IMPORTANT INFORMATION
The R8GD Series single packaged gas/electrics are high efficiency self contained cooling units that can be installed on the roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.
WARRANTY
- This product offers a 10 year All Parts Warranty.
- This product offers a 10 year Quality Pledge to replace the entire unit, if the unit’s major component (heat exchanger or compressor) fails within the first 1 0years of operation, to the original owner.
- Consumer product registration required for both 10 year All Parts Warranty and Quality Pledge within a limited period of time after the installation. See current warranty document or visit our consumer web site listed on the back of this document for warranty details.
FEATURES and BENEFITS
- Quality Compressor: State of the art Copeland Scroll compressor is standard equipment.
- Proven, Industry Standard Components: Easier service and availability.
- R-41 0A Refrigerant: Environmentally friendly.
- High and Low Pressure Switch: Added compressor protection.
- Micro-Channel Coils: Both indoor and outdoor all Aluminum coils are designed to optimize heat transfer, minimize size and cost, and increase durability and reliability.
- Liquid Line Filter Driers: Factory installed at a convenient location for service.
- Externally Accessible Service Ports: Quick access to refrigerant system without disrupting operation.
- Compact Footprint/Low Profile: Easy to handle and transport.
- Heavy-Gauge Full Perimeter Base Rails: Facilitates forklift handling and curb mounting.
- Convertible Air Delivery: Horizontal or downflow to accommodate rooftop or horizontal application.
- Galvanized Steel Cabinet: Polyurethane finish provides 950 hour salt spray protection to resist corrosion.
- Wire Guard Coated with Earth Friendly Epoxy and Mesh Hail Guard: Will never rust and protect the coil from being damaged by balls, lawnmowers, hail etc.
- Access to Controls and Major Components: Easy in and out service.
- Low Voltage Transformer: Includes 3Ampfuse to protect low voltage circuit.
- Corrosion-Resistant Drain Pan: Quickly drains away evaporator condensate.
- One Piece Top for Great Fit and Finish, Total Seal: Well designed, quality construction. Drip edge on top panels whisks away rainwater. Embossed bottom pan keeps blower component compartment dry.
- Quiet Operation: Low vibration . 20″ fan blade combined with custom venture condenser fan.
- SmartTee® Control Board: Provides extended life to igniters using hot surface ignition technology. Programmed to learn the heat-up characteristics of the igniter, then adapt the ignition time to the characteristics of the furnace so the igniter is energized appropriately.
- Hot Surface igniter: Innovative application of an appliance type igniter with a 20 year history of reliability.
- Accessories: Roof curbs and more.
MODEL IDENTIFICATION CODE
DIMENSIONS
Model Number RSGD| Unit Weight| Shipping Weight| Center of
Gravity| Height in inches (C)
---|---|---|---|---
A| B| with base rails| without base rails
024K045t| 397| 413| 26.5| 26.5| 35.0| 31 .3
024K072t| 405| 421| 26.0| 26.5| 35.0| 31 .3
030K045t| 398| 414| 26.5| 26.5| 35.0| 31 .3
030K072t| 406| 422| 26.0| 26.5| 35.0| 31 .3
036K072t| 403| 419| 26.5| 26.5| 35.0| 31 .3
036K096t| 411| 427| 26.5| 26.5| 35.0| 31.3
042K072t| 435| 453| 27.0| 26.5| 39.0| 35.3
042K096t| 443| 461| 27.0| 26.5| 39.0| 35.3
048K096t| 453| 470| 27.5| 26.5| 39.0| 35.3
048K120t| 461| 478| 27.5| 26.5| 39.0| 35.3
X60K096t| 472| 489| 27.5| 26.5| 43.0| 39.3
X60K120t| 480| 497| 27.5| 26.5| 43.0| 39.3
Denotes ”C” or ”X”
SPECIFICATIONS AND ELECTRICAL DATA
SINGLE PHASE
MODEL RSGD| -024K045() -024K072()| -030K045()|
-030K072()| -036K072()| -036K096()| -042K72()|
-042K96()| -048K96()| -048K120() -X60K096() X60K120()
---|---|---|---|---|---|---|---|---|---
Performance
Heating Input Btuh| 45,000| 72,000| 45,000| 72,000| 72,000| 96,000| 72,000|
96,000| 96,000| 120,000| 96,000| 120,000
Heating Output Btuh| 36,000| 57,600| 36,000| 57,600| 57,600| 76,800| 57,600|
76,800| 76,800| 96,000| 76,800| 96,000
Capacity-Cooling Btuh| 23,600| 23,600| 29,000| 29,000| 35,800| 35,800| 42,000|
42,000| 46,000| 46,000| 57,000| 57,000
AFUE| 80| 80| 80| 80| 80| 80| 80| 80| 80| 80| 80| 80
Efficiency — SEER| 13.0| 13.0| 13.0| 13.0| 13.0| 13.0| 13.0| 13.0| 13.0| 13.0|
13.0| 13.0
Efficiency — EER| 11.0| 11.0| 11.0| 11.0| 11.0| 11.0| 11.0| 11.0| 11.0| 11.0|
11.0| 11.0
Electrical Rating – 60 Hz
Phase| 1| 1| 1| 1| 1| 1| 1| 1| 1| 1| 1| 1
Operating Voltage Range| 187 – 253| 187 – 253| 187 – 253| 187 – 253| 187 –
253| 187 – 253| 187 – 253| 187 – 253| 187 – 253| 187 – 253| 187 – 253| 187 –
253
Minimum Circuit Ampacity| 18.3| 18.3| 22.4| 22.4| 28.3| 28.3| 32.7| 32.7|
36.8| 36.8| 44.6| 44.6
Max . Overcurrent Protection| 30| 30| 35| 35| 45| 45| 50| 50| 60| 60| 70| 70
Compressor Data
Volts| 208 I 230| 208 I 230| 208 I 230| 208 I 230| 208 I 230| 208
I 230| 208 I 230| 208 I 230| 208 I 230| 208 I 230| 208 I 230| 208
I 230
Rated Load Amps| 12.8| 12.8| 15.7| 15.7| 18.6| 18.6| 22.1| 22.1| 24.3| 24.3|
29.3| 29.3
Lock Rotor Amps| 58.3| 58.3| 73| 73| 79| 79| 109| 109| 117| 117| 134| 134
Indoor Blower
Wheel Diameter| 10 X 10| 10 X 10| 10 X 10| 10 X 10| 10 X 10| 10 X 10| 11 X 10|
11 X 10| 11 X 10| 11 X 10| 11 X 10| 11 X 10
Motor Type| PSC| PSC| PSC| PSC| Fixed Torque| Fixed Torque| Fixed Torque|
Fixed Torque| Fixed Torque| Fixed Torque| Fixed Torque| Fixed Torque
Motor HP| 1/4| 1/4| 1/4| 1/4| 1/2| 1/2| 1/2| 1/2| 3/4| 3/4| 1| 1
Motor Amps| 1.3| 1.3| 1.3| 1.3| 3.6| 3.6| 3.6| 3.6| 5.0| 5.0| 6.5| 6.5
Outdoor Fan
Motor HP| 1/5| 1/5| 1/4| 1/4| 1/4| 1/4| 1/4| 1/4| 1/4| 1/4| 1/3| 1/3
Motor Amps| 1.0| 1.0| 1.46| 1.46| 1.46| 1.46| 1.46| 1.46| 1.46| 1.46| 1.5| 1.5
Fan Diameter/CFM| 20″ I 3800| 20″ I 3800| 20″ I 3800| 20″ I 3800| 20″
I 3800| 20″ I 3800| 20″ I 3800| 20″ I 3800| 20″ I 3800| 20″ I
3800| 20″ I 3800| 20″ I 3800
Refrigerant Charge (oz)| 60| 60| 64| 64| 59| 59| 71| 71| 62| 62| 64| 64
Sound Rating| 71| 71| 76| 76| 78| 78| 78| 78| 77| 77| 78| 78
AIRFLOW DATA
Model Number RSGD| Heating Input (Btu/h)| Heating Output
(Btu/h)| Heating Rise Range (Btu/h)| Blower Size| Motor HP|
Motor Tap| External Static Pressure Drop – inches water
column
---|---|---|---|---|---|---|---
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
(cfm)| (OF) Rise| (cfm)| (OF) Rise| (cfm)| (OF)
Rise| (cfm)| (OF) Rise| (cfm)| (OF) Rise| (cfm)|
(OF) Rise| (cfm)| (OF) Rise| (cfm)| (OF) Rise
024K045(t)| 45,000| 36 ,000| 30-60| 10 X 10| 1/4| LOW | 1015| 34| 955| 36|
880| 39| 805| 43| 715| 48| 635| 54| 545| 63| 485| 71
MED| 1255| 28| 1190| 29| 1125| 31| 1055| 33| 965| 36| 860| 40| 765| 45| 680|
51
HIGH| 1460| 24| 1385| 25| 1315| 26| 1240| 28| 1160| 30| 1050| 33| 935| 37|
830| 42
024K072(t)| 72,000| 57,600| 40-70| 10 X 10| 1/4| LOW| 1015| 55| 955| 58| 880|
63| 805| 69| 715| 77| 635| 87| 545| 102| 485| 114
MED | 1255| 44| 1190| 46| 1125| 49| 1055| 52| 965| 57| 860| 64| 765| 72|
680| 81
HIGH| 1460| 38| 1385| 40| 1315| 42| 1240| 45| 1160| 48| 1050| 53| 935| 59|
830| 67
030K045)(| t 45,000| 36,000| 30-60| 10 X 10| 1/4| LOW | 1015| 34| 955| 36|
880| 39| 805| 43| 715| 48| 635| 54| 545| 63| 485| 71
M ED | 1255| 28| 1190| 29| 1125| 31| 1055| 33| 965| 36| 860| 40| 765| 45|
680| 51
HIGH| 1460| 24| 1385| 25| 1315| 26| 1240| 28| 1160| 30| 1050| 33| 935| 37|
830| 42
030K072)(| t 72,000| 57,600| 40-70| 10 X 10| 1/4| LOW| 1015| 55| 955| 58| 880|
63| 805| 69| 715| 77| 635| 87| 545| 102| 485| 114
MED *| 1255| 44| 1190| 46| 1125| 49| 1055| 52| 965| 57| 860| 64| 765| 72|
680| 81
HIGH| 1460| 38| 1385| 40| 1315| 42| 1240| 45| 1160| 48| 1050| 53| 935| 59|
830| 67
036K072(t)| 72,000| 57,600| 40 -70| 10 X 10| 1/2| TapT1| 1085| 51| 1025| 54|
975| 57| 925| 60| 850| 65| 790| 70| 745| 74| 695| 80
TapT2 *| 1249| 44| 1178| 47| 1123| 49| 1065| 52| 979| 57| 908| 61| 858| 64|
800| 69
TapT3| 1390| 40| 1310| 42| 1250| 44| 1185| 47| 1090| 51| 1010| 55| 955| 58|
890| 62
Tap T4 | 1495| 37| 1445| 38| 1400| 40| 1355| 41| 1305| 42| 1260| 44| 1210|
46| 1155| 48
TapT5| 1560| 35| 1515| 37| 1470| 38| 1420| 39| 1370| 40| 1325| 42| 1280| 43|
1225| 45
036K096(t)| 96,000| 76,800| 45-7 5| 10 X 10| 1/2| TapT1| 1085| 68| 1025| 72|
975| 76| 925| 80| 850| 87| 790| 93| 745| 99| 695| 106
TapT2| 1249| 59| 1178| 63| 1123| 66| 1065| 69| 979| 75| 908| 81| 858| 86| 800|
92
TapT3 | 1390| 53| 1310| 56| 1250| 59| 1185| 62| 1090| 68| 1010| 73| 955| 77|
890| 83
Tap T4 *| 1495| 49| 1445| 51| 1400| 53| 1355| 54| 1305| 57| 1260| 59| 1210|
61| 1155| 64
TapT5| 1560| 47| 1515| 49| 1470| 50| 1420| 52| 1370| 54| 1325| 56| 1280| 58|
1225| 60
- Denotes factory set cooling speed
** Denotes factory set heating speed
** Denotes factory set cooling and heating speed
Part number may contain a C or X.
Heat rise: Btu/h (Input) = CFM △ T 1.08
△ T = (Btu/h 0.83) I (CFM * 1.08)
Model Number R8GD| Heating Input (Btu/h)| Heating Output
(Btu/h)| Heating Rise Range (Btu/h)| Blower Size| Motor
HP| Motor Tap| External Static Pressure Drop – inches
water column
---|---|---|---|---|---|---|---
0.1| 0.2| 0.3| 0.4| 0.5| 0.6| 0.7| 0.8
(cfm)| (OF) Rise| (cfm)| (O F) Rise| (cfm)| (OF)
Rise| (cfm)| (O F) Rise| (cfm)| (O F) Rise|
(cfm)| (OF) Rise| (cfm)| (O F) Rise| (cfm)| (OF)
Rise
042K072(t)| 72,000| 57,600| 35-65| 11 X 10| 1/2| TapT1| 1140| 49| 1075|
51| 1110| 50| 940| 59| 850| 65| 770| 72| 715| 77| 640| 86
TapT2 | 1310| 42| 1250| 44| 1180| 47| 1130| 49| 1050| 53| 975| 57| 895| 62|
830| 67
Tap T3 | 1490| 37| 1440| 38| 1380| 40| 1320| 42| 1255| 44| 1175| 47| 1090|
51| 1020| 54
TapT4| 1621| 34| 1571| 35| 1511| 37| 1466| 38| 1409| 39| 1336| 41| 1255| 44|
1185| 47
TapT5| 1665| 33| 1615| 34| 1555| 36| 1515| 37| 1460| 38| 1390| 40| 1310| 42|
1240| 45
042K096(t)| 96,000| 76 ,800| 40-70| 11 X 10| 1/2| TapT1| 1310| 56| 1250| 59|
1180| 63| 1130| 65| 1050| 70| 975| 76| 895| 82| 830| 89
Tap T2 | 1490| 50| 1440| 51| 1380| 53| 1320| 56| 1255| 59| 1175| 63| 1090|
68| 1020| 72
TapT3 | 1556| 47| 1506| 49| 1446| 51| 1393| 53| 1332| 55| 1256| 59| 1173|
63| 1103| 67
TapT4| 1621| 46| 1571| 47| 1511| 49| 1466| 50| 1409| 52| 1336| 55| 1255| 59|
1185| 62
TapT5| 1665| 44| 1615| 46| 1555| 47| 1515| 49| 1460| 51| 1390| 53| 1310| 56|
1240| 59
048K096(t)| 96,000| 76 ,800| 40-70| 11 X 10| 3/4| TapT1| 1270| 58| 1205|
61| 1140| 65| 1050| 70| 980| 75| 920| 80| 830| 89| 770| 96
Tap T2 | 1540| 48| 1465| 50| 1400| 53| 1345| 55| 1275| 58| 1210| 61| 1150|
64| 1085| 68
Tap T3 *| 1775| 42| 1710| 43| 1650| 45| 1600| 46| 1540| 48| 1485| 50| 1425|
52| 1365| 54
TapT4| 1878| 39| 1821| 41| 1764| 42| 1716| 43| 1654| 45| 1594| 46| 1534| 48|
1479| 50
TapT5| 2015| 37| 1970| 37| 1915| 39| 1870| 39| 1805| 41| 1740| 42| 1680| 44|
1630| 45
048K120(t)| 1 20,000| 96 ,000| 45-75| 11 X 10| 3/4| TapT1| 1405| 66|
1335| 69| 1270| 73| 1200| 77| 1125| 82| 1065| 87| 990| 93| 925| 100
Tap T2 *| 1640| 56| 1565| 59| 1500| 61| 1445| 64| 1375| 67| 1310| 70| 1250|
74| 1185| 78
Tap T3 | 1775| 52| 1710| 54| 1650| 56| 1600| 58| 1540| 60| 1485| 62| 1425|
65| 1365| 68
TapT4| 1878| 49| 1821| 51| 1764| 52| 1716| 54| 1654| 56| 1594| 58| 1534| 60|
1479| 62
TapT5| 2015| 46| 1970| 47| 1915| 48| 1870| 49| 1805| 51| 1740| 53| 1680| 55|
1630| 57
060K096(t)| 96,000| 76 ,800| 40-70| 11 X 10| 1| TapT1| 1240| 59| 1185| 62|
1130| 65| 1065| 69| 1010| 73| 940| 78| 880| 84| 820| 90
Tap T2 | 1635| 45| 1595| 46| 1510| 49| 1485| 50| 1425| 52| 1365| 54| 1305|
57| 1245| 59
Tap T3 *| 1900| 39| 1855| 40| 1795| 41| 1750| 42| 1700| 43| 1650| 45| 1595|
46| 1535| 48
TapT4| 2045| 36| 2010| 37| 1955| 38| 1890| 39| 1835| 40| 1790| 41| 1740| 42|
1695| 44
TapT5| 2250| 33| 2235| 33| 2180| 34| 2150| 34| 2120| 35| 2080| 35| 2025| 36|
2005| 37
060K120(t)| 1 20,000| 96 ,000| 45-75| 11 X 10| 1| TapT1| 1240| 74| 1185| 78|
1130| 82| 1065| 87| 1010| 91| 940| 98| 880| 105| 820| 112
Tap T2 *| 1635| 56| 1595| 58| 1510| 61| 1485| 62| 1425| 65| 1365| 68| 1305|
71| 1245| 74
Tap T3 | 1900| 49| 1855| 50| 1795| 51| 1750| 53| 1700| 54| 1650| 56| 1595|
58| 1535| 60
TapT4| 2045| 45| 2010| 46| 1955| 47| 1890| 49| 1835| 50| 1790| 52| 1740| 53|
1695| 54
TapT5| 2250| 41| 2235| 41| 2180| 42| 2150| 43| 2120| 44| 2080| 44| 2025| 46|
2005| 46
- Denotes factory set cooling speed
** Denotes factory set heating speed
*** Denotes factory set cooling and heating speed
Part number may contain a C or X.
Heat rise: Btu/h (Input) = CFM △T 1.08
△ T = (Btu/h 0.83) / (CFM 1.08)
EXPANDED RATINGS
R8GD-024K
O.D.T| 65°F| 75°F| 85°F| 95°F| 105 °F|
115°F
---|---|---|---|---|---|---
CFM| E . D . B .| E . W . B
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.
900
| 80| 62| 26 .5| 23 .2| 1 .55| 25.6| 23.0| 1.72| 24.6| 22.9| 1.90| 23.7| 22.2|
2.10| 22.6| 21.6| 2.31| 20.6| 19.6| 2.56
80| 67| 28.7| 19.1| 1.58| 27.2| 18.9| 1.74| 26.2| 19.2| 1.92| 25.0| 18.0|
2.11| 23.8| 18.6| 2.33| 20.7| 16.1| 2.57
80| 72| 31.4| 14.4| 1.62| 30.1| 14.4| 1.78| 28.8| 14.7| 1.96| 27.5| 14.5|
2.15| 26.1| 14.3| 2.36| 22.5| 12.7| 2.60
75| 63| 26.4| 18.3| 1.55| 25.4| 18.2| 1.72| 24.3| 18.3| 1.90| 23.2| 18.0|
2.09| 21.9| 15.1| 2.31| 18.7| 16.7| 2.56
1100
| 80| 62| 28.1| 25.3| 1.57| 27.1| 25.3| 1.74| 26.1| 24.4| 1.92| 25.1| 23.7|
2.11| 23.9| 23.1| 2.33| 21.8| 21.0| 2.60
80| 67| 29.4| 21.4| 1.59| 28.2| 21.9| 1.75| 27.0| 21.4| 1.93| 25.8| 21.3|
2.12| 24.5| 21.3| 2.34| 22.1| 17.5| 2.62
80| 72| 32.0| 16.0| 1.63| 30.6| 16.6| 1.79| 29.3| 16.2| 1.97| 27.9| 16.1|
2.16| 26.5| 16.2| 2.37| 23.9| 13.7| 2.64
75| 63| 27.3| 20.5| 1.56| 26.1| 20.9| 1.73| 25.0| 20.4| 1.90| 23.9| 20.2|
2.10| 22.6| 20.1| 2.31| 19.6| 18.1| 2.62
1200
| 80| 62| 28.6| 26.0| 1.58| 27.7| 25.8| 1.74| 26.6| 24.8| 1.92| 25.5| 24.2|
2.12| 24.4| 23.6| 2.34| 23.2| 23.1| 2.58
80| 67| 29.8| 22.7| 1.59| 28.7| 22.9| 1.76| 27.4| 22.4| 1.94| 26.2| 22.4|
2.13| 24.9| 22.2| 2.34| 23.5| 22.2| 2.59
80| 72| 32.3| 17.1| 1.64| 31.0| 17.3| 1.80| 29.6| 16.9| 1.98| 28.2| 16.9|
2.17| 26.8| 16.9| 2.38| 25.2| 17.1| 2.61
75| 63| 27.9| 21.9| 1.57| 26.5| 21.9| 1.73| 25.4| 21.5| 1.91| 24.2| 21.3|
2.10| 23.0| 21.1| 2.32| 21.6| 21.0| 2.56
R8GD-030K
O.D.T| 65°F| 75°F| 85 °F| 95°F| 105 °F| 115
°F
---|---|---|---|---|---|---
CFM| E . D . B .| E . W . B
.| T.C.| s.c.| K . W .| T.C.| s.c.| K.W .|
T.C.| s.c.| K.W .| T.C.| s.c.| K . W .| T.C.|
s.c.| K . W .| T.C.| s.c.| K.W .
900| 80| 62| 31 .4| 26.7| 1.83| 29.1| 25.0| 2.14| 28.0| 25.1| 2.34| 26.8|
24.7| 2.56| 25.6| 25.2| 2.82| 21.8| 21.4| 2.90
80| 67| 33.0| 21.5| 1.85| 31.4| 20.3| 2.15| 30.2| 20.5| 2.36| 28.8| 20.2|
2.58| 27.4| 19.9| 2.83| 22.9| 17.0| 3.12
80| 72| 36.0| 15.8| 1.87| 34.6| 15.7| 2.17| 33.1| 16.0| 2.38| 31.7| 15.8|
2.60| 30.1| 15.6| 2.85| 25.3| 14 .3| 3.13
75| 63| 31.3| 20.5| 1.85| 29.0| 19.7| 2.14| 27.8| 19.8| 2.34| 26.6| 19.5|
2.56| 25.3| 15.8| 2.82| 20.8| 16.9| 3.03
1100| 80| 62| 32.3| 28.7| 1.95| 30.7| 28.6| 2.15| 29.6| 27.6| 2.35| 28.4|
26.8| 2.58| 27.2| 26.3| 2.83| 23.2| 23.0| 3.10
80| 67| 33.9| 22.8| 1.97| 32.5| 23.4| 2.16| 31.1| 22.9| 2.36| 29.7| 22.7|
2.58| 28.3| 22.7| 2.84| 25.0| 19.8| 3.17
80| 72| 36.8| 17.4| 1.99| 35.1| 18.1| 2.18| 33.5| 17.6| 2.38| 32.0| 17.4|
2.60| 30.4| 17.5| 2.85| 26.7| 16.4| 3.18
75| 63| 32.1| 22.6| 1.94| 30.0| 22.5| 2.14| 28.8| 22.0| 2.35| 27.4| 21.8|
2.57| 26.0| 21.8| 2.82| 22.5| 18.9| 3.13
1200| 80| 62| 31.8| 28.5| 1.96| 30.7| 28.6| 2.15| 29.7| 27.7| 2.35| 28.6|
27.1| 2.57| 27.4| 26.5| 2.82| 26.2| 26.1| 3.10
80| 67| 34.2| 23.8| 1.96| 32.9| 24.0| 2.16| 31.0| 23.3| 2.36| 30.1| 23.4|
2.58| 28.7| 23.3| 2.83| 27.1| 23.4| 3.11
80| 72| 37.8| 18.5| 2.00| 35.9| 18.7| 2.17| 33.9| 18.1| 2.38| 32.4| 18.2|
2.60| 30.9| 18.1| 2.85| 29.2| 18.4| 3.12
75| 63| 31.5| 22.9| 1.96| 30.3| 23.1| 2.14| 29.1| 22.6| 2.34| 27.8| 22.5|
2.56| 26.4| 22.3| 2.82| 25.0| 22.3| 3.10
R8GD-036K
O.D.T| 65°F| 75°F| 85 °F| 95°F| 105 °F| 115
°F
---|---|---|---|---|---|---
CFM| E . D . B.| E . W.B .| T.C.| s.c.|
K . W.| T.C.| s.c.| K . W .| T.C.| s.c.|
K.W .| T.C.| s.c.| K . W .| T.C.| s.c.| K
. W.| T.C.| s.c.| K . W .
1150| 80| 62| 37 .3| 30 .9| 2.15| 36.0| 30.7| 2.37| 34.6| 30.8| 2.62| 33.2|
30.2| 2.90| 31.6| 31.1| 3.23| 29.9| 29.4| 3.61
80| 67| 40.6| 25.4| 2.16| 39.0| 25.2| 2.39| 37.5| 25.5| 2.64| 35.9| 25.1|
2.90| 34.1| 24.8| 3.22| 32.1| 23.4| 3.60
80| 72| 44.4| 19.6| 2.19| 42.9| 19.5| 2.42| 41.2| 20.0| 2.66| 39.4| 19.7|
2.93| 37.5| 19.5| 3.23| 35.3| 20.0| 3.59
75| 63| 37.4| 24.6| 2.15| 36.0| 24.4| 2.37| 34.6| 24.7| 2.62| 33.0| 24.2|
2.90| 31.2| 22.4| 3.23| 29.4| 24.0| 3.62
1300| 80| 62| 38.4| 33.1| 2.15| 37.1| 33.6| 2.38| 35.8| 32.8| 2.62| 34.2|
32.2| 2.90| 32.7| 31.6| 3.23| 31.1| 30.8| 3.60
80| 67| 41.3| 27.0| 2.17| 39.8| 27.8| 2.40| 38.3| 27.3| 2.64| 36.7| 27.1|
2.91| 34.8| 27.1| 3.22| 32.8| 27.1| 3.60
80| 72| 45.2| 20.7| 2.20| 43.5| 21.7| 2.43| 41.8| 21.2| 2.67| 39.9| 21.1|
2.93| 38.0| 21.3| 3.23| 35.8| 21.5| 3.59
75| 63| 38.2| 26.2| 2.15| 36.8| 26.9| 2.38| 35.3| 26.3| 2.62| 33.7| 26.0|
2.90| 31.9| 26.0| 3.23| 30.0| 25.9| 3.61
1450| 80| 62| 39.4| 35.2| 2.16| 37.9| 35.3| 2.38| 36.6| 34.1| 2.62| 35.3|
33.5| 2.90| 33.8| 32.6| 3.22| 32.1| 31.9| 3.60
80| 67| 42.1| 29.2| 2.18| 40.6| 29.5| 2.40| 39.0| 28.9| 2.65| 37.3| 28.9|
2.91| 35.4| 28.8| 3.22| 33.4| 28.9| 3.59
80| 72| 45.8| 22.3| 2.20| 44.1| 22.8| 2.43| 42.2| 22.3| 2.67| 40.4| 22.4|
2.94| 38.5| 22.4| 3.24| 36.3| 22.7| 3.58
75| 63| 38.9| 28.2| 2.16| 37.5| 28.5| 2.38| 36.0| 27.8| 2.62| 34.3| 27.7|
2.90| 32.5| 27.5| 3.23| 30.6| 27.5| 3.61
R8GD-042K
O.D.T| 65°F| 75°F| 85°F| 95°F| 105 °F|
115°F
---|---|---|---|---|---|---
CFM| E . D . B .| E . W . B
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.| T.C.| s.c.| K . W .| T.C.| s.c.| K . W
.
1250| 80| 62| 44.0| 34.9| 2.64| 43.1| 34.5| 2.90| 41.9| 34.9| 3.20| 39.1|
34.2| 3.59| 37.3| 35.5| 3.98| 35.5| 33.9| 4.41
80| 67| 48.1| 29.2| 2.69| 45.3| 28.5| 2.96| 47.9| 30.8| 3.24| 42.8| 28.3|
3.59| 40.5| 27.8| 3.97| 38.3| 26.1| 4.39
80| 72| 53.0| 22.6| 2.68| 50.3| 23.1| 3.14| 47.9| 21.6| 3.49| 46.2| 19.9|
3.64| 42.5| 19.1| 4.06| 41.9| 18.9| 4.50
75| 63| 44.5| 28.1| 2.65| 42.7| 27.8| 2.93| 41.1| 28.1| 3.24| 39.3| 27.1|
3.60| 37.9| 25.4| 3.96| 35.7| 27.5| 4.41
1400| 80| 62| 45.2| 37.1| 2.65| 43.6| 35.5| 2.94| 42.1| 34.2| 3.33| 40.3|
32.0| 3.60| 38.7| 30.8| 3.97| 36.7| 29.8| 4.38
80| 67| 49.2| 32.5| 2.63| 48.1| 30.9| 2.95| 46.3| 29.7| 3.10| 43.2| 27.8|
3.64| 41.2| 27.0| 4.03| 39.1| 25.9| 4.45
80| 72| 55.3| 27.1| 2.71| 51.4| 25.2| 3.01| 49.4| 24.2| 3.36| 47.1| 23.6|
3.96| 44.7| 21.9| 4.10| 42.6| 21.3| 4.50
75| 63| 45.3| 29.6| 2.65| 43.8| 30.4| 2.92| 41.1| 30.8| 3.27| 40.0| 28.9|
3.60| 38.2| 29.2| 3.99| 36.2| 29.3| 4.42
1550| 80| 62| 46.3| 39.7| 2.66| 47.8| 42.1| 2.92| 45.9| 41.1| 3.22| 41.2|
38.4| 3.61| 39.2| 37.9| 4.01| 37.5| 37.4| 4.44
80| 67| 50.9| 33.2| 2.71| 48.1| 33.3| 2.96| 49.5| 34.2| 3.26| 47.3| 34.1|
3.60| 42.4| 32.9| 3.97| 42.6| 34.2| 4.40
80| 72| 55.5| 25.6| 2.67| 51.4| 24.2| 3.15| 49.3| 25.6| 3.50| 48.9| 26.9|
3.64| 45.5| 25.9| 4.07| 43.1| 25.8| 4.51
75| 63| 46.3| 31.7| 2.67| 45.2| 32.2| 2.96| 42.8| 27.8| 3.26| 40.7| 30.7|
3.61| 38.8| 30.7| 4.00| 36.8| 31.0| 4.43
R8GD-048K
O.D.T | 65°F | 75°F | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|---|---|
CFM | E.D. B. | E.W.B. | T.C. | s.c . | K.W. | T.C. |
T.C. | s.c . | K.W. | T.C. | s.c. | K.W. | T.C. |
1400 | 80 | 62 | 46.8 | 37.8 | 2.88 | 45.1 |
33.4 | 3.91 | 40.5 | 33.7 | 4.31 | 38.2 | 31.8 |
80 | 67 | 50.2 | 31.1 | 2.99 | 47.3 | 29.7 |
3.96 | 41.1 | 24.6 | 4.37 | 40.4 | 29.2 | 4.85 |
80 | 72 | 53.8 | 26.9 | 2.93 | 52.1 | 24.0 |
4.00 | 47.3 | 21.2 | 4.48 | 43.6 | 20.6 | 4.91 |
75 | 63 | 47.8 | 30.5 | 2.84 | 45.3 | 30.0 |
3.92 | 39.5 | 27.7 | 4.35 | 37.4 | 29.5 | 4.80 |
1600 | 80 | 62 | 49.1 | 40.9 | 2.85 | 45.8 |
40.1 | 3.92 | 41.1 | 39.6 | 4.36 | 38.7 | 38.4 |
80 | 67 | 51.3 | 35.9 | 3.00 | 51.2 | 34.8 |
3.97 | 43.8 | 33.4 | 4.38 | 39.9 | 29.1 | 4.97 |
80 | 72 | 56.3 | 28.2 | 3.10 | 53.3 | 27.1 |
4.06 | 47.1 | 23.4 | 4.42 | 43.4 | 22.2 | 4.99 |
75 | 63 | 48.1 | 32.2 | 2.88 | 46.1 | 32.9 |
3.93 | 40.6 | 31.9 | 4.33 | 34.9 | 29.0 | 4.91 |
1800 | 80 | 62 | 49.3 | 43.2 | 3.10 | 46.8 |
40.1 | 4.00 | 41.9 | 33.3 | 4.39 | 40.3 | 34.1 |
80 | 67 | 52.1 | 36.3 | 3.30 | 51.5 | 36.6 |
3.97 | 46.1 | 28.4 | 4.39 | 42 .1 | 31.4 | 4.97 |
80 | 72 | 54.4 | 26.7 | 3.50 | 53.0 | 27.4 |
4.03 | 47.2 | 26.9 | 4.43 | 45.3 | 27.8 | 5.01 |
75 | 63 | 49.8 | 34.9 | 3.10 | 46.3 | 34.5 |
3.98 | 41.4 | 33.8 | 4.38 | 39.3 | 33.9 | 4.95 |
R8GD-X60K
O.D.T | 65°F | 75°F | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|---|---|
CFM | E. D.B . | E.W.B. | T.C. | s.c. | K.W. | T.C. |
T.C. | s.c. | K.W. | T.C. | s.c. | K.W. | T.C. |
1500 | 80 | 62 | 58.3 | 44.0 | 3.75 | 56.2 |
43.0 | 5.11 | 48.9 | 45.1 | 5.68 | 46.1 | 42.5 |
80 | 67 | 63.8 | 37.0 | 3.82 | 61.4 | 36.7 |
5.18 | 53.2 | 35.8 | 5.77 | 50.0 | 33.3 | 6.43 |
80 | 72 | 70.8 | 29.0 | 3.90 | 68.0 | 28.8 |
5.28 | 58.6 | 28.3 | 5.88 | 54.9 | 29.0 | 6.57 |
75 | 63 | 59.0 | 35.9 | 3.77 | 56.8 | 35.6 |
5.11 | 49.3 | 32.4 | 5.69 | 46.3 | 34.5 | 6.36 |
1700 | 80 | 62 | 60.1 | 47.1 | 3.78 | 57.9 |
46.3 | 5.13 | 50.3 | 46.0 | 5.71 | 43.5 | 41.0 |
80 | 67 | 65.6 | 39.4 | 3.84 | 63.0 | 40.5 |
5.20 | 54.5 | 38.7 | 5.79 | 51.1 | 38.7 | 6.46 |
80 | 72 | 72.5 | 30.5 | 3.93 | 69.6 | 31.9 |
5.31 | 59.6 | 30.9 | 5.90 | 55.6 | 31.0 | 6.59 |
75 | 63 | 60.7 | 38.1 | 3.78 | 58.4 | 39.1 |
5.14 | 50.5 | 37.2 | 5.72 | 47.4 | 37.0 | 6.38 |
1900 | 80 | 62 | 61.6 | 50.7 | 3.80 | 59.3 |
49.3 | 5.15 | 51.5 | 48.5 | 5.73 | 46.9 | 44.8 |
80 | 67 | 67.0 | 42.4 | 3.85 | 64.4 | 42.9 |
5.22 | 55.5 | 41.0 | 5.81 | 52.0 | 41.1 | 6.48 |
80 | 72 | 73.8 | 32.8 | 3.94 | 70.7 | 33.5 |
5.32 | 60.1 | 32.3 | 5.91 | 56.2 | 32.6 | 6.61 |
75 | 63 | 62.0 | 40.9 | 3.79 | 59.7 | 41.0 |
5.15 | 51.5 | 39.3 | 5.73 | 48.3 | 39.3 | 6.40 |
R8GD ACCESSORIES
Description | Part Number |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14″) | 547831 |
Roof Curb (18″) | 547850 |
Roof Curb (24″) | 547851 |
Cap, Duct Adapter, 12″ Round | 913811A |
Cap, Duct Adapter, 14″ Round | 913812A |
Supply/return transition, 16″ | 547834 |
Supply/return transition, 18″ | 547835 |
Concentric diffuser, flush, 16″ | 547836 |
Concentric diffuser, flush, 18″ | 547837 |
Concentric diffuser, step down 16″ | 547838 |
Concentric diffuser, step down 18″ | 547839 |
Manual Fresh Air Damper | 547832 |
Motorized Fresh Air Damper | 547840 |
Economizer, Downflow, Modulating w/filter (does not require filter kit) 2 –
2.5 Ton| 547833
Economizer, Downflow, Modulating w/filter (does not require filter kit) 3 – 5
Ton| 558870
Economizer, Horizontal, Modulating 2 – 5 Ton| 547841
Power Exhaust, Downflow (application requires downflow economizer) (Special
Order)| 547842
Power Exhaust, Horizontal (application requires horizontal economizer)
(Special Order)| 547843
Filter Kit R6GD 024 – 042| 547888
Filter Kit R6GD 048 – 060| 547889
Filter Kit, All Downflow Applications (not required with economizer)| 547885
Hood Type Hail Guard, Coil Dim. 30″ X 76″ 2, 2.5, 3 Ton| 547844
Hood Type Hail Guard, Coil Dim. 34″ X 76″ 3.5 – 4 Ton| 547846
Hood Type Hail Guard, Coil Dim. 38″ X 76″ 5 Ton| 547847
DUCT SMOKE DETECTOR PHOTO ELEC| 558863
MULTI SIGNAL CONTROL| 547893
SAMPLING TUBE DST3, 2-4ft| 558864
SAMPLING TUBE DST5, 4-8ft| 558865
Low Ambient Kit| 918837
U.S. – LP Gas/High Elevation Conversion Kit, 1 & 2 Stage models (0 – 10,000
ft. above sea level)| 904404A
Canada – LP Gas/High Elevation Conversion Kit, 1 & 2 Stage models (0 – 4,500
ft. above sea level)| 904405A
Outdoor Thermostat Kit| 913852
Universal Hard Start Kit| 912933
Skirt Trim Kit| 919729
Extreme High Wind Kit – Roof Curb Mount| 903696
Extreme High Wind Kit – Ground Mount| 903695
Freeze stat Kit| 917108
Control, CO2 Sensor, Wall Mount| 920317
Control, CO2 sensor, Duct Mount| 920318
GENERAL TERMS OF LIMITED WARRANTY
NORDYNE will furnish a replacement for any part of this product which fails in normal use and service within the first ten years of installation, in accordance with the terms of the warranty.
For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the NORDYNE warranty department for a copy.
8000 Phoenix Parkway | O’Fallon, MO 63368-3827
Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.S.A (05/2012)
CUSTOMER SUPPORT
917D-0512 (Replaces 917D-0412)
NuTone® trademark used under license. © Nortek Global HVAC, LLC. All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>