Honeywell HON-CGW-MBB Clss Horizon Gateway User Guide

August 30, 2024
Honeywell

Honeywell HON-CGW-MBB Clss Horizon Gateway

Specifications

Connected Life Safety Services (CLSS) LAN-Connected Horizon is a PC-based application for fire system monitoring via Ethernet on a local Area Network. It allows personnel to pinpoint, investigate, and respond to alarm events. Paired with the CLSS Gatewaycommunicator, CLSS Horizon can monitor single buildings or entire campuses and includes features like mobile app alerts, test tools, remote diagnostics, and central station alerting.

System Requirements

  • Ethernet Network CLSS Gateway ports: 53, 80, 123, 443,2017
  • LAN-Connected Horizon Workstation ports: 25, 123, 1884, 2004,2017, 4016

Product Usage Instructions

Setting up CLSS Horizon:

  1. Ensure your Ethernet network meets the specified requirements.
  2. Install the CLSS Gateway on the network following the provided guidelines.
  3. Activate the LAN-Connected Horizon software using the One Time\ Activation or Subscription option.

Monitoring Fire Systems:

  1. Access the CLSS Horizon application on the workstation.
  2. Use the graphical display to monitor alarm events and respond accordingly.
  3. Utilize features like mobile app alerts and remote diagnostics for efficient monitoring.

FAQs

What are the key verticals for CLSS Horizon?

The key verticals include Healthcare, Education, Commercial/Mixed-Use, Manufacturing, and Hospitality.

What optional equipment is available for CLSS Horizon?

Optional equipment includes CLSS Gateway Cellular Modules for mobile applications and NUP Cables for gateway subscriptions.

Where can I find more detailed technical information?

For detailed technical information, refer to the provided Data Sheets and Manuals with the corresponding part numbers.

Connected Life Safety Services (CLSS) LAN-Connected Horizon is a PC-based application for fire system monitoring via Ethernet on a Local Area Network. The intuitive, graphical display allows personnel to rapidly pinpoint, investigate, and respond to alarm events. Paired with the CLSS Gateway communicator, CLSS Horizon can be used to monitor a single building or an entire campus and can easily meet the needs of expanding systems.\ CLSS Horizon users can access other CLSS platform features including mobile app alerts, digital test and inspection tools, remote diagnostics, and central station alerting.

APPLICATION NOTES

For installations on NOTIFIER-only systems with NOTI-FIRE-NET™ – a CLSS Gateway is installed on the NOTI-FIRE-NET.
For installations on NOTIFIER-only systems with standalone fire panels – a CLSS gateway is installed in each NOTIFIER fire panel.
Key verticals: Healthcare, Education, Commercial/Mixed-Use, Manufacturing, Hospitality

SYSTEM REQUIREMENTS

Ethernet Network

  • CLSS Gateway: The following ports must be available for the CLSS Gateway.
PORT TYPE DIRECTION PURPOSE
53 UDP and TCP OUT DNS Resolution
80 TCP IN Web Based Configuration
123 UDP OUT SNTP
443 TCP IN/OUT HTTPS Communications
2017 TCP IN Connection from workstation

(events and commands)

4016| TCP| IN| Upgrades

RESTRICTIONS

Each CLSS Gateway must have a static IP address The following are not supported:

  • DHCP
  • Web access through an HTTP proxy server
  • Use of a NAT (Network Address Translation)

LAN-CONNECTED HORIZON WORKSTATION

The following ports must be available to the workstation:

PORT TYPE DIRECTION PURPOSE
25 TCP OUT SMTP
123 UDP IN AND OUT SNTP
1884 TCP IN AND OUT MQTT
2004 TCP N/A (Internal) Workstation **plug-in

access
2017| TCP| OUT| Connection to the CLSS Gateway
4016| TCP| IN| Database import/export**

EQUIPMENT

REQUIRED

PART NUMBER DESCRIPTION DATA SHEET MANUAL
HON-CGW-MBB CLSS Gateway HON- 62034 LS10248-000HW-E
50160636- 001 CLSS Gateway Kit: 30” NUP Cable + Lock & Key set
HON- 62034 LS10248-000HW-E
LAN-Connected Horizon – One-Time Activation **Gateway Feature License
(per gateway)**   LS10315-000HW-E
LAN-Connected Horizon – 5-year Subscription **Horizon Software
Subscription** HON- 62125 LS10315-000HW-E
  Standalone INSPIRE or ONYX Series Panels or NOTI-FIRE-NET TM
Network (5.0 or higher) DN- 6971 51584

OPTIONAL

PART NUMBER DESCRIPTION DATA SHEET MANUAL
CCM-ATT-HON CLSS Gateway Cellular Module (AT &T) **for CLSS Mobile
applications (Internet Required)** HON- 62034 LS10248-000HW-E
CCM-VZ-HON CLSS Gateway Cellular Module **(Verizon) for CLSS Mobile
applications (Internet Required)** HON- 62034

LS10248-000HW-E
32351718- 001| 10’ NUP Cable for CLSS Gateway| HON- 62034| LS10248-000HW-E
Enhanced Monitoring| Subscription. Live Fire System Status vis CLSS Mobile App & Web Browser|  |
CheckPoint Premium| Subscription. CLSS Mobile ITM Tool|  |
NCM- W/F| Standard speed network cards for network applications| DN- 6861| 51533
 | NOTI-FIRE-NET network (5.0 or higher)| DN- 6971| 51584
HS NCM-xxx| High-speed network cards for high-speed network applications| DN- 60454| 54014
 | High-speed NOTI-FIRE-NET| DN- 60455| 54013

ARCHITECTURE

CAMPUS APPLICATION

References