TROLEX TX6373 Toxic Gas Detector Transmitter Instruction Manual
- June 16, 2024
- Trolex
Table of Contents
- TX6373 Toxic Gas Detector Transmitter
- PRINCIPAL OPERATING FEATURES
- APPLICATION
- DIMENSIONS
- TECHNICAL DETAILS
- INSTALLATION
- CONNECTIONS
- CONTROLS AND INDICATORS
- CALIBRATION
- MAINTENANCE
- APPROVALS AND CERTIFICATION
- FUNCTIONAL SAFETY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TX6373
TOXIC GAS SENSOR/TRANSMITTER
TX6373 Toxic Gas Detector Transmitter
INSTALLATION & OPERATING DATA
PRINCIPAL OPERATING FEATURES
Stationary gas sensors for the detection of a wide range of flammable gases.
Suitable for use in SIL 1 and SIL 2 applications, in accordance with any
conditions or restrictions
Poison resistant CATALYTIC COMBUSTION sensors.
Pre-calibrated plug-in gas sensing module with a standardised output signal
for convenient replacement and servicing.
Calibration available for a wide range of flammable gases.
LCD readout of gas concentration with OVERRANGE indication.
Convenient push button calibration of ZERO and SPAN.
Signal fix during calibration to prevent false alarms.
Output signal versions:- 4 to 20 mA 0.4 to 2 V 5 to 15 Hz.
Stainless steel reinforced polycarbonate housing.
Intrinsically safe for use in Group I and Group II hazardous areas.
Special versions with weatherproof plug and socket connections in place of
cable glands.
APPLICATION
Fixed gas monitoring for point-source hazards and perimeter protection in
arduous duty and exposed locations.
Safety protection for toxic gas risk occurring in hazardous areas and general
industrial applications.
Petrochemical processing.
Mining and tunnelling.
Offshore platforms.
Manufacturing and process plants.
Storage areas and warehousing.
Water management and sewage treatment.
Power generation.
Gas storage and distribution.
Marine and shipping applications.
Telecommunications.
A choice of output signals for direct interfacing with most standard
industrial monitoring systems.
A range of primary instrumentation and monitoring modules is available from
Trolex to which the sensors can be directly connected to provide a flexible
choice of display and control functions.
TRIP AMPLIFIER for use with analogue output sensors.
CONFIGURABLE SENSOR CONTROLLER for monitoring up to 8 analogue output sensors.
COMMANDER DISTRIBUTED I/O SYSTEM
for large scale general plant monitoring systems and the mining and tunnelling
industries.
DIMENSIONS
TECHNICAL DETAILS
4.1 Specification
Operating Temp. Limits:| –10 to +40°C (Ambient temp. range for explosion
protection: -20 to + 40°C)
---|---
Storage Temperature:| –25 to +60°C
Ambient Pressure Limits:| 1000 mbar ± 200 mbar absolute
Humidity:| 95% RH non-condensing
Protection Classification:| Dust and waterproof to IP66. Gas inlet port to
IP54
Housing Material:| Reinforced polymer – proof against electrostatic discharge
Nett Weight:| 450 g
Cable Entries:| M20 x 1.5
Electrical Connections:| 4 mm Barrier/clamp terminals
Information Display:| Graphic LCD
Impact Limits:| 20 joules (Housing)
GAS SENSING MODULE
Plug-in gas sensing module with signal conditioning. Precalibrated and standardised output signal.
Measuring Range:| 0 to 5% v/v CH4. Calibrated for Methane
Alternative sensing ranges available to specification
---|---
Linearity:| ±1% 0 to 60% FULL SCALE
±5% from 60% up to 100% FULL SCALE
Maximum Drift @ 25°C:| ±0.25% v/v per month
Response Time t(90):| <30 seconds response time is tested by flowing test gas
using the calibration kit referred
to in section 9 maintenance
Sensing Element Life:| >5 years in clean atmosphere
Warm Up Time:| <5 mins in air or 1% v/v CH4.
Stabilisation Time:Calibration:| >15 minutes
Digitally controlled ZERO and SPAN. Pushbutton setting
Signal Fix:| The transmitted output signal of the sensor is FIXED at 00.0
during calibration
Overrange:| If the measured gas concentration exceeds the calibration range of
the sensor:
The STATUS indicator will flash
The display value will be CLAMPED
The transmitted output signal will be CLAMPED
Pellistor Protection:| The supply to the gas sensing element will be switched
off to prevent oxidisation damage occurring if the gas concentration exceeds
safe limits.
The sensor will attempt to switch back on at 5 minute intervals until the gas
concentration has reduced to a safe level
The table shows the response variation of the gas sensing module on exposure to a range of gases and vapours at the same %LEL concentration. The figures are experimentally derived and expressed relative to the methane signal (=100).
Gas/Vapour:| Relative Sensitivity| Gas/Vapour| Relative
Sensitivity
---|---|---|---
Methane| 100| Carbon Monoxide| 130
Propane| 70| Hydrogen| 120
n-Butane| 70| Ammonia| 155
n-Pentane| 60| Cyclohexane| 55
n-Hexane| 60| Ethylene| 90
Acettylene| 85| |
TX6383.0 1 GROUP I APPLICATIONS (12 V dc)
Output:| 0.4 to 2 V dc|
---|---|---
Min Load| 10 k ohms
Supply| 6.5 to 16.5 V dc
Max Current| 80 mA
Output:| 4 to 20 mA
Max Load @ 12 V| 140 ohms
Supply| 6.5 to 16.5 V dc
Max Current| 24 mA
Output:| 5 to 15 Hz
Max Load| Opto isolated. 2 mA max
Supply| 6.5 to 16.5 V dc
Max Current| 80 mA
TX6383.02 GROUP II APPLICATIONS (24 V dc)
Output:| 4 to 20 mA|
---|---|---
Max Load @ 24 V| 240 ohms
Supply| Minimum 6.5 V at the sensor
supply terminals (3 and 4)
Max Current| 100 mA
TX6383.03 GENERAL PURPOSE APPLICATIONS (24 V dc)
NOT SUITABLE F OR U SE IN CLASSIFIED HAZARDOUS AREAS.
Output:| 4 to 20 mA|
---|---|---
Max Load @ 24 V| 240 ohms
Supply| 6.5 to 30 V dc
Nominal Current| 100 mA
INSTALLATION
5.1 Conformity Check
(Refer to Test Certificate provided with the sensor).
Does the output signal of the sensor concur with the input requirement of the
monitoring equipment being used?
Is the correct supply voltage available for the sensor?
Is the type of gas and its anticipated maximum level of concentration, within
the operating parameters of the sensor?
Is the temperature variation range, at the installation, within the stated
temperature range of the sensor?
Is the hazardous area classification correct?
If the hazard is Group II – are the correct safety barriers fitted?
STANDARD OPTIONS AVAILABLE
TX6383.01 FLAMMABLE GAS SENSOR/ TRANSMITTER GROUP I
TX6383.02 FLAMMABLE GAS SENSOR/ TRANSMITTER GROUP II
TX6383.03 FLAMMABLE GAS SENSOR/ TRANSMITTER GENERAL
PURPOSE
TX6383.84.01 FLAMMABLE GAS SENSOR/ TRANSMITTER GROUP I with Remote Gas Sensing
Module
TX6383.84.02 FLAMMABLE GAS SENSOR/ TRANSMITTER GROUP II with Remote Gas
Sensing Module
TX6383.84.03 FLAMMABLE GAS SENSOR/ TRANSMITTER GENERAL with Remote Gas Sensing
Module
PURPOSE
5.2 Location
It is recommended that user refer to EN/IEC 60079-29-2 for useful information
on the selection, installation, use and maintenance of gas detectors for
potentially explosive atmospheres.
Each installatio n needs to be consid ered in i ts own right, wit h refe rence
to safety au thorities and in c omplia nce wit h mandatory local safety r
egula tio ns.
The sensor must be operated in accordance wit h the Installatio n and
Operating Da ta to main tain safe ty, r elia bility and to preserve Intrinsic
Safet y in tegrity w here applicable.
It is important that sensors are located in positions determined in
consultation with those who have specialised knowledge of the plant or
installation and of the principles of gas dispersion. Reference should also be
made to those responsible for the engineering layout and topology of the
plant as they will be most familiar with the nature of the potential dangers
and the most likely sources of gas release.
It is also important to recognise that the characteristics of the gas source
can be influenced by many factors; including the relative density or buoyancy
of the gas, the pressure at the point of release, the ambient temperature and
the ventilation of the site.
Sensor coverage cannot be simply expressed in terms of ‘number per unit area’.
Sensors need to be sited where they are capable of monitoring those parts of a
plant where gas may accumulate or when a source of gas release is expected to
occur. This way the earliest possible warning of a gas release can be given to
initiate shutdown functions, alarm functions or safe evacuation of the
premises.
5.3 System Integrity
If a gas monitoring system should fail for any reason, it is important that
the system is capable of immediately alerting operational staff to this fact.
The sensor will indicate a system failure or mechanical defect and this
information can be utilised to initiate a warning alarm. It is good practice
to provide emergency facilities to protect against the loss of the mains power
supply.
Standby batteries can be incorporated with automatic changeover facilities, so
guaranteeing continued operation of the gas sensing system even in the event
of a plant breakdown as a result of a power supply failure.
Certainly, in critical plants, duplication or triplication of sensors is
recommended.
The Trolex TX9042 or TX9044
Programmable Sensor Controller can be programmed to operate with sensors in
the multiple voting mode.
5.4 Sensor Management
A very important part of an efficient gas monitoring system is the training of
plant personnel in operation and maintenance of the sensors and the complete
monitoring system. Training facilities can be provided by qualified Trolex
application engineers.
Once a sensor installation is complete, the sensor locations and types should
be formally recorded and a planned test and maintenance procedure instituted.
5.5 Relative Density
The relative density or buoyancy of the gas or vapour with respect to air is a
very important consideration. This determines its propensity to rise or fall
when released into the atmosphere.
Gases or vapours with a buoyancy less than air will tend to rise from the
source of release.
Conversely, gases or vapours heavier than air will tend to fall and accumulate
in concentrations for long periods of time.
This is a particular problem in pits, trenches, machine rooms, etc. Normal air
movements in and around such gas concentrations will have the inevitable
effect of producing zones of highly flammable mixtures.
This knowledge of the characteristics of the gas assists when positioning the
gas sensor.
The behaviour of the gas accumulation will also be affected by the velocity
and location of the gas release and by ambient air movement caused by
ventilation systems or draughts.
Pockets of gas can be trapped in trenches or ceiling cavities, all of which
adds to the unpredictability of critical gas concentrations.
Hydrogen | LIGHTER THAN AIR |
---|
Town Gas
Methane
Ammonia
Acetylene
Carbon Monoxide
Ethylene
Methyl alcohol| HEAVIER THAN AIR
Propane
Ethanol
Acetone
Butane
Pentane
Benzene
Hexane
Ethylacetate
Toluene
Petrol
O-Xylene
Octane
5.6 Hazardous Areas
Do not disassemble the sensor whilst in the hazardous area or use a sensor
that has a damaged housing in the hazardous area.
5.7 Evacuation
If a dangerous level of gas concentration is detected by the instrument, leave
the area immediately.
5.8 Operating Limits of Catalytic Combustion Sensors
Catalytic combustion gas sensors POSITIVELY detect the presence of any
flammable gas. They rely upon the presence of oxygen in the atmosphere and
should only be used for gas concentration up to the Lower Explosive Limit
(LEL).
After this point, the output becomes non linear and may erroneously indicate
that the gas concentration is below the LEL. they should not be used in oxygen
enriched or deficient atmospheres.
5.9 Discrimination
Catalytic combustion sensors can detect a wide range of flammable gases but
they cannot discriminate between individual gases. They will respond to most
or all of the flammable components present in the atmosphere without
distinguishing between them. (See section 4.1 for relative sensitivities)
5.10 Contamination
The response of catalytic combustion gas sensors can be affected by air borne
contaminants which will reduce the sensitivity. Substances such as silicones,
tetraethyl lead, sulphur compounds and phosphate esters can cause permanent
degradation (poisoning). Halogenated carbons may also cause temporary
inhibition.
5.11 Interference
If the atmosphere to be monitored contains a gas that dilutes or displaces the
air, this may reduce the response of catalytic sensors. Similarly, steam laden
atmospheres and condensation can reduce the sensitivity.
Air velocity may have a minor effect on the accuracy of the gas sensor.
5.12 High Concentrations of Flammable Gas
Exposure of low concentration catalytic combustion sensors to concentrations
of flammable gas greater than the LEL can affect the sensitivity and zero
stability of catalytic elements and the calibration should be checked after
such an exposure.
If the gas concentration does exceed 100% LEL, the supply voltage to the
catalytic combustion sensing element will be automatically switched off to
prevent damage to the element.
The sensor output signal will be CLAMPED, the display will indicate OVERRANGE
and the STATUS indicator will FLASH.
5.13 Toxicity
Be aware that most flammable gases and vapours are also toxic at low
concentrations of LEL.
5.14 New Installations
Flammable gas sensors based on pellistor technology require regular zero and
span check and adjustment operations to ensure that they remain accurate.
The pellistor device ages during its lifetime and its baseline and sensitivity
characteristics will change. These operations are normally performed three
weekly.
The pellistors baseline tends to drift throughout it’s lifetime. In the early
stages of the lifetime, the baseline tends to move at a relatively fast rate.
This movement slows down with age.
The pellistor fitted to the TX6383 will have a baseline change equivalent of
upto ±2.5%LEL (0.11% v/v) in its first month of usage, then a further ±1.5%
LEL (0.066% v/v) in the second month.
For newly installed equipment, end users should consider performing a zero
offset adjustment and span check adjustment every two weeks for the first two
months.
This will ensure that the offset movement is kept below ±2% LEL (0.088% v/v)
during the ‘settling in’ period.
CONNECTIONS
OUTPUTSIGNAL OPTIONS
TX6383 FLAMMABLE GAS SENSOR/ TRANSMITTER
6.1 0.4 to 2 V Output Signal
A low impedance two-wire voltage output signal requiring a separate power
supply to the sensor.
This can be derived from a TX9132
Trip Amplifier or TX9042 Programmable Sensor Controller, when one of those is
used as the monitoring instrument.
This connection configuration works well up to about 10 m distance between the
sensor and the monitoring equipment.
Both the signal and the power supply to the sensor are being carried in the
common 0 V conductor so at some point –influenced by the length of the cable
and the resistance of the cable cores – the current flowing in the 0 V
conductor will impose an unacceptable voltage error onto the signal.
This effect can be reduced on long distance connections by increasing the size
of the cable cores, or even better, running a separate 0 V conductor to power
the sensor enabling operating distances up to 1000 m.
APPLICATION
GROUP I HAZARDOUS AREAS
4 to 20 mA Output Signal
The sensor may be connected the 3 or 4 wire connection mode.
The power supply for the sensor may be sourced from the monitoring equipment (eg. TX9131 Trip Amplifier or a TX9042 Programmable Sensor Controller) or from a separate power supply.
APPLICATION
GROUP I HAZARDOUS AREAS
GROUP II HAZARDOUS AREAS
GENERAL PURPOSE
6.3 5 to 15 Hz Output Signal
A square wave, frequency variable output that is proportional to the
measured value.
The output device is an open collector NPN transistor.
Output:| 5 to 15 Hz
(zero = 5 Hz)
(span = 15 Hz)
---|---
Maximum Voltage:| 15.4 V
Maximum Current:| 2 mA
Minimum Pulse Rise Time:| 5 V/ms
APPLICATION
GROUP I HAZARDOUS AREAS
6.4 Using Gas Sensors in Hazardous Areas
6.4.1 GROUP I HAZARDOUS AREAS (MINING)
TX6383.01 FLAMMABLE GAS SENSOR/ TRANSMITTER
All options of the TX6383.01sensor (0.4 to 2 V, 4 to 20 mA and 5 to 15 Hz) are
certified Intrinsically Safe for use in Group I hazardous areas (Mining) when
used with approved equipment eg. TX9131 Trip Amplifier or a TX9042
Programmable Sensor Controller.
THE COMPLETE SYSTEM, BOTH SENSOR AND MONITORING DEVICE, CAN BE MOUNTED IN THE
HAZARDOUS AREA.
The interconnecting cable between the sensor and the monitoring device must
have steel wire armoured protection or a braided earth screen. The cross
sectionalarea of the conductors must be a minimum of 1 mm2.
6.4.2 GROUP II HAZARDOUS AREAS (24 V dc)
TX6383.02 TOXIC GAS SENSOR/ TRANSMITTER
This version of the sensor (4 to 20 mA) is certified Intrinsically Safe for
use in industrial hazardous areas, when used in conjunction with safety
barriers.
THE SAFETY BARRIERS ARE MOUNTED IN THE SAFE AREA, ONLY THE SENSOR IS MOUNTED
IN THE HAZARDOUS AREA.
The system may be used with either zener safety barriers or isolation safety
barriers.
Group II sensor connections using zener safety barriers.
Power Safety Barrier: MTL779+
Signal Safety Barrier: MTL787S+
Max. Cable Length: 1 km using 1.5 mm2 cable conductors.
Group II sensor connections using isolation safety barriers.
Power Isolation Barrier: Pepperl & Fuchs
KFD2–SL2–EX 2B
Signal Isolation Barrier: Pepperl & Fuchs
KFD2–STC4-EX 1
Max. Cable Length: 1 km using 1.5 mm2 cable conductors.
If you require any help with the use and connection of hazardous area equipment please contact the Trolex Technical Department.
CONTROLS AND INDICATORS
TX6383 FLAMMABLE GAS SENSOR/
TX6383.84 FLAMMABLE GAS SENSOR/ TRANSMITTER REMOTE GAS SENSING MODULE.
This version uses the same pre-calibrated gas sensing module as the TX6383.
The module is fitted into a robust metal housing which can be mounted at a
remote location where space is constricted or the operating conditions are
extremely harsh.
Connections:| 2 m, flexible cable in a flexible armoured conduit (other
lengths available to specification. Max 10 m).
---|---
Protection Classification| Dust and waterproof to IP66. Gas inlet port to
IP54.
Housing Material:| Brass or Stainless steel.
Maximum Cable Length:| Extendible up to 500 m using 1.5 mm2 cable conductors.
(General Purpose only)
DISCONNECTING THE REMOTE GAS SENSING MODULE
The connecting cable between the remote gas sensing module and the Transmitter
is normally supplied connected at both ends.
The cable can be disconnected via a plug and socket connector inside the
Transmitter housing for servicing or transportation.
CALIBRATION
The gas sensing module will gradually change its response characteristics, by
a small amount, during normal use.
The output signal is standardised so the module can be quickly changed when
necessary.
Ser vice replacement modules can be supplied by our Product Support
Department.
Alternatively the gas sensing module may be re-calibrated when required, using
a Trolex TX6520.32 Gas Test Kit equipped with both Air and Test Gas canisters.
Maximum time interval between calibrations should be three weeks.
For newly installed equipment, end users should perform a zero offset
adjustment and a span check/adjustment every two weeks for the first two
months
8.1 Prepare to Calibrate
The sensor should be powered for a minimum of 15 minutes prior to commencing
calibration, to allow the sensor to stabilise.
Connect the application tube of the gas test kit to the inlet aperture of the
gas sensing module.
The indicator will be GREEN denoting the NORMAL operating condition.
8.2 Prepare to Calibrate
Press BOTH pushbuttons on the gas sensing module for about 5 seconds.
Then release.
The indicator will be RED denoting that the module is now setup ready for:
Calibrate ZERO
OR
Calibrate
When the Gas Sensing Module is setup into the CALIBRATE MODE it will instruct
the transmitted output signal of the sensor to be FIXED at ZERO SCALE. This
will prevent the possibility of false alarm signals being activated in the
monitoring equipment during the calibration process.
The display will continue to show the measured value of gas concentration
during the calibration process.
The gas sensing module will automatically return to the normal measuring mode
if the pushbuttons are operated within 60 seconds.
8.3 Calibrate ZERO
Apply purge air, at a flow rate of 0.2 to 1 l/min, for 20 seconds to clear all
remnants of gas.
Press CALIBRATE ZERO until the indicator is flashing GREEN (about 3 seconds).
The CALIBRATE ZERO will NOT function if any level of gas concentration is
detected by the sensing element – The indicator will NOT flash GREEN.
Release and the indicator will briefly show RED to denote ZERO setup.
The Gas Sensing Module will immediately return to the NORMAL measuring mode.
Switch off the purge air supply.
The Gas Sensing Module will automatically return to the NORMAL measuring mode if NO pushbuttons are operated within 60 seconds.
8.4 Calibrate SPAN
Apply test gas, at a flow rate of 0.2 to 1 l/min, until the display value
stabilises.
The Gas Sensing Module will automatically return to the NORMAL measuring mode
if NO pushbuttons are operated within 50 seconds.
Press CALIBRATE SPAN until the indicator is flashing YELLOW (3 times).
DO NOT PRESS CALIBRATE SPAN UNTIL THE DISPLAYEDVALUE HAS FULLY STABILISED.
The CALIBRATE SPAN will NOT function if the level of gas concentration
detected by the sensing element is less than about 25% FULL SCALE.
The indicator will NOT flash YELLOW.
Release and the indicator will show RED to denote READY.
Press and hold the calibration pushbuttons to SCROLL the display value UP/DOWN
until it concurs with the value of gas concentration marked on the test gas
canister.
Switch off the test gas supply.
5 seconds after SCROLLING has ceased the gas sensing module will automatically
return to the NORMAL measuring mode.
Re-apply the test gas for a few seconds to verify the response of the sensor.
The Gas Sensing Module will automatically return to the NORMAL measuring mode
if NO pushbuttons areoperated within 60 seconds.
8.5 Over Range Indication
Erroneous readings will be given by a pellistor gas sensing element if it is
exposed to gas concentrations that exceed its normal working range of 0 to 5%
v/v CH4.
The increase in gas concentration displaces the oxygen in the atmosphere so
the pellistor becomes progressively less effective, to the point where its
output signal actually starts to as the gas concentration continues to
When OVER RANGE is detected, four conditions will be initiated: The display
will indicate OVER RANGE to prevent ambiguous readings.
The transmitted output signal will be CLAMPED at FULL SCALE to prevent an
ambiguous output signal from being transmitted.
The STATUS indicator will FLASH alternate RED and GREEN.
The pellistor in the gas sensing module will be switched into a PROTECT state
to prevent oxidisation damage.
RESET
Briefly interrupt the power supply to the sensor to RESET the OVER RANGE
condition.
This will only be effective when the gas concentration has receded and the
pellistor in the gas sensing module has reset itself from the PROTECT state.
8.6 Pellistor Protection
Catalytic combustion sensors can be damaged if exposed to excess
concentrations of gas for long periods.
If the OVER RANGE condition is initiated the gas sensing module will be
switched into the PROTECT state to prevent oxidisation damage.
The status indicator will flash RED/GREEN to indicate that the pellistor is
the PROTECT state.
The gas sensing module will reset itself to NORMAL operation after 5 minutes
if the gas has cleared. It will continue to attempt to reset itself at 5
minute intervals until the gas has cleared.
It will now be necessary to RESET the OVER RANGE condition.
MAINTENANCE
It is good safety practice to carry out regular preventative maintenance to confirm correct operation. The periodicity for preventative maintenance should be in line with best practice for the industry where the gas sensor is being used and take into consideration local operating conditions.
9.1 Output Signal
Check the response of the sensor at pre-determined intervals by injecting a
test gas using a Trolex TX6520.32 Gas Test Kit.
Compare the value of the display with the value marked on the test gas
canister.
9.2 Proof Test.
Calibrate the TX6383 using the instructions in Section 8.
Insert an approved test meter into the signal line.
Inject a test gas using a Trolex TX6520.32 Gas Test Kit.
Compare the value on the test meter display with the measured line value.
If the value on the test meter does not match the value on the display:
Recalibrate and then carry out the proof test again OR change the gas sensing
module, calibrate and then carry out the proof test.
9.3 Gas Sensing Modules
The gas sensing modules should be changed at regular intervals to ensure
accuracy of response.
The response of the Pellistor sensor will gradually shift due to normal device
decay. The average life is about 5 years, influenced mostly by the operating
environment and the mean level of exposure to flammable gas during its
lifetime.
The shifting response of the cell should be checked at regular intervals
particularly on new installations.
The modules are conveniently replaceable giving a pre-calibrated standardised
output signal. They can be changed in seconds.
Service replacement modules can be supplied by our Product Support Department
on a regular basis.
Simply insert the new module into the instrument and return the original for
checking and calibration.
The sensor will transmit an alarm signal if a replacement gas sensing module is not fitted within 15 seconds.
9.4 Annual Safety Check
The main transmitter itself will not normally require maintenance or
calibration but it is advisable to return it to the Trolex Product Support
Department for an annual safety check.
9.5 Damaged Sensors
A Sensor that has been dropped or damaged in any way should be taken out of
service immediately for inspection, repair and re-calibration.
9.6 Water and Dust ingress (IP)
IP ratings do not imply that the equipment will detect gas, during and after
exposure to those conditions.
If it is suspected that the gas inlet port has been exposed to water in
conditions that exceed IPx4, the sensor should be dried and the response of
the sensor checked
9.7 Record Keeping
Institute a regular calibration and maintenance procedure and keep a record.
Incorrect use of the Sensor or inadequate maintenance may not necessarily be
self evident in the Sensor and consequently it must be regularly checked and
maintained.
9.8 Remove Gas Sensing Modules (TX6383.84)
Insert a bar into one of the radial holes in the gas inlet bush (take care not
to damage the internal filter) and unscrew the gas inlet bush.
Remove the filter from the gas inlet bush. Clean or replace the filter as
necessary. Fit a new or cleaned filter to the gas inlet bush.
Using a spanner, remove the sensor retaining nut from the remote housing.
Remove the gas sensing module from the remote housing. Fit a new gas sensing
module to the remote housing, refit the sensor retaining nut and tighten.
Refit the gas inlet bush and tighten using a bar inserted into one of the
radial holes, taking care not to damage the filter.
9.9 Maintenance and Calibration Log
Order Reference: TX
Serial Number:| Date Purchased:
Gas Type:| Location:
Date| Scheduled
Check| Fault| Recalibrate| Change
Sensor| Return
to Trolex| Comments
---|---|---|---|---|---|---
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
APPROVALS AND CERTIFICATION
10.1 Europe (ATEX)
Complies with the ATEX directive (2014/34/EU)
TX6383 Flammable Gas Sensor / Transmitter (Group I)
Ex Certificate number: SIRA 01ATEX2299
Ex Certification code: I M1 Ex ia I Ma
TX6383 Flammable Gas Sensor / Transmitter (Group II)
Ex Certificate number: SIRA 02ATEX2300
Ex Certification code: II 2G Ex ia d IIB T4 Gb
General Conditions for Safe Use
Prior to installation, it is essential that user refers to the above
certificates to ensure that the termination and cable parameters are fully
complied with and are compatible with the application. Copies of certificates
are available from Trolex.
ATEX Directive (2014/34/EU)
EMC Directive (2014/30/EU)
10.2 Australia and New Zealand
TX6383 Flammable Gas Sensor/Transmitter
Ex Certificate Number: ANZEx 12.3021X
Ex Certification Code: Ex ia I
Ex ia d IIB T4
Conditions for Safe Use:
Prior to installation, it is essential that the user refers to the above
certificate to ensure that the termination and cable parameters are fully
complied with and are compatible with the application. Copies of certificates
are available from Trolex.
New South Wales Design Registration
If the equipemt label contains an MDR number, the equipment is design
registered. This indicates that the equipment is in conformance with the
performance standard, IEC 60079-29-1, as modified by NSW Government
regulations.
10.3 Russia (Customs Union)
Ex certificate number:
Ex certification codes:
RU C-GB.AA87.B.00077/19
PO Ex ia s I Ma V
1 Ex ia IIB T4 Gb
Conditions of Use:
Prior to installation, it is essential that user refers to the above
certificate for any specific conditions of use. The user must ensure that the
termination and cable parameters are fully complied with and are compatible
with the application. Copies of certificates are available from Trolex.
10.4 South Africa
Ex certificate number: MASC MS/11-293
Ex certification codes: Ex ia I (-20°C≤Ta≤+40°C)
Ex ia d IIB T4 (-20°C≤Ta≤+40°C)
General Conditions for Safe Use
Prior to installation, it is essential that user refers to the above
certificates to ensure that the termination and cable parameters are fully
complied with and are compatible with the application.
Copies of certificates are available from Trolex.
FUNCTIONAL SAFETY
11.1 Overview of Safety Integrity Level
The following instructions are applicable when the TX6383 Flammable Gas
Sensor/Transmitter is used as an element in a safety instrumented function
that is specified to achieve a Safety Integrity Level (SIL), eg. SIL 1, 2,
etc.
The reliability of the TX6383 Flammable Gas Sensor/Transmitter has been
independently assessed in accordance with IEC 61508 for use in SIL
applications. The compliance with IEC 61508 includes hardware reliability
(probabilistic type failures) and measures to address systematic type
failures.
The information that follows forms the ‘Safety Manual’ required by IEC 61508-2
and is intended to allow correct product selection, system integration,
installation, operation and maintenance to enable the SIL specified for the
safety instrumented function to be achieved and maintained, as far as the
TX6383 Flammable Gas Sensor/Transmitter is concerned.
The actual SIL will depend on many system considerations that are outside the
scope of the TX6383 Flammable Gas Sensor/Transmitter and will rely on
personnel who are competent in the functional safety aspects of the various
lifecycle activities mentioned above.
11.2 SIL Suitability
The versions and configurations of the TX6383 Flammable Gas Sensor/Transmitter
identified in Table 1 in Section 11.3 below and are suitable for use in gas
detection safety functions that have a specified Safety Integrity Level (SIL)
in accordance with IEC 61508 or IEC 61511 up to and including:
SIL 2 – when used in a ‘Low Demand’ safety function [1] SIL 1 – when used in a
‘High Demand’ safety function [1] The functional safety data in Tables 1 and 2
in Section 11.3 must be taken into account by integrators and end-users,
including compliance with the restrictions in use (Section 11.4) and all other
provisions and conditions in this manual.
System integrators and end users responsible for other lifecycle phases
(system specification, integration, installation, commissioning, operation,
maintenance, etc) need to perform assessments on the complete scope of their
activities to ensure a target SIL for the safety function is and continues to
be met. [1] Low Demand and High Demand modes of operation are defined in IEC
61508-4, 3.5.16
11.3 Summary of the Verified Functional Safety Data
The product, configuration and safety manual that have been assessed are shown
in Table 1.
Product Information | Details |
---|---|
Product identification |
TX6383.01.12/TX6383.84.01.12/TX6383.02.12/TX6383.84.02.12 – Flammable Gas
Detector
Product specification| See Section 4 of this manual
Product configuration| 4 to 20 mA output Sensor type: CH4
System configuration| 2/3-wire loop, or 4-wire powered connection; power
supply and load as specification (noting Group I certified equipment
requirements)
Element safety function| To produce a 4 to 20 mA output that correlates with 0
to 5% v/v concentration range of methane
Safety Manual| See Section 11 of this manual
Table 1 Basic Element Information
The hardware failure data for the TX6383 element safety function based on an
extensive analysis of field failure data with a 90% single sided confidence
limit is shown in Table 2.
Parameter | Value |
---|---|
Dangerous undiagnosed failure rate (Aou) | 4.E-07 |
Dangerous diagnosed failure rate (ADD) | 5.E-06 |
Safe failure rate (AS) | N/R Li] |
Safe failure fraction (SFF) | N/R [1] |
Element type | Type B |
Hardware fault tolerance (internal architecture) | 0 |
Diagnostic coverage (DC) | 96% |
Diagnostic test interval | N/A [2] |
Probability of Failure on Demand (PFDAVG) [1 year proof test 24hr MTTR] |
2.E-03
Probability of Failure on Demand (PFDAvG) [3mth proof test 24hr MTTR]| 5.E-04
Probability of dangerous Failure per Hour (PFH)| 4.E-07
Table 2 Hardware Failure Data
- Not required by Route 2H
- This parameter is determined by the controller being used
11.4 Conditions or Restrictions for use in SIL Applications
The sections of this Installation and Operating Data manual shall be strictly
complied with to ensure validity of the failure data and systematic safety
integrity. The following additional restrictions and conditions apply when the
unit is used in SIL applications:
-
The host controller must monitor the TX6383 Flammable Gas Sensor/Transmitter output at an appropriate frequency for the application (safety time) and initiate a safe action (eg. process shutdown, evacuation, etc) or be repaired within the MTTR assumed in the PFD calculations shown in the table above if an out-of-range (low) output signal is indicated.
-
If the MTTR or the proof test interval (T1) is different from those assumed in this manual, then the PFDAVG should be re-calculated and the SIL capability reverified accordingly (refer to the Safety Manual in Section 11.5 below.
-
The display is for indication only and is not part of the safety function.
-
The environmental limits are restricted to:
• – 20 to +40°C
• relative humidity <95% -
IEC 61508-2, 7.4.4.3.1c limits use to SIL 1 in high or continuous mode of operation when used in a non-redundant configuration.
-
The unit must be calibrated at commissioning and at 3 month intervals during operation and the sensor head replaced as indicated by the calibration check.
11.5 Proof Testing
Periodic proof tests of the element safety function must be performed to
identify any dormant dangerous failures, particularly when used in ‘low
demand’ safety functions
– refer to Section 9.2 of this manual, for the proof test procedure. (Note
that calibration alone does not operate the 4 to 20 mA signal). Faults
identified by this test must be repaired within the MTTR and the unit returned
to full working order.
A suitable proof test interval (T1) should be used in order to achieve the
required average probability of failure on demand (PFDAVG). A nominal interval
of 8,760 hrs (1 year) and Mean Time to Repair (MTTR) of 24 hours has been used
in the derivation of PFDAVG for illustration purposes. If different values are
used, the PFDAVG for a non-redundant arrangement (ie. where the safety
function relies on a single element)can be re-calculated as follows:
PFDAVG = (λDU + λDD) tCE
Where tCE (the channel equivalent down time) = ( λDU/λD) (T1/2 + MTTR) + (
λDD/λD) MTTR
For redundant arrangements refer to IEC 61508-6 for the equations.
Those responsible for specifying proof testing of safety functions should
refer to IEC 61508-6:2010 clause B.3.2.5 for considerations of the effect of
non-perfect proof tests.
11.6 System Configuration Drawing
The illustration below shows how the TX6383 is to be used with other system
elements.
If a controller other than the TX9042 is used then the out of range (fault indication) signal from the TX6383 must be detected and acted upon to assert a system fault.
TROLEX LIMITED
NEWBY ROAD, HAZEL GROVE, STOCKPORT,
CHESHIRE SK7 5DY, UK
+44 (0)161 483 1435
sales@trolex.com
www.trolex.com
References