Chillers and Inverter Air/Water heat pumps with axial fans
Technical Bulletin
Models
i-290 0121/i-290 0123
i-290 0125/i-290 0127
i-290 0121 Inverter Air Water Heat Pumps with Axial Fans
This manual has been created for informative purpose. The company declines any responsibility for the results of any projecting or any installation based on the explanations and/or on the technical specifications provided in this manual. It is besides forbidden the reproduction under any form of the texts of the figures contained in this manual. This manual is a translation from the official italian language version. For reasons of environmental respect the Company will not provide the hard copy in the original language which could be directly requested or downloaded from the Company website at any time. In case of any dispute, the original language manual will be the trusted one. Even partial reproduction PROHIBITED © – Advantix SpA
00 | 10-2023 | AL.B | A.R. | First issue |
---|---|---|---|---|
Rev | Date | Author | Approved | Note |
Catalogo | Serie | |||
BTE02060120000_00 | INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS |
DESCRIPTION OF UNIT AND TECHNICAL SPECIFICATIONS
The i-290 heat pumps were designed for outdoor use in residential and
commercial applications only: They are extremely versatile and prepared for
heat pump operation with hot water production for ambient heating and for
sanitary use at a temperature of 78 °C. The refrigerant employed is R290 gas,
which, thanks to its low GWP, ensures a long term solution in terms of
efficiency and environmental sustainability. Use of the INVERTER-controlled
brushless compressor technology, coupled with electronic expansion valve,
circulator pump and variable speed fan ensures excellent performance, due to
the optimisation of the specifics consumption and the high modulating
capacity, which in turn translate into high COP, EER, SCOP and SEER values.
1.1 FRAMEWORK
All units of the range are manufactured from continuously hot-dip galvanised
sheet steel and painted with polyurethane powders in an oven at 180°C to
ensure the best weather resistance. The frame is self-supporting with
removable panels for easier inspection and maintenance of the inner
components. All screws and rivets for outdoor installation are in galvanised
steel.
1.2 COMPRESSORS
The DC inverter compressor is scroll type, are designed to operate with R290,
equipped with thermal protection and mounted on rubber vibration dampers. The
compressors re installed in a compartment separated from the air flow to
reduce noise. They are
also equipped with crankcase heater to prevent oil dilution and consequently
galling.
The compressors can be inspected by removing the side and front panels of the
unit, so that they can be serviced even with the units running.
1.3 AIR SIDE HEAT EXCHANGER
The air heat exchangers are made of copper pipes and prepainted aluminium
fins. The pipes are mechanically expanded into aluminium fins to increase the
thermal exchange factor. The shape of these exchangers allows a low air side
pressure drops and therefore fans can run at low speed (thus reducing unit
noise).
As optional the coils can be supplied with a “SILVER LINE” to allow greater
resistance to acidity and salt spray resulting in increased hydrophilic
ability and performance compared to a battery with simple aluminium fins. The
air side exchangers are designed to minimise the refrigerant gas charge.
1.4 UTILITY SIDE HEAT EXCHANGER
The utility heat exchangers are the brazed plate type, made of stainless steel
AISI 304, insulated at the factory with closed cell material. They can be
equipped with anti-freeze electric heater (optional KA accessory). Each
evaporator is protected by a temperature sensor used as an antifreeze
protective probe which activates the circulator, even when the machine is
switched off, if the conditions imposed on the control occur.
1.5 FAN (EC)
The fans are made of plastic, the axial type with airfoil blades. They are all
statically and dynamically balanced and are supplied complete with protective
grid. All electric motors used are brushless modulating to optimise the
evaporation/condensation pressure in summer/winter operation so as to allow
the correct operation of the machine. The motors are directly coupled and
equipped with integrated thermal protection with IP54rating.
1.6 COOLING CIRCUIT
The cooling circuit is made with components of leading international companies
and in compliance with UNI EN standard 13134 on braze-welding procedures. The
coolant is the new R290 (GWP equal to 3) ecological gas. The basic version of
the cooling circuit includes: 4-way cycle reversing valve, electronic
expansion valve, liquid separator, liquid receiver, safety device (high-
pressure switch), pressure transducers to carefully measure evaporation and
condensing pressure, dehydrating filter to prevent clogging of the lamination
valve, liquid flow indicator and presence of moisture. The suction line is
thermally insulated with flexible, closed-cell elastomeric foam.
A pressure test is performed to detect any potential leakage and the unit is
supplied already charged with the optimal amount of gas for proper
functioning.
LEGEND
ACRONYM| NUM.| DESCRIPTION| ACRONYM| NUM.|
DESCRIPTION
INVC| 1| VARIABLE SPPED COMPRESSOR| W-OUT| | SYSTEM WATER OUTLET LINE
CO/EV| 1| CONDENSER (IN CHILLER OPERATION)| W-IN| | SYSTEM WATER INLET LINE
EV/CO| 1| EVAPORATOR (IN CHILLER OPERATION)| TRH| 1| HIGH PRESSURE TRANSDUCER
EEV| 1| ELECTRONIC EXPANSION VALVE| TRL| 2| LOW PRESSURE TRANSDUCER
Y4W| 1| 4-WAY CYCLE REVERSING VALVE| TE EXT| 1| OUTDOOR AIR TEMPERATURE PROBE
TH| | SAFETY THERMOSTAT| TE SD| 1| SUCTION LINE TEMPERATURE PROBE
F| 1| FILTER| TE DT| 1| COMPRESSOR DISCHARGE TEMPERATURE PROBE
SV| | FILLING CONNECTION| PSH| 1| HIGH-PRESSURE SWITCH
HC| 1| CRANKCASE HEATER| TE IN| 1| USER INPUT TEMPERATURE PROBE
MAF| 1| AXIAL FAN| TE OUT| 1| USER OUTLET TEMPERATURE PROBE
CV| 1,2,3,4| NON-RETURN VALVE| DV| | DRAIN TAP
SL| | LIQUID SEPARATOR| RV| | SAFETY VALVE
RS| | SUCTION LINE| FM| 1| FLOWMETR
RD| | DISCHARGE LINE| P| | ELECTRONIC CIRCULATOR
RL| | LIQUID LINE| AV| | AUTOMATIC AIR VENT VALVE
RD/RS| | DISCHARGE/SUCTION LINE| DA| | DEAERATOR
RS/RD| | SUCTION/DISCHARGE LINE| KAS| 1| PLATE EXCHANGER ANTIFREEZE HEATER
SG| 1| MOISTURE INDICATOR| LR| 1| LIQUID RECEIVER
1.7 ELECTRICAL PANEL
The electric panel is designed in compliance with current European standards.
The electric panel can be accessed by removing the cover on the unit using a
specific tool. The electric panel has an IPX4 protection rating. The panel is
also supplied with an auxiliary board for electrical connections and
utilities. The auxiliary board has digital inputs with voltage-free contact
for:
- ON-OFF remoto.
- Summer/winter mode.
- Double set-point control.
There are also analogue inputs for:
- Domestic hot water sensor.
- Storage sensor.
Below listed the digital inputs (max. voltage available for input: 0,5 A):
- Machine stall alarm.
- 3-way valve for Domestic Hot Water control.
- Double set-point control.
The system is pre-fitted with connectivity arrangement for ModBus RTU RS-485
monitoring and 12 VAC supply i-CR wall-mounted controller.
1.8 CONTROL SYSTEM
All i-290 units are equipped with microprocessor with overheating control
logic by means of an electronic thermostatic valve managed according to the
signals sent by the pressure transducers. The CPU also controls the following
functions: water temperature control, antifreeze protection, compressor
timing, alarm reset, alarm management and operating LEDs. The control system,
with the INVERTER technology and on board sensors, monitors and continuously
adapts the performance of the inverter compressor, of the circulator and of
the fan.
1.9 CONTROL AND PROTECTIVE DEVICES
All the units are standard supplied with the following control and protective
devices: return water temperature sensor, installed on water return
pipe from the system, working and antifreeze probe installed on the water
discharge pipe to the system, high pressure transducer, low pressure
transducer, temperature probes on both the compressor’s suction and discharge
lines, compressor thermal protection, fan thermal protection,
water side flowmeter protecting the evaporator, high pressure switch.
1.10 HYDRAULIC CIRCUIT
i-290 chillers are supplied with a built-in water circuit which includes:
modulating circulator with high-efficiency brushless motor (EEI≤0,23),
suitable for the use of chilled water and managed directly by the machine’s
controller, plate heat exchanger, flowmeter, safety valve (6 bar) to
be connected to an exhaust and deaerator system with air release valve.
DESCRIPTION OF VERSIONS AND ACCESSORIES
12.1 VERSIONS
i-290: reversible heat pump with built-in hydronic unit (safety valve,
modulating circulator, flowmeter, filling/drain valve).
Available models: 0121, 0123, 0125, 0127. The power supply is three-phase.
The unit code consists of the following elements:
- 7 fixed digits.
- The symbol # as separator.
- 10 variable digits (fields) identifying the sizes, power supply and factory mounted accessories.
- 2 variable digits (MC field) which identify the i-290 series in any customisations.
0112822#(RV)(CT1)(SIL)(KA)(TR)(RP)(MB)(AC1)(MC)
Order code | 0112822# | i-290 |
---|---|---|
Configuration | 57 | Reversible heat pump |
Size | 24 | 0121 |
40 | 0123 | |
41 | 0125 | |
42 | 0127 | |
– | 0 | – |
Antifreeze kit | 0 | – |
1 | With antifreeze kit (KA) | |
7 | Base resistance (KA3) | |
Heat exchanger treatment | 0 | – |
8 | With Silverline treatment (TR2) | |
Protection grids | 0 | – |
1 | With protection grids (RP) | |
Modbus | 0 | – |
1 | Modbus connectivity (CM) | |
– | 0 | – |
– | 01 | – |
CAUTION: The antifreeze kit is a factory mounted accessory. It is not
possible to install it later.
2.1 LIST OF ACCESSORIES
The available accessories for the i-290 heat pumps are listed below.
| Accessory| Standard| Factory-fitted| Supplied separately
---|---|---|---|---
AG – Vibration damper kit| x| | | x
KA – Antifreeze kit| x| | x|
KA3 – Antifreeze kit (base frame only)| x| | x|
TR2 – Coils anticorrosion treatment| x| | x|
RP – Coils protection grids| x| | x| x
FY – Y-filter| x| | | x
Filling /drain valve| | x| x|
Water side safety valve| | x| x|
VDIS3 – Diverter valve (1”1/4) Kvs 20,8| x| | | x
Electronic throttling valve| | x| x|
SAS – Domestic hot water probe / System remote probe| x| | | x
SPS – Solar panel probe for GI3| x| | | x
Flowmeter (flow presence signal)| | x| x|
Hi-TV415 – Multifunctional touch screen remote control| x| | | x
i-CR – Wall-mounted remote control| | x| x|
GI3 – External system management module| x| | | x
FD – Dirt separator| x| | | x
Deaerator| | x| x|
Electronic circulator| | x| x|
Remote on/off voltage-free contact| | x| x|
BMS connectivity arrangement – ModBus protocol included (CM)| x| | x| x
USB/RS485 Serial converter (ISK)| x| | | x
Local LAN/WiFi converter (LNC)| x| | | x
OpenVPN LAN/Wifi 3G Remote Converter (OVPN)| x| | | x
Editing the dynamic set-point – climate curve (via external air probe fitted
in the unit)| | x| | x
Dry contact for summer/winter selection| | x| | x
Machine block signal| | x| x|
Enabling maximum Hz ()| | x| | x
Enabling minimum Hz ()| | x| x|
Digital input for double set-point| | x| | x
(*) Functions can be enabled as an alternative.
2.2 DESCRIPTION OF ACCESSORIES
2.2.1 Component supplied as standard
Electronic circulator – standard on the unit, electronically controlled and
high efficiency.
Flowmeter (flow presence signal) – this device monitors and signals water
circulation in the plate heat exchanger. This component is essential because
it switches off and secures the unit preventing the formation of ice.
Electronic throttling valve – expansion valve, designed for the control and
continuous regulation of the amount of refrigerant entering the evaporator. To
optimise consumption, changes in thermal load can be monitored quickly.
Water side safety valve – valve installed on the hydraulic circuit to control
overpressure – setting 3 bar.
Filling / drain valve – there is always a service valve in the unit that is
used to fill/discharge the amount of water in the system or adjust the glycol
percentage.
Deaerator – component to continuously capture and expel air and any other
gases dissolved in the water in the hydraulic circuit. The removal efficiency
of this device is very high, allowing the elimination of non-condensable gases
present in the circuits down to microbubble level.
i-CR – wall-mounted remote control – Modbus remote control with negative LCD
and capacitive keys. The device is to be used as a remote machine keyboard
with local temperature detection, replicating the functionality of the on-
board control.
Remote on/off voltage-free contact – contact on the auxiliary board which
allows the unit to be switched on and off.
Changing the dynamic set-point – climate curve (via the outside air probe in
the unit) – the controller allows the set-point to be changed by adding a
value according to the temperature of the outside air probe.
Dry contact for Summer/Winter selection – possibility to remotely control the
heating or cooling mode of operation of the heat pump.
Machine block signalling – control system signalling of locked unit (can be
reset manually). Alternatively, one of the following functions can be
activated (contact after-sales service):
- Alarm signalling;
- Defrosting signalling;
- Compressor running signalling;
- Season signalling;
- System integration resistor management;
- Sanitary integration resistor management;
Enabling minimum Hz – With the activation of this function (which must be done
following the procedure described in the control manual) the unit will reduce
the power consumption by approximately 10% of the nominal reference value,
resulting in a reduction in capacity. Alternative function at maximum Hz.
Enabling maximum Hz – With the activation of this function (which must be
enabled by the after-sales service) the unit will increase the capacity by
approximately 10% over the reference nominal value, resulting in an increase
in power consumption. Alternative function at minimum Hz.
Digital input for double set-point – input to change the set point.
Fan silent mode – Digital input that can be activated by external contact,
allowing the sound power level to be reduced by acting on the ventilation. The
mode is particularly suitable during night operation. Below are the decreases
in capacity and sound power level when the fan silent mode function is active.
The reduction refers to test condition (3) of the technical data tables; the
value is determined on the basis of measurements carried out in accordance
with UNI EN ISO 9614-1, in compliance with the requirements of Eurovent
certification.
Model i-290| Yield reduction factor [-] A7W35| Sound power level
reduction [dB(A)]
---|---|---
0121| 0,989| -1
0123| 0,981| -1
0125| 0,978| -1
0127| 0,972| -1
2.2.2 Factory-fitted accessories
KA – Antifreeze kit – It involves the use of a self-heating cable that is
fixed to the base of the unit in the vicinity of the condensation coil and a
PET resistance placed on the face of the plate heat exchanger.
KA3 – Antifreeze kit (base frame only) – This only involves the use of a
self-heating cable that is applied to the base of the unit near the
condensation coil.
TR2 – Coil anticorrosion treatment – With the treatment the coil becomes
flexible to withstand contractions and thermal expansions, it is mechanically
resistant, UV-protected and dirt repellent. Heat transmission losses are very
low. The treatment ensures coil
protection in all environmental conditions: from marine to rural settings,
from industrial to urban areas.
For specific cleaning instructions for coils treated in this way, please refer
to the chapter in the user-installer manual ‘Cleaning of Corrosion Treated
Coils’.
The treatment withstands 6000 h according to ASTM B117.
BMS connectivity arrangement – ModBus protocol included (CM) – accessory to
connect the unit to external controllers via serial cable with RS-485 electric
standard and ModBus RTU protocol. This accessory can also be activated after
sales.
RP – Battery protection grids – wire mesh to prevent the intrusion of foreign
bodies inside the battery and to protect the battery from accidental contact
with things or people (can also be ordered as a separate accessory).
2.2.3 Accessories supplied separately
AG – Vibration damper kit – they prevent transmitting vibrations to the
structure; they must be fitted into the appropriate holes underneath the unit.
GI3 – External plant management module – allows management of the following
functions:
- Recirculation circulator management.
- System-side mixing valve management.
- Solar thermal integration management.
VDIS3 – Diverter valve – 3-way motorised ball valve Kvs 20.8, connections F 1″ 1/4 complete with servo-control.
Permitted substances: water from 0°C to +110°C.
Maximum differential pressure: 6 bar
Please refer to the document enclosed with the product for more information.
CAUTION: Install the valve outside the danger and safety zones indicated
in Chapter 3.6.
FY – Y-filter – contains a stainless steel mesh sieve (500 μm filtration)
that collects solids in the water. Filtration prevents clogging and/or damage
to devices installed downstream of the filter. Alternatively, it is possible
to install a dirt separator which guarantees a filtration degree of no more
than 1 mm (in this case, it is no longer necessary to install the Y-filter).
SPS – Solar panel pobe for GI3 – probe required to measure the
temperature of the solar panels if the unit is integrated with a solar thermal
system.
FD – Dirt separator – blocks and retains the heaviest impurities in the
hydraulic circuit, which are captured by a synthetic filtering grid and
collected in a settling chamber. A magnetic device placed inside the body of
the dirt separator also allows ferromagnetic particles to be intercepted.
SAS – Domestic hot water probe / System remote probe – In some system
solutions (e.g. heat pump in parallel to boiler on same hydronic circuit and
shut off diverter valve) it might be necessary to enable a system temperature
probe so that the machine controller can correctly process the control. The
system remote probe controls the temperature of the heat pump only during the
compressor start-up phase. Shutdown is managed by the probe on the heat pump
delivery line.
Hi-TV415 – Multi-purpose touch screen remote control – touch screen remote
control for centralised management of a chiller/heat pump network. It
includes humidity and temperature sensors for the thermal hygrometric analysis
of the environment and for the management of the double set point for radiant
floor heating systems that use a dehumidification system.
ISK – USB/RS485 Serial converter – interface device capable of reading and
writing control registers via the RS485 standard and converting it to a USB
port that can be connected to any supervisory system.
LNC – Lan-Wifi Router – device that allows the unit to be connected to a local
network via Ethernet cable or Wifi coverage for internal monitoring.
OVPN – Router Lan-Wifi 3G con tunnel VPN – device that allows the unit to be
connected remotely with industrial routers using the secure
OPENVPN service. device that allows the unit to be connected to a local
network via Ethernet cable or Wifi coverage for internal monitoring.
2.3 SAFETY RULES FOR R290 UNITS TRANSPORT AND STORAGE
Before opening the unit’s packaging, ensure there are no gas leaks in the
ambient with an appropriate gas detector. Check that there are no ignition
sources near the unit.
No smoking near the unit.
Transport and storage must be performed in accordance with the national
regulations in force. Specifically, according to ADR provisions, the total
maximum quantity by transport unit in terms of net mass for flammable gases is
333 kg. In addition, for road transport, use vehicles that are preferably open
or equipped with a ventilation system and operated by trained personnel.
For prerequisites on the transport by sea of equipment loaded with flammable
refrigerant refer to the International Maritime Dangerous Goods Code (IMDG),
and for transport by air check the regulations prescribed by the International
Air Transport Organisation (IATA).
If it is necessary to store the unit for medium to long periods, please
observe the following precautions:
- if storage is in a closed location, leave the machine in a dedicated place that is always dry, cool, well ventilated and protected from possible ignition sources, direct sunlight or other heat sources. It is also recommended to use one flammable gas detection sensor every 36-40 m2. Please refer to national regulations;
- if storage is carried out in an open area, observe the minimum safety distances from drains, cisterns, sewers and other underground areas, in compliance with the national regulations in force;
- do not remove covers and packaging;
- ensure that all panels are correctly mounted;
- do not obstruct the openings and holes made in the machine panels;
- avoid cleaning the unit with aggressive detergents or chemicals;
- it is advisable to remove any heating water inside the unit to prevent possible corrosion or, in cold climates, damage to components caused by freezing.
CAUTION: During transport and storage of the unit, beware of possible refrigerant gas leaks that could start a fire.
INSTALLATION
CAUTION: All the operation described below must be done by QUALIFIED
PERSONNEL only (IEC 60335-2-40 Annex HH).
Before any operation on the unit, make sure that power supply is disconnected.
Also ensure, by means of appropriate locks, that the power supply cannot be
accidentally switched on again until all operations have been completed.
3.1 GENERAL
When installing or when work is to be carried out on the refrigeration
circuit, it is necessary to scrupulously comply with the regulations in this
manual, observe the indications on the unit and in any case apply all
necessary precautions. Failure of this may lead to dangerous situations.
After receiving the unit, immediately check its integrity. The unit left the
factory in perfect condition; any damage must be immediately reported to the
carrier and recorded on the Delivery Note before signing it.
The company must be informed, within 8 days, of the extent of the damage. The
customer should prepare a written statement of any severe damage.
| The units are designed to be installed outdoors. Under no circumstances
should the outdoor ambient temperature exceed 46°C when the unit is not in
operation. Above this value, the unit is no longer covered by current pressure
equipment safety regulations.
---|---
| The installation place must be without any fire risks. All necessary
measures must therefore be taken to prevent the risk of fire at the
installation site (see Chapter 3.6 for more details). The device must not be
placed in the vicinity of open flames, ignition sources or heat sources.
The wall of the buildings near the unit must have an adequate fire resistance
class, in order to contain any fire that may develop inside the rooms.
However, it is recommended to place a fire extinguisher near the unit.
| The unit must be installed in order to allow maintenance and repair. The
warranty does not cover costs for platforms or other lifting equipment needed
for any interventions.
| All the maintenance operations and tests must be done by QUALIFIED PERSONNEL
(IEC 60335-2-40 Annex HH). All equipment used during maintenance operations
must be compatible with the refrigerant gas R290.
| Before any operation on the unit, make sure that the power supply is
disconnected and cannot be switched on again acci- dentally. After
disconnecting the power supply from the unit, wait at least 5 minutes before
performing any operation on the machine to allow the condenser to discharge.
| Do not use equipment to speed up the defrost process or for cleaning except
for those recommended by the manufacturer.
| The appliance must be placed outside, in a place without continuously
operating ignition sources (e.g. open flames, an oper- ating gas appliance or
electric heater). Refer to Chapter 3.6.
| Cable ducts and electrical conduits to the machine must not contain
potential ignition sources.
| Do not perforate or burn. Do not make mechanical modifications to the unit.
---|---
| There are some moving parts inside the unit. Use extreme caution when
working near them, even if the power supply is disconnected. In particular,
pay attention to the fan blades when removing the front protective grilles. Do
not touch or insert any objects into the moving parts.
| The compressor heads and discharge pipework are at quite high temperatures.
The pipes on the suction side of the compres- sor, can reach very low
temperatures. Uninsulated pipes can cause burns or freezer burns: only handle
these components when their temperature is close to ambient.
| Be particularly careful when working near batteries. Aluminium fins are very
sharp and can cause serious injury.
| After the maintenance operations, close the panels by fixing them with
screws.
| After maintenance or replacement of components, reconnect the cables in the
same position as in the factory.
| Routine maintenance operations can be carried out with the machine charged,
while in the case of extraordinary operations, repairs or replacement of
components and heavy work in the vicinity of the machine (e.g. construction
sites), drain the ma- chine of coolant gas and move it to a safe area if
necessary (in accordance with Chapter 3.6).
| Insulating materials are not self-extinguishing: remove them when working on
the unit, if necessary.
| Do not remove, replace or make illegible the adhesive labels on the unit and
packaging. Do not cover the labels after installa- tion of the unit.
3.2 TRANSPORT AND STORAGE TEMPERATURE LIMITS
Minimum storage temperature [°C] | -10 °C |
---|---|
Maximum sorage temperature [°C] | +50 °C |
3.3 LIFTING AND HANDLING
The handling must be performed by qualified personnel, properly equipped with
appropriate tools to the weight and the encumbrance of the unit, in compliance
with safety regulations of accident preventing.
It is recommended:
- Check the weight on unit technical label or on table of technical data;
- Check moving the unit there are no disconnected paths, ramps, steps, doors that could affect the movement and damage the unit;
- Check that the unit remains horizontal when moving;
- During handling, do not carry out abrupt and sudden manoeuvres in order to not destabilise the unit;
- Before handling the unit, check that the equipment is suitable for lifting and preserving the integrity of the unit;
- Berform lifting only by one of the listed procedures;
- Before starting handling make sure, the unit is in stable equilibrium.
Note that the weight of the unit is concentrated more on the side of the
refrigeration circuit: take into consideration the weight distribution of the
machine when transporting it manually with ropes, in order not to lift
excessive loads and avoid damage or personal injury.
It is recommended to remove the packaging only after the machine has been
placed in the actual installation location. Dispose of the different packaging
materials in accordance with national regulations.
| Before commissioning, carefully inspect the unit and packaging for damage or
refrigerant leakage.
---|---
| Do not proceed with the start-up of the unit if damage was found during
transport. Immediately inform the Company of the problem.
The company is not liable for any damage to the product caused by handling and
transporting the unit in a manner not in accordance with this manual and the
regulations in force.
3.3.1 Lifting mode
Following lifting modes are allowed:
- forklift truck;
- ropes / bands.
Make sure to tension the lifting ropes gradually and check their correct positioning.
| Lifting through forklift truck.
---|---
| Lifting with ropes / bands.
3.4 UNIT DIMENSIONS, PLUMBING CONNECTIONS AND WEIGHTS
3.4.1 Net dimensions and with packaging
Model i-290| Lenght [mm]| Widht [mm]| Height [mm]|
Plumbing connections IN/OUT| Dimensions with packaging (length x
width x height)[mm]
---|---|---|---|---|---
0121 / 0123 / 0125 / 0127| 1610| 710| 1270| 1” 1/2 G| 1780x820x1430
IN/OUT: 1” 1/4 G
E: power supply input.
3.4.2 Weights
Model i-290 | Shipping weight [kg] | Operating weight [kg] |
---|---|---|
121 | 276 | 254 |
123 | 276 | 254 |
125 | 285 | 264 |
127 | 285 | 264 |
3.4.3 Positioning the centre of gravity and vibration dampers
The position of the centre of gravity of each machine is indicated in the
tables, with reference to the dimensions shown in the image.
Models i-290| L [mm]| P [mm]| H [mm]| Xg [mm]| Yg
[mm]| Zg [mm]
---|---|---|---|---|---|---
0121| 1610| 710| 1270| 810| 395| 655
0123| 1610| 710| 1270| 810| 395| 655
0125| 1610| 710| 1270| 800| 410| 655
0127| 1610| 710| 1270| 800| 410| 655
The positions provided for the installation of vibration dampers for each type of machine are shown in the pictures below
Models i-290| A [mm]| B [mm]| C [mm]| D [mm]| E
[mm]
---|---|---|---|---|---
0121 / 0123 / 0125 / 0127| 331| 308,5| 30| 962,5| 640
3.5 POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All models of i-290 are designed and constructed for outdoor installations.
The company is not liable for any damage to property, animals and/ or persons
resulting from failure to comply with the instructions on installing the unit
described in this manual.
It is advisable to create an adequately sized support base for the unit. The
units transmit a small amount of vibrations to the ground: however, it is
advisable to place anti-vibration mounts between the base frame and the
supporting surface. It is preferable to install the unit away from places
sensitive to noise and vibration (e.g. windows and glass panes).
Always make an environmental impact assessment based on the power and sound
pressure data in chapter “3.7.7 Deaerator” and the sound emission limits
according to the installation area of the unit, with reference to the DPCM of
14/11/1997. An assessment must also be made if the unit is installed near
workers, according to D. LGS. 81/2008 Art. 189 and following or according to
the installation area of the unit.
To reduce vibrations and noise, the use of rubber seals is recommended for
wall installation.
| Suspended installation is prohibited.
---|---
| The support plane must have enough capacity to support the unit weight,
which can be checked both on the technical label of the unit and on this
technical manual under “Technical data” chapter.
The support plane must not be inclined to ensure the unit works properly and
avoid a possible overturning. The support plane must not be smooth, to avoid
water/ice deposit as potential sources of danger.
| Unit installation place must be free from foliage, dust, etc., which could
clog or cover the coil. Installation in areas subject to water stagnation or
fall, for example from gutters, should be avoided.
Also, avoid areas subject to snow accumulation (such as corners of buildings
with sloping roofs). In case of installation in areas subject to snowfall, it
is advisable to place the unit on a base raised from the ground by 20-30 cm,
to prevent the for- mation of snow accumulations around the machine, which can
obstruct the battery and the perforations on the side panels and base of the
machine.
---|---
| It is recommended that sufficient air exchange be ensured to dilute R290 gas
in the event of its accidental escape, thus preventing the formation of
explosive atmospheres. For this reason, a minimum distance (depending on the
unit) must be maintained from any openings or manholes, in which the gas could
accumulate. Respect national regulations for the installa- tion of the
machine.
| The units are suitable for installation in urban, industrial, coastal and
rural areas.
If the unit is installed in an environment with aggressive atmospheres, the
air sucked in by the fan may contain substances that can cause damage to the
panels, grilles and internal components of the unit. In this case, the
operating life of the unit will be limited.
| It is forbidden to install the unit under roofs of any kind, such as roofs,
canopies, carports and the like, at a height of less than 1.5 m from the unit
cover.
| It is prohibited to install the unit in a location below ground level (such
as cellars, underground car parks, basement or un- derground work rooms,
etc.).
It is very important to avoid recirculation between intake and delivery air,
so as not to downgrade performance of the unit or even to interrupt its normal
operation.
This is why the minimum clearances shown below must be strictly guaranteed.
MODEL | A1 | A2 | B1 | B2 |
---|---|---|---|---|
i-290 0121 | mm | 1500 | 400 | 400 |
i-290 0123 | mm | 1500 | 400 | 400 |
i-290 0125 | mm | 1500 | 400 | 400 |
i-290 0127 | mm | 1500 | 400 | 400 |
Obstruction or covering of ventilation openings on the top cover must be |
avoided.
---|---
| For strong wind installation place refer to the classification of the area
according to the Beaufort table. If the value is > 7 (strong wind, average
wind speed = 13, 9-17, 1 m/s) it is strictly necessary to keep the fan always
powered, thus preventing involuntary rotation of the same.
| If the unit is installed at a distance of less than 1 km from coastal and
maritime areas, the presence of salt and sand in the air greatly increases the
likelihood of corrosion. Install the unit so that it is protected from direct
sea wind if necessary, provide windbreaks on site (observing the minimum
distances indicated).
In the event of side-by-side units, the minimum Lmin dsitance
between them is 1 m.
|
---|---
Covering with canopies or placing near plants or walls should be avoided to
prevent air recirculation.|
In the event of winds stronger than 13,9-17,1 m/s (strong wind ac- cording to
the Beaufort scale) the use of the wind barriers is recom- mended.|
3.6 DANGER AND SAFETY ZONES
The i-290 series units contain R290 refrigerant gas. The density of this gas
is greater than that of air, so in the event of leakage it tends to disperse
and stratify, accumulating in niches, depressions in the ground or underground
regions.
It is mandatory to comply with the danger and safety zones given in this
manual, when installing the units. These zones have been designed in
accordance with EN 60079-10-1, estimating an appropriate refrigerant loss, in
order to guarantee the safety of the units in the installation area. A danger
zone is defined as a area around the machine in which, in the event of a
leakage of refrigerant gas, a flammable atmosphere is formed for a short time,
within which it is necessary to implement all the precautions described in the
manual. In the absence of specific standards or regulations, when using the
unit in an industrial or working environment, it is advisable to carry out the
classification of places with explosion hazards considering the ATEX Directive
1999/92 (Directive 89/391). There must NOT be any sources of ignition in the
danger zones, including:
- Flammable gases and sprays, self-igniting powders;
- Electrical equipment that is not suitable for use in potentially explosive areas (zone 2 according to Directive 89/391);
- Naked flames, heated surfaces (maximum surface temperature of 360°C) and processing by heat; smoking is prohibited, including for electronic cigarettes;
- Sparks, electrostatic charges, direct and indirect lightning effects, eddy currents and cathodic protection;
- Ignition sources due to remote processes (ionising and non-ionising radiation);
- Permanent electrical sources (switches, lamps, etc.) or other possible triggers;
In addition, danger zone must NOT:
- Include potentially dangerous areas or elements such as wells, manholes, openings to the sewage system and other openings to underground places and premises (e.g. garages), river drains, power lines, flammable deposits, electrical installations, etc.;
- Include doors, windows or glass panes, to prevent the possible return of the gas inside the building;
- Extending towards neighbouring residential properties, parking areas, public access sites, roads or railways.
A safety zone extending beyond the danger zone must also be identified. Within the safety zone, in the event of a refrigerant leak, the concentration of the gas in the air is typically below the critical levels for the formation of flammable or hazardous atmospheres. Compliance with the following provisions remains mandatory:
- Prevent accumulation and stagnation in underground spaces, drains, manholes, cellars, etc.;
- Do not place building vents inside or near the safety zone;
- Do not use naked flames and other direct heat sources.
In any case, comply with national and local regulations for the installation
of machinery (where applicable) in order to prevent the formation of fire
hazards and to prevent gases from seeping underground into openings to the
ground or floors below.
No structural modifications may be made in the danger and safety zones that
would alter their extent or change the behaviour of the air-coolant mixture.
It is also strictly forbidden to tamper with, alter, remove or compromise,
even partially, the functionality of the devices, guards and prescriptions
provided for the safety of property and persons.
In this manual, different types of outdoor installation are considered, as
indicated in the following paragraphs.
3.6.1 Free-field ground installation
For unit installed in open field terrain, the danger (continuos red line) and
safety zones (dashed black line) are shown in the figures below:
MODEL i-290 | X | Y | L1 | L2 | L3 | L4 | d |
---|---|---|---|---|---|---|---|
0121 / 0123 | mm | 1500 | 2000 | 4600 | 5600 | 3640 | 4640 |
0125 / 0127 | mm | 1500 | 2000 | 4600 | 5600 | 3640 | 4640 |
3.6.2 Ground installation in front of a wall
In the case of units installed on the ground in front of a wall, the danger
(continuous red line) and safety zones (dashed black line) are shown in the
figures below:
MODEL i-290 | X | Y | L1 | L2 | D | d |
---|---|---|---|---|---|---|
0121 / 0123 | mm | 1500 | 2000 | 4600 | 5600 | 400 |
0125 / 0127 | mm | 1500 | 2000 | 4600 | 5600 | 400 |
3.6.3 Ground installation in a corner
For units installed on ground in a corner, the danger (continuous red line)
and safety zones (dashed black line) are shown in the figures below:
MODEL i-290| X| Y| X1| Y1| B| C| D|
d
---|---|---|---|---|---|---|---|---
0121| mm| 1500| 2000| 2750| 3250| 700| 400| 400| 250
0123| mm| 1500| 2000| 2750| 3250| 700| 400| 400| 250
0125| mm| 1500| 2000| 2750| 3250| 700| 400| 400| 250
0127| mm| 1500| 2000| 2750| 3250| 700| 400| 400| 250
3.6.4 Flat floor installation
The installation configuration on a flat roof is similar to that on a free-
field ground, although some additional aspects must be considered:
- place the machine at a sufficient distance from side walls and protrusions, which must therefore be beyond the safety zone;
- ensure that the roof structure of the building is solid;
- choose a location where no accumulations of snow, dust or foliage can form;
- pay attention to noise emissions and maintain an adequate distance from surrounding buildings;
- if high air velocities are detected, install the protections listed in the previous chapter.
3.6.5 Multiple installation
When installing several machines side by side, follow the above
configurations, maintaining a respect distance of L between each machine. As
an example, see the following respect zones (danger and safety) for the case
of a generic number “n” of units installed on open field terrain:
MODEL i-290 | X | Y | L |
---|---|---|---|
0121 | mm | 1500 | 2000 |
0123 | mm | 1500 | 2000 |
0125 | mm | 1500 | 2000 |
0127 | mm | 1500 | 2000 |
For other types of installation not covered in this manual, contact technical
support. If in doubt about the installation of the units, request a technical
assessment by the fire brigade or a fire prevention expert.
3.7 PLUMBING CONNECTIONS
The plumbing connections must be made in accordance with national and/or local
regulations; pipes can be made of steel, galvanised steel, multilayer
steel or PVC. Pipes must be accurately sized according to the maximum water
flow rate of the unit and the pressure drops of the water circuit. All pipes
must be insulated with closed-cell material of adequate thickness. The chiller
must be connected to the pipes using new flexible joints, not reused ones. The
water circuit should include the following components.
- Well thermometers to monitor the circuit’s temperature.
- Manual gate valves to isolate the chiller from the water circuit.
- Metal Y filter or a dirt separator (installed on the return pipe) with metal mesh no larger than 1 mm.
- Loading group and exhaust valve where necessary.
| When sizing the pipes, make sure not to exceed the maximum pressure drop on
system side reported in the technical data table in Chapter 3.7.7 (see useful
head).
---|---
Connect the pipes to their fittings always using the key-to-key method.
Create a suitable drain for the safety valve.
CAUTION: The installer has to verify if the expansion tank fits with the
real capacity of the installation.
CAUTION: The return pipe from the system must be at the “WATER INPUT”
label otherwise the evaporator may freeze.
CAUTION: It is mandatory to install a metal filter (with mesh no larger
than 1 mm) on the return pipe from the system labelled “WATER INLET”.
Alternatively, it is possible to install a dirt separator that guarantees a
filtration degree of no more than 1 mm; in this case is not necessary to
install the Y-filter.
If the flowmeter is tampered with or altered, or if the metal filter or the
dirt separator are not present on the system, the warranty shall expire. The
filter (or the dirt separator) must be kept clean, therefore, after installing
the unit, you must make sure that they are still clean and check them
regularly.
CAUTION: All the units leave the company supplied with flowmeter
(installed in factory). If the flowmeter is altered or removed or if the water
filter and dirt separator are missing from the unit, the guarantee shall
expire. Refer to the wiring diagram attached to the unit to connect the
flowmeter. Never jumper connections of the flowmeter in the terminal block.
The heating system and the safety valves must comply with the requirements of
standard EN 12828.
3.7.1 Characteristics of the circuit water
To guaratee correct operation of the unit, the water must be appropriately
filtered (see the instructions at the start of this paragraph) and there must
be only a minimum amount of dissolved substances. The maximum allowed values
are shown below:
MAXIMUM CHEMICAL-PHYSICAL PROPERTIES ALLOWED FOR THE CIRCUIT WATER
PH| 7,5 – 9
Electrical conductivity| 100 – 500 μS/cm
Total hardness| 4,5 – 8,5 dH
Temperature| ˂ 78 °C
Oxygen content| ˂ 0,1 ppm
Max glycol quantity (*)| 10 %
Phosphates (PO4)| ˂ 2 ppm
Manganese (Mn)| < 0,05 ppm
Iron (Fe)| < 0,3 ppm
Alkalinity (HCO3)| 70 – 300 ppm
Chloride ions (Cl–)| < 50 ppm
Sulphate ions (SO4)| < 50 ppm
Sulphide ions (S)| No one
Ammonium ions (NH4)| No one
Silice (SiO2)| < 30 ppm
(*) It is preferable to use pure water. Do not add more antifreeze than the
maximum quantity specified in this manual.
3.7.2 Typical plumbing diagram
Refer to the “Handbook” for further information regarding possible unit
installation configurations.
Num. | Description |
---|---|
1 | Heat pump |
2 | Remote control |
3 | Mixing valve |
4 | Expansion tank |
5 | Y-filter or Dirt separator with integrated filter |
6 | Expansion tank |
7 | Technical storage |
8 | Booster pump for zone 1 |
9 | Booster pump for zone 2 |
10 | Mixing probe |
11 / 11 bis | Local thermostat |
3.7.3 Minimum water content and hydraulic circuit volumes
The table shows the minimum system water content recommended for the unit. The
volume of the hydraulic circuit is also indicated. To ensure proper operation
of the heat pump, this minimum content must be met. Taking into consideration
the volume of water in the primary circuit piping, size the thermal flywheel
to achieve the indicated volume.
Model i-290 | 0121 | 0123 | 0125 | 0127 |
---|---|---|---|---|
Minimum system water content [L]. | 175 | 175 | 200 | 200 |
Hydraulic circuit volume [L] | 3,6 | 3,6 | 4,0 | 4,0 |
3.7.4 Plumbing diagram inside unit
Since the pipes are well insulated, condensation production is minimal and
does not lead to water accumulating inside the refrigeration compartment. All
heat pumps have a condensate drain hole in the basement, which is abundant
especially in the post-defrost
phase.
|
---|---
FOR HEAT PUMP UNITS, IN PARTICULARLY COLD CLIMATES, WE RECOMMEND THE
INSTALLATION OF THE KA ACCESSORY, WHICH PREVENTS THE FORMATION OF ICE ON THE
BASEMENT.
ATTENTION: For heat pump units, if the prepared ducting system is not
used, a limited amount of water (possible ice in winter) from the condensate
drainage system may be deposited in the vicinity of the unit, posing a
slip/fall hazard.
Each unit is provided with a hole on the base frame of the hydronic kit (at
the side of the coil) for draining any condensate that may percolate from the
plumbing pipes and the water that forms as a result of the defrosting process.
In the event of a leak, the refrigerant gas may escape from the unit through
the hole in the base panel, so it is advisable to always direct the condensate
drain to an open place near the unit (within the danger zone defined in
Chapter 3.6). If the unit is installed on the ground, it is also possible to
direct the condensate into a bed of rubble or gravel for drainage. For typical
free-field ground installation, refer to the following pictures:
MODEL | Z |
---|---|
i-290 0121 | mm |
i-290 0123 | mm |
i-290 0125 | mm |
i-290 0127 | mm |
Caution: Do not obstruct the hole in the base panel for condensate
drainage.
Especially in very cold climate regions, it is recommended to install
elevation supports in order to allow ice formation under the unit without
damaging it by freezing.
3.7.5 System load
| CAUTION: Supervise all filling/reintegration operations.
---|---
CAUTION: Before filling/reintegration the system, disconnect power to the
units.
CAUTION: The filling / reintegrating of the system must always take place
under controlled pressure (max. 1). Ensure that a pressure reducer and safety
valve is installed on the filling/reintegration line.
CAUTION: The water in the filling/reintegration line must be properly
pre-filtered from impurities and suspended particles. Ensure that a removable
cartridge filter and a dirt separator are installed.
CAUTION: Regularly check and vent the air built up in the system.
CAUTION: Install an automatic air venting valve at the highest point of
the system.
3.7.6 System discharge
If the unit needs to be drained completely, first close the manual inlet and
outlet gate valves (not included in supply) and then detach the pipes on the
outside of the water inlet and outlet to drain liquid from the unit (to make
this operation easier, it is recommended to install two drain valves between
the unit and manual gate valves on the outside of the water inlet and outlet).
If it is necessary to top up the system or adjust the glycol content, the
service tap can be used. Unscrew the cap of the service tap (A) and connect a
pipe of 14 or 12 mm (inertial diameter measurements – check the tap model
installed on your unit) connected to the water mains to the hose connector,
then fill the system by unscrewing the ring nut (B). Once the operation is
completed, tighten the ring nut (B) again and screw the cap (A). In any case,
it is advisable to use an external tap to fill the system.
3.7.7 Deaerator
The unit is equipped with a high-efficiency deaerator that continuously
captures and eliminates air and any refrigerant gas that may accumulate within
the hydraulic circuit, avoiding undesirable effects such as premature
corrosion and wear, reduced efficiency and exchange yield, as well as possible
contamination of the water by R290 gas. The exhaust capacity is very high,
with automatic gas expulsion down to micro-bubble level. The deaerator is made
of brass, a strong and durable material. The mixture of water and glycol can
greatly reduce the deaerator’s ability to remove dissolved gases: it is
recommended to limit the glycol concentration to a maximum of 10%. Use
products with a low tendency to foam, which could completely nullify the
degassing effect and damage the system.
Do not exceed the maximum amount of glycol indicated in the manual, as this may reduce the deaerator’s ability to remove gas, causing damage to the component.
| Access to the moving parts that control the vent is obtained, after tapping
the system, by removing the top cover.|
---|---|---
| After tapping the system, unscrew the part of the body containing the vent
valve, to which the separator element is attached, for cleaning. This part is
not removable.|
GENERAL TECHNICAL DATA
Performance referring to the following conditions, according to standard UNI EN 14511:2022:
- Cooling: outdoor air temperature 35 °C; in/out water temperature 12/7°C.
- Cooling: outdoor air temperature 35 °C; in/out water temperature 23/18°C.
- Heating: outdoor air temperature 7 °C db 6 °C db; in/out water temp. 30/35°C.
- Heating: outdoor air temperature 7 °C db 6 °C db; in/out water temp. 47/55 °C.
- Cooling: low temperature,variable output, fixed flow rate.
- Heating: average climatic conditions; Tbiv = -7 °C; low temperature,variable output, fixed flow rate.
- Indicative data subject to changes. For the correct value, always refer to the technical label on the unit.
- Calculated for a decrease in system water temperature of 10°C with a defrost cycle lasting 6 minutes.
- Sound mode: mode (1); value determined on the basis of measurements made in accordance with UNI EN ISO 9614-1.
- Sound pressure: value calculated from the sound power level in condition (9) using the standard UNI EN ISO 3744:2010.
- Sound mode: heating mode according to EN 12102:2022 Annex A; value determined on the basis of measurements made in accordance with UNI EN ISO 9614-1, in compliance with Eurovent certification requirements.
- Heating: outdoor air temperature 7 °C db. 6 °C db; in/out water temp. 55/65 °C.
(*) activating the maximum Hz function.
N.B. performance data are indicative and are subject to change. Furthermore the performance declared in points (1), (2), (3) and (4) is intended to refer to instantaneous power according to EN 14511:2022. The value declared in point (5) and (6) is determined according to UNI EN 14825:2022.
TECHNICAL CHARACTERISTICS | Unit | i-290 |
---|---|---|
0121 | 0123 | 0125 |
Cooling | Cooling capacity (1) | kW |
Power input (1) | kW | 5,26 |
EER (1) | W/W | 3,31 |
Cooling capacity (2) | kW | 19,6 |
Power input (2) | kW | 4,02 |
EER (2) | W/W | 4,88 |
SEER (5) | W/W | 5,27 |
Water flow (1) | L/s | 0,83 |
Heating | Heating capacity (3) | kW |
Power input (3) | kW | 4,3 |
COP (3) | W/W | 4,87 |
Heating capacity (4) | kW | 19,6 |
Power input (4) | kW | 6,1 |
COP (4) | W/W | 3,20 |
Heating capacity (12) | kW | 19,7 |
Power input (12) | kW | 7,4 |
COP (12) | W/W | 2,67 |
SCOP (6) | W/W | 4,75 |
Water flow (4) | L/s | 0,59 |
Energy efficiency – water 35°C / 55°C low temperature / medium temperature | ||
Class | A+++ / A++ | A+++ / A++ |
Compressor | Type | – |
Quantity | – | 1 |
Refrigerant oil (type) | – | PZ46M |
Refrigerant oil (quantity) | mL | 900 |
Refrigerant circuits | – | 1 |
Refrigerant | Type | – |
Refrigerant quantity (7) | kg | 1,7 |
Refrigerant quantity in tonnes of CO2 equivalent (7) | ton | 0,0 |
Design pressure (high/low) heat pump mode | bar | 30,3 / 1,7 |
Design pressure (high/low) chiller mode | bar | 30,3 / 0,7 |
Fans | Type | – |
Quantity | – | 1 |
Nominal power (1) | kW | 0,40 |
Maximum power input | kW | 0,83 |
Maximum current input | A | 1,2 |
Nominal air flow | m³/h | 12520 |
Internal heat exchanger | Internal heat exchanger type | – |
BPHE
N° internal heat exchanger| –| 1| 1| 1| 1
Water content| L| 1,71| 1,71| 2,07| 2,07
Hydronic circuit| Useful head (1)| kPa| 128| 121| 128| 117
Useful head (4)| kPa| 150| 146| 149| 142
Water content of the hydronic circuit| L| 4| 4| 4| 4
Maximum pressure hydronic kit (safety valve setting)| bar| 6| 6| 6| 6
Water connections| inch| 1″ 1/4 M| 1″ 1/4 M| 1″ 1/4 M| 1″ 1/4 M
Minimum water volume (8)| L| 175| 175| 220| 225
Nominal pump power (1)| kW| 0,35| 0,35| 0,35| 0,35
Maximum pump power input| kW| 0,35| 0,35| 0,35| 0,35
Maximum pump current input| A| 2,50| 2,50| 2,50| 2,50
Noise| Sound power level Lw (9)| dB(A)| 72| 73| 75| 76
Sound pressure Lp1 (10)| dB(A)| 41| 42| 44| 45
Sound power level Lw (11)| dB(A)| 64| 64| 65| 65
Electrical data| Power supply| –| 400V/3P+N+T/50Hz
Maximum power input| kW| 11| 11| 13| 13
Maximum current input| A| 19| 19| 21| 21
Max. power input with antifreeze kit| kW| 11| 11| 13| 13
Max. current input with antifreeze kit| A| 19| 19| 22| 22
4.1 ELECTRICAL AND AUXILIARY DATA
Power supply | V/~/Hz | 400/3PH+PE/50 |
---|---|---|
On board controller circuit | V/~/Hz | 12/1/50 |
Remote controller circuit | V/~/Hz | 12/1/50 |
Fans power supply | V/~/Hz | 400/3PH+PE/50 |
NOTE: The electrical data are subject to change due to updates. It is therefore always necessary to refer to the technical specifications label applied on the right side panel of the unit.
CORRECTION FACTORS
5.1 CORRECTION FACTORS FOR USE OF GLYCOL WATER MIXTURE
The correction factors of the water flow rate and pressure drops must be
applied to the values obtained without use of glycol. The correction factor
for the water flow rate is calculated to maintain the same temperature
difference which would be achieved without the use of glycol.
Glycol percent- age| Freezing point [°C]| Performance
correction factor| Absorbed power correction factor| Water
flow rate correction factor| Pressure drops cor rection factor
---|---|---|---|---|---
10%| -3,2| 0,992| 1,01| 1,03| 1,11
Do not add more glycol than the maximum quantity indicated in this manual, as
this may severely restrict the deaerator’s ability to remove gases, possibly
resulting in damage to the component.
5.2 SCALING CORRECTION FACTORS
The correction factors due to fouling of the internal gas/water heat exchanger
are reported below.
m ² °C/kW| Output power correction factor| Input power correction
factor
---|---|---
0,44 x 10-¹| 1,00| 1,00
0,88 x 10-¹| 0,99| 1,00
1,76 x 10-¹| 0,98| 1,00
5.3 INSTRUMENTATION CALIBRATIONS AND PROTECTIONS
Description | Value |
---|---|
High pressure switch | 31,5 bar |
High pressure alarm | 30,3 bar |
Low pressure alarm | 0,7 / 1,7 |
Maximum number of restarts/hour after high/low | 3 |
Antifreeze protection | Allarm triggered: 3 °C |
Allarm return: 5 °C
Hydronic circuit safety valve| 6 bar
5.4 CORRECTION FACTORS ACCORDING TO ALTITUDE
The performance correction factors according to altitude are calculated for
cooling at conditions (1) and for heating at conditions (3) of the previous
technical data tables and are provided for altitudes of 500, 1000, 1500 and
2000 m.
i-290
Altitude [m]| 500| 1000| 1500| 2000
Thermal output correction factor| 0,9992| 0,9979| 0,9970| 0,9958
Power input correction factor in heating| 0,9985| 0,9962| 0,9939| 0,9916
Cooling output correction factor| 0,9961| 0,9873| 0,9796| 0,9746
Power input correction factor in cooling| 1,0021| 1,0103| 1,0149| 1,0205
HYDRONIC UNIT DATA
6.1 USEFUL HEADS
The following are the characteristic curves of the head-flow rate net of the
pressure drops of the hydronic kit. The optimal operating point at the
conditions specified at the apex (1) and (3) in the technical data table is
highlighted on each curve.
The system must be designed to guarantee the nominal flow rate relative to the
working points shown below.
p [kPa] | Useful head |
---|---|
Q [l/s] | Water flow rate |
6.2 CIRCULATOR CURVES
Below is the range of useful heads which guarantee the unit during modulating
of the circulator.
6.3 ACCESSORY PRESSURE DROPS Y-FILTER, DIRT DEFLECTOR AND 3-WAY VALVE
Flow rate [l/s] | Y-filter pressure drops for 0121 and 0123 [kPa] |
---|---|
0,4 | 1,23 |
0,6 | 2,76 |
0,8 | 4,91 |
1,0 | 7,67 |
1,2 | 11,0 |
1,4 | 15,0 |
1,6 | 19,6 |
1,8 | 24,8 |
2,0 | 30,7 |
Flow rate [l/s] | Y-filter pressure drops for Y 0125 for 0127 [kPa] |
---|---|
0,4 | 0,92 |
0,6 | 2,07 |
0,8 | 3,69 |
1,0 | 5,76 |
1,2 | 8,29 |
1,4 | 11,3 |
1,6 | 14,7 |
1,8 | 18,7 |
2,0 | 23,0 |
Flow rate [l/s] | Pressures losses dirt separator filter [kPa] |
---|---|
0,4 | 0,09 |
0,6 | 0,19 |
0,8 | 0,35 |
1,0 | 0,54 |
1,2 | 0,78 |
1,4 | 1,06 |
1,6 | 1,38 |
1,8 | 1,75 |
2,0 | 2,16 |
Flow rate [l/s] | Diverter valve pressure loss [kPa] |
---|---|
0,4 | 0,48 |
0,6 | 1,08 |
0,8 | 1,92 |
1,0 | 3,00 |
1,2 | 4,31 |
1,4 | 5,87 |
1,6 | 7,67 |
1,8 | 9,71 |
2,0 | 12,0 |
SOUND EMISSIONS
7.1 FULL LOAD UNITS
The sound levels refer to the unit operating at full load and under normal
test conditions in cooling mode (outdoor air b.s. (b.u.) temperature =35 °C
(24 °C), inlet-outlet water temperature = 12-7 °C). The tolerance on the total
sound power level value is 2 dB(A). The value is determined in accordance with
EN 12102-1:2022, used in conjunction with EN ISO 9614-1:2009, which describes
the test methods and techniques for measuring sound power using the
intensimetric method. Sound pressure values are calculated from the sound
power level usingUNI EN ISO 3744:2010, considering units operating in the
open field.
Model i-290| Octave band sound power level [dB(A)]| Sound
power level Lw(A) [dB(A)]| Sound pressure level at 1m [dB(A)]|
Sound pres- sure level at 10m [dB(A)]
---|---|---|---|---
63 Hz| 125 Hz| 250 Hz| 500 Hz| 1000 Hz| 2000 Hz|
4000 Hz
0121| 59,4| 56,9| 62,5| 65,7| 66,6| 65,5| 59,5| 72| 56| 41
0123| 59,0| 59,2| 63,2| 66,5| 68,1| 66,2| 60,2| 73| 57| 42
0125| 59,2| 61,8| 64,6| 69,5| 70,1| 67,7| 61,7| 75| 59| 44
0127| 58,7| 62,1| 64,5| 70,5| 70,8| 69,8| 62,7| 76| 60| 45
7.2 PARTIAL LOAD UNIT
The sound levels are referred to units at full load operating under conditions
that guarantee a thermal capacity equal to that declared at a temperature of
7°C for average climate, in accordance with EN 14825:2022. The tolerance on
the value of the total sound power level is 2 dB (A). The value is calculated
according with EN 12102-1:2022 regulation used in conjunction with UNI EN ISO
9614-1:2009 which describes the test methods and sound power measurement
techniques with the intensimetric method. The sound pressure values are
calculated from the sound power level using UNI EN ISO 3744: 2010, considering
units operating in the open field.
Model i-290| Octave band sound power level [dB(A)]| Sound
power level Lw (A) [dB(A)]| Suond pressure level at 1m [dB(A)]|
Sound pres- sure level at 10m [dB(A)]
---|---|---|---|---
63 Hz| 125 Hz| 250 Hz| 500 Hz| 1000 Hz| 2000 Hz|
4000 Hz
0121| 42,4| 50,5| 52,3| 61,0| 56,9| 54,6| 47,6| 64| 48| 33
0123| 42,8| 51,0| 52,8| 61,5| 57,4| 55,1| 48,0| 64| 48| 33
0125| 50,6| 50,8| 56,3| 62,5| 54,7| 53,0| 44,3| 65| 49| 34
0127| 51,2| 51,5| 56,9| 63,2| 55,3| 53,6| 44,8| 65| 49| 34
OPERATING LIMITS
8.1 EVAPORATOR WATER FLOW
The nominal water flow rate refers to a temperature difference between the
inlet and outlet of the evaporator of 5 °C. The maximum permissible flow rate
is the one with a temperature difference of 3 °C and the minimum is the one
with a temperature difference
of 10 °C at nominal conditions as stated in the data sheet.
Insufficient water flow rates can cause excessively low evaporation
temperatures causing the safety devices to trigger and stopping the unit and,
in some extreme cases, forming ice in the evaporator and resulting in serious
failures to the cooling circuit.
For greater details, we have attached a table below with the minimum flow
rates for the plate heat exchanger to guarantee proper operation according to
the model (please note: the water flowmeter is applied to protect against
failed triggering of the antifreeze probe due to the lack of flow but does not
guarantee the minimum water flow rate required for correct operation of the
unit).
Model i-290 | Chiller mode |
---|---|
0121 | 0123 |
Minimum water flow to be assured in chiller mode (condition (1) technical
sheet) [l/s]| 0,42| 0,45| 0,47| 0,53
Maximum water flow to be assured in chiller mode (condition (1) technical
sheet) [l/s]| 1,39| 1,51| 1,58| 1,77
Flowmeter intervention rate – decreasing / increasing flow* [l/s]| 0,24| 0,25|
0,29| 0,31
Pay attention to the pressure levels of the hydraulic system: too low values
can cause malfunctions of the unit.
For very low hydraulic system pressure values, the flowmeter may show an
unstable reading, so it is recommended to have an automatic loading system or
a pressure monitoring system.
It is periodically check the state of the deaerator, especially if very high
temperature differences are read between the inlet and outlet on the water
side, as the presence of air bubbles in the circuit reduces the available
water flow rate, altering the flowmeter reading.
As an approximation, and without any other measurement systems, the correct
flow rate to guarantee the best performance of the unit can be verified with
the circulator at maximum speed, by looking at the pressure gauges to check
the pressure difference between the return and discharge water on the external
plumbing fittings of the unit and making sure that this reading is equal to or
lower than the useful head indicated on the curves shown in Paragraph 6.2 for
the respective models.
8.2 COLD WATER PRODUCTION (SUMMER MODE)
A minimum temperature of 5°C is allowed at the evaporator outlet: for lower
temperatures, contact the Technical Department. In this case, contact our
technical department for a feasibility study and evaluation of the
modifications to be made according to the requirements. A maximum temperature
of 20°C can be maintained at the evaporator outlet in steady-state operation.
Slightly higher temperatures can however be tolerated durient transients and
in the phases of operation.
8.3 HOT WATER PRODUCTION (WINTER MODE)
When the system has reached steady state, the water inlet temperature must not
drop below 10 °C: lower values, not due to transient phases or reaching
steady-state, can cause system failures and could possibly break the
compressor. The maximum outlet water temperature must not exceed 78 °C.
Temperatures higher than those indicated, especially in conjunction with low
water flow rates, could lead to malfunctioning of the unit, or in the most
critical cases safety devices could be triggered.
8.4 AMBIENT AIR TEMPERATURE AND SUMMARY TABLE
The units are designed and built to operate in summer mode, with condensation
control, at outdoor air temperatures between 10°C and 46°C. In heat pump mode,
the allowed temperature range of the outdoor air goes from-20°C to +45°C
depending on the outlet water temperature as shown in the table below.
Water chiller mode
Air source temperature| Minimum +10 °C| Maximum +46 °C
Outlet water temperature| Minimum +5 °C| Maximum +20 °C
Heat pump mode
Air source temperature| Minimum -20 °C| Maximum +20 °C
Outlet water temperature| Minimum +20 °C | Maximum +78 °C
Heat pump mode for domestic hot watert
Air source temperature with water at maximum 60°C| Minimum -20 °C| Maximum +45
°C
Air source temperature with water at maximum 65°C| Minimum -14 °C| Maximum +45
°C
Air source temperature with water at maximum 78°C| Minimum 0 °C| Maximum +38
°C
The minimum and maximum permissible temperatures depend on the outside air
temperature. Set the desired value considering the envelope.
Below are the graphed operating limits for heating, cooling and domestic hot
water production. Please note that operating the unit outside the stated
operating limits causes blocking alarms that lead to product shutdown, with
possible damage to components and/or safety organs.
8.5 ENVELOPE IN HEATING AND COOLING**
Tw = water temperature
Ta = air temperature
A = maximum Hz functionality has no effect
8.6 ENVELOPE IN DHW
Tw = water temperature
Ta = air temperature
A = maximum Hz functionality has no effect
PERFORMANCE TABLES
The tables show the capacity, power input and efficiency values for different
outside air temperatures. The data shown are calculated according to EN
14511:2022. They are indicative and may be subject to change. (*) Data
obtained for a water temperature variation of 5°C unless otherwise specified.
9.1 UNIT HEATING
9.2 COOLING
9.3 SANITARY
The tables show the heating capacity, input power and COP values at various
outdoor air temperatures during summer for technical water at 45 / 50 / 55 /
60 / 65 / 70 / 75 °C for domestic hot water production. The technical data are
indicative and are subject to change.
(*) Data obtained for a water temperature variation of 5°C.
10. SEASONAL PERFORMANCE AT DIFFERENT TEMPERATURE LEVELS
The values of the seasonal performance coefficients SCOP, heating energy
efficiency ηs,h and design heat output Pdesign for the i-290 series units are
shown. The data are calculated for three temperature levels according to UNI
EN 14825: low (LT), medium (MT) and high (HT).
- LT: Heating in medium climate conditions, Tbiv= -7 °C, low temperature (35 °C), variable output, fixed flow rate.
- MT: Heating in medium climate conditions, Tbiv= -7 °C, medium temperature (55 °C), variable output, fixed flow rate.
- HT: Heating in medium climate conditions, Tbiv= -7 °C, high temperature (65 °C), variable output, fixed flow rate.
Model i-290| Pdesign (LT)| SCOP (LT)| ηs,h (LT)|
Pdesign (MT)| SCOP (MT)| ηs,h (MT)| Pdesign (HT)| SCOP
(HT)| ηs,h (HT)
---|---|---|---|---|---|---|---|---|---
kW| W/W| %| kW| W/W| %| kW| W/W|
%
0121| 20| 4,75| 187| 19| 3,70| 145| 20| 3,28| 128
0123| 21| 4,72| 186| 21| 3,74| 147| 22| 3,25| 127
0125| 22| 4,49| 177| 22| 3,66| 143| 25| 3,20| 125
0127| 24| 4,46| 175| 23| 3,56| 140| 25| 3,21| 125
11. DATA FOR THE ENERGY CERTIFICATION OF BUILDINGS ACCORDING TO UNI/TS
113004 FOR HEAT PUMPS
The supplementary data of heat pumps for the calculation of the energy
performance of buildings according to UNI/TS 11300 part 4 are given below.
The characteristics quantities that will be provided for each model are
explained below, according to statement 30 of the standard.
| E| A Tbival| B| C| D
---|---|---|---|---|---
Reference temperature| -10 °C| -7 °C| 2 °C| 7 °C| 12 °C
PLR (T des = -10°C)| 100%| 88%| 54%| 35%| 15%
Power DC at full load| | DCA = DC bival| DCb| DCc| DCD
COP at partial load| | COPa| COPb| COPc| COPD
COP at full load| | COP’a| COP’b| COP’c| COP’D
CR| >1| 1| (0,54 x Pdes) / DCb| (0,35 x Pdes) / DCc| (0,15 x Pdes) / DCD
Correction factor Fp| 1| 1| COPb/COP’b| COPc/COP’c| COPD/COP’D
PLR| part load ratio – climatic load factor
CR| heat pump load factor
DC| full load power at indicated temperatures
DCbival| full load power at -7/35°C
Pdesign| full load with temperate climate
COP| COP with CR load at the same temperature conditions as COP’
COP’| COP at full load under the same temperature conditions as COP
Model i-290 0121
Operating limits
COLD source: | OUTDOOR AIR |
---|---|
Operating temperature (cut- off) | min |
max | 20 °C |
HOT source: | WATER |
--- | --- |
Operating temperature (cut- off) | min |
max | 78 °C |
Performance data measured in partial load conditions, according to UNI/TS 11300-4
Operating conditions | A Tbival | B | C | D |
---|---|---|---|---|
Reference temperature | [°C] | -7 | 2 | 7 |
PLR (T des = -10°C) | [%] | 88 | 54 | 35 |
Power DC at full load | [kW] | 17,3 | 20,5 | 21,0 |
COP at partial load | 2,86 | 4,11 | 5,32 | |
COP at full load | 2,86 | 4,06 | 4,87 | |
CR | 1,00 | 1,00 | 0,74 | |
Corrective factor Fp | 1,00 | 1,01 | 1,09 |
Model i-290 0123
Operating limits
COLD source: | OUTDOOR AIR |
---|---|
Operating temperature (cut- off) | min |
max | 20 °C |
HOT source: | WATER |
--- | --- |
Operating temperature (cut- off) | min |
max | 78 °C |
Performance data measured in partial load conditions, according to UNI/TS 11300-4
Operating conditions | A Tbival | B | C | D |
---|---|---|---|---|
Reference temperature | [°C] | -7 | 2 | 7 |
PLR (T des = -10°C) | [%] | 88 | 54 | 35 |
Power DC at full load | [kW] | 18,6 | 22,8 | 22,8 |
COP at partial load | 2,75 | 3,89 | 5,30 | |
COP at full load | 2,75 | 3,87 | 4,77 | |
CR | 1,00 | 1,00 | 0,79 | |
Corrective factor Fp | 1,00 | 1,00 | 1,11 |
Model i-290 0125
Operating limits
COLD source: | OUTDOOR AIR |
---|---|
Operating temperature (cut- off) | min |
max | 20 °C |
HOT source: | WATER |
--- | --- |
Operating temperature (cut- off) | min |
max | 78 °C |
Performance data measured in partial load conditions, according to UNI/TS 11300-4
Operating conditions | A Tbival | B | C | D |
---|---|---|---|---|
Reference temperature | [°C] | -7 | 2 | 7 |
PLR (T des = -10°C) | [%] | 88 | 54 | 35 |
Power DC at full load | [kW] | 19,6 | 23,9 | 24,8 |
COP at partial load | 2,71 | 3,94 | 5,09 | |
COP at full load | 2,71 | 3,83 | 4,62 | |
CR | 1,00 | 1,00 | 0,75 | |
Corrective factor Fp | 1,00 | 1,03 | 1,10 |
Model i-290 0127
Operating limits
COLD source: | OUTDOOR AIR |
---|---|
Operating temperature (cut- off) | min |
max | 20 °C |
HOT source: | WATER |
--- | --- |
Operating temperature (cut- off) | min |
max | 78 °C |
Performance data measured in partial load conditions, according to UNI/TS 11300-4
Operating conditions | A Tbival | B | C | D |
---|---|---|---|---|
Reference temperature | [°C] | -7 | 2 | 7 |
PLR (T des = -10°C) | [%] | 88 | 54 | 35 |
Power DC at full load | [kW] | 21,0 | 26,1 | 27,0 |
COP at partial load | 2,77 | 3,95 | 4,91 | |
COP at full load | 2,77 | 3,66 | 4,35 | |
CR | 1,00 | 1,00 | 0,82 | |
Corrective factor Fp | 1,00 | 1,08 | 1,13 |
11.1 EER DATA TO CALCULATE THE ENERGY PERFORMANCE OF BUILDINGS, ACCORDING
TO UNI/TS 11300-3
The EER coefficients under partial load conditions for i-290 reversible heat
pumps are provided.
The conditions of reference under partial load specified by standard UNI/TS
11300-3 for air-water reversible chillers and heat pumps are shown below.
The EER are also provided for load factors lower than 25%.
Test| Load factor| Outdoor air dry bulb temperature| Chilled water temperature on fan coil input/
output
---|---|---|---
1| 100%| 35| 12/7
2| 75%| 30| ()/7
3| 50%| 25| ()/7
4| 25%| 20| (*)/7
(*) temperature set by the full load water flow rate
Model i-290 0121
| | |
---|---|---|---
Outdoor air dry bulb temperature [°C]| Load factor F%| EER| Cooling capaci- ty
[kW]
35| 100%| 3,31| 17,4
30| 75%| 4,23| 13,1
25| 50%| 5,19| 8,7
20| 25%| 5,38| 8,3
C | Load factor F% | EER @20°C x C |
---|---|---|
0,95 | 20% | 5,11 |
0,94 | 15% | 5,05 |
0,87 | 10% | 4,68 |
0,71 | 5% | 3,82 |
0,46 | 2% | 2,47 |
0,29 | 1% | 1,56 |
Model i-290 0123
Outdoor air dry bulb temperature [°C]| Load factor F%| EER| Cooling capaci- ty
[kW]
---|---|---|---
35| 100%| 3,21| 18,9
30| 75%| 4,06| 14,0
25| 50%| 5,09| 9,5
C | Load factor F% | EER @20°C x C |
---|---|---|
0,95 | 20% | 5,27 |
0,94 | 15% | 5,21 |
0,87 | 10% | 4,82 |
0,71 | 5% | 3,94 |
0,46 | 2% | 2,55 |
0,29 | 1% | 1,61 |
Model i-290 0125
Outdoor air dry bulb temperature [°C]| Load factor F%| EER| Cooling capaci- ty
[kW]
---|---|---|---
35| 100%| 3,20| 19,8
30| 75%| 4,11| 14,0
25| 50%| 4,75| 9,9
C | Load factor F% | EER @20°C x C |
---|---|---|
0,95 | 20% | 4,50 |
0,94 | 15% | 4,45 |
0,87 | 10% | 4,12 |
0,71 | 5% | 3,36 |
0,46 | 2% | 2,18 |
0,29 | 1% | 1,37 |
Model i-290 0127
Outdoor air dry bulb temperature [°C]| Load factor F%| EER| Cooling capaci- ty
[kW]
---|---|---|---
35| 100%| 3,10| 22,3
30| 75%| 4,13| 16,7
25| 50%| 4,72| 11,2
C | Load factor F% | EER @20°C x C |
---|---|---|
0,95 | 20% | 4,65 |
0,94 | 15% | 4,60 |
0,87 | 10% | 4,26 |
0,71 | 5% | 3,48 |
0,46 | 2% | 2,25 |
0,29 | 1% | 1,42 |
REFRIGERANT SAFETY DATA SHEET
Name: | R290 |
---|
HAZARDS IDENTIFICATION
Main hazards:| Highly flammable gas.
Vapours are heavier than air and can cause asphyxiation due to reduced oxygen levels.
Specific hazards:| Contact with the liquid can cause frost burns.
FIRST AID MEASURES
General information:| In high concentrations it can cause asphyxia.
Symptoms may include loss of mobility and/or consciousness. In low
concentrations it may have a narcotic effect.
Inhalation:| Move the victim to an uncontaminated area while wearing
self-contained breathing apparatus. Use oxygen or artificial respiration
artificial respiration if necessary. Keep the patient lying down and warm.
Call a doctor.
Eye contact:| Carefully rinse with plenty of water for at least 15
minutes.
Skin contact:| Wash immediately with plenty of water for at least 15
minutes. Immediately remove contaminated clothing.
FIRE FIGHTING MEASURES
Extinguishing media:| Water spray, dry powder.
Specific hazards:| Exposure to flames may cause the vessel to
rupture or explode.
Specific methods:| Cool down the containers with a water spray from
a safe position. Stop the product leakage if possible. Use water spray, if
possible, to abate the fumes. Move the vessels away from the area of the fire
if this can be done without posing any risks.
ACCIDENTAL RELEASE MEASURES
Personal precautions:| Try to stop the leak.
Evacuate personnel to safety areas. Eliminate the ignition sources.
Ensure proper ventilation.
Avoid entering sewers, basements, excavations and areas where accumulation can
be dangerous. Use personal protective equipment.
Remain upwind.
Environmental precautions:| Try to stop the leak.
Cleaning methods:| Ventilate the area.
HANDLING AND STORAGE
Handling:
Technical measures/precautions:| Ensure sufficient air exchange and/or
suction in the working area. Do not smoke. Keep away from sources of ignition
(including electrostatic charges).
Use only appropriate equipment, suitable for the product.
Advice for safe use:| Do not inhale the gas.
Storage:| Close carefully and store in a cool and well ventilated area.
Storage containers should be checked periodically. Do not store with other oxidants in general or other combustible substances. Containers must not be stored in conditions that could lead to corrosion.
All electrical equipment in the storage area are compliant with the risk of explosive atmospheres formation.
EXPOSURE CONTROLS/PERSONAL PROTECTION
Control parameters:| OEL: data not available.
DNEL: data not available.
PNEC: data not available.
Respiratory protection:| Filter masks can be used if the ambient
conditions and duration of use are known.
Eye protection:| Safety goggles.
Hand protection:| Work gloves.
Hygienic measures:| No smoking.
PHYSICAL AND CHIMICAL PROPERTIES
Colour:| Colourless.
Odour:| Odourless.
Boiling point:| -42,1 °C at atm press
Flash point:| 470°C
Relative gas density (air=1) Relative liquid density (water=1)| 1,50
0,58
Solubility in water:| 75 mg/l.
STABILITY AND REACTIVITY
Stability:| Stable under normal conditions.
Materials to avoid: Decomposition products hazardous:| Air, oxidising
agents . Keep away from heat sources/sparks/open flames/heated surfaces.
Under normal conditions of storage and use, dangerous decomposition products
should not be generated.
TOXICOLOGICAL INFORMATION
Acute toxicity: Local effects:
Long term toxicity:| CL50/inhalation/4 hours/on rat = 20000 ppm. No
known effect.
No known effect.
ENVIRONMENTAL INFORMATION
Global warming potential GWP (R744=1):| 3
Ozone Depletion Potential ODP (R11=1):| 0
Disposal consideration:| Refer to the supplier’s gas recovery programme.
Avoid direct discharge into the atmosphere. Do not discharge where
accumulation can be dangerous. Ensure that the emissions limits required by
local regulations or specified in authoriza- tions are not exceeded.