OH-1202H Universal Humidity Touchscreen Thermostat Instruction Manual
- June 15, 2024
- OH
Table of Contents
OH-1202H
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Universal Humidity Touchscreen Thermostat with Humidity/Dehumidity Control and
Automatic Heat/Cool Changeover Option
Single Stage, Multi-Stage, Heat Pump Installation and Operating Instructions
Programming Choices
7 Day| 5+1+1 Day| Non-Programmable
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
Thermostat Configuration Options| Thermostat Applications|
Maximum HeaVCool
---|---|---
Single Stage 1
No Heat Pump (SS1)| Gas, Oil, Electric, Heat Only, Cool Only or Heat/Cool
Systems, 2 or 3 wire Hydronic Zone (Hot Water or Steam) Systems, 24 Volt or
Millivolt| 1/1
Multi Stage 2
No Heat Pump (MS2)| 2/2
Heat Pump 1 Single Stage Compressor Heat Pump (HP1)| Single Stage Compressor
Heat Pump Systems – up to 2 Stages Aux./Emergency Heat| 3/1
Heat Pump 2 Two Stage or Two Compressor Heat Pump (HP2)| Two Stage or Two
Compressor Heat Pump systems – up to 2 Stages Aux./Emergency Heat| 4/2
SPECIFICATIONS
Electrical Rating:
Battery Power …………………….. mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire ……………………. 20 to 30 VAC
Terminal Load ……………………….. 1.5A per terminal, 2.5A maximum all terminals
combined
Setpoint Range ………………………. 45 to 99°F (7 to 37°C)
Rated Differentials: Fast. Slow
Heat (Single Stage/Multi-Stage) ………… 0.6°F 1.5°F
Cool (Single Stage/Multi-Stage) ………… 1.2°F 1.7°F
Heat Pump ………………………. 1.2°F 1.7°F
Emer Heat ………………………. 0.6°F 1.7°F
Operating Ambient…………………….. 32°F to +105°F (0 to +41°C)
Operating Humidity ……………………. 90% non-condensing max.
Shipping Temperature Range …………….. -40 to +150°F (-40 to +65°C)
Dimensions Thermostat…………………. 4-9/16″H x 5-13/16″W x 1-3/16″D
Humidity Setpoint Range ………………… 5 to 50%
Dehumidification Setpoint Range ………….. 40 to 95%
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power
to system at main fuse or circuit breaker box until installation is complete.
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this product may replace a
product that contains mercury.
Mercury and products containing mercury must not be discarded in household
trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean
up any spilled mercury and place in a sealed container. For proper disposal of
a product containing mercury or a sealed container of spilled mercury, place
it in a suitable shipping container. Refer to www.thermostat-recycle.org for
loca- tion to send the product containing mercury.
INSTALLATION
WARNING
Thermostat installation and all components of the control system shall
conform to Class II circuits per the NEC code.
Remove Old Thermostat
Before removing wires from old thermostat, mark wires for terminal
identification so the proper connections will be made to the new thermostat.
Installing New Thermostat
- Pull the thermostat body off the thermostat base. Forcing or prying on the thermostat will cause damage to the unit.
- Place base over hole in wall and mark mounting hole locations on wall using base as a template.
- Move base out of the way. Drill mounting holes. If you are using existing mounting holes and the holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure the base.
- Fasten base snugly to wall using mounting holes shown in Figure 1 and two mounting screws. Leveling is for appearance only and will not affect thermostat operation.
- Connect wires to terminal block on base using appropriate wiring schematic.
- Push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
- Carefully line the thermostat up with the base and snap into place.
Battery Location
2 “AA” alkaline batteries are included in the thermostat at the factory with a
battery tag to prevent power drainage. Remove the battery tag to engage the
batteries.
To replace batteries, set system to OFF, remove thermostat from wall and
install the batteries in the rear along the top of the thermostat (see Figure
1). For best results, use a premium brand “AA” alkaline battery such as
Duracell® or Energizer®. If the home is going to be unoccupied for an extended
period (over 3 months) and is displayed, the batteries should be replaced
before leaving.
Power Stealing Switches
The Power Stealing Switches (Fig. 1) should be left in the “On” position for
most systems. The information in the following table details the thermostat
power method and switch options.
Thermostat Power Method | Switch Position/Description |
---|---|
Battery Powered, no 24 Volt system power available. | Switches “On”, thermostat |
runs on batteries.
Hardwired with Battery Back-up, for 24 Volt systems with common connection
from transformer to “C” terminal on thermostat.| Switches “On”, thermostat
runs on power directly from transformer with battery backup.
*Battery Powered with Power Stealing Assist, for 24 Volt systems with no common connection from transformer to “C” terminal on thermostat.| Switches “On”, thermostat runs on batteries and supplemental power drawn through the heat or cool circuit.
*Power Stealing Assist is very reliable to increase battery life, but on a small number of heating or cooling systems with high impedance electronic modules you may observe one of the following conditions:
- The furnace draft inducer motor may run with no call for heat.
- The furnace fan may turn on with no call for heat or may not turn off.
- The furnace may not turn off when the call for heat ends.
- The air conditioner may not turn off when the call for cool ends.
If the Power Stealing Assist method is not compatible with your system, place the Power Stealing Switches to “Off”. This cancels Power Stealing Assist, operates the thermostat on batteries and corrects the condition.
WIRING DIAGRAMS
Figure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single Transformer
Single Stage and Multi-Stage Connections
Refer to equipment manufacturers’ instructions for specific system wiring
information.
This thermostat is designed to operate a single-transformer or twotransformer
system.
You can configure the thermostat for use with the following fossil fuel
systems:
SINGLE STAGE (SS 1) gas, oil or electric.
MULTI-STAGE (MS 2) gas, oil or electric.
After wiring, see INSTALLER CONFIGURATION section for proper thermostat
configuration.
Heat Pump Connections
If you do not have a heat pump system, refer to figures 3 & 4.
Refer to equipment manufacturers’ instructions for specific system wiring
information.
You can configure the thermostat for use with the following heat pump systems.
HEAT PUMP TYPE 1 (HP 1). Single stage compressor system; gas or electric
backup.
HEAT PUMP TYPE 2 (HP 2). Multi-stage compressor or two compressor system with
gas or electric backup.
After wiring, see INSTALLER CONFIGURATION section for proper thermostat
configuration.
Figure 4 – Humidity and Sensors
HM | DHM | + | S | – |
---|
Humidification Te rminal, Energizes on call for heat if Humidity setpoint is
above room humidity.
Can also be used to provide humidification independent of a call for heat
and/or in cooling mode if Automatic Humidification is selected in
Configuration Menu item #41| De-energizes on call for Dehumidification to
lower the fan speed. The DHM terminal is only used on systems with a
compatible dehumidification feature that have the required terminal connection
on the contol module or have a relay installed to lower the fan speed|
Supply voltage to remote temperature sensor| Remote temperature sensor
signal| Supply voltage to remote temperature sensor
Dehumidification wiring without an electronically controlled variable speed blower system for single stage compressor system only.
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed as shown in Fig 7 to switch the fan speed to the next lower speed on a call for dehumidification from the thermostat. The reduction in air flow allows the coil to remove more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti-freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks the compressor circuit when the suction line drops below 38 °F and re-make the circuit at 46°F.
Figure 5 – Typical Wiring for Dehumidifier System
THERMOSTAT QUICK REFERENCE
Home Screen Description
Programming and Configuration Items
-
Displays and “Keypad Lockout” when in keypad lockout mode.
Displays and “Temperature Limit” and “Keypad Lockout” when limited range is activated and locked.
Displays only “Temperature Limit” when limited range is activated. -
Indicates period of day being programmed.
-
RUN SCHEDULE (run program) key.
-
SET TIME key or HOLD temperature key.
-
Displays “Change Filter”/”Change Pad”/”Change UV Lamp” when the system has run for the programmed filter/humidity pad/UV lamp time period as a reminder to change or clean your filter/humidity pad or to replace UV lamp.
-
COPY key or INSTALLER CONFIG key.
-
CLEAN DISPLAY key allows 30 seconds to wipe off the display or ADVANCE DAY key for programming.
-
Used in programming to set time and in configuration menu to change selections.
-
“Hold Until” indicates the time when a temporary hold period will end.
-
“Hours” and “Days” displays during steps in installer configuration.
-
The words “Hold At” are displayed when the thermostat is in the HOLD mode. “Temporary Hold At” is displayed when the thermostat is in a temporary HOLD mode.
-
“Humidity” indicates that the “Set At” display is Humidity setpoint.
-
“System On” indicates when heating or cooling stage is energized. “+2” indicates when a second stage is energized.
-
“Copy” indicates the copy program feature is being used during programming.
Figure 9 – Programming & Configuration Items
-
A steady “Cool Savings” display indicates the feature is enabled in the installer menu. A flashing “Cool Savings” display indicates the feature is active.
-
“Remote” indicates that the indoor remote temperature sensor, is being accessed. “Outdoor Remote” indicates the outdoor remote temperature sensor is being accessed.
-
Display time, remote temperature or humidity.
-
“Heat Pump” displays when the system configuration is set in HP1/HP2.
-
Call for Service” indicates a fault in the heating/cooling systems. It does not indicate a fault in the thermostat.
-
Auto Schedule key for Auto Schedule function or Humidity key to display current Humidity and Humidity setpoint.
-
In Configuration Menu, shows screen number.
INSTALLER/CONFIGURATION MENU
To enter the menu: Press the Menu touch key. Press and hold for 5 seconds the
Installer Config touch key. This displays screen reference #1 in the table
below. Screen Reference numbers appear in top right corner of display. Press
to advance to the next menu item or to return to a previous menu item. Press
or to change a menu item option. Shaded items are
not available if selected for Non-Programmable. Write the options selected in
the “Option Selected” column of the menu.
Installer Note: To default the programming, clock and Configuration Menu
to the Factory Default Settings, press the , and SYSTEM keys simultaneously.
The thermostat display will go blank for a few seconds, and then all segments
will display momentarily. For heat pump systems, Configuration Menu items 1
and 3 must be set to match the heat pump system.
CONFIGURATION MENU
Screen Reference Number| SS1 MS2| HP1 HP2| Press
key
| Displayed Factory (Default)| Press or to select from listed options|
Comments| Option Selected
1| ⚫| ⚫| **| MS 2| HP 1, HP 2, SS 1| Selects Multi-Stage (MS2,
No Heat Pump), Heat Pump 1 (HP1, 1 compressor), Heat Pump 2 (HP2, 2 compressor
or 2 speed compressor), or Single Stage.|
2| ⚫| ⚫| **| (GAS)| ELE| GAS setting: furnace controls blower.
ELE setting: thermostat controls blower.|
3| | ⚫| **| 0b (0)| b| Selects Reversing Valve (This item is only to
appear if HP1 or HP2 is selected above.)|
4| ⚫| ⚫| **| Days, (7) P| 5 or 0| Programs per
week. (7 days, 5+1+1 days or non-programmable)|
5| ⚫| ⚫| **| (4) PS| 2**| Programs per day.
4 = Morning, Day, Evening, Night 2 = Day, Night
Not available if 4 is 0
|
6| ⚫| | **| Cool-Off- Heat-Auto| Cool-Off-Heat, Heat Off, Heat, Cool-
Off, Auto Off| System switch configuration in non heat pump mode.|
| ⚫| **| Cool-Off-Heat- Em-Auto| Cool-Off-Heat-Em, Off-Em-Auto|
System switch configuration, heat pump mode.
7| ⚫| ⚫| **| (On) E| OFF| Selects Energy Management
Recovery. Not available if 4 is 0|
8| ⚫| ⚫| **| (FA) Heat, Cr| SL| Selects Adjustable Anticipation,
cycle rate, Heat|
9| ⚫| ⚫| **| (FA) Cool, Cr| SL| Selects Adjustable Anticipation,
cycle rate, Cool|
10| | ⚫| **| (FA) Cr/AU, Em| SL| Selects Adjustable Anticipation,
cycle rate auxiliary, (This item is only to appear if HP1 or HP2 is selected
above).|
11| ⚫| ⚫| **| (OFF) CL| On| Selects Compressor Lockout.|
12| ⚫| ⚫| **| (On) dL| OFF| Selects Continuous Display
backlight.|
13| ⚫| ⚫| ****| 0
(Temperature)
| 5, LO to 5, HI| Selects Adjustable Ambient Temperature Display [range -5
(LO) to +5 (HI)].|
14| ⚫| ⚫| **| °F| °C| Selects °F/°C Display
(temperature units in Fahrenheit or Celsius).|
15| ⚫| ⚫| **| (On) b| OFF| Selects audible Beeper On/Off.|
16| ⚫| ⚫| **| (On) dS| OFF| Selects Daylight Saving Time
calculation.|
17| ⚫| ⚫| **| (On) Heat, AS| OFF| Selects Automatic Schedule
for comfort temperature Programming, heat mode. Not available if 4 is 0|
18| ⚫| ⚫| **| (On) Cool, AS| OFF| Selects Automatic Schedule
for comfort temperature Programming, cool mode. Not available if 4 is 0|
19| ⚫| | **| (OFF) CS| On| Selects Cool Savings Feature On of
Off.|
20| ⚫| ⚫| **| CS Cool Savings (3)| 1-2-3-4-5-6| Selects
amount of Cool Savings adjustment.|
21| ⚫| ⚫| **| (Off) CO| On| Select Compressor Optimization
(not available on earlier models)|
22| ⚫| ⚫| **| (OFF) CA| On| Selects Comfort Alert Feature On or
Off. (not available on earlier models)|
23| ⚫| ⚫| **| (99) Heat, HL| 62-98| TEMPERATURE LIMIT, HEAT
(max. heat set point).|
24| ⚫| ⚫| **| (45) Cool, LL| 46-82| TEMPERATURE LIMIT, COOL
(min. cool set point).|
25| ⚫| ⚫| **| OFF,
Keypad Lockout
| L (total), P (partial), Temperature Limit (limited temperature
range)| Selects Keypad Lockout.|
26| ⚫| ⚫| **| 000| 001-999| Selects Keypad Lockout Combination
(active only if keypad Lockout is selected).|
27| ⚫| ⚫| **| (On) Heat, FS| OFF| Fast second stage of heat (not
available if SS1 is selected above).|
28| ⚫| ⚫| **| (On) Cool, FS| OFF| Fast second stage of cool (not
available if SS1 or HP1 is selected above).|
29| ⚫| ⚫| **| Remote (OFF)| On| Remote temperature sensor,
enable/disable.|
30| ⚫| ⚫| **| Remote, In| Outdoor Remote| Remote temperature
sensor (Indoor/Outdoor).|
31| ⚫| ⚫| **| (On) LS| OFF| Local temp. Sensor enable/disable
(only when Indoor Remote is selected On).|
32| | ⚫| **| (OFF) dF| On| Selects Dual Fuel feature On or OFF (this
item appears if HP1 or HP2 is selected above).|
33| | ⚫| **| (35) dF| -5 – 50| Selects Dual Fuel setpoint (°F), dF
selected On with outdoor sen- sor available.|
---|---|---|---|---|---|---|---
34| | ⚫| | (05) dF| 0 – 09| Selects Dual Fuel setpoint (°F), dF selected
On with no outdoor sensor.|
35| | ⚫| **| (60) Cd| 0-99| Selects compressor off delay in seconds,
dF selected On|
36| | ⚫| **| (80) AO| -5 – 79| Selects Auxiliary Heat cut out
temperature. This item appears if HP1 or HP2 is selected and outdoor sensor is
installed and enabled.|
37| | ⚫| **| (80) bP| 79-20| Selects Blower balance point. Selection
of 80 disables this feature. This item appears if HP1 or HP2 is selected and
outdoor sensor is installed and enabled.|
38| ⚫| ⚫| **| (OFF) Hd| On| Selects Humidity Display alternate
with time.|
39| ⚫| ⚫| ****| Humidity 00 (Room Humidity)| -20 LO
20 HI
| Selects Humidity Display adjustment.|
40| ⚫| ⚫| **| (OFF) HR| LO, HI| Selects Auto Humidity
reduction.|
41| ⚫| ⚫| **| (OFF) AH| H, C, A| Selects Automatic
Humidification.|
42| ⚫| ⚫| **| (OFF) CH| On| Selects Cycle Humidifier.|
43| ⚫| ⚫| **| OC (0)| od, OFF| Selects Optimum Comfort or
Optimum Dehumidification or Off.|
44| ⚫| ⚫| **| (OFF) Change UV Lamp| On| Selects Change UV Lamp
feature.|
45| ⚫| ⚫| **| 350 Days| 25-1975| Change UV Lamp duration days.|
46| ⚫| ⚫| ****| (OFF)
Change Pad
| On| Selects Change Humidifier Pad feature.|
47| ⚫| ⚫| **| 100 Hrs| 25-1975| Change Humidifier Pad duration
hours.|
48| ⚫| ⚫| **| OFF
Change Filter
| On| Selects Change Filter feature.|
49| ⚫| ⚫| ****| 200 Hrs| 25-1975| Change Filter duration hours.|
-
This control can be configured for:
MS2 – Multi-Stage System (2 heat/2 cool)
HP1 – Heat Pump with one stage of compressor (2 heat/1 cool)
HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup; (Dual Fuel see screen reference number 33) (4 heat/2 cool)
SS1 – Single Stage System (3 wire zone see wiring diagrams. -
GAS or Electric (ELE) fan operation. If the heating system requires the thermostat to energize the fan, select ELE. Select GAS if the heating system energizes the fan on a call for heat. Note: Resetting the thermostat switches the option to GAS.
-
O/B Terminal selection – Selects the operation of the reversing valve (when item 1 is set to HP1 or HP2 only).
When set to “O” the changeover valve will be energized in COOL to accommodate the majority of heat applications. If the heat pump requires the changeover valve to energize in HEAT, select “B”. -
Programs per week – This control can be configured for 7 independent day or 5+1+1 day programming or nonprogrammable modes.
Default is 7-day mode.
The display indicates “7 Days” as default. Other options “5 Days” or “0 Days” can be selected. If “0 Days” is selected for nonprogrammable mode, the step for EMR will be skipped, as this feature will not be available in this mode. -
Program Steps per day – Not available if configured for non-programmable. This control can be configured for 4 or 2 program steps per day. Default is “4 PS” and can be toggled between 4 PS and 2 PS.
-
System Switch Configuration (MS2/SS1) – This thermostat is configured for Heat and Cool with Auto changeover default (Cool-Off-Heat-Auto). It can be configured as Heat & Cool (Cool-Off-Heat), or Heat Only (Off-Heat), or Cool Only (Cool-Off).
When the control is in heat pump configuration (HP1/ HP2), the system switch configuration will have an additional mode, Em for Emergency. -
Energy Management Recovery (EMR) – (this step is skipped if configured as non-programmable). When set to “On” causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify.
Example: The heating program is 65°F at night and 70° at 7 AM. If the building temperature is 65°F, the difference is 5°F. Allowing 5 minutes per °F rise, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per °F, because it takes longer to reach temperature. -
9 & 10. Cycle Rate Selection – The factory default setting is fast cycle (FA Cr) in all modes (Heat, Cool, Em). To change to slow cycling (SL, Cr), press touch keys or toggle between FA & SL. The cycle rates are below:
Mode| Med| Slow
---|---|---
Heat| 0.6°F| 1.5°F
Cool| 1.2°F| 1.7°F
Heat Pump| 1.2°F| 1.7°F
Emer Heat| 0.6°F| 1.7°F -
Select Compressor Lockout (CL) – Selecting (CL On) will cause the thermostat to wait 5 minutes between cooling cycles.
This is intended to help protect the compressor from short cycling. Some of the newer compressors have
OPERATING YOUR THERMOSTAT
Check Thermostat Operation
NOTE
To prevent static discharge problems, touch side of thermostat to release
static build-up before touching any keys.
If at any time during testing your system does not operate properly, contact a
qualified service person.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
- Turn on power to system.
- Press FAN key to ON position. The blower should begin to operate.
- Press FAN key to AUTO position. The blower should stop immediately.
CAUTION
Do not allow the compressor to run unless the compressor oil heaters have been
operational for 6 hours and the system has not been operational for at least 5
minutes.
Heating/Humidifier
-
Press SYSTEM key to select HEAT. If the auxiliary heating system has a standing pilot, be sure to light it.
-
Press to adjust thermostat setting to 1° above the room temperature. The heat pump system should begin to operate. The display should show “System On”. However, if the system configuration is set to HP1 or HP2 and setpoint temperature display is flashing, the 5 minute compressor lockout feature is operating (see Configuration menu, item 11).
-
Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP1 or HP2, the auxiliary heat system should begin to operate and the display will show “System On +2”. -
Press to adjust the thermostat below room temperature.
The heating system should stop operating.
To check the humidifier when System On appears and the heating system is
running press the HUMIDITY button once.
Press to adjust the humidity 2% or more above the room humidity level setpoint
range. (Humidity setpoint can be adjusted from 5 to 50%.) Hum On will appear
indicating it is calling for the humidifier.
Note: If Auto Schedule is displayed instead of Humidity, Auto Schedule must be turned off in the Configuration Menu.
CAUTION
To prevent compressor and/or property damage, if the outdoor temperature is
below 50°F, DO NOT operate the cooling system.
Cooling/Dehumidifier
-
Press SYSTEM to select “Cool”.
-
Press to adjust the thermostat setting below room temperature.
The blower should come on immediately on high speed, followed by cold air circulation.
The display should show “System On”. If the setpoint temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 11). -
Adjust temperature setting to 3° below room temperature.
The second stage cooling should begin to operate and the display should show “System On +2”. -
Press to adjust the temperature setting above room temperature. The cooling system should stop operating. To check the dehumidifier when System On appears and the cooling system is running press HUMIDITY* button once. Press to adjust the humidity 2% or more below the room humidity level setpoint range. DeHum On will appear indicating it is calling for the dehumidification.
If the room humidity is lower than the adjustment range, press to 40% and hold it for four seconds.
This will force the DeHum On for one complete cooling cycle to test the dehumidification equipment.
After adjusting the humidity setting the display will return to temperature in approximately 10 seconds.
To switch the display back to temperature immediately after adjusting humidity setting press HUMIDITY again.
*Note: If Auto Schedule is displayed instead of Humidity, Auto Schedule must be turned off in the Configuration Menu.
Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the fan only when the
heating or cooling system is on.
Fan On selection runs the fan continuously for increased air circulation or to
allow additional air cleaning.
Tip: Running the fan more frequently will increase your energy consumption.
Most systems use a 1/2 or 1/3 HP electric motor to power the fan.
Choose the System Setting (Cool, Off, Heat, Em, Auto)
Press the SYSTEM key to select:
Cool: Thermostat controls only the cooling system.
Off: Heating and Cooling systems are off.
Heat: Thermostat controls only the heating system.
Em: Setting is available only when the thermostat is configured in HP1 or HP2
mode.
Auto: Auto Changeover is used in areas where both heating and cooling may be
required on the same day.
AUTO allows the thermostat to automatically select heating or cooling
depending on the indoor temperature and the selected heat and cool
temperatures.
When using AUTO, be sure to set the Cooling temperatures more than 1°
Fahrenheit higher than the heating temperature.
Manual Operation for Non-Programmable Mode
Press the SYSTEM key to select “Heat” or “Cool” and use the keys to adjust the
temperature to your desired setting.
After selecting your desired settings you can also press the SYSTEM key to
select AUTO to allow the thermostat to automatically change between “Heat” and
“Cool”.
Manual Operation (Bypassing the Program)
Programmable Mode
Manual operation will bypass the program and allow you to adjust the
temperature as you desire. The temperature you set in Hold will be maintained
indefinitely. Press or to adjust the temperature. The HOLD key will appear.
Press the HOLD key. “Hold At” will appear next to the setpoint temperature and
the thermostat will maintain the new setpoint temperature until Run Schedule
is pressed to resume pro- gram operation.
Program Override (Temporary Override)
Press or keys to adjust the temperature. This will override the temperature
setting for a (default) four hour override period.
The override period can be shortened by pressing or lengthened by pressing .
Program Override period can range from 15 minutes to 7 days.
Example: If you turn up the heat during the morning program, it will be
automatically lowered later, when the temporary holdperiod ends. To cancel the
temporary setting at any time and return to the program, press Run Schedule.
If the SYSTEM key is pressed to select AUTO the thermostat will change to
“Heat” or “Cool”, whichever ran last. If it switches to “Heat”, but you want
“Cool”, or it changes to “Cool”, but you want “Heat”, press both keys
simultaneously to change to the other mode.
PROGRAMMING
Set Current Time and Day
- Press Menu key to enter installer menu. Then press Set Time once to indicate hour & AM or PM designation in clock display.
- Press and hold either the or touch key until you reach the correct hour and AM or PM designation.
- Press Set Time again to display minutes only in clock display.
- Press and hold either the or touch keys until you reach the correct minutes.
- Press Set Time once again to display year.
- Press either the or touch key until you reach the correct year.
- Press Set Time once again to display month.
- Press either the or touch key until you reach the correct month.
- Press Set Time once again to display date of the month along with day of the week at top row (which is automatic).
- Press and hold either the or touch key until you reach the correct day of the month and day of the week displayed at the top row.
- Press Run Schedule once or twice to remove the key.
Now the display will show the correct time and room temperature.
Automatic Daylight Saving Calculation
The Real Time Clock will adjust automatically for daylight savings time, in
the following manner:
Increment one hour at 2 AM on the second Sunday of March and decrement one
hour at 2 AM on the first Sunday of November.
The daylight saving feature can be enabled or disabled in installer
configuration menu. Default is DS ON (enabled).
After entering installer configuration mode, momentarily press touch key until
the display indicates dS (in actual temperature digits) and on (default – in
clock digits). and keys will toggle display and operation from on to OFF.
Programming Tip: Copy Program
When programming your thermostat, you may copy the program from one day to
another day or group of days using the Copy key. In 7 day programming mode, a
day can be copied to another day or all six other days. In 5+1+1 day
programming mode the weekday (Mon – Fri) program can be copied into Sat and
Sun or either Sat or Sun.
To copy a program from one day to another:
- In Set Schedule mode, enter the program for the day or select the day you wish to copy by pressing Advance Day.
- Press Copy. The display will show “Copy” next to the SYSTEM key and the day of the week that will be copied.
- Press Advance Day. The day being copied will be indicated and the other days will be flashing.
- If you wish to copy to all days skip to next step or press Advance Day until the day you wish to copy to is flashing.
- Press Copy. “Copy” will disappear, the day you copied from will disappear and the day(s) you copied to will be on.
- If you wish to copy this same program into other days, press Copy and repeat steps 3, 4 and 5.
- Press Run Schedule to return to normal operation.
Fill in the blank schedule on the next page then:
Enter the Heating Program
-
Press the Menu key and then press Set Schedule. Press SYSTEM key to select “Heat” in the system switch area indicating the active mode being programmed. You can switch to the other mode by pressing the system switch at any time.
-
The top of the display will show the day(s) being programmed.
The time and set at temperature are also displayed.
“Morning” will also be displayed to indicate the period. -
Press or key to change the temperature to your selected temperature for the 1st heating period (Morning).
-
Press or key to adjust the start time for period.
The time will change in 15 minute increments. -
Press FAN to select Auto or Prog.
-
After you have set the time and the temperature for the period to begin, press Set Schedule to advance to the next program period.
-
Repeat steps 2 through 6 until all of the program times and temperatures are set for all program periods on that day.
-
Press “Advance Day” to change to the next day and repeat steps 2 through 8.
-
When programming is complete and all of the times and temperatures match your desired heating schedule, press Run Schedule. The thermostat will now run your program.
Enter the Cooling Program
- Press the SYSTEM key until the “Cool” icon appears.
- Follow Enter Heating Program instructions for entering cooling times and temperatures.
Automatic Schedule
Auto Schedule Heat is a fast way to program all the heating temperatures
during the day to a comfortable temperature and then lower the temperature 6°
at night. Auto Schedule Cool will program all of the cooling time periods to
the same temperature.
Note: Auto Schedule is available only when the thermostat is first
powered on, after the thermostat has been reset, or anytime you turn AS on in
the Configuration Menu (item 17 AS Heat or 18 AS Cool). After use in heating
and cooling, Auto Schedule on the display will change to Humidity.
Heating Example:
- In Heat mode, press Auto Schedule once.
- Press or to select a comfortable day time temperature (example 72°).
- Press Auto Schedule again. Your thermostat is now programmed for 72° from 6:30 AM until 10:30 PM at 72°. At 10:30 PM, your thermostat will set back 6° to 66°.
Your heating program for each day of the week will look like this:
6:30 | 72° |
---|---|
8:00 | 72° |
5:00 | 72° |
10:30 | 66° |
Programmable Fan Option
In the Set Schedule mode, the Fan key is used to select the fan operation
during a program period. The default state of the Fan key is FAN Auto (fan
runs during a call for cool but not on a call for heat). It can be changed to
FAN Prog (fan runs during a program period). Each press of the FAN key will
change the mode of the fan between Auto and Prog. In the Run mode, when a
program period that has FAN Prog begins, the fan will turn on and stay on
during the complete period. The display will show FAN On Prog. Pressing the
FAN key will change FAN On Prog to On (fan running continuously) or Auto.
To return to FAN On Prog, press Run Schedule.
Energy Saving Factory Pre-Program
This thermostat is programmed with the energy saving settings shown in the
table below for all days of the week. If this program suits your needs, simply
set the thermostat clock and press the RUN key. The table below shows the
factory set heating and cooling schedule for all days of the week.
| Wake Up| Leave For Work| Return Home| Go To Bed
---|---|---|---|---
| (Morning)| (Day)| (Evening)| (Night)
Heating Program| 6:00 AM| 70°F| 8:00 AM| 62°F| 5:00 PM| 70°F| 10:00 PM| 62°F
Cooling Program| 6:00 AM| 75°F| 8:00 AM| 83°F| 5:00 PM| 75°F| 10:00 PM| 78°F
-
You can eliminate these two program periods in the configuration menu (reference #5) if the building is occupied all day.
Day period will change to 6:00 AM and 70° and can be programmed as required.
Planning Your Program – Important
The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
The thermostat comes configured for 7 day programming and can also be configured for 5+1+1 programming (see configuration section).
Factory settings are listed on Monday, Saturday and Sunday. If you are re- programming a 5+1+1 day schedule, pencil in your own times and temperatures directly below the factory times and temperatures.
If you are re-programming a 7 day schedule, fill in all lines with the times and temperatures you want.
Keep the following guidelines in mind when planning your program.- In Heating, lower temperatures will save energy.
- In Cooling, higher temperatures will save energy.
- If you plan on using Auto Changeover, do not program the heating temperature higher than the cooling temperature.
Worksheet for Re-Programming 5+1+1 and 7 Day Program
Heating
Program| Wake Up (Morning) Fan| Leave For Work
(Day) Fan| Return Home (Evening) Fan| Go To Bed
(Night)
Fan
---|---|---|---|---
MON| 6:00 AM| 70- F| Auto| 8:00 AM| 62- F| Auto| 5:00 PM| 70°F| Auto| 10:00
PM| 62°F| Auto
| | | | | | | | | | |
TUE| | | | | | | | | | | |
WED| | | | | | | | | | | |
THU| | | | | | | | | | | |
FRI| | | | | | | | | | | |
SAT| 6:00 AM| 70°F| Auto| 8:00 AM| 62°F| Auto| 5:00 PM| 70°F| Auto| 10:00 PM|
62°F| Auto
| | | | | | | | | | |
SUN| 6:00 AM| 70°F| Auto| 8:00 AM| 62°F| Auto| 5:00 PM| 70°F| Auto| 10:00 PM|
62°F| Auto
| | | | | | | | | | |
| | | | | | | | | | | |
Cooling
Program| Wake Up (Morning) Fan| Leave For Work
(Day) Fan| Return Home (Evening) Fan| Go To Bed
(Night)
Fan
MON| 6:00 AM| 75`F| Auto| 8:00 AM| 83 F| Auto| 5:00 PM| 75 F| Auto| 10:00 PM|
78°F| Auto
| | | | | | | | | | |
TUE| | | | | | | | | | | |
WED| | | | | | | | | | | |
THU| | | | | | | | | | | |
FRI| | | | | | | | | | | |
SAT| 6:00 AM| 75°F| Auto| 8:00 AM| 83°F| Auto| 5:00 PM| 75°F| Auto| 10:00 PM|
78°F| Auto
| | | | | | | | | | |
SUN| 6:00 AM| 75°F| Auto| 8:00 AM| 83°F| Auto| 5:00 PM| 75°F| Auto| 10:00 PM|
78°F| Auto
| | | | | | | | | | |
Wired Remote Temperature Sensing
One remote temperature sensor can be installed indoor or outdoor and connected
to the thermostat by a maximum cable length of 100 meters (300 feet).
Terminals +, S and – on the terminal block allow connection of the remote
sensor. The thermostat must have 24 VAC Common connection to terminal C for
the remote sensor to operate. The remote sensor can be enabled or disabled in
the Installer/Configuration menu, item 29.
When remote sensor, Remote, is selected Off (factory de-fault), no remote
sensor is enabled. When remote sensor is selected On, the next step is to
select the remote as indoor, Remote In, or outdoor, Outdoor Remote. If the
remote is selected as Remote In, an additional step will be to select if the
temperature shown on the display will be from the thermostat, LS On, or the
remote sensor LS Off.
In normal operation, when a remote sensor is enabled the time digits of the
display will alternate between the time and the remote temperature for three
seconds each. Above the remote temperature will be Remote, for indoor sensor
or Outdoor Remote, for outdoor sensor. If the remote sensor is an indoor
sensor and the local display has been disabled, the temperature displayed as
the room temperature will be the remote sensor temperature. Sensing Range:
Outdoor temperature range is -40 o F to 140 o F Indoor temperature range is 32
°F to 99 °F
Averaging or Weighting Remote Sensors
The thermostat will weight or average the temperature of the indoor remote
sensor with the local sensor in the thermostat for each program period. The
averaging will be active only when the local sensor and the indoor remote
sensor are both functional and enabled in the Installer/Configuration menu.
When the thermostat is in the Set Schedule mode, the weight of the indoor
sensor will be shown in the current temperature digits of the display. The
weight will show as A2 (average and default), H4 (high) or L1 (low). Pressing
the and keys at the same time will change the weight for the program period.
The weight of the thermostat sensor is fixed. In normal operation of the
thermostat, the current temperature displayed will be the weighted average of
the local sensor and the remote sensor using the formula (local sensor weight
x local sensor temperature) + (remote sensor weight x remote sensor
temperature) / (local sensor weight + remote sensor weight).
Example: Local sensor temperature is 80° and the remote sensor is 70°.
If weight is selected H4, the averaged temperature of 72° will be displayed.
(1 x 80) + (4 x 70) / 5 = 72°
If weight is selected A2, the average temperature of 73° will be displayed. (1
x 80) + (2 x 70) / 3 = 73.3°
If weight is selected L1, the average temperature of 75° will be displayed. (1
x 80) + (1 x 70) / 2 = 75°
The example shows that the weight selected would prioritize the overall
averaged temperature between the two sensors.
The high weight selection caused the remote sensor to have a higher influence
in the calculated temperature average than the local sensor and the low weight
selection caused the remote sensor to have less influence.
Dual Fuel Temperature Setpoint
When the thermostat is configured for Heat Pump mode and the Dual Fuel feature
is selected on, the thermostat can monitor the outside temperature using
remote sensor F145-1378 or use software logic to determine when to switch to
gas heat and shut down the compressor.
This eliminates the need for a fossil fuel kit.
The user selectable temperature is called the dual fuel temperature setpoint,
dF and is set in the Installer/Configuration menu, items 33 or 34.
With outdoor remote sensor installed and enabled, the dual fuel temperature
setpoint (menu item 33) can be set to a temperature of -5° through 50°.
When outdoor remote sensor is not installed, a software logic based dual fuel
number (menu item 34) from 01 to 09 can be selected. A higher temperature or
dual fuel setting will provide a smaller stage separation between the heat
pump and Aux to give more comfort. A lower temperature or number will provide
a larger stage separation for more economy.
After the dual fuel temperature setpoint is set and is pressed, a delay, Cd,
can be set for compressor shutdown after the auxiliary stage is energized.
This delay can be set from 0 seconds to 99 seconds to minimize the time that
the system may blow cooler air until the alternate source of heat comes on.
Default setting for delay is 60. When setting the delay, if the or keys are
held depressed, the setpoint will increase or decrease at the rate of one
degree every half second for the first three seconds and double the speed
after three seconds.
Blower Balance Point for Heating
Requires DHM connection from thermostat to heat pump system. Air to air heat
pumps use a fast fan speed to circulate warm air for first stage heating. As
outdoor temperatures drop, the heat pump produces less heat and a high fan
speed makes the air from the ducts feel cooler. Blower Balance Point allows
you to select an outdoor temperature to slow the fan speed so the air from the
duct feels warmer. Select an outdoor temperature where the air from the ducts
starts to feel cool (Installer Configuration Menu item 37). When the outdoor
temperature drops to the selected temperature, the thermostat will slow the
fan speed so the outlet air feels warmer.
TROUBLESHOOTING
Comfort Alert Codes The Comfort
Alert diagnostics product monitors the air conditioning outdoor systems with
single phase Copeland Scroll compressors. Abnormal system and electrical
conditions are indicated by flashing ALERT codes on the yellow LED on the
Comfort Alert module. The flash codes are transmitted to the thermostat by the
Comfort Alert Thermostat interface module. The Comfort Alert compatible
thermostat displays “Call For Service” that flashes at the same rate as the
yellow LED on the Comfort Alert module.
Comfort Alert Codes
1 Flash | Long run time |
---|---|
2 Flashs | System pressure trip |
3 Flashs | Short cycling |
4 Flashs | Locked rotor |
5 Flashs | Open circuit |
6 Flashs | Open start circuit |
7 Flashs | Open run circuit |
8 Flashs | Welded Contactor |
9 Flashs | Low voltage |
Reset Operation
Note: If a voltage spike or static discharge blanks out the display or causes
erratic thermostat operation, you can reset the thermostat by removing the
thermostat from the wall plate and removing batteries for 2 minutes. After two
minutes, replace the batteries and replace thermostat on wall plate. If the
thermostat has been reset and still does not function correctly contact your
heating/cooling service person or place of purchase.
Symptom | Possible Cause | Corrective Action |
---|---|---|
No Heat/No Cool/No Fan (common problems) | 1.Blown fuse or tripped circuit |
breaker.
2.Furnace power switch to OFF.
3.Furnace blower compartment door or panel loose or not properly installed.
4.Loose connection to thermostat or system.| Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety interlock or door
switch.
Tighten connections.
No Heat| 1.Pilot light not lit.
2.Furnace Lock-Out Condition. Heat may also be intermittent.
3.Heating system requires service or thermostat requires replacement.| Re-
light pilot.
Many furnaces have safety devices that shut down when a lock-out condition
occurs. If the heat works intermittently contact the furnace manufacturer or
local HVAC service person for assistance.
Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room
temperature. Within a few seconds the thermostat should make a soft click
sound. This sound usually indicates the thermostat is operating properly. If
the thermostat does not click, try the reset operation listed above. If the
thermostat does not click after being reset contact your heating and cooling
service person or place of purchase for a replacement. If the thermostat
clicks, contact the furnace manufacturer or a HVAC service person to verify
the heating is operating correctly.
No Cool| 1. Cooling system requires service or
thermostat requires replacement.| Same as diagnostic for No Heat condition
except set the thermostat to COOL and lower the setpoint below the room
temperature. There may be up to a five minute delay before the thermostat
clicks in Cooling.
Heat, Cool or Fan Runs Constantly| 1.Possible short in wiring.
2.Possible short in thermostat.
3.Possible short in heat/cool/fan system.
4.FAN Switch set to Fan ON.| Check each wire connection to verify they are not
shorted or touching together. No bare wire should stick out from under
terminal block. Try resetting the thermostat as de-scribed above. If the
condition persists the manufacturer of your system or service person can
instruct you on how to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
Thermostat Setting & Thermostat Thermometer Disagree| 1. Thermostat
thermometer setting requires adjustment.| The thermometer can be adjusted +/-
4 degrees. See Temperature Display Adjustment in the Configuration Menu
section.
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide
temperature swing)| 1. The location of the thermostat and/or the size of the
Heating System may be influencing the cycle rate.| Digital thermostats provide
precise control and cycle faster than older mechanical models. The system
turns on and off more frequently but runs for a shorter time so there is no
increase in energy use. If you would like
an increased cycle time, choose SL for slow cycle in the Configuration menu,
step 7 (heat) or 8 (cool). If an acceptable cycle rate is not achieved,
contact a local HVAC service person for additional suggestions.
Forgot Keypad Lockout Code| | Press the menu key (key will disappear) and hold
in for 20 seconds. This unlocks the thermostat.
Blank display any or keypad not responding| 1. Voltage Spike or static
discharge| Use the Reset Operation shown above.
ONE HOUR HELP LINE: 1-888-616-0030
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>