MITSUBISHI ELECTRIC JG79B784H08 Split Type Air Conditioners
BEFORE INSTALLATION
MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT
**| WARNING
** (Risk of fire)| This unit uses a flammable refrigerant.
If refrigerant leaks and comes in contact with fire or heating part, it will
create
harmful gas and there is risk of fire.
---|---|---
| Read the OPERATING INSTRUCTIONS carefully before operation.
| Service personnel are required to carefully read the OPERATING INSTRUCTIONS
and INSTALLATION MANUAL before operation.
| Further information is available in the OPERATING INSTRUCTIONS, INSTALLATION
MANUAL, and the like.
THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
- Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air
- Before starting the connection setup of the Wi-Fi interface, check the safety precautions in OPERATING INSTRUCTIONS of the room air
- Be sure to observe the warnings and cautions specified here as they include important items related to
- After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future
WARNING (Could lead to death, serious injury, etc.)
- Do not install the unit by yourself (user). Incomplete installation could cause fire, electric shock, injury due to the unit falling, or leakage of water. Consult the dealer from whom you purchased the unit or a qualified
- Perform the installation securely referring to the installation manual. Incomplete installation could cause fire, electric shock, injury due to the unit falling, or leakage of water.
- When installing the unit, use appropriate protective equipment and tools for safety. Failure to do so could cause injury.
- Install the unit securely in a place which can bear the weight of the unit. If the installation location cannot bear the weight of the unit, the unit could fall causing injury.
- Electrical work should be performed by a qualified, experienced electrician, according to the installation Be sure to use an exclusive circuit. Do not connect other electrical appliances to the circuit. If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
- Earth the unit correctly. Do not connect the earth to a gas pipe, water pipe, lightning rod, or telephone earth. Defective earthing could cause electric shock.
- Do not damage the wires by applying excessive pressure with parts or screws. Damaged wires could cause fire or electric shock.
- Be sure to cut off the main power in case of setting up the indoor P.C. board or wiring works. Failure to do so could cause electric shock.
- Use the specified wires to connect the indoor and outdoor units securely and attach the wires firmly to the terminal block connecting sections so the stress of the wires is not applied to the sections. Do not extend the wires, or use intermediate connection. Incomplete connecting and securing could cause fire.
- Do not install the unit in a place where inflammable gas may If gas leaks and accumulates in the area around the unit, it could cause an explosion.
- Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet. It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
- Be sure to use the parts provided or specified parts for the installation work. The use of defective parts could cause an injury or leakage of water due to a fire, an electric shock, the unit falling, etc.
- When plugging the power supply plug into the outlet, make sure that there is no dust, clogging, or loose parts in both the outlet and the plug. Make sure that the power supply plug is pushed completely into the outlet. If there is dust, clogging, or loose parts on the power supply plug or the outlet, it could cause electric shock or fire. If loose parts are found on the power supply plug, replace it.
- Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely. If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
- Do not discharge the refrigerant into the atmosphere. If refrigerant leaks during installation, ventilate the room. Check that the refrigerant does not leak after installation has been completed. If refrigerant leaks and comes in contact with fire or heating part of such a fan heater, kerosene heater, or cooking stove, it will create harmful gas.
- Use appropriate tools and piping materials for installation. The pressure of R32 is 1.6 times more than R22. Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury.
- When installing the unit, securely connect the refrigerant pipes before starting the compressor. If the compressor is started before the refrigerant pipes are connected and when the stop valve is open, air could be drawn in and the pressure in the refrigeration cycle could become abnormally high. This could cause the pipes to burst or injury.
- When installing, relocating, or servicing the unit, make sure that no substance other than the specified refrigerant (R32) enters the refrigerant Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury. The use of any refrigerant other than that specified for the system will cause mechanical failure, system malfunction, or unit breakdown. In the worst case, this could lead to a serious impediment to securing product safety.
- When pumping down the refrigerant, stop the com- pressor before disconnecting the refrigerant If the refrigerant pipes are disconnected while the compressor is running and the stop valve is open, air could be drawn in and the pressure in the refrigeration cycle could become abnormally high. This could cause the pipes to burst or injury.
- Fasten a flare nut with a torque wrench as specified in this manual. If fastened too tight, a flare nut may break after a long period and cause refrigerant leakage.
- The unit shall be installed in accordance with national wiring regulations. If the refrigerant leaks and comes in contact in fire or heating part, it will create harmful gas and there is risk of fire. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
- Pipe-work shall be protected from physical
- The installation of pipe-work shall be kept to a minimum.
- Compliance with national gas regulations shall be
- Keep any required ventilation openings clear of obstruction.
- Do not install the indoor unit equipped with the Wi-Fi interface nearby the automatic control devices such as automatic doors or fire It can cause accidents due to malfunctions.
- Do not use the indoor unit equipped with the Wi-Fi interface nearby the medical electrical equipment or people who have a medical device such as a cardiac pacemaker or an implantable cardioverter- defibrillator. It can cause an accident due to malfunctions of the medical equipment or device.
- This indoor unit equipped with the Wi-Fi interface should be installed and operated with a minimum distance of 20 cm between the device and the user or bystanders.
- The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater). Be aware that refrigerants may not contain an Do not pierce or When using a gas burner or other flame-producing equipment, completely remove all of the refrigerant from the air conditioner and ensure that the area is well-ventilated.
CAUTION (Could lead to serious injury in particular environments when operated incorrectly
- Install an earth leakage breaker depending on the installation place. If an earth leakage breaker is not installed, it could cause electric shock.
- Perform the drainage/piping work securely ac- cording to the installation manual. If there is defect in the drainage/piping work, water could drop from the unit, soaking and damaging household goods.
- Do not touch the air inlet or the aluminum fins of the outdoor unit. This could cause injury.
- Do not install the outdoor unit where small animals may live.
- If small animals enter and touch the electric parts inside the unit, it could cause a malfunction, smoke emission, or fire. Also, advise user to keep the area around the unit clean.
- Do not operate the air conditioner during interior construction and finishing work, or while waxing the floor. Before operating the air conditioner, ventilate the room well after such work is performed. Otherwise, it may cause volatile elements to adhere inside the air conditioner, resulting in water leakage or scattering of dew.
- To prevent damage from static electricity, touch a nearby metal body to discharge static electricity from yourself before touching the indoor unit equipped with the Wi-Fi interface. Static electricity from the human body may damage the Wi-Fi interface unit.
- Do not use the indoor unit equipped with the Wi-Fi interface nearby other wireless devices, microwaves, cordless phones, or facsimiles. It can cause malfunctions.
SELECTING THE INSTALLATION LOCATION
INDOOR UNIT
WARNING
The unit should be installed in rooms which have the floor space specified
below. MSZ-LN25/35VG: 1.7 m² MSZ-LN50VG: 2.5 m² MSZ-LN50VGHZ/60VG: 3.9 m² As
for the details, please refer to the Installation Service Manual for New
Refrigerant System.
- Where airflow is not blocked
- Where cool (or warm) air spreads over the entire room
- Rigid wall without vibration
- Where it is not exposed to direct sunshine. Do not expose to direct sunshine also during the period following unpacking to before use
- Where easily drained
- At a distance 1 m or more away from your TV and radio. Operation of the air conditioner may interfere with radio or TV An amplifier may be required for the affected device.
- In a place as far away as possible from fluorescent and incandescent In order to make the infrared remote control operate the air conditioner normally. The heat from the lights may cause deformation or the ultraviolet may cause deterioration.
- Where the air filter can be removed and replaced easily
- Where it is away from the other heat or steam source
- Please ensure that the Router supports the WPA2-AES encryption setting before commencement of the installation of this indoor unit equipped with the Wi-Fi interface
- The End user should read and accept the terms and conditions of the Wi-Fi service before commencement of the installation of this indoor unit equipped with the Wi-Fi service before
- This indoor unit equipped with the Wi-Fi interface should not be installed and connected to any Mitsubishi Electric system which is to provide application critical cooling or heating
**REMOTE CONTROLLER**
- Where it is easy to operate and easily visible
- Where children cannot touch it
Select a position about 1.2 m above the floor and check that signals from the remote controller are surely received by the indoor unit from that position (‘beep’ or ‘beep beep’ receiving tone sounds). After that, attach remote controller holder to a pillar or wall and install wireless remote controller
Note:
In rooms where inverter type fluorescent lamps are used, the signal from
the wireless remote controller may not be received.
OUTDOOR UNIT
- Where it is not exposed to strong If the outdoor unit is exposed to a wind during defrosting, the defrosting time will be longer.
- Where airflow is good and dustless
- Where rain or direct sunlight can be avoided as much as possible
- Where neighbors are not annoyed by operation sound or hot (or cool) air
- Where rigid wall or support is available to prevent the increase of operation sound or vibration
- Where there is no risk of combustible gas
- When installing the unit at a high level, be sure to secure the unit vibration
- Where it is at least 3 m away from the antenna of TV set or radio. Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak. An amplifier may be required for the affected device unit legs
- Install the unit horizontally
- Please install it in an area not affected by snowfall or blowing snow. In areas with heavy snow, please install a canopy, a pedestal and/or some baffle boards
Note:
It is advisable to make a piping loop near outdoor unit so as to reduce
vibration transmitted from there
Note:
When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.
- Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind
- To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
- To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit
Avoid the following places for installation where air conditioner trouble is liable to occur.
- Where flammable gas could leak
- Where there is much machine oil
- Where oil is splashed or where the area is filled with oily smoke (such as cooking areas and factories, in which the properties of plastic could be changed and dam- aged).
- Salty places such as the seaside seaside
- Where sulfide gas is generated such as hot spring, sewage, waste water
- Where there is high-frequency or wireless equipment
- Where there is emission of high levels of VOCs, including phthalate compounds, formaldehyde, etc., which may cause chemical cracking
- The appliance shall be stored so as to prevent mechanical damage from occurring
SPECIFICATIONS
Model| Power supply *1| Wire specifications| Pipe size
(thickness 3, 4)
|
Maximum amount of refrigerant charge *7
---|---|---|---|---
Indoor unit| Outdoor unit| Rated Voltage| Frequency| Breaker
capacity| Power supply 2| Indoor/outdoor
connecting wire 2| Gas / Liquid
MSZ-LN25VG MSZ-LN35VG| MUZ-LN25VG(HZ) MUZ-LN35VG| 23O V| 5O Hz| 1O A| 3-core
1.O mm2| 4-core
1.O mm2| 09.52 / 6.35 mm (O.8 mm)| 126O g
MSZ-LN35VG| MUZ-LN35VGHZ| 12 A| 3-core 1.5 mm2
MSZ LN5OVG| MUZ-LN5OVG| 16 A| 3-core 2.O mm2| 151O g
MUZ-LN5OVGHZ| 191O g
MSZ LN6OVG| MUZ LN6OVG| 012.7 / 6.35 mm (O.8 mm)
- Connect to the power switch which has a gap of 3 mm or more when open to interrupt the source power phase. (When the power switch is shut off, it must interrupt all phases.)
- Use wires in conformity with design 6O245 IEC 57.
- Never use pipes with thickness less than specified. The pressure resistance will be insufficient.
- Use a copper pipe or a copper-alloy seamless pipe.
- Be careful not to crush or bend the pipe during pipe bending.
- Refrigerant pipe bending radius must be 1OO mm or more.
- If pipe length exceeds 7 m, additional refrigerant (R32) charge is required. (No additional charge is required for pipe length less than 7 m.) Additional refrigerant = A x (pipe length (m) – 7)
- Insulation material : Heat resisting foam plastic O.O45 specific gravity
- Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installation of the indoor unit and insufficient thickness may cause dew droppage.
(LN25, 35, 5O/5OHZ, 6O)
Pipe length and height difference
Max. pipe length| 2O/3O m
Max. height difference| 12/15 m
Max. number of bends 5, 6| 1O
Refrigerant adjustment A 7| 2O g/m
Insulation thickness 8, *9| 8 mm
INSTALLATION DIAGRAM
ACCESSORIES
Check the following parts before installation.
(1) | Installation plate | 1 |
---|---|---|
(2) | Installation plate fixing screw 4 x 25 mm | 5 |
(3) | Wireless remote controller | 1 |
(4) | Felt tape (For left or left-rear piping) | 1 |
(5) | Corner box R | 4 |
(6) | Corner box L | 4 |
(7) | Battery (AAA) for (3) | 2 |
(8) | Air cleaning filter | 1 |
(9) | Air purifying device | 1 |
(1O) | Drain socket (VG type only) | 1 |
---|
PARTS TO BE PROVIDED AT YOUR SITE
(A) | Indoor/outdoor unit connecting wire*1 | 1 |
---|---|---|
(B) | Extension pipe | 1 |
(C) | Wall hole sleeve | 1 |
(D) | Wall hole cover | 1 |
(E) | Pipe fixing band | 2 to 5 |
(F) | Fixing screw for (E) 4 x 2O mm | 2 to 5 |
(G) | Piping tape | 1 |
(H) | Putty | 1 |
(I) | Drain hose (or soft PVC hose, 15 mm inner diameter or hard PVC pipe | |
VP16) |
1 or 2
(J)| Refrigeration oil| 1
(K)| Power supply cord*1| 1
Note:
- *1 Place indoor/outdoor unit connecting wire (A) and power supply cord (K) at least 1 m away from the TV antenna wire.
This indoor unit is equipped with the built-in Wi-Fi interface.
- *3 When any 2 sides of left, right and rear of unit are clear
- *4 The manufacturing year and month is indicated on the spec name plate.
Appearance of the outdoor unit may differ from some models.
IMPORTANT NOTES
Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
Drain piping for outdoor unit
< VG type only>
- Provide drain piping before indoor and outdoor pip- ing
- Connect drain hose (I) I.D.15 mm as shown in the
- Make sure to provide drain piping with a downhill grade for easy drain
NOTE
Install the unit horizontally
Do not use drain socket (1O) in cold regions. Drain may freeze and make the
fan stop.
The outdoor unit produces condensate during the heating operation. Select the
installation place to ensure to prevent the outdoor unit and/or the grounds
from being wet by drain water or damaged by frozen drain water.
INDOOR UNIT INSTALLATION
FIXING OF INSTALLATION PLATE
- Find a structural material (such as a stud) in the wall and fix installation plate (1) horizon- tally by tightening the fixing screws (2)
- To prevent installation plate (1) from vibrating, be sure to install the fixing screws in the holes indicated in the For added support, fixing screws may also be installed in other holes.
- When the knockout is removed, apply vinyl tape to the knockout edges to prevent damaging the wires
- When bolts recessed in the concrete wall are to be utilized, secure installation plate (1) using 11 x 2O · 11 x 26 oval hole (45O mm pitch).
- If the recessed bolt is too long, change it for a shorter one available in the market
WALL HOLE DRILLING
- Determine the wall hole position
- Drill a 065 mm The outdoor side should be 5 to 7 mm lower than the indoor side.
- Insert wall hole sleeve (C).
CONNECTING WIRES FOR INDOOR UNIT
You can connect indoor/outdoor lead wire without removing the front panel.
- Open the front
- Remove VA
- Remove VA
- Pass indoor/outdoor unit connecting wire (A) from the back of the indoor unit and process the end of the connecting wire (A) to the terminal block. Be careful not to make miswiring. Fix the wire to the terminal block securely so that no part of its core is appeared, and no external force is conveyed to the connecting section of the terminal block.
- Firmly tighten the terminal screws to prevent them from After tightening, pull the wires lightly to confirm that they do not move.
- Secure indoor/outdoor unit connecting wire (A) and the earth wire with the VA Never fail to hook the left claw of the VA clamp. Attach the VA clamp securely.
- For future servicing, give extra length to the connecting wires
- Make earth wire a little longer than (More than 6O mm)
- Do not fold the excess wire, or cram it into small space. Take caution not to damage the wires
- Be sure to attach each screw to its correspondent terminal when securing the cord and/or the wire to the terminal block.
Note: Do not place the wires between the indoor unit and the installation plate (1). Damaged wire could cause heat generation or wires
PIPE FORMING AND DRAIN PIPING
Pipe Forming
- Place the drain hose below the refrigerant piping
- Make sure that the drain hose is not heaved or snaked
- Do not pull the hose when applying the tape
- When the drain hose passes the room, be sure to wrap insulation material (obtainable at a store) around it
Rear, right, or downward piping
- Put the refrigerant piping and the drain hose together, then firmly apply piping tape (G) from the end
- Insert the piping and the drain hose into the wall hole sleeve (C), and hook the upper part of the indoor unit on the installation plate (1).
- Check if the indoor unit is hooked securely on the installation plate (1) by moving the unit to left and right
- Thrust the lower part of the indoor unit into the installation plate (1).
Drain Piping
- If the extension drain hose has to pass through a room, be sure to wrap it with commercially sold insulation
- The drain hose should point downward for easy drain flow. (Fig. 1)
- If the drain hose provided with the indoor unit is too short, connect it with drain hose (I) that should be provided at your site. (Fig. 2)
- When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it securely into the pipe. (Fig. 3)
Do not make drain piping as shown below.
Left or left-rear piping
Note:
Be sure to reattach the drain hose and the drain cap in case of left or
left-rear piping. Otherwise, it could cause drops of water to drip down from
the drain hose.
Note:
Be sure to reattach the drain hose and the drain cap in case of left or
left-rear piping. Otherwise, it could cause drops of water to drip down from
the drain hose.
- Put the refrigerant piping and the drain hose together, then firmly apply felt tape (4) from the end.
- Felt tape (4) overlap width should be 1/3 the tape width. Use a bandage stopper at the end of felt tape (4).
- Pull out the drain cap at the rear right of the indoor (Fig. 1)
- Hold the convex section at the end and pull the drain cap.
- Pull out the drain hose at the rear left of the indoor (Fig. 2)
- Hold the claw marked by the arrows and pull out the drain hose
- Put the drain cap into the section to which the drain hose is to be attached at the rear of the indoor (Fig. 3)
- Insert not sharp-edged tools such as screwdrivers into the hole at the end of the cap and insert the cap fully into the drain
- Insert the drain hose fully into the drain pan at the rear right of the indoor unit. (Fig. 4)
- Check if the hose is hooked securely to the projection of its inserting part at the drain
- Insert the drain hose into wall hole sleeve (C), and hook the upper part of indoor unit on installation plate (1). Then, move the indoor unit completely to the left in order to make placing the piping in the back space of the unit easier.
- Cut out a piece of cardboard from the shipping box, roll it up, hook it onto the back rib, and use it as a spacer to lift the indoor unit. (Fig. 5)
- Connect the refrigerant piping with the extension pipe (B).
- Thrust the lower part of the indoor unit into the installation plate (1).
ASSEMBLING OF CORNER BOX
- The corner boxes are stowed in the cushioning materials on the right and left sides
- Check the markings (RIGHT/LEFT) on the parts, and use the appropriate parts
-
Each right and left corner box is assembled from 2
-
Arrange the two parts so that the 2 marks align. Move 1 part about 9O degrees around the hinge point you have just created to put the parts
-
Press the base of portion with the mark to snap into place
-
Attach the assembled corner box to the indoor unit.
-
Assemble the corner box L in the same manner.
- When changing the part, disassemble by moving the part in a reverse direction
- The parts that were not used may be necessary in the future if the air conditioner is relocated, so ask customers to keep those parts
OUTDOOR UNIT INSTALLATION
CONNECTING WIRES FOR OUTDOOR UNIT
- Open the service panel.
- Loosen terminal screw, and connect indoor/outdoor unit connecting wire (A) from the indoor unit correctly on the terminal block. Be careful not to make miswiring. Fix the wire to the terminal block securely so that no part of its core is appeared, and no external force is conveyed to the connecting section of the terminal block.
- Firmly tighten the terminal screws to prevent them from loosening. After tightening, pull the wires lightly to confirm that they do not move.
- Connect power supply cord (K).
- Fix indoor/outdoor unit connecting wire (A) and power supply cord (K) with the cord clamp.
- Close the service panel securely.
- Make earth wire a little longer than (More than 1OO mm)
- For future servicing, give extra length to the connecting wires
- Be sure to attach each screw to its correspondent terminal when securing the cord and/or the wire to the terminal block
FLARING WORK
- Cut the copper pipe correctly with pipe cutter. (Fig. 1, 2)
- Completely remove all burrs from the cut cross section of pipe. (Fig. 3) .Put the end of the copper pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the piping.
- Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (Not possible to put them on after flaring work.)
- Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A mm from the table according to the tool you use.
- Check .
- Compare the flared work with Fig.
- If flare is noted to be defective, cut off the flared section and do flaring work again.
Pipe diameter (mm)
|
Nut (mm)
| A (mm)| Tightening torque
---|---|---|---
Clutch type tool for R32,
R41OA
| Clutch type tool for R22| Wing nut type tool for R22| NM| kgf cm
06.35 (1/4″)| 17| O to O.5| 1.O to 1.5| 1.5 to 2.O| 13.7 to
17.7
| 14O to
18O
09.52 (3/8″)| 22| 34.3 to 41.2| 35O to 42O
012.7 (1/2″)| 26| 2.O to 2.5| 49.O to
56.4
| 5OO to
575
015.88 (5/8″)| 29| 73.5 to 78.4| 75O to 8OO
PIPE CONNECTION
- Fasten flare nut with a torque wrench as specified in the table.
- When fastened too tight, flare nut may break after a long period and cause refrigerant leakage.
- Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
Indoor unit connection
Connect both liquid and gas piping’s to indoor unit.
- Apply a thin coat of refrigeration oil (J) on the flared ends of the pipes. Do not apply refrigeration oil on screw threads. Excessive tightening torque will result in damage on the screw.
- For connection, first align the center, then tighten the first 3 to 4 turns of flare nut.
- Use tightening torque table above as a guideline for indoor unit side union joint section, and tighten using two wrenches. Excessive tightening damages the flare section.
WARNING
To avoid risk of fire, flare connection should be installed outdoors.
Reusable mechanical connectors and flared joints are not allowed indoors.
When connecting the refrigerant piping by brazing, rather than using flare
connections, complete all brazing prior to connecting indoor unit to outdoor
unit.
Outdoor unit connection
Connect pipes to stop valve pipe joint of the outdoor unit in the same manner
applied for indoor unit.
- For tightening, use a torque wrench or spanner and use the same tightening torque applied for indoor unit.
WARNING
When installing the unit, securely connect the refrigerant pipes before
starting the compressor
INSULATION AND TAPING
- Cover piping joints with pipe cover valves
- For outdoor unit side, surely insulate every piping including
- Using piping tape (G), apply taping starting from the entry of outdoor unit
- Stop the end of piping tape (G) with tape (with adhesive agent attached).
When piping have to be arranged through above ceiling, closet or where the temperature and humidity are high, wind additional commercially sold insulation to prevent condensation
PURGING PROCEDURES, LEAK TEST, AND TEST RUN
PURGING PROCEDURES AND LEAK TEST
- Remove service port cap of stop valve on the side of the outdoor unit gas (The stop valves are fully closed and covered in caps in initial state.)
- Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit
-
in the same position. Confirm that pressure gauge shows -O.1O1 MPa [Gauge] (-76O mmHg).
-
Remove gauge manifold valve quickly from service port of stop valve
WARNING
To avoid risk of fire, make sure that there are no flammable hazards or ignition risks before opening the stop valves. -
After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and liquid Operating without fully opening lowers the performance and this causes trouble.
-
Refer to 1-3., and charge the prescribed amount of refrigerant if Be sure to charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant in the system may be changed and affect performance of the air conditioner.
-
Tighten cap of service port to obtain the initial status
-
Leak test
TEST RUN
- Insert power supply plug into the power outlet and/or turn on the breaker.
- Press the O. SW once for COOL, and twice for HEAT operation. Test run will be performed for 3O minutes. If the left lamp of the operation indicator blinks every O.5 seconds, inspect the indoor/ outdoor unit connecting wire (A) for miswiring. After the test run, emergency mode (set temperature 24°C) will start.
- To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for
- Checking the remote (infrared) signal reception
- Press the OFF/ON button on the remote controller (3) and check that an electronic sound is heard from the indoor Press the OFF/ON button again to turn the air conditioner off.
- Once the compressor stops, the restart preventive device operates so the compressor will not operate for 3 minutes to protect the air conditioner
AUTO RESTART FUNCTION
This product is equipped with an auto restart function. When the power supply is stopped during operation, such as during blackouts, the function automatically starts operation in the previous setting once the power supply is resumed. (Refer to the operating instructions for details)
Caution:
- After test run or remote signal reception check, turn off the unit with the E.O. SW or the remote controller before turning off the power Not doing so will cause the unit to start operation automatically when power supply is resumed.
To the user
- After installing the unit, make sure to explain the user about auto restart
- If auto restart function is unnecessary, it can be deactivated. Consult the service representative to deactivate the Refer to the service manual for details.
SETTING THE INSTALLATION POSITION
Be sure to set the remote controller in accordance with the installed position of the indoor unit.
Installation position:
- Left: Distance to objects (wall, cabinet, etc.) is less than 5O cm to the left
- Center: Distance to objects (wall, cabinet, etc.) is more than 5O cm to the left and right
- Right: Distance to objects (wall, cabinet, etc.) is less than 5O cm to the right
Note:
The installation position can be set only when all the following conditions are met:
- The remote controller is powered off
- Weekly timer is not set
- Weekly timer is not being edited
- Hold down on the remote controller for 2 seconds to enter the position setting mode.
- Select the target installation position by pressing . (Each press of the displays the positions in order: center — right —left )
- Press to complete the position setting
EXPLANATION TO THE USER
- Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (how to use the remote controller, how to remove the air filters, how to clean, precautions for operation, etc. ).
- Recommend the user to read the OPERATING INSTRUCTIONS carefully
CONNECTION SETUP OF THE Wi-Fi INTERFACE
**** This product is equipped with the Wi-Fi Interface as standard.
Refer to the SETUP QUICK REFERENCE GUIDE and OPERATING INSTRUCTIONS provided
with the indoor unit for connection with the router.
RELOCATION AND MAINTENANCE
REMOVING AND INSTALLING THE PANEL ASSEMBLY
Removal procedure
- Insert a screwdriver deeply into the holes
- Pry off the right and left arm holders by moving the screwdriver down and towards the back wall
- Remove the safety string from the upper center of the panel assembly.
CAUTION
Hold the panel with your hand while detaching it to avoid injury.
Installation procedure
- Install the panel assembly following the removal procedure in reverse
- Be sure to press the positions as indicated by the arrows in order to attach the assembly completely to the unit
REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
When releasing the corner boxes, release both left and right bottom corner
part of indoor unit and pull it down- ward and forward as shown in the figure
on the right.
PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
- Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
- Fully close the stop valve on the liquid pipe side of the outdoor unit.
- Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge] (0 kgf/cm*).
- Start the emergency COOL operation. To start the emergency operation in COOL mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug and/ or turn on the breaker, and then press the E.0. SW once. (The emergency COOL operation can be performed continuously for up to 30 minutes.)
- Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm).
- Stop the emergency COOL operation. Press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.
WARNING
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.
This product is designed and intended for use in the residential, commercial and light-industrial environment. HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 1OO-831O, JAPAN