AVENTICS R414000771 Pressure Regulator
About this Documentation
Documentation validity
This documentation applies to ED07 series electro pneumatic pressure regulators and contains important information on the safe and appropriate assembly, operation and maintenance of the ED07 pressure regulator and how to remedy simple malfunctions yourself.
- Read this documentation completely, paying special attention to Chapter 2 “For your safety”, before working with the ED07 pressure regulator.
- Verify by the device name plate and description in Chapter 5 what device you are dealing with and whether the ED07 pressure regulator corresponds to your order.
Related documents
The ED07 pressure regulator is a system component. Also follow the
instructions for the other system components. This includes:
- the system documentation from the system manufacturer
Abbreviations used
Presentation of information
Warnings
In this documentation, there are warnings before the steps whenever there is a
risk of personal injury or damage to equipment. The measures described to
avoid these hazards must be followed.
Safety instructions are set out as follows:
SIGNAL WORD
Hazard type and source Consequences
- Precautions
-
Warning signs and signal words have the following meanings:
-
DANGER
Indicates a hazardous situation which, if not avoided, will certainly result in death or serious injury. -
WARNING
Indicates a hazardous situation which, if not avoided, could result in death or serious injury. -
CAUTION
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. -
NOTICE
Indicates that damage may be inflicted on the product or the environment.
For Your Safety
The ED07 pressure regulator has been manufactured according to the accepted rules of safety and current technology. Even so, there is a risk of injury or damage if the following general safety instructions and the specific warnings given before the steps in this documentation are not observed.
- Read this documentation completely before working with the ED07 pressure regulator.
- Keep this documentation in a location where it is accessible to all users at all times.
- Always include the operating instructions when you pass the ED07 pressure regulator on to third parties.
Intended use
The ED07 pressure regulator is a pneumatic device with integrated electronics
that is only designed to regulate pneumatic pressures.
Air that is dry and free of condensate is the permissible medium. Operation
with pure oxygen is not permitted.
-
The ED07 pressure regulator is for industrial applications only.
An individual license must be obtained from the authorities or an inspection center if the ED07 pressure regulator is to be used in a residential area (residential, business, and commercial areas). In Germany, these individual licenses are issued by the Regulating Agency for Telecommunications (Regulierungsbehörde für Telekommunikation). -
The pressure regulator may only be used within the limits listed in the technical data.
-
Only use the ED07 pressure regulator inside.
Intended use includes having read and understood these instructions, especially Chapter 2 “For your safety”.
Improper use
Use of the ED07 pressure regulator is deemed improper
- when it is used for any application not stated in this documentation,
- when it is used under operating conditions that deviate from those described in this documentation.
Personnel qualifications
Assembly and commissioning require basic electrical and pneumatic knowledge, as well as knowledge of the appropriate technical terms. Assembly and commissioning may therefore only be carried out by qualified electrical or pneumatic personnel or an instructed person under the direction and supervision of qualified personnel. Qualified personnel are those who can recognize possible hazards and institute the appropriate safety measures, due to their professional training, knowledge, and experience, as well as their understanding of the relevant regulations pertaining to the work to be done. Qualified personnel must observe the rules relevant to the subject area.
The following must be observed for the ED07 pressure regulator
General instructions
- Observe the regulations for accident prevention and environmental protection in the country where the product is used and at the workplace.
- Do not modify or convert the device.
- Only use the device within the performance range provided in the technical data. W Do not place any mechanical loads on the device under any circumstances. Never use the device as a handle or step. Do not place loose objects on it.
Prior to installation
Let the process controller acclimatize itself for several hours before
installation, otherwise water may condense in the housing.
On installation
- Make sure the relevant system component is not under pressure or voltage before assembling or when connecting and disconnecting plugs. Protect the system against being switched on. Hang signs on the main switches that warn workers against switching the system on.
- Always mount the ED07 pressure regulator on a base plate For devices with the pressure range 16/20°bar, you must use the single subbase, ED07 series (order no.:°5610211052).
- Lay the cables so that no one can trip over them.
- Only use pre-assembled and tested plugs and cables, thus avoiding voltage reversal.
- The device complies with protection class IP65. Before commissioning, make sure that all the connection seals and plugs are leak-tight to prevent fluids and foreign bodies from penetrating the device or plug-type connections.
During commissioning
- Water entering the device destroys the electronics. Never open the seal of the compensating port. Ensure that the four mounting screws are tightened with the correct torque. Never open the two fastening screws on the housing cover.
During operation
- If the device is not fastened correctly, other parts may be damaged by uncontrolled device movements. Please ensure that the device is securely fastened to a base plate, which in turn is secured to the machine or a mounting plate.
- Touching the valve coils during operating may lead to burns. Let the device cool off before disassembling. Do not touch the device during operation.
- If the housing ventilation port is closed, there is no atmospheric equalization and the characteristics curve will change. Ensure that the air can circulate freely through the housing ventilation port. Never operate the device in an atmosphere containing oil.
During cleaning
Never use solvents or aggressive detergents. Only clean the device using a
slightly damp cloth. Only use water and, if necessary, a mild detergent.
Disposal
Dispose of the device in accordance with the currently applicable
regulations in your country.
Delivery Contents
The delivery contents include:
- 1 ED07 pressure regulator
- 1 gasket
- 4 screws M5x90 (DIN EN ISO 4762, formerly DIN 912)
- 1 set of operating instructions
Applications for the ED07 Pressure Regulator
The ED07 pressure regulator converts an electrical set point into pressure. In
doing so, a pressure sensor integrated in the ED07 pressure regulator records
the outlet pressure.
The integrated control electronics regulates the outlet pressure. Due to this,
the controlled outlet pressure remains constant if there are disturbance
variables such as flow changes or supply pressure fluctuations. With the ED07
pressure regulator, you can
- electrically change pressures,
- remotely adjust pressures.
Additionally, you can use the ED07 pressure regulator as an actuator to control brake forces, clamping forces, flow rates, or turbine speeds.
Device Description
The ED07 pressure regulator is available in three connection versions and various output pressures.
- Refer to the name plate of your version for further details.
ED07 pressure regulator with three M12 connections
-
Inlet connection
-
Outlet connection
-
Exhaust
-
Compensating port seal
-
Housing cover mounting screw
-
Housing ventilation port
-
Valve solenoids
-
Coding bore
-
Fixing pins for gasket
-
Screws M5x90 (DIN EN ISO 4762, formerly DIN 912)
-
Gasket
-
Housing gasket
For devices with a M12 connection: -
Integrated plug XPC, connection for
supply voltage and control
For devices with two M12 connections:- Integrated plug X1S,
connection for supply voltage 14 M12 integrated socket X2M,
control connection
For devices with three M12 connections: 13 Integrated plug X1S, connection for supply voltage
- Integrated plug X1S,
-
M12 integrated socket X2A, control connection
-
M12 integrated socket X2N, external sensor connection
Nameplate
In the following the nameplate example illustrated is the ED07 pressure regulator with three connections.
- 16 X2N connection assignment
- 17 Connection ID X2N
- 18 X2N technical data
- 19 QR code
- 20 Series
- 21 Warning sign “Caution! Hot surface!” 22 CE mark
- 23 Internal factory designation
- 24 Production date 1)
- 25 Serial number
- 26 Connection ID X2A/X2M
- 27 X2A/X2M technical data
- 28 X2A/X2M connection assignment 29 X1S/XPC connection assignment 30 X1S/XPC connection ID
- 31 Manufacturer’s address
- 32 Data matrix code
- 33 Country of manufacture
- 34 Device technical data
- 35 Logo
The production date, year (YY) and week (WW) is encoded in the format
Mounting ED07 pressure regulator
The ED07 pressure regulator must always be fastened to a base plate (single subbase or base plate for stacking assembly).
Before assembly
-
Make sure the relevant system part is not under voltage or pressure.
-
Let the ED07 pressure regulator acclimate itself for several hours before installation, otherwise water may condense in the housing.
NOTICE
Risk due to incorrectly mounted device!
An incorrectly mounted device may result in uncontrolled movements that could damage other system parts.- Please ensure that the device is securely fastened to a base plate, which in turn is secured to the machine or a mounting plate.
-
Fasten the base plate in the control cabinet or onto a mounting plate. Vertical mounting is preferable for the ED07 pressure regulator.
- 36 vertical axis
- 37 horizontal axis
The device can be mounted in any orientation if the compressed air is dry and oil-free.
-
NOTICE
Malfunction caused by closed housing ventilation port!
If the housing ventilation port is closed, there is no atmospheric equalization and the characteristics curve will change.- Ensure that the air can circulate freely through the housing ventilation port (6).
- Never operate the device in an atmosphere containing oil.
-
O Before installation, ensure that the housing ventilation port (6) is open and not, for example, painted shut.
Insert gasket
- Insert the gasket (11) on the underside of the ED07 pressure regulator so that the three pneumatic openings are not covered.
- Apply slight pressure to the gasket so that it attaches to the three fixing pins (9).
The three fixing pins ensure that the gasket sits correctly on the contours of the pneumatic openings.
Mounting the ED07 pressure regulator on the base plate
The base plate has a coding pin (38), which fits into the matching coding
boring (8) of the ED07 pressure regulator. Correct assembly is thus ensured.
- Rotate the ED07 pressure regulator so that the coding pin (38) and coding boring (8) are on the same side and can engage with each other.
- Place the ED07 pressure regulator on the base plate. When you do so, make sure the gasket does not shift. The base plate coding pin fits into with the coding boring on the ED07 pressure regulator.
Some base plates have two coding pins. For this reason, there is a second coding boring on the same side of the ED07 pressure regulator. There is no risk of confusion.
Firmly screw the ED07 pressure regulator onto the base plate
- Insert the four M5x90 screws into the four holes as shown in the figure and screw tight. Tightening torque: 6 Nm
- Make sure again that the gasket and the housing gasket (12) sit properly in order to ensure the IP65 protection class. The gasket and housing gasket may not overlap on the side.
Connecting the supply voltage, set point, and external sensor
WARNING
Danger of injury due to the failure of the external sensor on connection X2M! The pressure regulator opens fully. The maximum permissible pressure in the system may be exceeded. Severe injuries are possible. If you use an external sensor:
- Always install safety equipment that monitors the function of the external sensor on connection X2M.
NOTICE
Missing seals and plugs will lead to non-compliance with the IP65 protection
class!
Liquids and foreign objects could penetrate the device and plug connections
and destroy the electronics.
- Use IP65 protection class plug-type connections.
- Make sure that the seals are integrated in the plug and not damaged.
- Make sure that all plugs are mounted before starting the system.
To operate the ED07 pressure regulator, you must supply the device with compressed air, connect the 24 V DC supply voltage, and control the device with a set point. The actual value (-) and set point (-) are always connected to 0 V. The following applies for all devices with 0…10 V voltage control: If the analog trigger signal is not electrically isolated, please heed the line resistances to minimize set point/actual value drifting and the controlled pressure. Use a shielded line to connect XPC, X2M, and X2N. The shield must be connected to the plug housing. O Please heed the following tables containing the plug assignments for the different series.
- Make sure before connecting the plugs that all seals and caps are included and not damaged.
- Only use pre-assembled and tested plugs and cables,
- Protect the supply voltage with an external M2.5A fuse.
As the 0 V lines are linked in the case of the X2M and X1S connections, as well as X2N and X1S, you must ensure that all the plug-type connections are correctly poled. Short-circuiting occurs due to pole confusion of the supply voltage or set point voltage. For devices controlled via potentiometer, integrated plug X1S and integrated socket X2M:
- Connect the lines to the X2M integrated socket as illustrated in the figure opposite. Voltage can now be supplied to the ED07 pressure regulator and the set point adjusted on the potentiometer.
Commissioning the EV07 pressure regulator
NOTICE
Risk of destruction by water!
Water entering the device destroys the electronics.
- Ensure that the compensation port is sealed.
- Ensure that the four mounting screws are tightened with the correct torque. O Never open the two fastening screws on the housing cover.
Prior to commissioning the EV07 pressure regulator
Attach base plate pneumatic connections
Depending on the application, the base plate is a single subbase or base plate for stacking assembly.
- Connect the supply line to inlet connection°1 on the base plate (39).
- Connect the outlet line to the output connection (unlabeled connection) on the opposite side.
- Always connect a silencer or line for restricted exhaust to exhaust 3 (40).
CAUTION
Danger caused by escaping compressed air!
Device is operating under pressure. On opening the additional input connection
(41) on the base plate, the seal screw can be hurled into the surrounding area
and may cause bodily harm and material damage.
- Never undo the seal screw during operation.
- Only connect another input connection when no pressure is supplied.
Exhaust 3 (40) in the single subbase must not be sealed by a screw.
- Always mount the exhaust on an appropriate silencer (see Chapter 13 „Accessories“) or line for restricted exhaust.
Output pressure -1 bar…+1 bar:
On the ED07 pressure regulator with the pressure range -1 bar…+1 bar a vacuum
must be connected to exhaust 3.
Switching on the pneumatic and electrical supplies
Proceed as follows to commission the ED07 pressure regulator:
- First switch on the pneumatic supply.
- Then switch on the 24 V DC supply voltage.
Setting the set point
- Enter the desired set point in the controller or potentiometer.
- Please observe Chapter „Selecting the correct supply pressure“.
Triggering the ED07 pressure regulator
You can continually adjust the pressure once you have connected the pneumatic and electrical supply on the ED07 pressure regulator. To do this, the ED07 pressure regulator is e.g. controlled via a controller or potentiometer using a set point. The electronics compares the set point with the output pressure, which is measured by a pressure sensor, and generates a control variable, which in turn triggers the venting or exhaust valve via the U/I converter and proportional solenoids. This sets the stipulated pressure.
- Inlet connection for supply pressure
- Outlet connection
- Ventilation
- 42 Supply voltage
- 43 Nominal input value
- 44 Actual output value
- 45 Switch output
Selecting the correct supply pressure
A permanent deviation will occur if the supply pressure is less than the
outlet pressure stipulated by the electrical set point. The electronics
reduces the current consumption and thus the maximum nominal width to prevent
the ED07 pressure regulator becoming hot.
CAUTION
Danger of burns caused by hot coils!
Touching the valve coils during operating may lead to burns.
- Let the device cool off before disassembling it.
- Do not touch the device during operation.
- Always select a supply pressure that is higher than the outlet pressure.
“Pressure reached” switch output
The “Pressure reached” switch output is only featured on “ED07 pressure
regulators with M12 integrated plug X1S and M12 integrated socket X2M, M12”.
The ED07 pressure regulator with M12 integrated plug X1S and M12 integrated
socket X2M recognizes whether the required output pressure is set within a
tolerance band of 2% FS.
The switch output on pin 1 of the M12 integrated socket X2M is triggered at a
value equal to the supply voltage or 2.0 V lower (high level) as long as the
actual value is close to the set point in the tolerance band. If the actual
value is outside the tolerance band, a voltage of < 2.0 V DC (low level) is
supplied to the switch output. This signal can be used to enable further
process steps, for instance.
Controlling the pressure
Depending on the version, the output pressure of the ED07 pressure regulator
can be controlled via the current, voltage or a potentiometer. Depending on
the version, the characteristic curves in the following section depicts the
linear interrelation between current and outlet pressure or voltage and outlet
pressure. The device generates the supply voltage for the potentiometer in
devices with an external potentiometer. The potentiometer sliding contact is
connected to the set point input (see „Connecting the supply voltage, set
point, and external sensor“).
- Select the right characteristic curve according to the output pressure and device number.
- Define the required output pressure.
- Refer to the current or voltage characteristic curve to set the required output pressure.
- Depending on the model, control the outlet pressure either via the controller or a potentiometer.
Characteristics
The characteristic curves for all ED07 pressure regulator versions are listed
in the following.
NOTICE
Malfunction caused by closed housing ventilation port!
If the housing ventilation port is closed, there is no atmospheric
equalization and the characteristics curve will change.
- Ensure that the air can circulate freely through the housing ventilation port (6).
- Never operate the device in an atmosphere containing oil.
Disassemble, replace and dispose of ED07 pressure regulator
Disassembling the EV07 pressure regulator
NOTICE
Connecting or disconnecting plugs when under voltage will damage the device!
Large differences in potential occur when connecting or disconnecting plugs
under voltage, which could damage the device.
- Make sure the relevant system component is not under voltage before assembling the device or when connecting and disconnecting plugs.
CAUTION
Danger of burns caused by hot coils!
Touching the valve coils during operating may lead to burns.
- Let the device cool off before disassembling it.
- Do not touch the device during operation.
The following switch-off sequence must be observed in order to disassemble the ED07 pressure regulator.
- Stipulate a set point of 0 bar to exhaust the ED07 pressure regulator and the outlet line on the outlet pressure connection.
- Switch off the 24 V DC supply voltage.
- Remove the connected plugs.
- Switch off the supply pressure.
- Undo the four M5x90 screws.
The ED07 pressure regulator can now be removed.
Exchange the ED07 pressure regulator
To replace the ED07 pressure regulator, you must first disassemble it as
described above and then assemble a new ED07 pressure regulator (see Chapter 6
„Mounting ED07 pressure regulator“).
Dispose of ED07 pressure regulator
- Dispose of the ED07 pressure regulator in accordance with the currently applicable regulations in your country.
Care for and maintain the ED07 pressure regulator
Servicing the ED07 pressure regulator
No special care is required for the ED07 pressure regulator.
NOTICE
Damage to components!
Solvents and aggressive detergents will destroy the surface, labeling and
seals of the device!
- Only clean the device using a slightly damp cloth. Only use water to do this and, if necessary, a mild detergent.
CAUTION
Danger of burns caused by hot coils!
Touching the valve coils during operating may lead to burns.
- Let the device cool off before disassembling.
- Do not touch the device during operation.
Check that all seals and plugs for the plug connections are firmly fitted so that no humidity can penetrate the ED07 pressure regulator during cleaning.
Maintaining the ED07 pressure regulator
The ED07 pressure regulator is maintenance-free.
- However, the system-specific maintenance intervals must be observed.
Check the ED07 pressure regulator seals
The seals in the ED07 pressure regulator may age faster under aggressive
ambient conditions. Defective seals will lead to pneumatic leaks and non-
compliance with the IP65 protection class.
- Every now and then, check that the seals on the pressure regulator are in perfect order.
If Malfunctions Occur
Malfunction Possible cause | Remedy |
---|---|
No output pressure present | No power supply |
Check the polarity of the power supply.
Switch on system component.
No set point stipulated| Stipulate a set point.
No supply pressure available| Connect the supply pressure.
Outlet pressure too low| Supply pressure too low| Increase the supply
pressure.
Outlet pressure less than the set point| Consumers that use a lot of air
(>1300 h l/min) cause a major drop of pressure in the device.| Reduce air
consumption
Use a device with a larger nominal width (e.g. ED12)
Outlet pressure does not correspond to the stipulated set point| Housing
ventilation port is closed| Make sure that the housing ventilation port is
open
Defective diaphragm in the housing ventilation port| Exchange the ED07
pressure regulator
Air is audibly escaping| Gasket is missing or damaged| Check the gasket and
exchange if necessary
The ED07 pressure regulator and base plate are not sealed tight| Tighten
screws with 6 Nm torque
ED07 pressure regulator is not leak-tight| Exchange the ED07 pressure
regulator
Replace pneumatic connections on the base plate| Correctly replace pneumatic
connections on the base plate (see „Attach base plate pneumatic connections“)
ED07 pressure regu- lator does not bleed| End plate exhaust is closed| Open
the exhaust and connect a silencer or a line for restricted exhaust.
Technical Data
General data|
---|---
Dimensions (width x height x depth)| 254 mm x 100 mm x 43 mm
Weight| 1.8 kg
Operating temperature range| 5 °C…50 °C
Storage temperature range| -20 °C…80 °C
control| Analog
Version| Poppet valve
Permissible medium| Air of quality class DIN ISO 8573-1 for solid impurities:
5 μm
for water content: 3
for total oil content: 1
Protection class according to EN 60529/IEC529| IP65
(only when assembled and with all plugs assembled)
Mounting orientation| preferred mounting orientation: vertical (see figure 3)
Any if used with dry and oil-free compressed air
The housing ventilation port must be open
Pneumatics
Flow rate at pre-pressure 7 bar (101.5 psi), rated pressure 6 bar (87 psi) and
pressure drop 0.2 bar (2.9 psi)| 1300 l/min
Supply pressure| Supply pressure| Output pressure
Max. 0.12 bar
(1.74 psi)
| at 0…0.05 bar (0… 0.73 psi)
Max.°0.7°bar (10°psi)| at 0…0.4 bar
(0…5.8°psi)
Max.°3°bar (43.5°psi)| at -1…1 bar
(-14.5… 14.5 psi)
Max.°8°bar (116°psi)| at 0…6 bar
(0…87 psi)
Max. 12°bar (174°psi)| at 0…10 bar
(0…145 psi)
Max. 18°bar (261°psi)| at 0…16 bar
(0…232 psi)
Max. 21°bar (304.5°psi)| at 0…20 bar
(0…290 psi)
Reproducibility| Reproducibility| Output pressure
0.01 bar (0.15 psi)| at 6/10 bar (87/145 psi)
0.005 bar (0.073 psi)| at -1…1 bar
(-14.5… 14.5°psi)
0.03 bar (0.435 psi)| at 16/20 bar (232/290 psi)
Hysteresis| Hysteresis| Output pressure
0.03 bar (0.44 psi)| at 6/10 bar (87/145 psi)
0.015 bar (0.218°psi)| at -1…1 bar
(-14.5… 14.5°psi)
0.09 bar (1.31 psi)| at 16/20 bar (232/290 psi)
Electronics
Supply voltage| 24 V DC (+30%/-20%)
Only use a power pack with safe isolation for the power supply
Permissible harmonic content| 5%
Power consumption| Max. 1.4 A
Input current resistance (set point)| Supply voltage switched on: 100 W Supply
voltage switched off: high-ohmic
Current output (actual value), external working resistance| < 300 W
Accessories
Component | Order number |
---|---|
Angle plug M12, 5-pin, A-coded for X2M and X2A | 1824484028 |
Angled socket M12, 5-pin, A-coded for XPC and
X1S
| 1824484029
Angle plug M12x1, series CN2, 5-pin, B-coded for
X2N
| 1824484026
Flat subbase ED07 with D12 plug-in cartridge and silencer| 5610231002
Mounting set, series ED07 (Sheet metal for mounting of ED07 flat subbase
(5610231002))| 5530010522
Single subbase ED07| 5610211052
Base plate, ED07 series (for stacking assembly)| 8985049932
End plate left, end plate right for base plate ED07| 1825503145
Gasket, series EDO7 (1 gasket and 4 screws DIN 912 – M5x90)| R414001681
Silencer, SI1 series for single subbase,
ED07 series (5610211052) and base plate for stacking assembly, ED07 series (8985049932)
| 1827000002
For ED07 pressure regulators with the pressure range 16/20°bar, you may only use the single subbase, ED07 series (order no.:°5610211052).
AVENTICS GmbH
Ulmer Straße 4
30880 Laatzen, GERMANY Phone +49 (0) 5 11-21 36-0 Fax: +49 (0) 511-21 36-2 69
www.aventics.com
info@aventics.com
Further addresses: www.aventics.com/contact