Barksdale BPS3000 Electronic Pressure Switch Instruction Manual
- June 4, 2024
- Barksdale
Table of Contents
Barksdale BPS3000 Electronic Pressure Switch
Intended Applications
The dual pressure switch monitors system pressures and has up to two switching
outputs and one analog output.
Operate the switch exclusively in the specified fields of application (see
chapter “Technical Data“ on page 12).
Observe the applicable national safety regulations for assembly, commissioning
and operation of the switch.
Do not use the switch as the only safety relevant element according to DGR
2014/68/EU (PED).
Safety Instructions
The safety instructions are intended to protect the user from dangerous
situations and/or prevent material damage.
In the operating instructions the seriousness of the potential risk is
designated by the following signal words:
Refers to imminent danger to life and health of men.
Nonobservance will result in serious injuries, or even life-threatening
injuries and death
Refers to a potential hazard.
Nonobservance may result in serious injuries, or even fatal injuries and death
Refers to a potential hazard.
Nonobservance may result in light injuries.
Refers to a potential hazard.
Nonobservance may result in damage to the switch and/or to the plant.
Refers to important information essential to the user
| Disposal
The switch must be disposed of correctly in accordance with the local
regulations for electric/electronic equipment.
The switch must not be disposed of with the household garbage!
---|---
Standards
The standards applied during development, manufacture and configuration are listed in the CE conformity and manufacturer’s declaration.
Warranty/Guaranty
Our scope of delivery and services is governed by the legal warranties and
warranty periods.
Terms of guaranty
We guaranty for function and material of the dual pressure switch under normal
operating and maintenance conditions in accordance with the statutory
provisions.
Loss of guaranty
The agreed guaranty period will expire in case of:
- incorrect use,
- incorrect installation or
- incorrect handling or operation contrary to the provisions of these operating instructions.
No liability is assumed for any damage resulting therefrom, or any
consequential damage.
Refer to Barksdale “Standard Terms and Conditions“.
Installation
Jolts and heavy vibrations must be avoided during transport. Even if the
switch casing remains undamaged, inside parts may be damaged and cause
malfunctions.
The pressure switch may only be installed and electrically connected by
trained and instructed staff according state-of-the-art standards.
Electric shock and/or explosion!
Install the switch only in systems where the maximum pressure Pmax is not
exceeded (see type label). Only install the switch when deenergized
(electrically and hydraulically/pneumatically). Mount the pressure switch from
the bottom to the fitting using a wrench SW 27 and tighten it to a torque of
20 Nm.
The damping screw from brass installed in the pressure inlet can be removed if
required, e. g. soiled medium or material incompatibility, using a slotted
screwdriver (max. width 3 mm). Attention: Removing the damping screw will
reduce the resistance of the device against pressure peaks.
Electrical connection is to be carried out dependent on the type of switch
(see type label) according to the chart below. Wrong assignment of the
connections may cause malfunctions or incorrect switch outputs.
Electrical connection
Plug M 12×1 4/5/8-pin
| Model with 2 switching points| Model with 1 switching point and 1
analog output| Model with 2 switching points and 1 analog
output| Model with 2 switching points (relay contacts)
---|---|---|---|---
| Signal output code 1, 7| Signal output code 2, 3|
Signal output code 4, 5, 8|
Signal output code 6
1
| +Ub| +Ub| +Ub| +Ub|
2| SP2| Signal| Signal|
SP1a
| ****
NC
3
| OV| 0V| 0V| SP1b
4| SP1 / IO link1| SP1| SP1 / IO link1|
0V
5
| –| –| SP2| SP2a|
NO
6
| –| –| –|
SP2b
7
| –| –| –| –
8| –| –| –|
Housing
1 only code 7 and 8
Plug
Commissioning / Operation
The pressure switch may only be commissioned and operated by authorized
staff.
Hot surfaces!
During operation with higher temperatures the casing surface may become
very hot! Wear protective gloves!
Electric sho ck!
Do not put the switch into operation when the switch itself or the connection
cable is damaged.
After having been switched on the switch runs through a self-test. If
thesoftware recognizes an error during the self-test or during operation, this
is signaled in the display by “Err“ and the corresponding message, refer to
Error list on page 7. The red LEDs S1 and S2 signal the activity of the two
switching points.
Operation via three plastic film keys is menu-driven. ▲ , ▼ and
The keys may be damaged by pointed, hard objects. Do not use any pointed, hard
objects for making entries.
For information about the factory settings for the parameters and how to
change them please refer to the next chapter 8 “Programming“.
IO-link version
General information
This device features an IO-link communication interface which requires an IO- link capable module (IO-link master) for operation. The IO-link interface permits direct access to process and diagnostic data and offers the possibility of parametrising the device during operation. Moreover communication via a point-to-point connection using a USB adapter cable is possible.
Device-specific information
The IODDs required for the configuration of the IO-link device and detailed information about process structure, diagnostic information and parameter addresses are available at ->IODD finder and on https://www.barksdale.de/de/download/iolink/. To find the required information please enter the order code in the search mask. IO-link devices manufactured before 04-01 2019 do not support different polarities of the switching outputs.
: Since process connection, seal and measuring cell have no influence on
the IO-link communication you must replace them by “xx”. E.g. BPS38GVM0400BP =
BPS38xxM0400Bx
TIP: Use the autocomplete function of the IODD finder by entering the
article no. character by character. If your device has been manufactured
before 04-01-2019 please take into account that the proposed device ID begins
with 0x010.
Programming
Navigation function | Symbol (membrane key) |
---|---|
Menu descending | ▼ |
Menu ascending | ▲ |
Horizontal movement in menu, select menu item | M |
Parameter change ascending | ▲ |
Parameter change descending | ▼ |
Adopt parameter change and return to current menu item | M |
Return to measured value display | Press ▲+▼simultaneously |
Parameter
Parameter | 14-segment display | Description |
---|---|---|
SP1/SP21 |
| Hysteresis function: switching point of solid state contact
FH1/FH21| | Window function: Window High solid state contact
rP1/rP21| | Hysteresis function: hysteresis of solid state contact
FL1/FL21| | Window function: Window Low solid state contact
EF|
| Extended programming functions
rES|
| Reset parameters to factory settings
dS1/dS21| | Switching time delay – the set contact rating must be permanently
exceeded to trigger a switching function
dr1/dr21| | Switching time delay – the contact rating must be permanently
lower than the set contact rating to trigger a switching function
Ou1/Ou21| | Switching function of solid state contact
Hno| = hysteresis function, NO contact
HNC| = hysteresis function, NC contact
FNO| = window function, NO contact
FNC| = window function, NC contact
DIA| = diagnostic function, NO contact (only Ou2)
Pol 1/ Pol 2 3| | Select polarity of switching output: PP, NPN, PNP
uni| | Select unit: bar, PSI, MPa
If the measuring range is outside the display range, unit selection is
impossible. The parameter “uni“ is not displayed.
OuA2|
| Analog output
I| = 4… 20 mA
U| = 0… 10 V
I.INV| = 20… 4 mA
U.INV| = 10… V
ASP2|
| Analog start value
AEP2|
| Analog end value
dPA2|
| Damping of analog output
ErS.A2|
| Error signal of analog output Values: < 3.6 or > 22 or Off
Hi|
| Saved value of highest pressure measured
Lo|
| Saved value of lowest pressure measured
COF|
| Offset correction (max. 10 % of measuring range)
ddis|
| Damping display
Fdis|
| Rotate display through 180°
udiS|
| Unit indication
Firm|
| Firmware version
LocK|
| Software lock
1 only models with 2nd switching contact
2 only models with analog output
3 only IO-link devices
Error list
Parameter | 14-segment display | Description |
---|---|---|
sens |
| Sensor defect
SC1|
| Short circuit, solid state contact 1
SC2|
| Short circuit, solid state contact 2
AOut|
| Open output, short circuit
OL|
| Sensor limit positive
UL|
| Sensor limit negative
KEY|
| Internal defect
Menu Structure
1 only models with 2nd switching contact
2 only models with analog output (ASP = 0.0% – 80.0% range, AEP =20,0% – 100%
range; ASP = AEP – 20,% range)
3 setting according to measuring range
4 only IO-link devices
Software lock
Maintenance/Cleaning
Maintenance
The pressure switch requires no maintenance.
Risk of injury!
Check the switch for functioning at regular intervals.
If the switch does not work properly, stop operation immediately.
Cleaning
Material damage!
The devices may be damaged by the use of unsuitable cleaning agents.
The following cleaning agents can be used for cleaning polycarbonates:
– mild soapy water or detergent
– isopropyl alcohol
Rinse with water immediately after cleaning. No cleaning agent must remain on
the surface.
Clean the devices only at room temperature, never in direct sun light.
The following cleaning agents may impair the condition of components from
polycarbonate and shall not be used.
– ZEP Fast 505, Pinesol, Formula 409
– brake cleaner
– halogenated solvents
– strong alkaline solutions
– MEK (methyl ethyl ketone)
– abrasives (abrasive additives)
Decommissioning
Electric shock and/or explosion!
Only remove the switch when deenergized (electrically and
hydraulically/pneumatically).
Disconnection of the switch from pressure and power supply must be carried out
by trained or instructed personnel according to state-of-the-art standards.
Hot surfaces!
During operation with higher temperatures the casing surface may become very
hot! Wear protective gloves!
Barksdale Inc.
3211 Fruitland Avenue Los Angeles, CA 90058-0843 U.S.A.
Phone: 323-589-6181
Fax: 323-589-3463
e-mail: sales@barksdale.com
www.barksdale.com
Barksdale GmbH
Dorn-Assenheimer Straße 27 D-61203 Reichelsheim
Phone: +49 (6035) 949-0
Fax: +49 (6035) 949-111 and 949-113
e-mail: info@barksdale.de
www.barksdale.de