AEMC PEL 52 Power and Energy Logger User Manual

June 16, 2024
AEMC

PEL 52 Power and Energy Logger

Product Information: Power & Energy Logger

Specifications:

  • Model: PEL 52
  • Serial #: 2137.69 / 2137.71

Introduction

The Power & Energy Logger is a device that allows you to
measure and record power and energy consumption. It is designed to
meet the instrument’s published specifications and comes with a
guarantee of compliance.

Precautions for Use

Before using the Power & Energy Logger, please take note of
the following precautions:

  • Read the user manual carefully before operation.

  • Ensure proper grounding and electrical safety measures are in
    place.

  • Avoid exposing the device to extreme temperatures or
    humidity.

  • Do not use the device in explosive or hazardous
    environments.

  • Keep the device away from water and other liquids.

Receiving Your Shipment

When you receive your Power & Energy Logger, please follow
these steps:

  1. Inspect the package for any signs of damage during
    transit.

  2. If there is any damage, contact our customer support
    immediately.

  3. Check that all the components listed in the user manual are
    included in the package.

  4. If any component is missing, contact our customer support for
    assistance.

Ordering Information

To order accessories or replacement parts for your Power &
Energy Logger, please refer to the following information:

  • Accessories: A list of available accessories
    can be found in the user manual. Please visit our website at
    www.aemc.com/accessories to place your order.

  • Replacement Parts: If you need to replace any
    part of the device, please refer to the user manual for the list of
    replacement parts. Contact our customer support for assistance in
    ordering the required parts.

Charging the Battery

To ensure proper operation, it is important to charge the
battery of your Power & Energy Logger. Please follow these
steps:

  1. Connect the provided charger to the device’s charging
    port.

  2. Plug the charger into a power outlet.

  3. Allow the battery to charge fully before disconnecting the
    charger.

  4. Once fully charged, disconnect the charger from the
    device.

Product Features

The Power & Energy Logger comes with the following
features:

  • Advanced power and energy measurement capabilities.
  • Multiple measurement modes for different applications.
  • Remote user interface for easy monitoring and control.
  • Information display for real-time data and settings.

Setup

Turning the Instrument On and Off

To turn on the Power & Energy Logger, follow these
steps:

  1. Press the power button located on the device.
  2. The device will boot up and display the main menu.

To turn off the Power & Energy Logger, follow these
steps:

  1. Press and hold the power button until the device shuts
    down.

  2. Disconnect the device from any power source.

Auto Off

The Power & Energy Logger is equipped with an auto-off
feature that automatically turns off the device after a period of
inactivity. To adjust the auto-off settings, please refer to the
user manual.

Battery Operation

The Power & Energy Logger can be operated using its built-in
battery. To switch to battery operation, disconnect the device from
any external power source. The battery status can be checked in the
information display.

Remote User Interface

The Power & Energy Logger can be accessed and controlled
remotely using a computer or mobile device. Please refer to the
user manual for instructions on how to connect and use the remote
user interface.

Information

The Power & Energy Logger provides detailed information
about measured values, settings, and system status. To access the
information display, navigate to the corresponding menu option and
follow the on-screen instructions.

Operation

Distribution Networks & Connections of the PEL

The Power & Energy Logger supports different distribution
network configurations. Follow the appropriate instructions based
on your specific setup:

Single-Phase 2-wire: 1P-2W1I

To connect the Power & Energy Logger in a single-phase
2-wire configuration, follow these steps:

  1. Identify the two wires representing the phase and neutral.
  2. Connect the phase wire to the L1 terminal of the device.
  3. Connect the neutral wire to the N terminal of the device.
  4. If available, connect an optional current sensor to the CT
    terminal.

Single-Phase 3-wire 2-currents: 1P-3W2I

To connect the Power & Energy Logger in a single-phase
3-wire 2-currents configuration, follow these steps:

  1. Identify the three wires representing the two phases and
    neutral.

  2. Connect one phase wire to the L1 terminal of the device.

  3. Connect the other phase wire to the L2 terminal of the
    device.

  4. Connect the neutral wire to the N terminal of the device.

  5. If available, connect two optional current sensors to the CT1
    and CT2 terminals.

Split-phase 3-wire (split-phase from a mid-tap transformer):

2P-3W2I

To connect the Power & Energy Logger in a split-phase 3-wire
configuration, follow these steps:

  1. Identify the three wires representing the two phases and
    neutral.

  2. Connect one phase wire to the L1 terminal of the device.

  3. Connect the other phase wire to the L2 terminal of the
    device.

  4. Connect the neutral wire to the N terminal of the device.

  5. If available, connect two optional current sensors to the CT1
    and CT2 terminals.

Recording

The Power & Energy Logger can record power and energy
consumption over a specific period. To start recording, navigate to
the recording menu and follow the on-screen instructions to set the
recording parameters.

Measured Value Display Modes

The Power & Energy Logger provides different display modes
for the measured values. Select the appropriate mode based on your
requirements:

Measurement Mode

In the measurement mode, the Power & Energy Logger displays
real-time measurements of voltage, current, power, and other
relevant parameters. Navigate to the measurement mode menu option
to view the measurements.

Energy Mode

In the energy mode, the Power & Energy Logger displays
accumulated energy consumption over a specific period. Navigate to
the energy mode menu option to view the energy consumption
data.

Maximum Mode

In the maximum mode, the Power & Energy Logger displays the
maximum values recorded for voltage, current, power, and other
parameters. Navigate to the maximum mode menu option to view the
maximum values.

FAQ

Q: How often should I calibrate my Power & Energy

Logger?

A: The recommended calibration interval for this instrument is
12 months. Calibration should be performed starting from the date
of receipt by the customer. For recalibration, please use our
calibration services. Refer to our repair and calibration section
at www.aemc.com/calibration for more information.

Q: Can I request an NIST traceable certificate for my Power

& Energy Logger?

A: Yes, an NIST traceable certificate may be requested at the
time of purchase or obtained by returning the instrument to our
repair and calibration facility for a nominal charge.

User Manual ENGLISH
Power & Energy Logger
Model PEL 52
POWER & ENERGY LOGGER
WITH AEMC® INSTRUMENTS

Copyright© Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All rights reserved.
No part of this documentation may be reproduced in any form or by any means (including electronic storage and retrieval or translation into any other language) without prior agreement and written consent from Chauvin Arnoux®, Inc., as governed by United States and International copyright laws.
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 15 Faraday Drive · Dover, NH 03820 USA Tel: 800-945-2362 or 603-749-6434 · Fax: 603-742-2346
This documentation is provided as is, without warranty of any kind, express, implied, or otherwise. Chauvin Arnoux®, Inc. has made every reasonable effort to ensure that this documentation is accurate; but does not warrant the accuracy or completeness of the text, graphics, or other information contained in this documentation. Chauvin Arnoux®, Inc. shall not be liable for any damages, special, indirect, incidental, or inconsequential; including (but not limited to) physical, emotional or monetary damages due to lost revenues or lost profits that may result from the use of this documentation, whether or not the user of the documentation has been advised of the possibility of such damages.

Statement of Compliance
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments certifies that this instrument has been calibrated using standards and instruments traceable to international standards.
We guarantee that at the time of shipping your instrument has met the instrument’s published specifications.
An NIST traceable certificate may be requested at the time of purchase, or obtained by returning the instrument to our repair and calibration facility, for a nominal charge.
The recommended calibration interval for this instrument is 12 months and begins on the date of receipt by the customer. For recalibration, please use our calibration services. Refer to our repair and calibration section at www.aemc.com/calibration.

Serial #: Catalog #: Model #:

2137.69 / 2137.71 PEL 52

Please fill in the appropriate date as indicated: Date Received: Date Calibration Due:

Chauvin Arnoux®, Inc. d.b.a AEMC® Instruments www.aemc.com

TABLE OF CONTENTS
1. INTRODUCTION……………………………………………………………..7
1.1 PRECAUTIONS FOR USE …………………………………………………….. 8 1.2 RECEIVING YOUR SHIPMENT …………………………………………….. 8 1.3 ORDERING INFORMATION………………………………………………….11
1.3.1 Accessories…………………………………………………………………..11 1.3.2 Replacement Parts ………………………………………………………..11 1.4 CHARGING THE BATTERY ………………………………………………… 12
2. PRODUCT FEATURES………………………………………………….13
2.1 DESCRIPTION……………………………………………………………………. 13 2.2 INSTRUMENT FRONT PANEL ……………………………………………. 14 2.3 INSTRUMENT TERMINAL BLOCK ……………………………………… 14 2.4 INSTRUMENT REAR PANEL ……………………………………………… 15 2.5 SD CARD SLOT………………………………………………………………….. 15 2.6 MOUNTING………………………………………………………………………… 16 2.7 BUTTON FUNCTIONS………………………………………………………… 16 2.8 LCD DISPLAY …………………………………………………………………….. 17 2.9 MEMORY CARD…………………………………………………………………. 19
3. SETUP ………………………………………………………………………….20
3.1 TURNING THE INSTRUMENT ON AND OFF ………………………. 20 3.1.1 Turning On…………………………………………………………………… 20 3.1.2 Auto Off ………………………………………………………………………. 20 3.1.3 Turning Off ………………………………………………………………….. 20 3.1.4 Battery Operation…………………………………………………………. 21
3.2 CONFIGURING THE INSTRUMENT……………………………………. 21 3.2.1 Network Type………………………………………………………………. 21 3.2.2 Wi-Fi ………………………………………………………………………….. 22 3.2.3 Nominal Primary Current………………………………………………. 26 3.2.4 Aggregation Period………………………………………………………. 27 3.2.5 Reset …………………………………………………………………………. 27
3.3 REMOTE USER INTERFACE ……………………………………………… 28 3.4 INFORMATION …………………………………………………………………… 30
4. OPERATION …………………………………………………………………32
4.1 DISTRIBUTION NETWORKS & CONNECTIONS OF THE PEL …… 32 4.1.1 Single-Phase 2-wire: 1P-2W1I ……………………………………….. 32 4.1.2 Single-Phase 3-wire 2-currents: 1P- 3W2I ……………………….. 33 4.1.3 Split-phase 3-wire (split-phase from a mid-tap transformer): 2P-3W2I……………………………………………………………………………… 33

4.2 RECORDING ……………………………………………………………………… 34

4.3 MEASURED VALUE DISPLAY MODES……………………………….. 34

4.3.1 Measurement Mode ………………………………………………. 35

4.3.2 Energy Mode ……………………………………………………….. 37

4.3.3 Maximum Mode

…………………………………………………… 38

5. PEL CONTROL PANEL – DATAVIEW® …………………………..41

5.1 INSTALLING DATAVIEW® …………………………………………………….41

5.2 PEL CONTROL PANEL ………………………………………………………. 45

6. SPECIFICATIONS …………………………………………………………46

6.1 REFERENCE CONDITIONS ……………………………………………….. 46

6.2 ELECTRICAL PROPERTIES……………………………………………….. 46

6.2.1 Voltage Inputs ……………………………………………………………… 46

6.2.2 Current Inputs……………………………………………………………… 47

6.2.3 Intrinsic Uncertainty (Excluding Current Sensors) ……………. 47

6.2.3.1 PEL Specifications …………………………………………….. 47

6.2.4 Current Sensors ………………………………………………………….. 49

6.2.4.1 Precautions For Use…………………………………………… 49

6.2.4.2 Characteristics ………………………………………………….. 50

6.2.4.3 Intrinsic Uncertainty …………………………………………… 54

6.3 VARIATION IN THE FIELD OF USE…………………………………….. 56

6.3.1 General ………………………………………………………………………. 56

6.3.2 Temperature ……………………………………………………………….. 56

6.3.3 Humidity……………………………………………………………………… 56

6.3.4 Continous Component………………………………………………….. 56

6.3.5 Frequency…………………………………………………………………… 56

6.3.6 Bandwidth…………………………………………………………………… 57

6.3.7 Disturbed Signals ………………………………………………………… 57

6.4 POWER SUPPLY………………………………………………………………… 57

6.5 ENVIRONMENTAL CHARACTERISTICS…………………………….. 58

6.6 Wi-Fi…………………………………………………………………………………… 58

6.7 MECHANICAL CHARACTERISTICS …………………………………… 58

6.8 ELECTRICAL SAFETY ……………………………………………………….. 59

6.9 ELECTROMAGNETIC COMPATIBILITY………………………………. 59

6.10 RADIO EMISSION …………………………………………………………….. 59

6.11 MEMORY CARD ……………………………………………………………….. 59

7. MAINTENANCE…………………………………………………………….60
7.1 CLEANING………………………………………………………………………….. 60 7.2 BATTERY……………………………………………………………………………. 60 7.3 UPDATING FIRMWARE ………………………………………………………. 61 7.4 REPAIR AND CALIBRATION ………………………………………………. 61 7.5 TECHNICAL AND SALES ASSISTANCE ……………………………… 62 7.6 LIMITED WARRANTY…………………………………………………………. 62
7.6.1 Warranty Repairs …………………………………………………………. 63
8. APPENDIX ………………………………………………………………….. 64
8.1 MEASUREMENTS………………………………………………………………. 64 8.1.1 Definition …………………………………………………………………….. 64 8.1.2 Sampling …………………………………………………………………….. 64 8.1.2.1 1 s (one second) Quantities…………………………………. 64 8.1.2.2 Aggregation ………………………………………………………. 65 8.1.2.3 Minimum and Maximum ……………………………………… 65 8.1.2.4 Calculation of Energies ………………………………………. 65
8.2 MEASUREMENT FORMULAS…………………………………………….. 65 8.3 AGGREGATION………………………………………………………………….. 66 8.4 SUPPORTED ELECTRICAL NETWORKS …………………………… 67 8.5 VALUES AVAILABLE ………………………………………………………….. 68 8.6 GLOSSARY………………………………………………………………………… 70

1. INTRODUCTION
Thank you for purchasing an AEMC® Instruments Power & Energy Logger Model PEL 52.
For the best results from your instrument and for your safety, you must read the enclosed operating instructions carefully and comply with the precautions for use. Only qualified and trained operators should use this product. Symbols & Definitions
Signifies that the instrument is protected by double or reinforced insulation
CAUTION – Risk of Danger! Indicates a WARNING. Whenever this symbol is present, the operator must refer to the user manual before operation Indicates a risk of electric shock. The voltage at the parts marked with this symbol may be dangerous
Indicates Important information to acknowledge
Magnet
SD Card
This product complies with the Low Voltage & Electromagnetic Compatibility European directives
The product has been declared recyclable
In the European Union, this product is subject to a separate collection system for recycling electrical and electronic components in accordance with directive WEEE 2012/19/EU Chauvin Arnoux® and AEMC® Instruments have adopted an Eco-Design approach in order to design this instrument. Analysis of the complete lifecycle has enabled us to control and optimize the effects of the product on the environment. In particular this instrument exceeds regulation requirements with respect to recycling and reuse
Definition of Measurement Categories (CAT) CAT IV corresponds to measurements performed at the primary electrical supply (< 1000 V). Example: primary overcurrent protection devices, ripple control units, and meters. CAT III corresponds to measurements performed in the building installation at the distribution level. Example: hardwired equipment in fixed installation and circuit breakers. CAT II corresponds to measurements performed on circuits directly connected to the electrical distribution system. Example: measurements on household appliances and portable tools.

Power & Energy Logger Model PEL 52 – User Manual

7

1.1 PRECAUTIONS FOR USE
This device complies with safety standard IEC/EN 61010-2-30 or BS EN 61010-2-030. The leads comply with IEC/EN 61010-031 or BS EN 61010-031. The current sensors comply with IEC/EN 61010-2-032 or BS EN 61010-2-032 for voltages up to 600 V in CAT III.
Failure to observe the safety instructions may result in electric shock, fire, explosion, destruction of the device, or destruction of the installations.
The operator and responsible authority must read and understand all precautions needed before using the instrument. This instrument requires the user to have knowledge and awareness of electrical hazards.
Use only the supplied leads and accessories. If you use leads or accessories with a lower voltage or category rating than the instrument, the combined instrument, leads, and accessories are limited to the lower voltage or category rating of the leads or accessories.
Before each use, check the condition of the insulation on the leads, housing, and accessories. Any items with a degree of deteriorated insulation must be set aside to repair or discard.
Do not use the instrument on networks where the voltage or category exceeds the instrument’s specifications.
Do not use the instrument if it seems to be damaged, incomplete, or poorly closed.
When removing and inserting the SD card, the device must be disconnected and turned off.
Use personal protection equipment when applicable.
When handling the leads and alligator clips, keep your fingers behind the physical guard.
If the device is wet, dry it before use.
All troubleshooting and calibration checks must be performed by competent, accredited personnel.
1.2 RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier, and notify your distributor at once with a detailed description of any damage. Save the damaged packing container to substantiate your claim.

8

Power & Energy Logger Model PEL 52 – User Manual

PRODUCT PACKAGING (2137.69)

Power & Energy Logger PEL 52
Cat. #2137.69

Soft Carrying Bag Cat. #2126.71

(2) MiniFlex® MA193-10-BK Cat. #2140.48

Adapter for Power Cord Cat. #5100.14

(1) USB SD Card Adapter Cat. #5000.45

(1) Power Cord, 5 ft 115 V
Cat. #5000.14

(1) 4 GB USB Drive with User Manual & Dataview® Software

(3) Black Leads & Alligator Clips Cat. #2140.44

Also Included: (1) Safety Sheet for the PEL (1) Safety Sheet for the MiniFlex® Sensors (1) Compliance Sheet (1) SD Card (1) Quick Start Guide (2) AAA Rechargeable Batteries (1) Battery Information Sheet

Power & Energy Logger Model PEL 52 – User Manual

9

PRODUCT PACKAGING (2137.71)

Power & Energy Logger PEL 52
Cat. #2137.71

Soft Carrying Bag Cat. #2126.71

(1) Power Cord, 5 ft 115 V
Cat. #5000.14

Adapter for Power Cord Cat. #5100.14

(1) USB SD Card Adapter Cat. #5000.45

(3) Black Leads & Alligator Clips Cat. #2140.44

(1) 4 GB USB Drive with User Manual & Dataview® Software

Also Included: (1) Safety Sheet for the PEL (1) Compliance Sheet (1) SD Card (1) Quick Start Guide (2) AAA Rechargeable Batteries (1) Battery Information Sheet

10

Power & Energy Logger Model PEL 52 – User Manual

1.3 ORDERING INFORMATION
Power & Energy Logger Model PEL 52…………………………… Cat. #2137.69 Includes Soft carrying bag, (2) MiniFlex® MA193-10-BK sensors, (3) black test leads and alligator clips, 115 V US power cord, adapter for power cord, SD card, USB SD card adapter, (2) AAA rechargeable batteries (installed), quick start guide, and USB drive with DataView® software and User Manual. Power & Energy Logger Model PEL 52 (No Probes) ……….. Cat. #2137.71 Includes Soft carrying bag, (3) black test leads and alligator clips, 115 V US power cord, adapter for power cord, SD card, USB SD card adapter, (2) AAA rechargeable batteries (installed), quick start guide, and USB drive with DataView® software and User Manual.
1.3.1 Accessories
AC Current Probe Model MN93-BK…………………………………… Cat. #2140.32 AC Current Probe Model SR193-BK………………………………….. Cat. #2140.33 AC Current Probe Model MN193-BK …………………………………. Cat. #2140.36 AmpFlex® Sensor 24 in Model 193-24-BK………………………….. Cat. #2140.34 AmpFlex® Sensor 36 in Model 193-36-BK………………………….. Cat. #2140.35 MiniFlex® Sensor 10 in Model MA193-10-BK………………………. Cat. #2140.48 MiniFlex® Sensor 14 in Model MA193-14-BK ……………………… Cat. #2140.50 MiniFlex® Sensor 24 in Model MA194-24-BK ……………………… Cat. #2140.80 AC Current Probe Model MN94 ………………………………………… Cat. #2140.81 Set of 2, color-coded (red/black) magnetized voltage probes (Rated 600 V CAT IV, 1000 V CAT III)………….. Cat. #5000.43 Set of 12, color input ID markers for the PowerPad Series …… Cat. #2140.45
1.3.2 Replacement Parts
Lead ­ (1) 10 ft (3 m) Black Lead with (1) Black Alligator Clip Lead rated 1000 V CAT IV 15 A, Clip rated 1000 V CAT IV 15 A, UL for PowerPad & PEL Series …………………….. Cat. #2140.44 USB SD – card adapter for PEL 102, PEL 103 & PEL 52………. Cat. #5000.45
Order Accessories and Replacement Parts Directly Online Check our Storefront at www.aemc.com/store for availability
Dataview® Software Updates are Available at www.aemc.com

Power & Energy Logger Model PEL 52 – User Manual

11

1.4 CHARGING THE BATTERY
Before using the device for the first time, fully charge the battery at a temperature between (50 to 104) °F (10 to 40) °C.

It takes approximately 5 h to charge a discharged battery.

PEL 52
POWER & ENERGY LOGGER

90 … 690 V 50 … 60 Hz

Figure 2

Connect the C8 / banana adapter between the V1 and N terminals.

Plug the power cord into the adapter and into the wall outlet.

The device will turn on.

When charging, the

symbol will blink and slowly fill up. When the

is full and steady, the battery is fully charged.

symbol

NOTE: The battery will take approximately 5 h to fully charge.

12

Power & Energy Logger Model PEL 52 – User Manual

2. PRODUCT FEATURES
2.1 DESCRIPTION
The Power & Energy Logger Model PEL 52 is an easy-to-use, single-phase, and split-phase Power and Energy Logger. The instrument has a large, backlit LCD display for crisp viewing and an SD card to store measurements. Designed to operate in 600 V CAT III or lower environments. The PEL records voltage, current, power, and energy on alternating current distribution networks (50 Hz or 60 Hz). The instrument is compact enough to fit into many different distribution panels, has a water and shock resistant housing, operates on phase 1 input, and has a backup battery that charges from the V1 input during measurements. The following measurements and calculations can be made:
Phase-to-neutral and phase-to-phase voltage measurements up to 600 V
Current measurements up to 25,000 A, current sensor dependent
Automatic recognition of the different types of current sensors Frequency measurements
Measurements of active power P (W), fundamental reactive power Q (var), and apparent power S (VA) power
Measurements of fundamental active power Pf (W), non-active power N (var), and distorting power D (var) using the PEL Control Panel
Measurements of active energy at source and load (W·h), reactive energy on 4 quadrants (varh), and apparent energy (VAh)
Total energy meter
Calculation of cos and power factor (PF) Phase angle measurement
Calculation of aggregations of values from 1 minute to 1 hour
In addition to the types of measurements, the PEL 52 offers the following features:
Storage of values on SD or SDHC card
Communication via Wi-Fi
PEL Control Panel for data recovery, configuration, communication in real time with a PC, and Dataview® software for report generation and analyzing
Web Server Interface which includes VNC mode function. When IP address is known, instrument status can be displayed from any web browser
Connection to DataViewSyncTM to communicate between private networks

Power & Energy Logger Model PEL 52 – User Manual

13

2.2 INSTRUMENT FRONT PANEL

Measuring terminals

Backlit LCD display
Navigation keys

Select button
SD Card slot

Figure 3

2.3 INSTRUMENT TERMINAL BLOCK

V2

I2

I1

600 V max

V1

N

600 V CAT III

On / Off button

3 voltage inputs (safety banana inputs 4 mm)
2 current inputs (specific 4-point sockets) Figure 4

NOTE: Before connecting a current sensor, consult the sensor’s corresponding safety data sheet or user manual. Also, the PEL must not be used when the SD card slot is open.

14

Power & Energy Logger Model PEL 52 – User Manual

2.4 INSTRUMENT REAR PANEL

2 magnets

4 non-slip pads

Figure 5
2.5 SD CARD SLOT
Before opening the SD card slot, disconnect the device, and turn it off. To unlock the protective cover, turn the screw a quarter turn. Open the protective cover to access the SD card. To remove the SD card, press it in until you hear a click, and then release. To insert the SD card, hold the PEL device with front panel facing up. With the
contacts on the SD card facing up and forward, gently push card straight into the card slot until you hear a click.
SD Card Slot

Screw Protective Cover

Figure 6

Power & Energy Logger Model PEL 52 – User Manual

15

2.6 MOUNTING
The PEL must be placed in a well-ventilated room where the temperature must not exceed the values specified in § 6.5.
The PEL can be mounted on a flat, ferromagnetic surface using the magnets incorporated in the PEL’s housing.

NOTE: The strong magnets can damage hard drives or medical devices.
2.7 BUTTON FUNCTIONS

Button

Description
ON / OFF Button A long press will turn the device ON or OFF. The device cannot be turned off while a recording is pending or in progress.

Select Button When pressed, this button allows the user to start or stop a recording and allows Wi-Fi mode to be chosen.

Navigation Buttons These buttons are used to configure the device and browse displayed
data.

Enter Button In configuration mode, cycles through the available setting options and determines the applied setting. In measurement and power display modes, displays phase angles. In select mode, starts or stops a recording after the Select button is
pressed. It also allows the type of Wi-Fi to be chosen.

Table 1 If any button is pressed, the backlight will turn on for 3 minutes.

16

Power & Energy Logger Model PEL 52 – User Manual

2.8 LCD DISPLAY

10

1

9

8 7

6

2

5

4

3 1. Mode indicators

Figure 7

Measurement mode (§ 4.3.1) Power and Energy mode MAX Mode (§ 4.3.3) Information mode (§ 3.4) Configuration mode (§ 3.2)

2. Display for data and messages
3. Power ON: Instrument is running on external USB power. Blinking: Instrument is running on external USB power and communicating via USB. OFF: Instrument is running on internal (battery) power.
4. Permanent mode ON: Permanent mode is enabled, so the instrument will not automatically power down. OFF: Permanent mode is disabled, so the instrument will automatically power down after a period of inactivity as defined by the PEL Control Panel.
5. Wi-Fi Direct ON (steady): Wi-Fi Direct is enabled and not transmitting. Blinking: Wi-Fi Direct is actively transmitting. OFF: Wi-Fi Direct is disabled.

Power & Energy Logger Model PEL 52 – User Manual

17

6. Wi-Fi (router connection ) ON (steady): Wi-Fi connection is enabled and not transmitting. Blinking: Wi-Fi is actively transmitting. OFF: Normal Wi-Fi connection is disabled.
7. Overload ON: At least one input is out of range and cannot be displayed. OFF: All inputs are within range.
8. Recording ON (steady): A recording is in progress. Blinking: A recording is pending. Blinking (slowly): A recording is in progress in extended recording mode. OFF: A recording is neither scheduled nor in progress.
9. Memory Empty : Instrument memory is empty. Partially filled : Instrument memory is partially full. Filled : Instrument memory is full. No recordings can be stored while the memory is full. To erase all memory use the Format SD Card button in the PEL Control Panel. The Delete Session Button can be used to erase selected recordings. For more information reference the Help File.
10. Battery Empty : The battery must be charged. Partially filled : The battery is partially charged. Filled : The battery is fully charged. Blinking: The battery is charging.

18

Power & Energy Logger Model PEL 52 – User Manual

2.9 MEMORY CARD

The PEL accepts FAT32 formatted SD and SDHC cards with 32 GB or less. The SD card must be formatted as 32 GB on a PC.

The PEL is delivered with a formatted SD card. If you want to install a new SD card:

Open the SD card slot protective cover marked

(see § 2.5).

Press the device’s current SD card in until you hear a click. The device will release the SD card.

Remove the SD card.

NOTE: Do not remove SD Card if a recording is in progress. Check that the new SD card is unlocked.

unlocked

LOCK

Format the SD card. The PEL Control Panel is the best way to format the SD card; otherwise, format the SD card using a PC.
Insert the new SD card. Press it in all the way until you hear a click (see § 2.5).
Close the SD card protective cover.

Power & Energy Logger Model PEL 52 – User Manual

19

3. SETUP
The PEL must be configured before any recording. Follow the below steps to configure the PEL: Establish a Wi-Fi connection with the PC (to use the PEL Control Panel, see § 5). Select the connection according to the type of distribution network. Connect the current sensor(s). Define the nominal primary current according to the current sensor used. Select the aggregation period.
To configure the device, you can use the Configuration mode (see § 3.2) or the PEL Control Panel.
NOTE: To avoid accidental changes, the PEL cannot be configured while recording or if a recording is pending.

3.1 TURNING THE INSTRUMENT ON AND OFF

3.1.1 Turning On

Connect the PEL to Network between the V1 and N, and it will turn on automatically. Otherwise, press and hold the ON/OFF button until the device turns on. If the instrument displays LOCK, the selection button is locked. The PEL Control Panel must be used to unlock the instrument (see § 5).
The battery will charge automatically when the PEL is connected to a voltage source between the V1 and N terminals. Battery life is approximately one hour when fully charged. This allows the device to continue operating during brief power cuts.

3.1.2 Auto Off
By default, the device operates in continuous mode, which is indicated by the symbol.
When the device is running on battery power, you can choose to have it turn off automatically after a period with no keyboard activity and no recording in progress to save battery life. This time will be defined in the PEL Control Panel (see § 5).

3.1.3 Turning Off
You cannot turn the PEL off while it is connected to a power source or while a recording is in progress or pending. This is a precaution intended to prevent a recording from being unintentionally stopped by the user.
To turn the PEL off: Disconnect the PEL.
Press and hold the ON/OFF button until the device turns off.

20

Power & Energy Logger Model PEL 52 – User Manual

3.1.4 Battery Operation
Powering the device from the network can disturb the in-progress measurement for certain applications, such as low fan-out generators.
To operate on the battery alone, press the and buttons simultaneously.
The symbol will blink. Use the same combination of buttons to return to powering from the network. After being turned off, the instrument will restart by being powered by the voltage at the terminals.
3.2 CONFIGURING THE INSTRUMENT
Several main functions can be configured directly on the device. For full configuration, use the PEL Control Panel (see § 5) once Wi-Fi communication has been established.
To enter Configuration mode from the device, press the or buttons until the symbol is selected.
The following screen is displayed:

Figure 8
NOTE: If the PEL is already being configured from the PEL Control Panel, it is not possible to enter Configuration mode on the device. In this situation, when an attempt is made to configure the device, the screen will display LOCK.

3.2.1 Network Type

To change the network, press the

button.

1P-2W1I: Single-phase 2-wire with a current sensor

1P-3W2I: Single-phase 3-wire (2 voltages in phase) with two current sensors

2P-3W2I: Split-phase 3-wires (2 voltages in opposite phases) with two current sensors

Power & Energy Logger Model PEL 52 – User Manual

21

3.2.2 Wi-Fi
From the initial screen, press the button to access the following screen.

Figure 9

NOTE: For the Wi-Fi to operate, the battery must be sufficiently charged ( or ).

Press the

button to activate or deactivate the Wi-Fi. The device will indicate

if the battery is too low to enable Wi-Fi.

To establish a Wi-Fi connection
Enable Wi-Fi.
This connection will then allow you to connect your instrument to another device, such as a PC, smartphone, or tablet. The connection procedure is detailed below.

Wi-Fi access point connection procedure
The first connection must be made in Wi-Fi access point mode.
Press the Select button first. The device will display START REC. PUSH ENTER TO START RECORDING.
Press the Select button a second time, and the device will display WIFI ST. PUSH ENTER FOR WIFI ST, WIFI OFF. PUSH ENTER FOR WIFI OFF or WIFI AP. PUSH ENTER FOR WIFI AP.

Figure 10

Figure 11

22

Power & Energy Logger Model PEL 52 – User Manual

Use the

button to select WIFI AP.

Your device’s IP address is 192.168.2.1 3041 UDP and is shown in the Information menu.
Connect your PC to the device’s Wi-Fi. In the Windows status bar, click the connection symbol.
Select your device from the list.

Figure 12
Start the PEL Control Panel (see § 5). Go to Instrument, Add an Instrument, PEL 52, to Wifi access point. When you are connected to the PEL Control Panel, you will be able to:
Configure the device. Access real-time measurements. Download the recordings. Change the access point SSID name and secure it with a password. Enter the SSID and password for a Wi-Fi network to which the device can
connect. Enter the DataViewSyncTM password. This allows the device to access
separate private networks.
If the username and password are lost, you can reset them to the factory configuration (see § 3.2.5).
Wi-Fi connection procedure (continued) Once your device is connected as a Wi- Fi access point, you can connect it to a Wi-Fi router. This will allow you to access your device from a smartphone, tablet, or even from DataViewSyncTM through a public or private network.

Power & Energy Logger Model PEL 52 – User Manual

23

Configuration of the Wi-Fi router connection

In the PEL Control Panel, go to the Configuration menu

,

Communication tab, and enter the network name (SSID) and password in

the Wifi Station mode (STA) dialog box, port 3041, UDP protocol.

The SSID is the name of your desired network, such as the network of your smartphone or tablet in access point mode.

Figure 13

Click OK to apply the configuration to the device.

Press the Select to WIFI ST.

button twice and the Enter

button twice to switch

Your device will connect to this Wi-Fi network.

The Wi-Fi access point connection will be lost.

Once the PEL is connected to the network, you can find the PEL’s IP address in information mode .

24

Power & Energy Logger Model PEL 52 – User Manual

In the PEL Control Panel, change the connection

to Ethernet

(LAN or Wi-Fi), and enter the IP address of your device, port 3041, UDP protocol. This lets you connect several PEL instruments on the same network.

Figure 14
Configuration of the DataViewSyncTM connection To connect the PEL to DataViewSyncTM, the PEL must be in WIFI ST,
and the connected network must have internet access in order to access DataViewSyncTM.

Power & Energy Logger Model PEL 52 – User Manual

25

In the PEL Control Panel, go to the Configuration menu

and then the

Communication tab. Enable DataViewSyncTM, and enter the password that will

be used to connect afterwards.

Figure 15
3.2.3 Nominal Primary Current
From the Wi-Fi screen, press the button to access the following screen.

Figure 16

Connect the current sensor(s).

The current sensor is automatically detected by the device.

If two current sensors are connected, they must be identical.

For AmpFlex® or MiniFlex® sensors, press the

button to select 300 A or 3000 A.

26

Power & Energy Logger Model PEL 52 – User Manual

The nominal currents of current sensors are as follows:

Sensor
SR193 clamp AmpFlex® 193 MiniFlex® MA193 or MA194

Nominal current 1000 A
(300 or 3000) A

MN193 clamp 5 A range

5 A

MN193 clamp 100 A range MN93 clamp MN94 clamp

100 A 200 A 200 A

Choice of gain –

to be configured in PEL Control Panel

Number of turns –
1, 2, or 3 to be configured in PEL Control Panel

Table 2
3.2.4 Aggregation Period
From the nominal primary current screen, press the key to access the following screen.

Figure 17
To change the aggregation period, press the 15, 20, 30, or 60 minutes.

key: 1, 2, 3, 4, 5, 6, 10, 12,

3.2.5 Reset
From the aggregation period screen, press the key to access the following screen.

Figure 18

To reset the device to the default Wi-Fi configuration (direct Wi-Fi, password

deleted), press the

key.

Power & Energy Logger Model PEL 52 – User Manual

27

It is possible to reset the Wi-Fi settings and other settings in the Set-up menu. The default settings are:

AP Mode: WIFI Mode:
DataViewSyncTM: Remote Password
Protection: SELECT Button:
Recording:

– SSID = PEL52-[serial_number] – Authentication = Open – No SSID – No Password – Protocol = UDP – Port = 3041 – Enabled
NOTE the DataViewSyncTM password is not reset – No password protection
– Unlocked
– Reset during recordings in progress is not possible (set-up is locked).

The device will ask for confirmation before performing the reset. Press

the

button to confirm or any other button to cancel.

3.3 REMOTE USER INTERFACE

The remote user interface runs on a PC, tablet or smartphone. It allows you to view device information.

Enable Wi-Fi on the PEL. The remote user interface can work with an access point Wi-Fi link or a router Wi-Fi link but not a DataViewSyncTM link.

On a PC, connect as indicated in § 3.2.2.

On a tablet or smartphone, share a Wi-Fi connection.

In an Internet browser, enter http://device_IP_address.

For a Wi-Fi access point connection, enter http://192.168.2.1

For a Wi-Fi router menu (see § 3.4).

connection, this address is indicated in the information

The following screen will be displayed:

Figure 19

NOTE: Refreshing the display is not automatic. You need to refresh regularly.

28

Power & Energy Logger Model PEL 52 – User Manual

On the second tab, measurements can be viewed:
Figure 20 On the third tab, the device information is displayed:

Figure 21

Power & Energy Logger Model PEL 52 – User Manual

29

On the fourth tab, information on the current or last recording made can be viewed:

Figure 22
3.4 INFORMATION
To enter Information mode, press the or buttons until the selected.
Using the and keys, scroll through the device information: Type of network

symbol is

30

Power & Energy Logger Model PEL 52 – User Manual

Nominal primary current and number of turns: 1t, 2t or 3t (to be defined via PEL Control Panel for Flex type current sensors)

Aggregation period

SR193 clamp: 1000 A AmpFlex® or MiniFlex®:
300 A or 3000 A MN193 clamp 5 A range:
5 A modifiable MN193 clamp 100 A range:
100 A MN93 clamp: 200 A
MN94 clamp: 200 A

Date Year, month, day

Time Hour, minute, second

IP address (scrolling)

Firmware version and scrolling serial number

After configuration is complete, the instrument is ready for use.

Power & Energy Logger Model PEL 52 – User Manual

31

4. OPERATION
4.1 DISTRIBUTION NETWORKS & CONNECTIONS OF THE PEL
Connect the current sensors and voltage measurement leads on your installation according to the type of distribution network.

Source

Load

NOTE: Always check that the arrow on the current sensor points toward the load. If so, the phase angle will be correct for power measurements and other phase dependent measurements. Otherwise, the PEL Control Panel allows a current sensor’s phase to be reversed under certain conditions.
4.1.1 Single-Phase 2-wire: 1P-2W1I
For single-phase 2-wire measurements: Connect the N measuring lead to the neutral conductor. Connect the V1 measuring lead to the L1 phase conductor. Connect the I1 current sensor to the L1 phase conductor.
L1 N
L1 N

V2

I2

I1

600 V max

V1

N

600 V CAT III

Figure 23

32

Power & Energy Logger Model PEL 52 – User Manual

4.1.2 Single-Phase 3-wire 2-currents: 1P-3W2I

For single-phase 3-wire measurements with 2 current sensors: Connect the N measuring lead to the neutral conductor. Connect the V1 measuring lead to the L1-I1 phase conductor. Connect the V2 measuring lead to the L1-I2 phase conductor. Connect the I1 current sensor to the L1-I1 phase conductor. Connect the I2 current sensor to the L1-I2 phase conductor.

L1 N

L1-I2 L1-I1
N

V2

I2

I1

600 V max

V1

N

600 V CAT III

Figure 24

4.1.3 Split-phase 3-wire (split-phase from a mid-tap transformer): 2P-3W2I
For split-phase 3-wire measurements with 2 current sensors: Connect the N measuring lead to the neutral conductor. Connect the V1 measuring lead to the L1 phase conductor. Connect the V2 measuring lead to the L2 phase conductor. Connect the I1 current sensor to the L1 phase conductor. Connect the I2 current sensor to the L2 phase conductor.

L2

L1

N
L1 N L2

V2

I2

I1

600 V max

V1

N

600 V CAT III

Figure 25

Power & Energy Logger Model PEL 52 – User Manual

33

4.2 RECORDING
To start a recording: Check that there is an unlocked SD card (see § 2.9) in the PEL with sufficient
memory space. Press the Select button first. The device will display START if the device
is able to make recordings.

NOTE: If the device displays INSERT SD CARD, there is no SD card in the device. If the device displays SD CARD WRITE PROTECT, the SD card is locked. If either message is displayed, recordings cannot be made.

Use the

button to start the recording. The

times before turning solid.

symbol will blink a few

Use the

button to stop the recording. The

symbol will disappear.

Recordings can be managed from the PEL Control Panel as well (see § 5).
While recording, the device configuration cannot be modified. To enable or disable Wi-Fi, press the Select button twice and then press the Enter button to choose WIFI AP , WIFI ST , or no Wi-Fi, WIFI OFF.

4.3 MEASURED VALUE DISPLAY MODES
The PEL has 3 measurement display modes, Measurement Mode , Energy Mode , and Maximum Mode , represented by the icons at the top of the display. To switch from one mode to another, use the or keys.
The displays can be accessed as soon as the PEL is turned on but the values will be zero. The values will update when voltage or current is present at the inputs.

34

Power & Energy Logger Model PEL 52 – User Manual

4.3.1 Measurement Mode
This mode displays the instantaneous values: voltage (V), current (I), active power (P), reactive power (Q), apparent power (S), frequency (f), power factor (PF), and phase shift (). The display depends on the configured network. Press the key to switch from one screen to the next.

Single-phase 2-wire (1P-2W1I)v

I

(I1, V1)

V

P

f

P

Q

S

PF

If the current sensor is not detected, all the quantities that depend on the current

(current, angle, powers, PF) are undefined (displays

).

Power & Energy Logger Model PEL 52 – User Manual

35

Single-phase 3-wire 2-currents (1P-3W2I) and split-phase 3-wire (2P-3W2I).

I1

(I2, I1)

I2

f

V1

(V2, V1)

V2

U12

f

P

(I1, V1)

Q

S

f

P

(I2, V2)

Q

S

f

P

Q

Sum of powers on L1 and L2.

S

If a current sensor is not detected,

all the quantities that depend

PF1

on this current (current, angle,

PF2

powers, PF) are undefined

(displays

).

36

Power & Energy Logger Model PEL 52 – User Manual

4.3.2 Energy Mode
This mode displays the energy: active energy (Wh), reactive energy (varh), apparent energy (VAh). The energies displayed are the total energies of the source or of the load. The energy depends on the duration. Press the key to switch from one screen to the next. You will scroll successively: Ep+: Total active energy consumed (by the load) in Wh. Ep-: Total active energy supplied (by the source) in Wh. Eq1: Reactive energy consumed (by the load) in the inductive quadrant
(quadrant 1) in varh. Eq2: Reactive energy supplied (by the source) in the capacitive quadrant
(quadrant 2) in varh. Eq3: Reactive energy supplied (by the source) in the inductive quadrant
(quadrant 3) in varh. Eq4: Reactive energy consumed (by the load) in the capacitive quadrant
(quadrant 4) in varh. Es+: Total apparent energy consumed (by the load) in VAh. Es-: Total apparent energy supplied (by the source) in VAh.
NOTE: The device does not display the h symbol. Therefore, you will see W for Wh.

Power & Energy Logger Model PEL 52 – User Manual

37

4.3.3 Maximum Mode
This mode displays the maximum values: maximum aggregated values of measurements and energy. Depending on the option selected in the PEL Control Panel, these may be the maximum aggregated values for the recording in progress or the maximum aggregated values of the last recording, or the maximum aggregated values since the last reset to zero.
Single-phase 2-wire (1P-2W1I)
I1 V1

P

Q

S

P

Q

S

38

Power & Energy Logger Model PEL 52 – User Manual

Single-phase 3-wire 2-currents (1P-3W2I) and split-phase 3-wire (2P-3W2I)
I1 I2

V1 V2 U12
P Q S
P Q S
P Q Sum of powers on the load on L1 and L2. S
P Q S

Power & Energy Logger Model PEL 52 – User Manual

39

P Q S
P Q Sum of powers on the source on L1 and L2. S

40

Power & Energy Logger Model PEL 52 – User Manual

5. PEL CONTROL PANEL – DATAVIEW®
5.1 INSTALLING DATAVIEW®
NOTE: For contextual information on using DataView®, refer to the Help Menu within the DataView® software.
When you purchase the instrument, the product package includes a USB thumb drive containing DataView® program files.
To begin installation: 1. Insert the DataView® thumb drive into an available USB port on your
computer. If Autorun is enabled, an AutoPlay window appears on your screen. Click Open folder to view files to display the DataView® folder. If Autorun is not enabled or allowed, use Windows Explorer to locate and open the USB drive labeled DataView. 2. When the DataView® folder is open, find the Setup.exe file located in
the root directory of the USB drive, and double-click the file to run the installation program. 3. The DataView® setup screen appears.

Figure 26

Power & Energy Logger Model PEL 52 – User Manual

41

In the upper left corner of the screen, choose the language version of the Setup interface. (All Setup screens and dialogs will immediately appear in the selected language.)
In the lower left corner are the available installation options. In addition to the DataView® software, you can select Adobe Reader. This links to the Adobe web site where you can download the latest version of Reader. This program is recommended to view DataView.pdf documents.
The option, Firmware Upgrades, links to the website where you can check for new firmware updates for the PEL.
Finally, the option, User Manuals, displays a list of .pdf files contained in the USB drive that accompanies DataView®. (DataView® also comes with a Help system that is installed with the program files.)
To install DataView®, select DataView in the Options list and click Install.
4. Select the language version of DataView® you want to install (English, French, or Spanish) then click Next. (By default, the language selected in step 3 is highlighted.)

Figure 27

42

Power & Energy Logger Model PEL 52 – User Manual

5. You are now prompted to select the software you want to install.

Figure 28
Each AEMC® Instruments product family has their own specially designed Control Panel. If you perform a Complete install, by default all available Control Panels are selected (a check mark next to the Control Panel indicates it is selected). Control Panels take up disk space on the computer; so unless you have other types of AEMC® instruments, we recommend that you select Power Energy Logger (PEL) only and deselect all other instruments. You should also check the option DataView Core, which is a requirement if you plan to create DataView® reports.
After you finish selecting and deselecting Control Panels and/or DataView Core, click Next.
6. The Setup program now informs you that it is ready to install DataView®. If you want to review any of your previous selections, click the Previous button to return to earlier screens. Otherwise, click Install to begin installation.

Power & Energy Logger Model PEL 52 – User Manual

43

7. The InstallShield program installs the selected software. If an earlier version of the software is already installed on your computer, for each selected program the InstallShield program will: (a) Ask you to confirm the installation of the program. Click Next. (b) Display a status bar indicating the progress of the installation. (c) Inform you when the program is installed. Click Finish to install the next selected program.
If the software is not installed (or if the installed software is the same version as the selected software), the software is installed without requesting confirmation.
When all programs are installed, a message appears informing you of this. Click Finish to return to the Setup screen. 8. You can now select additional Setup options to install (see step 3 above). When finished, click Exit. 9. The DataView® folder now appears on your computer desktop, within which is the PEL Control Panel icon and the icon(s) for any other Control Panel(s) that you have installed. 10. A warning message similar to the one below will appear. Click OK. There is no USB connection on the PEL 52, therefore ignore this automatic message that applies to other devices in the PEL range.
Figure 29
A shortcut has been added to your desktop or Dataview® directory. You can now open PEL Control Panel and connect your PEL to the computer.

44

Power & Energy Logger Model PEL 52 – User Manual

5.2 PEL CONTROL PANEL
Clicking the DataView icon in the DataView® folder on your desktop opens the core DataView® program. Clicking the PEL Control Panel icon opens the PEL Control Panel:

Figure 30
In general, core DataView® features are for creating, viewing, editing, and storing DataView® reports; while the PEL Control Panel is for connecting to, configuring, viewing measurements on, and downloading data from the instrument.
You can access all DataView® features through either the DataView® icon or the Control Panel icon. For users who interact with PEL 100 series instruments, we recommend primarily using the PEL Control Panel. However, there are situations where using the core DataView® icon may be more convenient for some users, such as when viewing multiple archived reports from different AEMC® Instruments product families.
For further information about using the PEL Control Panel, consult the Help system that comes with the product. To access Help, click the option Help in the PEL Control Panel’s menu bar at the top of the screen.

Power & Energy Logger Model PEL 52 – User Manual

45

6. SPECIFICATIONS

6.1 REFERENCE CONDITIONS

Parameter Ambient temperature Relative humidity Voltage Current Phase voltage Input voltage of current inputs (except AmpFlex®/MiniFlex®) Network frequency Harmonics
Preheating
Common mode
Magnetic field Electrical field

Reference conditions (73.4 ± 3.6) °F (23 ± 2) °C (45 to 75) % RH No DC component. No DC component. [100 VRMS; 600 VRMS] without DC (< 0.5 %)
[50 mV; 1.2 V] without DC (< 0.5 %)
(50 ± 0.1) Hz and (60 ± 0.1) Hz < 0.1 % The device must have been powered up for at least one hour. The neutral input and the casing are grounded. The device is powered by the battery. 0 A/m AC 0 V/m AC
Table 3

6.2 ELECTRICAL PROPERTIES
Uncertainties are expressed in % of reading (R) and an offset: ± (a % R + b).
6.2.1 Voltage Inputs

Operating range: Up to 600 VRMS for phase-neutral and phase-phase voltages from (45 to 65) Hz.
NOTE: Phase-to-neutral voltages less than 2 V and 1200 VRMS for phase-to-phase voltages less than 3.4 V are set to zero.

Input impedance: 903 K when the device is running on battery.
When the device is powered by the voltage at the terminals, the impedance on L1 is dynamic and the current source must be able to deliver up to 100 mA at 90 V and 500 mA at 600 V.
Sustained overload: 660 V. Above 690 V, the device will display the OL symbol.

46

Power & Energy Logger Model PEL 52 – User Manual

6.2.2 Current Inputs

NOTE: The outputs from current sensors are voltages.
Operating range: 0.5 mV to 1.7 Vpeak Peak factor: 2 except AmpFlex® / MiniFlex® current sensors (see Table 16) Input impedance: 1 M (except AmpFlex® / MiniFlex® current sensors)
12.4 k (AmpFlex® / MiniFlex® current sensors) Maximum overload: 1.7 V
6.2.3 Intrinsic Uncertainty (Excluding Current Sensors)
With: R: displayed value. Inom: nominal current of the current sensor for an output of 1 V, see Table 14
and Table 16. Pnom and Snom: active and apparent power for V = 230 V, I = Inom and PF = 1. Qnom: reactive power for V = 230 V, I = Inom and sin = 0.5.
6.2.3.1 PEL Specifications

Quantities Frequency (f) Phase-neutral voltage
(V1, V2) Phase-phase voltage
(U12) Current (I1, I2)
Active power (P1, P2, PT)
kW

Measurement range [45 Hz; 65 Hz] [10 V; 600 V]

Intrinsic uncertainty ± 0.1 Hz
± 0.2 % R ± 0.2 V

[20 V; 1200 V]

± 0.2 % R ± 0.4 V

[0.2 % Inom; 120 % Inom]

± 0.2 % R ± 0.02 % Inom

PF = 1 V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.3 % R ± 0.003 % Pnom

PF = [0.5 inductive; 0.8 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.7 % R ± 0.007 % Pnom

Power & Energy Logger Model PEL 52 – User Manual

47

Quantities

Measurement range

Intrinsic uncertainty

Reactive power (Q1, Q2, QT) kvar
Apparent power (S1, S2, ST) kVA

Sin = [0.8 inductive; 0.6 capacitive] V = [100 V; 600 V] I = [5 % Inom; 10 % Inom]

± 2 % R ± 0.02 % Qnom

Sin = [0.8 inductive; 0.6 capacitive] V = [100 V; 600 V] I = [10 % Inom; 120 % Inom]

± 1 % R ± 0.01 % Qnom

V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.3 % R ± 0.003 % Snom

Power factor (PF1, PF2, PFT)

PF = [0.5 inductive; 0.5 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom] PF = [0.2 inductive; 0.2 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.02 ± 0.05

Cos (Cos 1, Cos 2, Cos T)

Cos = [0.5 inductive; 0.5 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom] Cos = [0.2 inductive; 0.2 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.05 ± 0.1

Active energy (Ep1, Ep2, EpT)
kWh

PF = 1 V = [100 V; 600 V] I = [5 % Inom; 120 % Inom] PF = [0.5 inductive; 0.8 capacitive] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 0.5 % R ± 0.6 % R

48

Power & Energy Logger Model PEL 52 – User Manual

Quantities

Measurement range

Intrinsic uncertainty

Reactive energy (Eq1, Eq2, EqT)
kvarh
Apparent energy (Es) kVAh

Sin = [0.8 inductive; 0.6 capacitive] V = [100 V; 600 V] I = [5 % Inom; 10 % Inom] Sin = [0.8 inductive; 0.6 capacitive] V = [100 V; 600 V] I = [10 % Inom; 120 % Inom] V = [100 V; 600 V] I = [5 % Inom; 120 % Inom]

± 2.5 % R ± 1.5 % R ± 0.5 % R

Internal clock: ± 20 ppm

Table 4

6.2.4 Current Sensors 6.2.4.1 Precautions For Use

NOTE: Refer to the safety data sheet provided or the downloadable user manual.

Current clamps and flexible current sensors are used to measure the current flowing in a cable without opening the circuit.

They also isolate the user from dangerous voltages present in the circuit.

The choice of the current sensor to use depends on the current to be measured and the diameter of the cables. When installing current sensors, point the arrow on the sensor towards the load.

When a current sensor is not connected, the device displays

.

Power & Energy Logger Model PEL 52 – User Manual

49

6.2.4.2 Characteristics

The measurement ranges are those of the current sensors. Sometimes they may differ from the ranges measurable by the PEL.

a) MiniFlex® MA193

MiniFlex® MA193

Nominal range Measurement range

300 / 3000 Aac
0.4 A to 360 Aac for the 300 A range 2 A to 3600 Aac for the 3000 A range

Maximum clamping diameter

Length = 10 in (250 mm); Ø = 2.76 in (70 mm) Length = 14 in (350 mm); Ø = 3.94 in 100 (mm)

Influence of the conductor’s position in the sensor

2.5 %

Influence of an adjacent conductor carrying an AC current
Safety

40 dB typical at 50/60 Hz for a conductor in contact with the sensor and > 33 dB near the latching mechanism
IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 600 V CAT IV or 1000 V CAT III

b) MiniFlex® MA194

Table 5

Nominal range Measurement range

MiniFlex® MA194
300 / 3000 Aac 0.4 A to 360 Aac for the 300 A range 2 A to 3600 Aac for the 3000 A range

Maximum clamping diameter

Length = 24 in (609 mm); Ø = 7.48 in (190 mm)

Influence of the conductor’s position in the sensor Influence of an adjacent conductor carrying an AC current
Safety

2.5 %

40 dB typical at 50/60 Hz for a conductor in contact with the sensor and > 33 dB near the latching mechanism IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 600 V CAT IV, 1000 V CAT III

Table 6
NOTE: Currents < 0.4 A for the 300 A range and < 2 A for the 3000 A range are set to zero.

50

Power & Energy Logger Model PEL 52 – User Manual

c) AmpFlex® 193

AmpFlex® 193

Nominal Range
Measurement range Maximum clamping diameter (depending on the model)

300 / 3000 Aac
0.4 A to 360 Aac for the 300 A range 2 A to 3600 Aac for the 3000 A range Length = 24 in (609 mm; Ø = 7.48 in (190 mm) Length = 36 in (910 mm); Ø = 11.42 in (290 mm)

Influence of conductor’s position 2 % everywhere and 4 % near the latching

in the sensor

mechanism

Influence of an adjacent

40 dB typical at 50/60 Hz everywhere and > 33 dB

conductor carrying an AC current near the latching mechanism

Safety

IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 600 V CAT IV, 1000 V CAT III

Table 7
NOTE: Currents < 0.4 A for the 300 A range and < 2 A for the 3000 A range are set to zero.

Power & Energy Logger Model PEL 52 – User Manual

51

d) SR193 clamp

SR193 clamp

Nominal range

1000 Aac

Measurement range

0.5 A to 1200 Aac (I >1000 A for 5 minutes maximum)

Maximum clamping diameter

2.04 in (52 mm)

Influence of the conductor’s position in the clamp
Influence of an adjacent conductor carrying an AC current

< 0.1 % from DC to 440 Hz > 40 dB typical at 50/60 Hz

Safety

IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 600 V CAT IV, 1000 V CAT III

3
CURRENT CLAMP

Table 8

NOTE: Currents < 0.5 A are set to zero.

e) MN93 clamp

MN93 clamp

Nominal range

200 Aac for f 1 k Hz

Measurement range

0.5 A to 240 Aac max (I >200 A non-continuous)

Maximum clamping diameter
Influence of the conductor’s position in the clamp
Influence of an adjacent conductor carrying an AC current

.78 in (20 mm) < 0.5 %, at 50/60 Hz > 35 dB typical at 50/60 Hz

Safety

IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 300 V CAT IV, 600 V CAT III

MN 93A

Table 9 NOTE: Currents < 0.1 A are set to zero.

52

Power & Energy Logger Model PEL 52 – User Manual

f) MN193 clamp

MN193 clamp

Nominal range Measurement range

5 A and 100 Aac
5 mA to 6 A for the 5 A range 200 mA to 120 A for the 100 A range

Maximum clamping diameter

.78 in (20 mm)

Influence of the conductor’s position in the clamp

< 0.5 %, at 50/60 Hz

Influence of an adjacent conductor carrying an AC current

35 dB typical at 50/60 Hz

Safety

IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 300 V CAT IV, 600 V CAT III

MN 93A

Table 10 The 5 A range of MN193 clamp is suitable for measuring the secondary currents of current transformers.

NOTE: Currents < 2.5 mA for the 5 A range and < 50 mA for the 100 A range are set to zero.

g) MN94 clamp

Nominal range Measurement range
Maximum clamping diameter Influence of the conductor’s position in the clamp Influence of an adjacent conductor carrying an AC current
Safety

MN94 clamp 200 Aac 50 mA to 200 A .62 in (16 mm)
< 0.08 %, at 50/60 Hz

45 dB typical at 50/60 Hz
IEC/EN 61010-2-032 or BS EN 61010-2-032, pollution degree 2, 300 V CAT IV, 600 V CAT III

Table 11 NOTE: Currents < 50 mA are set to zero.

Power & Energy Logger Model PEL 52 – User Manual

53

h) Current sensor thresholds

Sensor SR193 clamp
AmpFlex® 193 MiniFlex® MA193 or MA194
MN193 clamp MN93 clamp MN94 clamp

Nominal current 1000 A
300 A
3000 A
5 A 100 A 200 A 200 A

Number of turns
1 turn 2 turns 3 turns 1 turn 2 turns 3 turns

Table 12 6.2.4.3 Intrinsic Uncertainty

Display threshold
0.50 A 0.40 A 0.21 A 0.15 A
2 A 1 A 0.7 A 2.5 mA 50 mA 0.1 A 50 mA

NOTE: The intrinsic uncertainties of current and phase measurements must be added to the intrinsic uncertainties of the instrument for the quantity concerned: powers, energies, power factors, etc.

The following characteristics are given for the reference conditions of the current sensors.

Characteristics of current sensors with an output of 1 V at Inom

I nominal

Current (RMS)

Intrinsic uncertainty at 50/60 Hz

Intrinsic Typical

uncertainty on

uncertainty on at

Resolution

at 50/60 Hz 50/60 Hz

SR193 clamp

[1 A; 50 A]

± 1 % R

1000 Aac [50 A; 100 A]

± 0.5 % R

± 1 °

+ 0.25 °

10 mA

[100 A; 1200 A]

± 0.3 % R

± 0.7 °

+ 0.2 °

MN93 clamp

[0.5 A; 5 A]

± 3 % R ± 1 A

200 Aac

[5 A; 40 A] [40 A; 100 A]

± 2.5 % R ± 1 A ± 2 % R ± 1 A

± 5 ° ± 3 °

+ 2 ° + 1.2 °

1 mA

[100 A; 240 A] ± 1 % R ± 1 A

± 2.5 °

± 0.8 °

54

Power & Energy Logger Model PEL 52 – User Manual

I nominal

Current (RMS)

Intrinsic uncertainty at 50/60 Hz

Intrinsic Typical

uncertainty on

uncertainty on at

Resolution

at 50/60 Hz 50/60 Hz

MN193 clamp

100 Aac

[200 mA; 5 A] [5 A; 120 A]

± 1 % R ± 2 mA ± 1 % R

± 4 ° ± 2.5 °

+ 0.75 °

1 mA

5 Aac

[5 mA; 250 mA] ± 1.5 % R ± 0.1 mA [250 mA; 6 A]

± 1 % R

± 5 °

+ 1.7 °

1 mA

MN94 clamp

200 Aac

[0.05 A; 10 A] [10 A; 240 A]

± 0.2 % R ± 20 mA

± 1 ° ± 0.2 °

± 0.2 ° ± 0.1 °

1 mA

Table 13

AmpFlex® and MiniFlex® characteristics

I nominal

Current (RMS)

Intrinsic uncertainty at 50/60 Hz

Intrinsic Typical

uncertainty on

uncertainty on

Resolution

at 50/60 Hz at 50/60 Hz

AmpFlex® 193

[0.5 A, 10 A]

300 Aac

± 1.2 % R ± 0.2 A

10 mA

[10 A; 360 A]

± 0.5 °

0 °

[1 A; 100 A] 3000 Aac
[100 A; 3600 A]

± 1.2 % R ± 1 A

± 0.5 °

100 mA
0 °

MiniFlex® MA193 or MA194

[0.5 A; 10 A]

300 Aac

± 1 % R ± 0.2 A

10 mA

[10 A; 360 A]

± 0.5 °

0 °

[1 A; 100 A] 3000 Aac
[100 A; 3600 A]

± 1 % R ± 1 A

± 0.5 °

100 mA
0 °

Table 14

Power & Energy Logger Model PEL 52 – User Manual

55

Crest factor: (2.8 to 360) A on the 300 A range. (1.7 to 3600) A on the 3000 A range.
AmpFlex® and MiniFlex® limitation Like all Rogowski sensors, the output voltage of AmpFlex® and MiniFlex® is proportionate to the frequency. High current at high frequency can saturate the current input of devices. This requirement does not consider the bandwidth limitation of the device, which can lead to other errors.
6.3 VARIATION IN THE FIELD OF USE
6.3.1 General
Internal clock drift: ± 5 ppm/year at (77 ± 5.4) °F (25 ± 3) °C
6.3.2 Temperature
V1, V2: 27.78 ppm/°F (50 ppm/°C) typical I1, I2: 83.33 ppm/°F (150 ppm/°C) typical, for 5 % Inom < I < 120 % Inom Internal clock: 5.56 ppm/°F (10 ppm/°C)
6.3.3 Humidity
Range of influence: (30 to 75) % RH / 85 % RH at 73.4 °F (23 °C) excluding condensation
V1, V2: ± 0.05 % typical
I1, I2 (1 % Inom I 10 % Inom): 0.1 % typical (10 % Inom < I 120 % Inom): 0.05 % typical
6.3.4 Continous Component
Range of influence: ± 100 Vdc Quantities influenced: V1, V2 Rejection: > 60 dB
6.3.5 Frequency
Range of influence: (45 to 65) Hz, – 60 ° +60 ° Quantities influenced: V1, V2, I1, I2, P1, P2 Influence: 0.1 %/Hz

56

Power & Energy Logger Model PEL 52 – User Manual

6.3.6 Bandwidth
Range of influence: 100 Hz to 5 kHz (harmonics) Presence of the fundamental at 50/60 Hz (THD = 50 %) V1, V2: 0.5 % @ 2.1 kHz / -3 dB @ 5 kHz I1, I2 (direct input): 0.5 % @ 1.75 kHz / -3 dB @ 5 kHz P1, P2: 0.5 % @ 1.25 kHz / -3 dB

6.3.7 Disturbed Signals
The following signal bandwidth is 6 kHz, 5 % Inom < I 50 % Inom.

Signal type

Sensor

Typical influence

Phase cut-off dimmer
Square

MN193 clamp MiniFlex® MA193 or MA194
MN193 clamp MiniFlex® MA193 or MA194

< 1 % < 3 % < 1 % < 3 %

Table 15 Bridge rectifiers have a waveform that is not supported by the PEL 52.

6.4 POWER SUPPLY Power supply (between terminals V1 and N)
Operating range: (100 to 600) V DC voltage of 100 V or more will prevent the operation of the power supply.
Power: (3 to 5) W depending on input voltage. Current:
at 100 Vac, 100 mApeak and 17 mARMS: Inrush current: 1.9 Apeak at 600 Vac, 500 mApeak and 0.026 mARMS: Inrush current: 5.3 Apeak

Battery (2) NiMH rechargeable elements type AAA 750 mA·h
Lifespan: at least 500 charge / discharge cycles or 2 years Charging time: approx. 5 h Charging temperature: (50 to 104) °F (10 to 40) °C Battery life with active Wi-Fi: 1 hr min, 3 h typical

NOTE: When power is off, the real-time clock is retained for more than 20 days.

Power & Energy Logger Model PEL 52 – User Manual

57

6.5 ENVIRONMENTAL CHARACTERISTICS
Temperature and Relative Humidity Relative Humidity (%)

95 85 75
3
45

2

1

10

-40

-20

0

20 26

Figure 31 1 = Reference range 1 + 2 = Operating range
1 + 2 + 3 = Storage range with battery

35 42 50

T (°C) 70

For indoor use. Altitude
Operating: (0 to 2000) m Storage: (0 to 10,000) m

6.6 Wi-Fi
2.4 G Hz IEEE 802.11 b/g band Tx (b) power: +17.3 dBm Tx (g) power: +14 dBm Rx sensitivity: -98 dBm Security: open / WPA2

6.7 MECHANICAL CHARACTERISTICS
Dimensions: (7.09 x 3.46 x 1.46) in (180 x 88 x 37) mm Weight: Approx. 14.11 oz (400 g) Degree of protection (provided by the enclosure according to IEC 60529):
IP 54 when the device is not connected IP 20 when the device is connected

58

Power & Energy Logger Model PEL 52 – User Manual

6.8 ELECTRICAL SAFETY
The devices comply with IEC/EN 61010-2-030 or BS EN 61010-2-030 for a voltage of 600 V measurement CAT III, pollution degree 2. The devices comply with BS EN 62749 for EMF. Product is intended for professional use only. Battery load between terminals V1 and N: 600 V surge CAT III, pollution degree 2. The test leads and alligator clips comply with standard IEC/EN 61010-031 or BS EN 61010-031.
6.9 ELECTROMAGNETIC COMPATIBILITY
Emissions and immunity in industrial environment compatible with IEC/EN 61326-1 or BS EN 61326-1. With the AmpFlex® and MiniFlex®, the typical influence on the measurement is 0.5 % of full scale with a maximum of 5 A.
6.10 RADIO EMISSION
The devices comply with the RED Directive 2014/53/EU and FCC regulations. FCC certification number for the Wi-Fi: FCC QOQWF121
6.11 MEMORY CARD
Transferring a large amount of data from the SD card to a PC can take a long time. In addition, some computers can have difficulty processing such large amounts of information, and spreadsheets only accept a limited amount of data. To transfer data faster, use the SD/USB card adapter. Do not exceed 32 recordings on the SD card or the SD card may become full. The maximum size of a recording is 4 GB. The recording duration is unlimited
(> 100 years).

Power & Energy Logger Model PEL 52 – User Manual

59

7. MAINTENANCE

NOTE: Except for the batteries, the device does not contain any parts that can be replaced by untrained or unaccredited personnel. Any unauthorized work or part replacement with equivalents may seriously compromise safety.

7.1 CLEANING
WARNING! Risk of electric shock. Before cleaning, disconnect all inputs.

The instrument should be cleaned periodically to keep the LCD clear and prevent the buildup of dirt and grease around the instrument’s buttons and keys. Clean the body of the instrument with a damp and soapy cloth. Do not submerge the instrument in water. Do not use solvents.

For current sensors:
Ensure that no foreign body interferes with the current sensor latching mechanism.
Keep the air gaps of the clamp completely clean. Do not spray water directly on the clamps.

7.2 BATTERY
The device is equipped with a NiMH battery. This technology has several advantages:
Long battery life for a limited volume and weight;
Significantly reduced memory effect, which means you can charge the battery even if it is not completely discharged;
Environmentally friendly with no polluting material, such as lead or cadmium, in accordance with applicable regulations.
The battery may be completely discharged after prolonged storage. If the battery is completely discharged, it must be fully charged. The device may not work during part of the charging. Charging a completely discharged battery may take several hours.

NOTE: If the battery is completely discharged, at least 5 charge/ discharge cycles will be necessary for the battery to regain 95 % of capacity. Refer to the battery data sheet delivered with the device.

To optimize the use of your battery and extend the battery effective life: Charge the device only at temperatures between (50 and 104) °F (10 and 40) °C. Comply with the conditions for use. Comply with the conditions for storage.

60

Power & Energy Logger Model PEL 52 – User Manual

7.3 UPDATING FIRMWARE
AEMC® Instruments strives to constantly improve our instruments and software. We offer firmware updates to keep your instrument updated and performing at the highest level possible.
When your device is connected to the PEL Control Panel via Wi-Fi, you will be informed when a new firmware version is available.
Start the update via the PEL Control Panel.
NOTE: Updating firmware may reset the configuration and cause loss of recorded data. As a precaution, back up the data in memory on a PC before updating the firmware.
7.4 REPAIR AND CALIBRATION
To ensure that your instrument meets factory specifications, we recommend that the instrument be sent back to our factory Service Center at one-year intervals for recalibration or as required by other standards or internal procedures.
For instrument repair and calibration:
You must contact our Service Center for a Customer Service Authorization Number (CSA#). Send an email to repair@aemc.com requesting a CSA#, you will be provided a CSA Form and other required paperwork along with the next steps to complete the request. Then return the instrument along with the signed CSA Form. This will ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# on the outside of the shipping container. If the instrument is returned for calibration, we need to know if you want a standard calibration or a calibration traceable to N.I.S.T. (includes calibration certificate plus recorded calibration data). Ship To: Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive Dover, NH 03820 USA Phone: 800-945-2362 (Ext. 360) / 603-749-6434 (Ext. 360) Fax: 603-742-2346 E-mail: repair@aemc.com
(Or contact your authorized distributor.) Contact us for the costs for repair, standard calibration, and calibration traceable to N.I.S.T.
NOTE: You must obtain a CSA# before returning any instrument.

Power & Energy Logger Model PEL 52 – User Manual

61

7.5 TECHNICAL AND SALES ASSISTANCE
If you are experiencing any technical problems or require any assistance with the proper operation or application of your instrument, please call, e-mail or fax our technical support team:
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments Phone: 800-343-1391 (Ext. 351) Fax: 603-742-2346 E-mail: techsupport@aemc.com
www.aemc.com
7.6 LIMITED WARRANTY
The instrument is warrantied to the owner for a period of two years from the date of original purchase against defects in manufacture. This limited warranty is given by AEMC® Instruments, not by the distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused, or if the defect is related to service not performed by AEMC® Instruments.
Full warranty coverage and product registration is available on our website at www.aemc.com/warranty.html
Please print the online Warranty Coverage Information for your records.
What AEMC® Instruments will do:
If a malfunction occurs within the warranty period, you may return the instrument to us for repair, provided we have your warranty registration information on file or a proof of purchase. AEMC® Instruments will repair or replace the faulty material at our discretion.
REGISTER ONLINE AT: www.aemc.com/warranty.html

62

Power & Energy Logger Model PEL 52 – User Manual

7.6.1 Warranty Repairs
What you must do to return an Instrument for Warranty Repair:
First, send an email to repair@aemc.com requesting a Customer Service Authorization Number (CSA#) from our Service Department. You will be provided a CSA Form and other required paperwork along with the next steps to complete the request. Then return the instrument along with the signed CSA Form. Please write the CSA# on the outside of the shipping container. Return the instrument, postage or shipment pre-paid to:
Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments 15 Faraday Drive, Dover, NH 03820 USA Phone: 800-945-2362 (Ext. 360) / 603-749-6434 (Ext. 360) Fax: 603-742-2346 E-mail: repair@aemc.com
Caution: To protect yourself against in-transit loss, we recommend that you insure your returned material.
NOTE: You must obtain a CSA# before returning any instrument.

Power & Energy Logger Model PEL 52 – User Manual

63

8. APPENDIX
8.1 MEASUREMENTS
8.1.1 Definition
Geometric representation of active and reactive powers.

Active power supplied

Active power consumed

Reactive power consumed Reactive power supplied

S

Q

P

V

Figure 32 The reference of this diagram is the current vector (fixed on the right-hand part of the axis).
The voltage vector V varies in its direction as a function of the phase angle . The phase angle , between voltage V and current I, is considered positive in the mathematical sense of the term (counterclockwise).
8.1.2 Sampling 8.1.2.1 1 s (one second) Quantities
The device calculates the following quantities every second on the basis of measurements over a cycle, according to § 8.2.
1 s quantities are used for: Real-time values. Trends over 1 second. Aggregation of values for aggregated trends . Determination of minimum and maximum values for the values of aggregated
trends.
All 1 s quantities can be recorded on the SD card during the recording session.

64

Power & Energy Logger Model PEL 52 – User Manual

8.1.2.2 Aggregation
An aggregated quantity is a value calculated over a period defined according to the formulas indicated in Table 17.
The aggregation period always begins at the start of an hour or a minute. The aggregation period is the same for all quantities. The following periods are possible: 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 min.
All aggregated quantities are recorded on the SD card during the recording session. They can be displayed in the PEL Control Panel.
8.1.2.3 Minimum and Maximum
Min and Max are the minimum and maximum values of the 1 s quantities for the aggregation period considered. They are recorded with their dates and times. The Max values of certain aggregated values are displayed directly on the device.
8.1.2.4 Calculation of Energies
Energies are calculated every second.
Total energies are available with the data of the recorded session.
8.2 MEASUREMENT FORMULAS

Quantities
AC RMS phase-neutral voltage (VL)

Formulas

Comments
vL = v1 or v2 incremental sample N = number of samples

AC RMS phase-phase voltage (UL)

ab = u12 incremental sample N = number of samples

AC RMS current (IL) Active power (PL)

iL = i1, i2 or i3 incremental sample N = number of samples

Table 16

L = I1 or I2 incremental sample N = number of samples PT[1 s]= P1[1 s] + P2[1 s]

Power & Energy Logger Model PEL 52 – User Manual

65

8.3 AGGREGATION
Aggregated quantities are calculated for a defined period according to the following formulas based on 1 s values. Aggregation can be calculated by arithmetic average, quadratic average or other methods.

Quantities Phase-neutral voltage (VL) (RMS)
Phase-phase voltage (Uab) (RMS)
Current (IL) (RMS)
Frequency (FL)

Formula

VL[agg] =

1 N

×

N -1

VL

2 x

[1s]

x=0

U ab [agg] =

1 N

×

N -1

U

2 abx

[1s]

x=0

I L[agg] =

1
N

N -1

×

I

2 Lx

[1s]

x=0

F[agg] =

1 N

×

N -1
Fx [1s] x=0

Active power (PL)
Reactive power (QL)
Apparent power (SL)
Source power factor with the associated quadrant (PFSL) Load power factor with the associated quadrant (PFLL) Cos ()S of the source with the associated quadrant

PL

[agg] =

1 N

×

N -1
PLx
x=0

[1s]

QL

[agg] =

1 N

×

N -1
QLx
x =0

[1s]

S L [agg] =

1 N

×

N -1
S Lx [1s] x=0

PFSL [agg] =

1 N

×

N -1
PFSLx [1s] x=0

PFLL [agg] =

1 N

×

N -1
PFLLx [1s] x=0

Cos(L )S[agg]

=

1 N

N -1
× Cos(L )Sx[1s] x=0

Cos ()L of the load with the associated quadrant

Cos( L ) L [agg] =

1 N

×

N -1
Cos( L ) L x [1s] x=0

Table 17
N is the number of 1 s values for the aggregation period considered (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, or 60 minutes).

66

Power & Energy Logger Model PEL 52 – User Manual

8.4 SUPPORTED ELECTRICAL NETWORKS
The following types of distribution networks are supported: – Single phase (single phase 2-wire 1 current) – Single phase (single phase 3-wire 2 currents) – Split-phase (split-phase single phase 3-wire)
V1, V2 are the phase-neutral voltages of the installation measured. [V1=VL1-N; V2=VL2-N].
The lower case letters v1, v2, v3 denote the sampled values. U12 is the voltage between phases of the installation measured. Lower case letters denote the sampled values [u12 = v1-v2]. I1, I2 are the currents flowing in the phase conductors of the installation
measured. The lower case letters i1, i2, i3 denote the sampled values.

Single phase (single phase 2-wire 1 current)

Abbreviation

Comments

Reference diagram

1P- 2W1I

Voltage is measured between L1 and N. Current is measured on conductor L1.

see § 4.1.1

Single phase (single phase 3-wire 2 currents)

Abbreviation

Comments

Reference diagram

1P- 3W2I

Voltage is measured between L1 and N. Current is measured on conductors L1 and L2.

see § 4.1.2

Split-phase (split-phase single phase 3-wire)

Abbreviation

Comments

Reference diagram

2P-3W2I

Voltage is measured between L1, L2, and N. Current is measured on conductors L1 and L2.

see § 4.1.3

Table 18

Power & Energy Logger Model PEL 52 – User Manual

67

8.5 VALUES AVAILABLE
available on the instrument and in the PEL Control Panel available in the PEL Control Panel
not available

Quantities

Symbol

Real-time Trend

value value

1 s

1 s

Phase-neutral voltage

V1, V2

Phase-phase voltage

U12

Current

I1, I2

Frequency

f

Active power

P1, P2, PT

Active power on the source

P1, P2, PT

Active power on the load

P1, P2, PT

Fundamental active power

Pf1, Pf2, PfT

Fundamental active power on the source

Pf1, Pf2, PfT

Fundamental active power on the load

Pf1, Pf2, PfT

Reactive power Q1, Q2, QT

Reactive power on the source

Q1, Q2, QT

Reactive power on the load

Q1, Q2, QT

Apparent power S1, S2, ST

Apparent power on the source

S1, S2, ST

Apparent power on the load

S1, S2, ST

Non-active power N1, N2, NT

Max value

Trend

Min/Max

value

1 s

aggregated aggregated

(1)

(1)

(1)

(1)

(1)

Quantities

Symbol

Real-time Trend

value value

1 s

1 s

Max value

Trend

Min/Max

value

1 s

aggregated aggregated

Distorting power D1, D2, DT

PF1,

Power factor

PF2,

PFT

Power factor on the source

PF1, PF2, PFT

Power factor on the load

PF1, PF2, PFT

Cos

Cos 1,

Cos 2,

Cos T

Cos on the source

Cos 1, Cos 2, Cos T

Cos on the load

Cos 1, Cos 2, Cos T

Total active energy on the source

EpT

Total active energy on the load

EpT

Reactive energy on quadrant 1

EqT

Reactive energy on quadrant 2

EqT

Reactive energy on quadrant 3

EqT

Reactive energy on quadrant 4

EqT

Apparent energy on the source

EsT

Apparent energy on the load

EsT

(I1, I2)

(V1, V2)

Quantities

Symbol

Real-time Trend

value value

1 s

1 s

Max value

Trend

Min/Max

value

1 s

aggregated aggregated

(I1, V1) (I2, V2)

Table 19

(1) No minimum value for P1, P2, PT, Q1, Q2, QT
8.6 GLOSSARY Prefixes of units of the International System (SI):

Prefix

Symbol

Multiplied by

milli

m

10-3

kilo

k

103

Mega

M

106

Giga

G

109

Tera

T

1012

Peta

P

1015

Exa

E

1018

Table 20

° % A AC Aggregation CF
cos
DC DataViewSyncTM
Ep Eq

Phase offset of the voltage relative to the current Degree Percentage Ampere (current unit) AC component (current or voltage) Different averages defined at § 9.3 Current or voltage peak factor: ratio of the peak value of a signal to the effective value Cosine of the phase shift of the voltage with respect to the current DC component (current or voltage) Internet Relay system that relays data between the recorder and a PC Active energy Reactive energy

Es Frequency Hz I L MAX MIN P PF Q RMS
S Nominal voltage U V VA var varh W W·h

Apparent energy Number of full cycles of voltage or current per second Hertz (unit of frequency) Symbol for current Phase of a multiphase network Maximum value Minimum value Active power Power Factor: Ratio of active power to apparent power Reactive power RMS (Root Mean Square) average quadratic value of the current or voltage. Square root of the average of the squares of instantaneous values of a quantity during a specified interval Apparent power Nominal voltage of a network Voltage between two phases Phase-neutral voltage or Volt (unit of voltage) Unit of apparent power (Volt x Ampere) Unit of reactive power Unit of reactive energy Unit of active power (Watt). Unit of active energy (Watt x hours)

10/23 99-MAN 100581 v04
AEMC® Instruments 15 Faraday Drive · Dover, NH 03820 USA Phone: +1 603-749-6434 · +1 800-343-1391 · Fax: +1 603-742-2346
www.aemc.com
© 2023 Chauvin Arnoux®, Inc. d.b.a. AEMC® Instruments. All Rights Reserved.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AEMC User Manuals

Related Manuals