4 mm) clearance around all four sides of the opening. Attach the perimeter
flange of the wall sleeve to the framed opening with appropriately sized
screws. Since electric heat can be added after the unit has been installed,
Eubank recommends that all installations have the 1” (25.4 mm) clearance
around the wall sleeve. When installing the wall sleeve, the supply opening
must be on top. The supply opening is smaller than the return air opening.
Ducting
Extensions should be cut flush with the inside wall for applications without
duct work. Applications using duct work should be designed and installed in
accordance with all applicable safety codes and standards. Eubank® strongly
recommends referring to the current edition of the National Fire Protection
Association Standards 90A and 90B before designing and installing duct work.
The duct system must be engineered to insure sufficient air flow through the
unit to prevent over-heating of the heater element. This includes proper
supply duct sizing, sufficient quantity of supply registers, adequate return
and filter area. Ductwork must be of correct material and must be properly
insulated. Duct work must be constructed of galvanized steel with a minimum
thickness of .019 inches for the first 3 feet (1 meter). Ductwork must be
firmly attached, secured and sealed to prevent air leakage. Do not use duct
liner on inside of supply duct within 4 feet (122cm) of the unit. Galvanized
metal duct extensions should be used to simplify connections to duct work and
grilles. Use fabric boots to prevent the transmission of vibration through the
duct system. The fabric must be U.L. rated to a minimum of 197°F (92°C).
Minimum Airflow Requirements
The duct system must be engineered to assure sufficient air flow through the
unit even under adverse conditions such as dirty filters, etc. Use Table 6
below and Table 1, CFM at External Static Pressure (Wet Coil) in section 1.4.
BASIC MODEL | MAXIMUM STATIC |
---|---|
1024A | .50 |
1030A,1036A, 1042A and 2036A, 2042A | .50 |
1048A, 1060A & 2048A, 2060A | .50 |
Maximum Static Pressure (For units with 2″ Pleated Filters)
Fresh Air Hood (non-economozer air conditioners only)
The fresh air hood is located on the inside, behind the slots on the bottom
front panel. To access the hood, remove the screws that hold the front panel.
The air flow can be adjusted from no (0%) fresh air to approximately 15% of
rated air flow of fresh air, in 5% increments. The hood is shipped from the
factory in the closed position (no fresh air). To provide fresh air, remove
the two screws on either side of the hood and reposition as desired.
Fresh Air Hood Damper, Models 1024A-1060A & 2036A-2060A
Bracket Installation
- All models have built-in mounting flanges.
- Apply a bead of silicone sealer on the wall side of the bottom support brackets on the unit. Circle the mounting holes with the silicone bead.
- Refer to Figure 4. Attach the bottom support bracket to the wall using appropriate 3/8″ diameter hardware.
For example, on wooden structures, use 3/8″ x 2-1/2″ all-thread lag screws. The screws must penetrate the center of the wall stud. Drill a pilot hole in the stud to prevent it from splitting.
Mounting The Unit
- For wiring into the back of unit, locate the lower of the two knockouts on the wall side of the unit. Drill a one inch hole in the shelter wall to match this opening. Allow sufficient clearance to run 3/4″ conduit through the hole and to the unit.
- Using an appropriate and safe lifting device, set the unit on the bottom support bracket mounted on the wall. You must stabilize the unit on the bracket with the lifting device or by some other means – the bracket alone is not sufficient.
- Make sure that the duct flanges are properly aligned with the wall opening. Adjust as necessary.
- Note the holes in each side flange. Using the holes for guides, drill holes through the wall with a 3/8″ drill bit. Insert the 3/8″ x 5″ bolts through the flanges. Install nuts and washers on the inside of the shelter. Tighten the bolts to secure the unit.
- Apply a bead of silicone where the mounting flange contacts the unit and the shelter wall.
- On the inside of the shelter, install the wall sleeves in the supply and return air openings. The sleeves may be trimmed to fit flush with the inside wall.
- Check the fit of each sleeve to its mating flange for possible air leaks. Apply silicone sealer to close any gaps. Install the air return and supply grilles.
For units with electric heat, a one inch clearance is required around the duct
extensions. The duct extensions must be constructed of galvanized steel with a
minimum thickness of .019” as per the NFPA standards 90A & 90B.
Eubank A/C Wall Mount Detail
Electrical Connections
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow safety warnings exactly could result in serious injury,
death, and/or property damage. Turn off electrical power at fuse box or
service panel BEFORE making any electrical connections and ensure a proper
ground connection is made before connecting line voltage.
Important
All electrical work must meet the requirements of local codes and ordinances.
Work should be done only by qualified persons. Units may incorporate an
internal crankcase heater for compressor protection. The crankcase heater must
be energized for at least 24 hours prior to starting the compressor. Scroll
compressors, like several other types of compressors, will only compress in
one rotational direction. The direction of rotation is not an issue with
single-phase compressors since they will always start and run in the proper
direction. However, three phase compressors will rotate in either direction
depending upon phasing of power. Since there is a 50-50 chance of connecting
power in such a way as to cause rotation in the reverse direction, it is
imperative to confirm that the compressor is rotating in the proper direction
at the initial field start-up of the system. Verification of proper rotation
is made by observing that the suction pressure drops and the discharge
pressure rises when the compressor is energized. An alternate method of
verification for self contained system with small critical refrigerant
charges, where the installation of gauges may be objectionable, can be made by
monitoring the temperature of the refrigerant lines at the compressor. The
temperature should rise on the discharge line while the suction line
temperature decreases. Reverse rotation also results in a substantially
reduced current draw when compared to tabulated values.
There is no negative impact on durability caused by operating three phase
compressors in the reversed direction for a short duration of time, usually
defined as less than one hour. However, after several minutes of operation the
compressor’s internal protector will trip. The compressor will then cycle on
the protector until the phasing is corrected. Reverse operation for longer
than one hour may have a negative impact on the bearings. To change the
rotation, turn off power to the unit and reverse L1 & L2 at the disconnect in
the air conditioner.
High Voltage Wiring – (Single Units)
The power supply should have the proper voltage, phase, and ampacity for the
selected model.
-
Refer to the electrical data on the data sticker on the unit for field wiring requirements of the unit. Size the incoming power supply lines and the fuse(s) or HACR breaker(s) according to requirements described in the National Electric Code. Run the power conductors through the knockouts on the side or back of the unit. Use appropriate conduit and strain reliefs.
CAUTION
Note: Power supply service must be within allowable range (+10% – 5%) of rated voltage stamped on the unit rating plate. To operate nominal 230/208V unit at 208V, change the transformer line tap from 240V to 208V following the instruction on wiring label in unit. -
Connect the wires to the input side of the internal breaker or terminal block (L1 & L2 for single-phase units; L1, L2, & L3 for three-phase models).
-
Install the ground wire on the ground lug.
-
For units designed for operation on 208/230V, 60Hz power supply, the transformer is factory wired for a 230V power supply. For a 208V power supply, remove the orange lead from the transformer and connect the red lead. Insulate the orange lead.
-
460V units have a step down transformer for 230V motors.
CAUTION
The external breaker(s) that provide power to the air conditioner must be
sized per the maximum Fuse Size (MFS) shown on the Unit’s data label.
Dual Unit Phasing
For applications where one controller operates two units, e.g., the CommStat 4
HVAC controller. Newer HVAC controllers sunch as the CommStat do not require
unit phasing. However, if other devices are connected to the control system,
phasing of the air conditioner is required. Earlier models; i.e., LL357,
LL357A, LL357D2 require the unit to be properly phased.
- Wire each unit as described in steps 1 through 4 above.
- Test for proper phasing as follows:
- Power up the units.
- Using an AC volt meter set to the 300 volt scale, measure voltage between terminal L1 on the compressor contactor of unit #1 and terminal L1 on the compressor contactor of unit #2 If voltage is present, units are wired out of phase and must be rewired.
- If units are not in phase, turn off power and reverse the field power leads connected to the internal circuit breaker on one of the units only.
- Restore power and retest the phase (step B). When the voltage reads “0”, the units are in phase.
- Turn off power and proceed.
Low Voltage Wiring
IMPORTANT. The following instructions are generic wiring instructions and
may not be applicable for air conditioners with various options. Always refer
to the wiring diagram in the air conditioner for the proper method to wire
your unit.
- On single units, pull the low voltage wiring (e.g., 18 gauge 4-conductor Class 2 thermostat wire) from the unit into the thermostat / subbase assembly. See Figure 9b for connections to various thermostats.
- Mount the thermostat on the wall of the shelter. The thermostat should be located so that the supply air from the unit does NOT blow directly on to the thermostat. Connect the thermostat to the terminal block in the air conditioner as shown in Figures 9a and 9b.
- On dual units, refer to the CommStat 4 or CommStat 3 HVAC Controller Specification sheet. Level and install the controller subbase. Wire the two A/C units to the Lead/Lag Controller, according to the wiring diagram on the specification sheet and as shown in Figure 9c or 9d (note: the diagram also appears on the back cover of the controller).
Remote Signalling: Terminals 5 & 7(N.O.) and 6 & 7 (N.C.) on the terminal
board are dry contacts which can be used for remote signalling in the event of
a/c cutoff on low or high pressure limit.
Continuous fan operation: For continuous indoor fan operation on single
units, install a jumper between terminals 8 and 3. For continuous indoor fan
operation on dual units using the older LL357D4, install jumper between 8 and
3 and remove jumper between 1 and 3.
CommStat 4 Lead /Lag Controller
Please refer to the Product Data sheet for the Commstat 4 controller for
complete instructions on installing and programming this controller.
Humidistat Wiring to a Eubank Air Conditioner with Reheat.
Thermostat Connection Diagram
- For immediate shutdown of HVAC upon a smoke fault, change setting 3 (Fan Purge) on the HVAC control board to N = No.
- The CommStat 4 terminal “2” is used to force mechanical cooling if the economizer cooling can’t maintain the required cooling demand. This output is only used on systems equipped with economizers.
- The CommStat 4 terminal “O/Y2” is only used on systems with 2 stage compressors (Y2) or Heat Pumps systems (O).
- The CommStat 4 terminal “MAR” is only used on systems with economizers. The MAR output forces the system into emergency ventilation mode upon a hydrogen fault.
- The CommStat 4 “AUX 1” and “AUX 2” terminals are used for economizer status monitoring from the connected HVAC. This feedback is required for the CommStat 4 to override economizer cooling if the economizer and force mechanical cooling if the economizer can’t maintain the required cooling demand. These inputs are only used with economizer equipped systems.
CommStat 4 Wiring Diagram
Start-Up
Check-Out of Cooling Cycle
Important: Be sure that the crankcase heater (if used) has been energized
for at least 24 hours before starting the unit(s). Double-check all electrical
connections before applying power. Eubank air conditioners with scroll
compressors running on 3Ø power must be checked for proper rotation during the
initial start-up. Please refer to Section 2.8 for determining if the 3Ø
compressors are rotating correctly. Incorrect rotation can damage the
compressor and is not covered by the warranty
Procedure:
-
Set the cooling set point temperature on the wall thermostat to a point higher than the ambient temperature. Set the heating set point temperature to a temperature that is lower than the ambient.
-
Set the thermostat system switch in the AUTO position. Nothing should operate at this time.
-
Set the time delay in the electrical control box to three minutes. Check the changeover setting of the enthalpy or dry bulb sensor and reset it if needed (economizer-equipped models only). See Section 1.6.
-
Slowly lower the thermostat’s cooling set point temperature until the switch closes. The indoor fan should operate. Once the indoor fan turns on, allow approximately three minutes for the compressor to start. Note that the outdoor fan may not come on immediately, because it is cycled by refrigerant pressures.
NOTE: (Economizer-Equipped models only) To check the system operation under different ambient conditions, the air temperature and enthalpy sensors must be “tricked”. When outdoor ambient condi-tions are higher than the control setting, a component cooler aerosol may be sprayed directly into the enthalpy sensor to simulate low enthalpy conditions, causing the economizer damper to open.
Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair dryer can be directed on the air temperature sensor to simulate warmer conditions, which will bring on mechanical cooling and start the compressor. -
To stop cooling, slowly raise the thermostat cooling set point to a temperature higher than the ambient.
If the unit fails to operate, refer to the troubleshooting information in
Chapter 4. Follow the same procedure for additional units.
NOTE: The fan purge allows the indoor fan to run for approximately 90
seconds after the compressor is off. This operation provides a small
improvement in system rated efficiency.
Check-Out of Heating Cycle
Procedure: (Applies only to units with resistance elements)
- Raise the heating set point temperature to a setting which is higher than the ambient temperature. The fan and electric heat should immediately cycle on.
- Move the system switch to the “OFF” position. All functions should stop.
NOTE: (Economizer Equipped models only) The damper blade should remain closed during the heating cycle (unless the minimum position potentiometer has been set for constant ventilation A fully counterclockwise position corresponds to full closure of the damper.
Troubleshooting
Overview
A comprehensive understanding of the operation of the air conditioner is a
prerequisite to troubleshooting. Please read the Chapter 1 for basic
information about the unit. Eubank air conditioners are thoroughly tested
before they are shipped from the factory. Although unlikely, it is possible
that a defect may escape undetected, or damage may have occurred during
transportation. However, the great majority of problems result from
installation errors. If you experience difficulties with your unit, please
review the installation steps in Chapter 2.
Much time can be saved by taking a thoughtful and orderly approach to
troubleshooting. Start with a visual check – are there loose wires, crimped
tubing, missing parts, etc? Begin deeper analysis only after making this
initial inspection. The troubleshooting information in this manual is basic.
The troubleshooting section contains problem/solution charts for general
problems, followed by a compressor section. Not every problem can be
anticipated. If you discover a problem that is not covered in this manual, we
would be very grateful if you would bring it to the attention of our service
department for incorporation in future revisions. As always, please exercise
caution and good judgement when servicing the unit. Use only safe and proven
service techniques. Use refrigeration goggles when servicing the refrigeration
circuit.
WARNING
**** The refrigerant circuit has hot surfaces, and the electrical voltages
inside of the unit may be hazardous or lethal. SERVICE MAY BE PERFORMED ONLY
BY QUALIFIED AND EXPERIENCED PERSONS.
Failure Symptoms Guide
PROBLEM/SYMPTOM | LIKELY CAUSE(S) | CORRECTION |
---|
A. Unit does not run.
NOTE : An internal anti-short-cycle timer will prevent the unit from
starting for .2 to 8 minutes following start-up.|
- Power supply problem.
- Tripped internal disconnect.
- Shut off by external thermostat or thermostat is defective.
- Unit off on high or low pressure limit.
- Internal component or connection failure.
|
- Check power supply for adequate phase and voltage. Check wiring to unit and external breakers or fuses.
- Check internal circuit protection devices for continuity.
- Check operation of wall-mounted thermostat.
- Reset pressure switch.
- Check for loose wiring. Check components for failure.
B. Unit runs for long periods or continu- ously; cooling is insufficient.|
- Dirty filter or reduced airflow
- Low refrigerant.
- Component failure.
- Unit undersized for job.
|
- Check air filter(s). Check blower operation. Remove airflow restriction.
- Check for proper charge and possible refrigerant leak.
- Check internal components, especially compressor for proper operation.
- Add additional units for greater capacity.
C. Unit cycles on high/low pressure limit.|
- Loss or restriction of airflow.
- Restriction in refrigerant circuit.
- Refrigerant overcharge (following field service)
- Defective pressure control.
|
- Check blower assembly for proper operation. Look for airflow restrictions, e.g.. the air filter. Check blower motor and condenser fan.
- Check for blockage or restriction, especially filter drier and capillary tube assembly.
- Evacuate and recharge to factory specifications.
- Check limit cutout pressures. Control is set to actuate at approximately 35 PSIG (low pressure) and 400 PSIG (high pressure).
---|---|---
D. Unit blows fuses or trips circuit breaker.|
- Inadequate circuit ampacity.
- Short, loose, or improper connection in field wiring.
- Internal short circuit. Loose or improper connection(s) in unit.
- Excessively high or low supply volt- age or phase loss (3ø only).
|
- Note electrical requirements in Chapter 2 and correct as necessary.
- Check field wiring for errors.
- Check wiring in unit. See wiring and schematic diagrams. Test components (especially the compressor) for shorts.
- Note voltage range limitations specific to the compressor troubleshooting section.
E. Water on floor near unit.|
- Obstruction in condensate line.
- Obstruction or leak in condensate pan.
- Unit is not level.
|
- Check for clog or restriction.
- Check pan for leak or blockage.
- Level unit.
F. No space heating or reduced heating (units equipped with resistance
elements)|
- Defective heating element(s).
- Thermal limit open.
- Defective heater contactor.
|
- Check resistance element(s) for continuity.
- Check continuity across thermal limit switch.
- Check relay for proper operation. Replace if defective.
Compressor Troubleshooting
NOTE: It is important to rule out other component failures before condemning
the compressor.
The following electrical tests will aid diagnosis:
-
Start-Up Voltage: Measure the voltage at the compressor contactor during start-up. The voltage must exceed the minimum shown in Table 5, section 2.2, or compressor failure is likely. A low voltage condition must be corrected.
-
Running Amperage: Connect a clip-on type ammeter to the (common) lead to the compressor. Turn on the supply voltage and energize the unit. The compressor will initially draw high amperage; it should soon drop to the RLA value or less. If the amperage stays high, check the motor winding resistances.
NOTE: Feel the top of the compressor to see if it has overheated. If it is hot, the internal overload may be open. You may have to wait several hours for it to reset. -
Motor Winding Resistances: Using a digital volt-ohm meter (VOM), measure the resistance across the compressor windings as shown below. Resistance can be measured as shown above. Any deviation from above values could indicate a defective compressor.
-
High Voltage/Insulation Test: Test internal leakage with a megoh meter. Attach one lead to the compressor case on a bare metal tube and to each compressor terminal to test the motor windings. A short circuit at high voltages indicates a motor defect. Do not do this test under vacuum.
-
On single phase models, check the capacitor by substitution.
Control Board Diagnosis
The control board (see section 1.6a for a complete description of the control
board) has a red diagnostic LED which indicates the lockout fault. The control
board will enter into and indicate lockout if either of the fault conditions
(LPS or HPS) occur twice. The contactor must be closed before the first fault
condition can be recognized by the control board. The contactor will be closed
3 minutes after the unit is energized and only if cooling is required. The
first fault condition will open the contactor and shutdown the unit. The
contactor on the unit that has the fault condition must be closed before the
second fault condition can be recognized by the control board. The contactor
on the unit with the fault condition will close after 3 minutes if the unit is
still calling for cooling and if the fault condition no longer exists. If you
get a second fault condition, the contactor will open and shutdown the unit.
The “red” led will have one blink if the high pressure switch has opened twice
and will have two blinks if the low pressure switch has opened twice. The unit
must be in the cooling mode (compressor contactor Closed) before a fault
condition can occur.
Maintenance
Scheduled Maintenance
Eubank strongly recommends that the air conditioner be serviced a minimum
of twice a year – once prior to the heating season and once prior to the
cooling season. At this time the filters, evaporator coil, condenser coil, the
cabinet, and condensate drains should be serviced as described below. Also at
this time, the air conditioner should be operated in the cooling and heating
cycles as described in Chapter 3, Start-Up.
In addition to this seasonal check-out, the AC unit should be maintained as
follows:
Air Filter
Replace the air filter whenever it is visibly dirty. Never operate the unit
without the filter in place.
Evaporator
If the evaporator becomes clogged or dirty, it may be cleaned by careful
vacuuming or with a commercial evaporator cleaning spray. DO NOT use a solvent
containing bleach, acetone, or flammable substances. Turn off power before
cleaning. Be careful not to wet any of the electrical components. Be sure the
unit has dried before restarting.
Condenser
Periodically inspect the outdoor condenser coil and the cabinet air reliefs
for dirt or obstructions. Remove foreign objects such as leaves, paper, etc.
If the condenser coil is dirty, it may be washed off with a commercial solvent
intended for this purpose.
TURN OFF POWER BEFORE CLEANING!
Be sure that all electrical components are thoroughly dry before restoring
power. Use a fin comb of the correct spacing to straighten mashed or bent
fins.
Cabinet
The cabinet may be cleaned with a sponge and warm, soapy water or a mild
detergent. Do not use bleach, abrasive chemicals or harmful solvents.
Drains
Regularly check the primary and secondary condensate drains. The secondary
drain has a stand pipe. An obstruction will force water to dump into the
middle of the unit and drain out the sides of the unit, causing discoloration
of the side panels. If discoloration is noted, service the drains. If a
commercial drain solvent is used, flush out the drain pan and system with
plenty of fresh water to prevent corrosion.
Lubrication
Oiling of the condenser fan motor or the evaporator blower motor is not
recommended.
DANGER
Sever hazard. The economizer contains moving parts capable of causing serious
injury or death. Disconnect power before removing the covering panel.
Warranty
Marvair, Inc. Limited Product Warranty
Marvair Inc., warrants its products to be free from defects in materials and
workmanship under normal use to the original purchaser for the period of time
in the table below. If any part of your product fails within 12 months from
start-up, or 18 months from shipment from the factory, whichever comes first,
Marvair, Inc. will furnish without charge, EXW Cordele, Georgia, the required
replacement part. The owner must provide proof of the date of the original
start-up. The contractor’s invoice, the certificate of occupancy, or similar
documents are examples of acceptable proof of the date of the original start-
up.
Marvair, ICE, Eubank Products
90 Days1 w/Flat Rate Labor2 (See Marvair, ICE, Eubank Flat Rate Labor
Guidelines)
1 Year Parts2,3
5 Years Compressor2
-
If any part of your Marvair, Inc. unit fails within 90 days of the commencement of the warranty, Marvair, Inc. will furnish without charge, EX Works, Cordele, Georgia, the
required replacement part and pay for the labor to replace the part in accordance with the Marvair, Inc. Flat Rate Labor Guidelines. -
All OTR (over the road) applications that are moved from one location to another: Factory Warranty applies only up to the point of initial start-up and test at all OEM manufacturing locations or subsequent facility. Once it goes into OTR service, the warranty expires immediately for compressor and sealed system components. This OTR exemption does not apply to relocatable classrooms, construction or office trailers.
-
All warranty replacement parts shall be shipped Ground only. Expedited shipping is available upon request for additional cost.
The responsibility of the equipment owner includes:
- To operate the equipment in accordance with the manufacturer’s instructions.
- To provide easy accessibility for servicing.
- To check and reset any circuit breaker(s) and/or disconnect(s) prior to calling for service.
- To keep the unit clean and free of dirt and containment and replace filters as required.
- To keep the outdoor coil clean and free of leaves, paper, or other debris.
- To pay the charges incurred when any of the above have not been done.
- To pay for repair or replacement of any material or part other than those within the Marvair unit or controller.
Marvair, Inc., will not be responsible for labor after 90 days, transportation costs, delays or failures to complete repairs caused by events beyond our control (labor hours incurred due to required site-specific training, time waiting to gain access, or extended drive time for remote sites).
This warranty does not cover:
- Any transportation, related service labor, diagnosis calls, filter, driers, refrigerant, or any other material charges.
- Damages caused by shipping, accident, abuse, negligence, misuse, fire, flood, or Acts of God.
- Damages caused by operating or staging the unit in a corrosive environment.
- Damages caused by improper application of the product.
- Damages caused by failing to perform proper routine maintenance.
- Expenses incurred for erecting, disconnecting or dismantling the product or installing the replacement part(s).
- Products not installed or operated according to the included instructions, local codes, and good trade practices.
- Products moved from the original installation site.
- Products lost or stolen
- Consequential damages or incidental expenses including losses to persons, property or business.
- Modifications to original unit after it leaves the factory, such as breaking into any part of the sealed systems unless authorized in advance in writing by Marvair, Inc..
- Damages as a result of operating as a construction site cooler / dehumidifier.
When labor (first 90 days only) is required, it must be performed during
normal working hours (8:00 AM – 5:00 PM) Monday – Friday and must be performed
by Marvair, Inc., personnel or a designated Service Representative. The owner
of the product may ship the allegedly defective or malfunctioning product or
part to Marvair, Inc.,, at such owner’s expense, and Marvair, Inc., will
diagnose the defect and, if the defect is covered under this warranty,
Marvair, Inc., will honor its warranty and furnish the required replacement
part. All costs for shipment and risk of loss during shipment of the product
to Marvair, Inc., and back to the owner shall be the responsibility and
liability of the owner. Upon written request by an owner, Marvair, Inc., may
arrange for remote diagnosis of the allegedly defective or malfunctioning
product or part but all costs for transportation, lodging and related expenses
with regard to such diagnostic services shall be the responsibility and
liability of the owner. An owner requesting performance under this Warranty
shall provide reasonable access to the allegedly defective or malfunctioning
product or part to Marvair, Inc., and its authorized agents and employees.
THIS WARRANTY CONSTITUTES THE EXCLUSIVE REMEDY OF ANY PURCHASER OF A MARVAIR
HEAT PUMP OR AIR CONDITIONER AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED
OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR USE, TO THE FULLEST EXTENT PERMITTED BY LAW. IN
NO EVENT SHALL ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR USE
EXCEED THE TERMS OF THE APPLICABLE WARRANTY STATED ABOVE AND MARVAIR SHALL
HAVE NO OTHER OBLIGATION OR LIABILITY. IN NO EVENT SHALL MARVAIR BE LIABLE FOR
INCIDENTAL OR CONSEQUENTIAL DAMAGES OR MONETARY DAMAGES. THIS WARRANTY GIVES
YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM
STATE-TO-STATE. Some states do not allow limitations or exclusions, so the
above limitations and exclusions may not apply to you.
Start-Up Check List
Start-Up & Commissioning Form
Please complete the information on this form and return to Eubank by mail or
fax. The mailing address and fax number can be found at the end of the form.
Refrigerant Piping
If leaks are found, report any leaks to Eubank Warranty Service Dept.
Check Rated Voltage at Terminal Block for Imbalance before starting of Unit.
A voltage deviation greater than 2% with the unit running should be addressed and corrected. Excess voltage deviation can cause the compressor to overheat and to operate inefficiently.
Measured Voltages:
L1 & L2 = 241 Volts
L1 & L3 = 243 Volts = 717 / 3 = 239 Average Voltage
L2 & L3 = 233 Volts
239 – 233 = 6
100 x 6/239 =2.5% Voltage Unbalance
Three phase units only check fan & compressor rotation.
Heating Mode Check & Record Readings
Cooling Mode Check & Record Refrigerant Pressures
Recheck voltage imbalance in cooling mode:
Measured Line to Line Volts L1&L2_V. L1&L3 ____V. L2&L3__V.
(L1&L2 + L1&L3 + L2&L3)/3 = Avg. Voltage = _____
Max. Deviation from avg. voltage = __volts
Voltage imbalance = (100 x Max. Deviation)/avg. Voltage = ___%
After 10 minutes of compressor operation, record the following:
APPENDIX A: Installation Instructions for Field Installed Electric Heat,
Models 1024A-1060A & 2036A-2060A
WARNING FIRE HAZARD
Improper adjustment, alteration, service, maintenance or installation could
cause serious injury, death and/or property damage. Installation or repairs
made by unqualified persons could result in hazards to you and others.
Installation MUST conform with local codes or, in the absence of local codes,
with codes of all governmental authorities have jurisdiction. The information
contained in this manual is intended for use by a qualified service agency
that is experienced in such work, is familiar with all precautions and safety
procedures required in such work, and is equipped with the proper tools and
test instruments.
Duct Work
General Information
Note: The following instructions are for general guidance only. Due to the
wide variety of installation possibilities, specific instructions will not be
given. When in doubt, follow standard and accepted installation practices, or
contact Eubank for additional assistance.
Wall Openings
Measure the dimensions of the supply and return ports on the unit. Cut the
openings in the exterior wall for the supply and return.
IMPORTANT: All units with electric heat must have 1″ (25.4 mm) clearance
on all four sides of the supply outlet duct flange on the unit. The 1″ (25.4
mm) clearance must extend on all sides of the supply duct for the first 3 feet
(1 meter) from the unit.
- Eubank requires a minimum of 1″ (25.4 mm) from the surface of any supply ducts to combustible material for the first 3 feet (1 meter) of the duct.
Ducting
Extensions should be cut flush with the inside wall for applications without
duct work. Applications using duct work should be designed and installed in
accordance with all applicable safety codes and standards. Eubank strongly
recommends referring to the current edition of the National Fire Protection
Association Standards 90A and 90B before designing and installing duct work.
The duct system must be engineered to insure sufficient air flow through the
unit to prevent over-heating of the heater element. This includes proper
supply duct sizing, sufficient quantity of supply registers, adequate return
and filter area. Ductwork must be of correct material and must be properly
insulated. Duct work must be constructed of galvanized steel with a minimum
thickness of .019 inches for the first 3 feet (1 meter). Ductwork must be
firmly attached, secured and sealed to prevent air leakage. Do not use duct
liner on inside of supply duct within 4 feet (122 cm) of the unit. Galvanized
metal duct extensions should be used to simplify connections to duct work and
grilles. Use fabric boots to prevent the transmission of vibration through the
duct system. The fabric must be U.L. rated to a minimum of 197°F (92°C).
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow safety warnings exactly could result in serious injury,
death, and/or property damage. Turn off electrical power at fuse box or
service panel BEFORE making any electrical connections and ensure a proper
ground connection is made before connecting line voltage.
Heater installation (see drawings and wiring diagram)
- Remove top front panel.
- Remove bottom front panel.
- Remove the control box cover.
- Remove the heater access cover plate on the upper right side of the unit by removing the three screws. Cut insulation on two sides and fold down out of way.
- Slide new heater assembly into place by lining up stem with hole on far end. Make sure stem of new heater assembly is inserted into correct hole. The hole nearest to the indoor coil is for three element heaters and the farthest away from indoor coil is for all other heaters.
- Install the two No. 10 screws in the heater assembly plate.
- Install wire harness in hole provided in drain pan and then through filter bracket and then into control box.
- Wire the heater as shown in the wiring diagram provided with the heater kit (the insulated terminal ends are to be connected at the heater)
- Install pop tie in appropriate hole in back panel to secure wire.
- Install closed cell strip around wires where they pass through the drain pan.
- Reinstall the heater access cover.
- Mount the heat contactor inside the control box where the mounting holes are provided for the heat contactor.
- Make the wiring connections inside the control box as shown in the wiring diagram provided with the heater kit. Bundle loose wires with wire ties.
- With a permanent marker, place an (X) in the space provided next to the heater kit rating of the installed heater on the unit data label.
- Place the wiring diagram provided with the heater kit inside the zip lock bag which is affixed to the back side of the control box cover.
- Replace the control box cover, the bottom front cover and the top front panel.
FAQ
-
Q: Where should the instructions be affixed for the installer and end user?
A: The installer should affix the instructions on the inside of the building adjacent to the thermostat. The end user should retain these instructions for future reference. -
Q: How can I access the most current version of the manual?
A: The most current version of the manual can be found at www.EubankWallMount.com. -
Q: What is the EER (Energy Efficiency Ratio) of the air conditioners?
A: The EER of the air conditioners is 11. -
Q: Can anyone perform service on the unit?
A: No, service should only be performed by qualified and experienced persons. -
Q: What precautions should be taken when transporting the unit?
A: The unit should be transported upright to avoid oil leaving the compressor and potential breakage or damage to other components.