Schneider Electric XB4BP-BW Push Test Pilot Light Instruction Manual

June 15, 2024
Schneider Electric

Schneider Electric XB4BP-BW Push Test Pilot Light

List of Standards

  • UL 60079-0, 6th Edition, Explosive atmospheres – Part 0: Equipment – General requirements – Revision Date 2017/10/20;
  • UL 60079-1, 7th Edition, Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures “d” – Issue Date 2015/09/18;
  • UL 60079-7, 5th Edition, Explosive Atmospheres – Part 7: Equipment Protection by Increased Safety “e” – Revision Date 2017/04/21;
  • UL 60079-18, 4th Edition, Explosive Atmospheres – Part 18: Equipment Protection by Encapsulation “m” – Revision Date 2017/02/20;
  • UL 60079-31, 2nd Edition, Explosive Atmospheres – Part 31 : Equipment Dust Ignition Protection by Enclosure “t” – Issue Date 2015/06/12;
  • CSA C22.2 No. 60079-0:15, Explosive atmospheres – Part 0: Equipment – General requirements – Edition 3 – Issue Date 2015/10;
  • CSA C22.2 No. 60079-1:16, Explosive Atmospheres – Part 1: Equipment Protection by Flameproof Enclosures “d” – Edition 3 – Issue Date 2016/05;
  • CSA C22.2 No. 60079-7:16, Explosive Atmospheres – Part 7: Equipment Protection by Increased Safety “e” – Edition 2 – Issue Date 2016/10;
  • CSA C22.2 No. 60079-18:16, Explosive Atmospheres – Part 18: Equipment Protection by Encapsulation “m” – Edition 2 – Issue Date 2016/08.
  • CSA C22.2 No. 60079-31:15, Explosive Atmospheres – Part 31: Equipment Dust Ignition Protection by Enclosure “t” – Edition 2 – Issue Date 2015/10;

Control and signaling units

  • Ex db eb mb IIC Gb – Ex tb IIIC Db – IP65
  • GB/T 3836.1-2021
  • GB/T 3836.3-2021
  • GB/T 3836.9-2021
  • GB/T 3836.31-2021
  • EC type-examination certificate INERIS:

Technical Considerations

  • EN/IEC 60079-0
  • EN/IEC 60079-7
  • EN/IEC 60079-18
  • EN/IEC 60079-31

Use of these devices must be solely limited to the function of the control and/or signaling unit. These devices must be installed, used, and maintained by:

  • Standard EN/IEC 60079-14 (Explosive atmospheres), part 14 (Electrical installations design, selection and erection).
  • Standard EN/IEC 60079-17 (Explosive atmospheres), part 17 (Electrical installations inspection and maintenance).
  • Standard NF C 15 100 (Low voltage electrical installations) – European equivalent: IEC 60364.
  • Regulations governing the setup of the zone or zones for which the devices were designed. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

Special conditions for safe use
During the installation, the user will take into consideration that the operator head of the metallic Push button assemblies, Cat. no. XB4B… and the operator head of the metallic LED pilot light assemblies, Cat. no. XB4BV… underwent only a shock corresponding to an energy of a low risk. The contact block type ZBE has to be integrated into an enclosure protected by a recognized type of protection adapted to the area.

Liability for manufacturer traceability (serial number specified on the certification label) is ensured at the first known delivery destination.

Characteristics : Illuminated pushbutton Push-to-test pilot light
XB4BP…BM5GEX XB4BW…BM5GEX
LED voltage 24…254 V
Light source Integrated LED
Service life Indicator lamp: 100,000 hours at ambient temperature Contact

block: 1,000,000 operating cycles
Degree of protection| IP 65 according to IEC 60529
Environmental ratings (Operating temperature)| – 20 °C < T° < + 75 °C (IECEx) / – 20 °C < T° < + 70 °C (UL)

Temperature class: T5

Storage temperature| – 40 °C < T° < + 70 °C
Electrical ratings| Ue = 24…254 V / Ie = 2…10 mA max

For US: Ue = 24…240 V / Ie = 2…10 mA max

Short-circuit protection| Cartridge fuse: 10A gG (gl)
Connection| Screw clamp terminal – 2 x 1,5 mm² or 1 x 2,5 mm² with cable end – For US: 2 x No. 16 AWG or 1 x No. 14 AWG
Product covered| Cl. I, Div. 2, Gr. A,B,C,D / Cl. II, Div. 2, Gr. F,G / Cl. III, Div. 1&2

Cl. I, Zone 1, AEx db eb mb IIC Zone 21, AEx tb IIIC

Operation

  • Before startup, check that the product has not been damaged (do not use a device if it is damaged).
  • Check that the product’s labeling specifications are compatible with the conditions permitted for the Ex zone at the site where it is being used: (Group II: Surface industries – Category 2: high protection level – G: Gas / D: Dust – IPxx: degree of protection (protection against solids and liquids)). These control and signaling devices must be installed in an ATEX II2GD-certified enclosure. In the case of XAW plastic boxes, the heads must be connected to the enclosure ground with an APZ plate.
    • Store products in their original packaging, in a dry place, T: -40 °C…+70 °C
    • On startup:
  • Connect the contacts (see tables below). Clamp screws tightening torque:  0.8…1.2 N.m
  • Assemble and adjust the product: see section A
  • Check that the seal below the head or the silicone cap replacing it (depending on the version) is in place

Operation

Schneider-Electric-XB4BP-BW-Push-Test-Pilot-Light-
FIG-1

  • Before startup, check that the product has not been damaged (do not use a device if it is damaged).
  • Check that the product’s labeling specifications are compatible with the conditions permitted for the Ex zone at the site where it is being used: (Group II: Surface industries – Category 2: high protection level – G: Gas / D: Dust – IPxx: degree of protection (protection against solids and liquids)). These control and signaling devices must be installed in an ATEX II2GD-certified enclosure. In the case of XAW plastic boxes, the heads must be connected to the enclosure ground with an APZ plate.
    • Store products in their original packaging, in a dry place, T: -40 °C…+70 °C
    • On startup:
  • Connect the contacts (see tables below). Clamp screws tightening torque: 0.8…1.2 N.m
  • Assemble and adjust the product: see section A
  • Check that the seal below the head or the silicone cap replacing it (depending on the version) is in place

Assembly, dimensions

Schneider-Electric-XB4BP-BW-Push-Test-Pilot-Light-
FIG-2

  • e = thickness of support from 1…6 mm (including APZ plate).

Electrical setup

Schneider-Electric-XB4BP-BW-Push-Test-Pilot-Light-
FIG-4

Servicing and maintenance
The intervals for carrying out servicing and maintenance must be set according to the environment and climatic variations.

  • Do not open the devices when on
  • Ensure that the device does not become covered in layers of dust: please vacuum regularly using equipment appropriate to the zone
  • Do not remove the heads (except to replace them)
  • The following items must be checked at least once a year or following a lengthy stoppage period:
  • All external parts must be undamaged
  • If any of the three parts constituting the control or signaling device is damaged, the entire device must be replaced by a product certified as identical
  • Once a year: the emergency stop must be operated 3 times in succession.

For Class I, Division 2 application only:
Contact Blocks, Cat. No. ZBE… and LED pilot light blocks, Cat. No. ZBV… are open-type devices and are meant to be installed in an enclosure suitable for the environment such that the equipment is only accessible with the use of a tool.Schneider-Electric-XB4BP-BW-Push-Test-Pilot-Light-
FIG-3

WARNING

EXPLOSION HAZARD

  • Substitution of component may impair suitability for CLASS I, DIVISION 2 Failure to follow these instructions can result in death, serious injury, or equipment damage.

For Class I, Zone 1 application only:
Contact Blocks, Cat. No. ZBE… and LED pilot light blocks, Cat. No. ZBV… must be mounted in a UL/CUL AEx/Ex enclosure certified for use in CLASS I, ZONE 1, GROUPS IIC and rated IP54 minimum per IEC 60529 when used in CLASS I, ZONE 1 environment such that the equipment is only accessible with the use of a tool. Metallic push button assemblies, Cat. No. XB4B…, Metallic illuminated push button assemblies, Cat. No. XB4B…BM… and metallic LED pilot light assemblies, Cat. No. XB4BV… must be mounted through the wall of a UL/CUL AEx/Ex enclosure certified for use in CLASS I, ZONE 1, GROUPS IIC and rated IP54 minimum following IEC 60529 when used in CLASS I, ZONE 1 environment such that the equipment is only accessible with the use of a tool.