Morningstar SS-MPPT-15L SunSaver Professional Series User Guide

June 15, 2024
Morningstar

SS-MPPT-15L Sun Saver Professional Series
User Guide

SS-MPPT-15L Sun Saver Professional Series

Scan QR Code to go directly to the Sun Saver MPPT Installation Manual and warranty information online.

http://www.morningstarcorp.com/wp- content/uploads/2014/2014/02/SSMPPT.IOM_.EN_.03-4-131.pdf Warranty Registration: https://www.morningstarcorp.com/product‐registration/

Safety Information

WARNING: Shock Hazard
The Sun Saver MPPT controller must be installed by a qualified technician in accordance with the electrical  regulations of the country of installation.
WARNING: Shock Hazard
This unit is not provided with a GFDI device.  This charge  controller must be used with an external GFDI device as  required by the Article 690 of the National Electrical Code  for the installation location.
IMPORTANT:  READ the  Sun Saver  MPPT Installation  Manual for  safety and  regulatory information,  instructions on configuration and  operation, and   warranty  information.
In the Box: Tools Required:
—  #2 Philips Screwdriver
—  3/16  (5 mm) & 3/32″ (2.5 mm) Flathead Screwdriver
—  Drill with a 3/32″ (2.5 mm) bit
—  Multimeter

Optional Accessories

SunSaver MPPT™ Charge Controller

Minimum Clearance Requirements: WARNING: Explosion Hazard
Never  install the  Sun Saver  MPPT in an  enclosure with  vented/flooded batteries.   Battery fumes are  flammable   and will corrode  and destroy the Sun Saver  circuits.
WARNING: Risk of Fire
If a  Remote  Temperature  Sensor  (RTS) is NOT  connected,   locate  the Sun Saver  MPPT within  3 m  (10 ft)  of the  batteries.    Internal  temperature compensation  will be  used if the  RTS  is  not  connected.   Use  of  the RTS is  strongly recommended.
CAUTION: Equipment Damage
Do not expose the Sun Saver MPPT to weather.  Locate in a dry,  protected area to prevent equipment damage.  Ensure the  minimum clearance requirements are followed to provide   equate ventilation and prevent the unit from overheating.

Mounting

Step 1: Choose Mounting Location
Locate the Sun Saver MPPT on a vertical surface  protected from direct sun, high temperatures, and water.
Step 2: Check for Clearance and Ventilation
Place the Sun Saver MPPT in the location where it will be  mounted. Verify that there is sufficient room to run wires  and that there is ample room above and below the  controller for air flow. Step 3: Mark Holes
Use a pencil or pen to mark the four (4)  mounting hole locations on the mounting surface.
Step 4: Drill Holes
Remove the controller and drill 3/32” (2.5 mm)  holes in the marked locations.
Step 5: Secure Controller
Place the controller on the surface and align the mounting  holes with the drilled holes in step 4.  Secure the controller  in place using the Mounting screws (included). Photovoltaic (PV) Array
See the Morningstar PV String Calculator at: http://string‐calculator.morningstarcorp.com/ IMPORTANT:
Array Voltage should NEVER exceed  the maximum input voltage.
STATUS LED

Color Indication Operating State
None OFF (with heartbeat¹) Night
Green ON Solid (with heartbeat²) Charging
Red Flashing Error
Red ON Solid (with heartbeat²) Critical Error

¹ heartbeat indication flickers the Status LED ON briefly every 5 seconds
²heartbeat indication flickers the Status LED OFF briefly every 5 seconds

Recommended Order of
Installation| Wiring and Torque Requirements
---|---
Component| Wire Size (Solid)| Wire Size (multistring)| Wire Size (fine strand)| Torque (Maximum)| Tool Required
1| Load Terminals| #6 AWG 16 mm2
(Maximum)| #6 AWG 16 mm2
(Maximum)| #8 AWG 10 mm2
(Maximum)| 10.6 in-lbs.
(1.2 Nm)| 3/1615 mm) Flathead Screwdriver
2| Battery Terminals
3| Solar Terminals
4| Remote Temperature
Sensor| #22 AWG / 0.3 mm2 (Minimum)

12 AWG / 3.0 mm2 (Maximum)| 3.5 in-lbs.

(0.4 Nm)| 3/32″ (2.5 mm) Flathead Screwdriver
5| Fuses or Disconnects| *Fuse or breaker sizing must be based on required wire ampacity.
If using a fuse, do NOT insert the fuse in the fuse-holder until after all the other connections have been completed.

IMPORTANT:  Example only.  Actual wiring may vary.  READ  the Sun Saver MPPT  Installation, Operations,  and Maintenance  Manual  for  mandatory safety requirements.   All configuration must comply with local and national electric codes.  Consult your local electric authority to ensure compliance.

BATTERY STATE-OF-CHARGE (SOC) LEDs

SOC LED| Indication| Battery Status| Load Status
Green| Fast Flashing (2 Flash / sec)| Equalize Charge| Load ON
Green| Medium Flashing (1 Flash / sec)| Absorption Charge| Load ON
Green| Slow Flashing (1 Flash / 2 sec)| Float Charge| Load ON
Green| ON Solid| Nearly Full| Load ON
Yellow | ON Solid| Half Full| Load ON
Red | Flashing (1 Flash / sec)| Battery Low| LVD Warning (Load On)
Red| ON Solid| Battery Empty| LVD (Load Off)

WARNING: Shock Hazard
Test  between all terminals and  ground  before  touching.
Power or accessory terminals are NOT electrically isolated from DC input and may be energized with hazardous solar voltage.
WARNING: Shock Hazard
Fuses, circuit breakers, and disconnect switches never open grounded system conductors. Only GFDI devices are permitted to disconnect grounded conductors.
IMPORTANT:
Ensure there is only 1 DC Negative‐to‐Ground Bond in the entire system.

Power UP Sequence:

  1. Connect Battery/Battery  Bank.
  2. Connect Solar.

Power DOWN Sequence:

  1. Disconnect Solar.
  2. Disconnect Battery/Battery  Bank.

Specifications:

| SS-MPPT-15L
---|---
Nominal Battery Voltage| 12 V or 24 V
Max. Solar Input Voltage| 60 V
Nominal Maximum Input Power| 200 W / 400 W
Maximum Battery Current| 15 A
Battery Voltage Range| 7 – 36 V
Rated Load Current| 15 A

Operational Configuration:

  1. Set points for this switch setting can be modified with custom programming.

Contact Information:
Technical Support : Support.morningstarcorp.com
Phone:  1‐215‐321‐4457

BATTERY SET POINTS
12-volt (24-volt)

Set Point| GEL| Sealed| AGM| Flooded
Absorption Voltage| 14.0 V
(28.0 V)| 14.1 V
(28.2 V)| 14.3 V
(28.6 V)| 14.4 V
(28.8 V)
Float Voltage| 13.7 V
(27.4 V)| 13.7 V
(27.4 V)| 13.7 V
(27.4 V)| 13.7 V
(27.4)
Time until Float| 3 hours| 3 hours| 3 hours| 3 hours
Equalize Voltage| N/A| N/A| 14.5 V| 14.9 V
Equalize Duration| N/A| N/A| 3 hours| 3 hours
Equalize Calendar (days)| N/A| N/A| 28| 28
Maximum Regulation Voltage*| 15 V (30 V)
LVD/ LVR (Switch 2 OFF)| 11.5 V /12.6 V @ 12 V (23.0 V/25.2 V @ 24 V)
LVD/LVR (Switch 2 ON)| 11.0 V/12.1 V @ 12 V (22.0 V/24.2 V @ 24 V)
Load HVD| 15.3 V (30.6 V)
Load HVR
| 14.5 V (29 V)
Array HVID (Temp. Comp.)| Highest voltage set point + 0.5 V
Array HVR (Temp. Comp.)| 13.8 V (27.6 V)
Not temperature compensated. 15 V @ 12 V nominal, 30 V @ 24 V nominal.
** Adjustable by DIP Switch 2. Not temperature compensated. Can be modified in custom settings.

1 For Custom Programming:
Use the software available at https://www.morningstarcorp.com/msview/.
See the Sun Saver MPPT Installation, Operations, and Maintenance Manual for additional information/guidance.
Switch 2: Load Control /
Low Voltage Disconnect/ Reconnects Switch 3: Auto-Equalization

Switch 4: Communication Mode -Meter/MODBUS®

Remote Meter, & Relay Driver
MODBUS®  Protocol for  MS View, Ethernet Meter bus  Converter, 3 rd. ‐Party Devices

© 2021 Morningstar Corporation.
All Rights Reserved.
MS‐003294 SS‐MPPT
QSG (3/16/2021) Rev C03

References