LAB GRUPPEN C164 Dedicated Amplifiers Instruction Manual

June 14, 2024
Lab gruppen

C164 Dedicated Amplifiers

Specifications

  • Model: C 88:4, C 68:4, C 48:4, C 28:4, C 16:4
  • Rev: 3.0.0
  • Type: Dedicated Installation Amplifiers

Important Safety Instructions

  1. Read these instructions.

  2. Keep these instructions.

  3. Heed all warnings.

  4. Follow all instructions.

  5. Do not use this apparatus near water.

  6. Clean only with a dry cloth.

  7. Do not block any ventilation openings. Install in accordance
    with the manufacturer’s instructions.

  8. Do not install near any heat sources such as radiators,
    heat

Approvals

This equipment conforms to the requirements of the EMC Directive
2014/30/EC and the requirements of the Low Voltage Directive
2014/35/EC.

Standards applied:

  • EMC Emission EN55103-1, E3

  • EMC Immunity EN55103-2, E3, with S/N below 1% at normal
    operation level.

  • Electrical Safety EN60065, Class I

This equipment is tested and listed according to the U.S. safety
standard ANSI/ UL 60065 and Canadian safety standard CSA C22.2 NO.
60065. Intertek made the tests and they are a Nationally Recognized
Testing Laboratory (NRTL).

Warnings

The lightning bolt triangle is used to alert the user to the
presence of un-insulated dangerous voltages within the unit’s
chassis that may be of sufficient magnitude to constitute a risk of
electric shock to humans.

The exclamation point triangle is used to alert the user to
presence of important operating and service instructions in the
literature accompanying the product.

User Responsibility Mains Connection Grounding

Your amplifier must be connected to a grounded socket
outlet.

Speaker Output Hazard on Amplifiers

Amplifiers are capable of producing hazardous output voltages.
To avoid electrical shock, do not touch any exposed speaker wiring
while the amplifier is operating. The external wiring connected to
the speaker terminals shall be installed by a qualified person, or
ready-made leads or cords of appropriate capacity shall be used. As
the power output channels on amplifiers produce high voltage, do
not connect or disconnect speaker cables when the mains power is
on.

Radio Interference

To minimize radio interference, ensure proper grounding and
shielding of all cables connected to the amplifier.

Speaker Damage

Amplifier apparatus is very powerful and can be potentially
dangerous to both loudspeakers and humans alike. Many loudspeakers
can be easily damaged or destroyed by overpowering them. Always
check the speaker’s continuous and peak power capabilities.
Although the amplifier’s attenuators can be used to reduce the
overall gain, an increase of the input signal can result in full
output power, which may cause damage to connected speakers.

Maintenance

The amplifier should be kept clean and free from dust. Use a dry
cloth for cleaning. Do not use any liquid or chemical cleaners on
the amplifier.

Product Usage Instructions

1. Introduction

1.1. Welcome

Welcome to the C Series Dedicated Installation Amplifiers. This
manual will guide you through the installation and operation of the
amplifier.

1.2. Main Features

The C Series amplifiers are designed for dedicated installation
applications. They provide high-quality audio amplification for
various audio systems.

2. Installation

2.1. Unpacking

When unpacking the amplifier, ensure that all the accessories
and components are included in the package. If anything is missing
or damaged, contact customer support.

2.2. Mounting

Mount the amplifier in a suitable location using the provided
mounting brackets. Ensure that the mounting surface is sturdy and
can support the weight of the amplifier.

2.3. Cooling

Proper cooling is essential for the amplifier’s performance and
longevity. Ensure that there is adequate ventilation around the
amplifier to prevent overheating. Do not block any ventilation
openings.

2.4. Operating Voltage

The amplifier is designed to operate within a specific voltage
range. Check the specifications to ensure that the operating
voltage matches the available power supply. Use a grounded socket
outlet for the amplifier’s power connection.

2.5. Grounding

Proper grounding is necessary for electrical safety. Connect the
amplifier to a grounded socket outlet to prevent electrical
shocks.

3. Product Overview

The C Series amplifiers feature multiple channels and are
designed for dedicated installation applications. They provide
high-quality audio amplification for various audio systems.

FAQ

Q: Can I use the amplifier near water?

A: No, the amplifier should not be used near water to avoid the
risk of electric shock.

Q: Can I clean the amplifier with a wet cloth?

A: No, the amplifier should only be cleaned with a dry cloth. Do
not use any liquid or chemical cleaners.

Q: Can I connect or disconnect speaker cables while the mains

power is on?

A: No, it is not safe to connect or disconnect speaker cables
while the mains power is on. Ensure that the power is turned off
before making any connections or disconnections.

Q: How can I prevent speaker damage?

A: To prevent speaker damage, always check the speaker’s
continuous and peak power capabilities. Do not overpower the
speakers and ensure that the amplifier’s gain is properly
adjusted.

Q: How should I clean and maintain the amplifier?

A: Clean the amplifier with a dry cloth to remove dust and
debris. Do not use any liquid or chemical cleaners as they may
damage the amplifier.

Rev. 3.0.0
Item no. OM­CS

C SERIES
Dedicated Installation Amplifiers

C 88:4 C 68:4 C 48:4 C 28:4 C 16:4
Operation Manual

1. Important safety instructions

1. Important safety instructions

Before using the device, be sure to carefully read the Safety Instructions. Keep this document with the device at all times.

1. Read these instructions. 2. Keep these instructions 3. Heed all warnings. 4. Follow all instructions. 5. Do not use this apparatus near water. 6. Clean only with a dry cloth. 7. Do not block any ventilation openings. Install in accordance
with the manufacturer’s instructions. 8. Do not install near any heat sources such as radiators, heat
registers, stoves, or other apparatus (including amplifiers) that produce heat. 9. Do not defeat the safety purpose of the polarized or grounding-type plug. A polarized plug has two blades with one wider than the other. A grounding-type plug has two blades and a third grounding prong. The wide blade or the third prong is provided for your safety. If the provided plug does not fit into your outlet, consult an electrician for replacement of the obsolete outlet. 10. Protect the power cord from being walked on or pinched, particularly at plugs, convenience receptacles, and the point where they exit from the apparatus. 11. Only use attachments/accessories specified by the manufacturer. 12. Use only with a cart, stand, tripod, bracket, or table specified by the manufacturer, or sold with the apparatus. When a cart is used, use caution when moving the cart/apparatus combination to avoid injury from tip-over. 13. Unplug this apparatus during lightning storms or when unused for long periods of time. 14. Refer all servicing to qualified service personnel. Servicing is required when the apparatus has been damaged in any way, such as power-supply cord or plug is damaged, liquid has been spilled or objects have fallen into the apparatus, the apparatus has been exposed to rain or moisture, does not operate normally, or has been dropped. 15. Use the mains plug to disconnect the appartus from the mains. 16. WARNING: To reduce the risk of fire or electric shock, do not expose this apparatus to rain or moisture. 17. Do not expose this equipment to dripping or splashing and ensure that no objects filled with liquids, such as vases, are placed on the equipment. 18. Do not connect the unit’s output to any other voltage source such as battery, mains source, or power supply, regardless of whether the unit is turned on or off. 19. Do not remove the top (or bottom) cover. Removal of the cover will expose hazardous voltages. There are no user serviceable parts inside and removal may void the warranty. 20. An experienced user shall always supervise this professional audio equipment, especially if inexperienced adults or minors are using the equipment. 21. The US National Differences clause 16.3 requires that network cables must be flame rated VW-1.

1.1. Approvals
This equipment conforms to the requirements of the EMC Directive 2014/30/EC and the requirements of the Low Voltage Directive 2014/35/EC.
Standards applied: EMC Emission EN55103-1, E3 EMC Immunity EN55103-2, E3, with S/N below 1% at normal operation level. Electrical Safety EN60065, Class I
This equipment is tested and listed according to the U.S. safety standard ANSI/ UL 60065 and Canadian safety standard CSA C22.2 NO. 60065. Intertek made the tests and they are a Nationally Recognized Testing Laboratory (NRTL).
1.2. Warnings
1.2.1. Explanation of warning symbols
The lightning bolt triangle is used to alert the user to the presence of un- insulated “dangerous voltages” within the unit’s chassis that may be of sufficient magnitude to constitute a risk of electric shock to humans.
The exclamation point triangle is used to alert the user to presence of important operating and service instructions in the literature accompanying the product.
1.2.2. Warnings
To prevent electric shock do not remove top or bottom covers. No user serviceable parts inside, refer servicing to qualified service personnel. Français: À prévenir le choc électrique n’enlevez pas les couvercles. Il n’y a pas des parties serviceable à l’intérieur, tous reparations doit etre faire par personnel qualifié seulment.

2 C SERIES Operation Manual rev 3.0.0

1. Important safety instructions

To completely disconnect this equipment from the AC mains, disconnect the power supply cord plug from the AC receptacle. The mains plug of the power supply cord shall remain readily operable. Français: Pour démonter complètement l’équipement de l’alimentation générale, démonter le câble d’alimentation de son réceptacle. La prise d’alimentation restera aisément fonctionnelle. To reduce risk of fire or electric shock, do not expose this apparatus to rain or moisture. Français: Pour réduire les risques d’incendie ou de choc électrique, n’exposez pas l’appareil à la pluie ou à l’humidité. Do not expose this system/apparatus to dripping or splashing and ensure that no objects filled with liquids, such as vases, are placed on the apparatus. Français: N’exposez pas ce système/appareil au ruissellement ni aux éclaboussures et assurez-vous qu’aucun objet contenant du liquide tel qu’un vase n’est placé sur l’appareil. This apparatus must be connected to a mains socket outlet with a protective earthing connection. Français: Cet appareil doit être raccordé à une prise secteur avec terre de protection. The mains plug is used as a disconnect device and shall remain readily operable. Français: Lorsque la prise du réseau d’alimentation est utilisés comme dispositif de déconnexion, ce dispositif doit demeuré aisément accessible.
1.2.3. Caution
To reduce the risk of fi re or electric shock, do not remove screws. No user- serviceable parts inside. Refer servicing to qualified service personnel. Français: Pour réduire le risque d’incendie ou de choc électrique, ne pas retirer les vis. Aucune pièce réparable par l’utilisateur. Confier l’entretien àpersonnel qualifié.
1.2.4. User responsibility Mains connection grounding
Your amplifier must be connected to a grounded socket outlet.
Speaker output hazard on amplifiers
Amplifiers are capable of producing hazardous output voltages. To avoid electrical shock, do not touch any exposed speaker wiring while the amplifier is operating. The external wiring connected to the speaker terminals shall be installed by a qualified person, or ready-made leads or cords of appropriate capacity shall be used. As the power output channels on amplifiers produce high voltage, do not connect or disconnect speaker cables when the mains power is on.

Radio interference
A sample of this product has been tested and complies with the limits for the European Electro Magnetic Compatibility (EMC) directive. This equipment has also been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference from electrical equipment. This product uses radio frequency energy and if not used or installed in accordance with these operating instructions, may cause interference to other equipment, such as radio receivers.
This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures: · Reorient or relocate the antenna. · Increase the separation between the equipment and
receiver. · Connect the equipment to an outlet on a circuit different
from that to which the receiver is connected. · Check if the affected unit complies with the EMC limits for
immunity, (CE-labeled). If not, address the problem with the manufacturer or supplier. All electrical products sold in the EC must be approved for immunity against electromagnetic fields, high voltage flashes, and radio interference. · Consult the dealer or an experienced radio/TV technician for help.
Speaker damage
Amplifier apparatus is very powerful and can be potentially dangerous to both loudspeakers and humans alike. Many loudspeakers can be easily damaged or destroyed by overpowering them. Always check the speaker’s continuous and peak power capabilities. Although the amplifiers attenuators can be used to reduce the overall gain, an increase of the input signal can result in full output power, which may cause damage to connected speakers.
Maintenance
For safe and reliable operation, the dust fi lters on both sides of the front panel, behind the grilles, should be removed and cleaned regularly to ensure maximum airflow through the device. If the dust filters are not maintained there will be safety risks; for example, high internal temperatures could ignite the dust and start a fire. There is also a risk that the unit will malfunction since it is dependent on constant airflow from front to rear. If the dust fi lters are not clean and the unit malfunctions, any resulting problems will not be covered by the warranty.

C SERIES Operation Manual rev 3.0.0

3

Table of Contents

Table of Contents

1. Important safety instructions

2

1.1. Approvals

2

1.2. Warnings

2

2. Introduction

5

2.1. Welcome

5

2.2. Main Features

6

3. Installation

8

3.1. Unpacking

8

3.2. Mounting

8

3.3. Cooling

8

3.4. Operating Voltage

9

3.5. Grounding

9

4. Product Overview

10

4.1. Front Panel Overview

10

4.2. Rear panel

12

4.3. NomadLink / Ethernet network setup

13

5. Operation and performance

15

5.1. Introduction

15

5.2. Operation precautions

15

5.3. Signal flow and headroom

15

5.4. Audio Input and Output connections, setup and features

17

5.5. GPIO connection and operation

22

5.6. Front-panel monitoring

25

5.7. NomadLink network and DeviceControl software

27

6. Appendix

31

6.1. Maintenance

31

6.2. FAQ

31

6.3. Additional documentation

32

6.4. Current Draw and Thermal Dissipation Specifications

33

7. Technical Specifications

38

8. Warranty and Support

39

8.1. General

39

8.2. Technical assistance and service

39

4 C SERIES Operation Manual rev 3.0.0

2. Introduction
2. Introduction
2.1. Welcome
Thank you for choosing LAB GRUPPEN C Series power amplifiers for your sound reinforcement system installation. We are confident that you will be very pleased with the performance, configuration flexibility, reliability, and long-term durability offered by the C Series products.
This manual provides a comprehensive guide to the features and functionality of C Series model C 88:4, C 68:4, C 48:4, C 28:4 and C 16:4 amplifiers. Please read through it in its entirely to become fully acquainted with the many configuration options and multiple layers of protection circuitry.
To facilitate timely installation and use of this C Series product, we have included a Quick Guide Overview (section 4). This brief summary, in conjunction with Installation (section 3), contains the basic information needed to safely install the amplifier and place it in service. However, we highly recommend reading through this manual in its entirety, beginning with Main Features and Technologies and continuing through Operation and Performance. As you become thoroughly familiar with all aspects of operation, you may learn of features or options that will affect your choices on amplifier modes or loudspeaker system configuration.
LAB GRUPPEN C Series power amplifiers are designed and built specifically for the unique demands of permanent installation applications. C Series amplifiers offer the optimum combination of high-quality audio reproduction, flexible features, ease of installation, and 100% reliability in normal use.
By packing four or eight channels of reconfigurable power amplification into a 2U chassis, the C Series achieves unprecedented power and channel density. The benefits of compact dimensions include reduced rack space requirements and minimal heat build-up. The flexible output stages enable each amplifier channel to be set for either low impedance or constant voltage (70 V / 100 V) mode. NomadLink, an easy-to-use network for monitoring and control, is implemented as a standard feature on all C Series amplifiers.
Although C Series features and facilities are tailored to installation applications, at the heart of each amplifier is the same advanced technology that has made LAB GRUPPEN the benchmark of quality for touring concert systems: exceptional sonic performance, rugged construction, proven reliability, and protection features that anticipate every unwelcome possibility.
NOTE: This manual is shipped with C Series amplifier models C 88:4, C 68:4, C 48:4, C 28:4 and C 16:4. All references to “C Series” in this manual apply to all four of these models. A different manual is shipped with models C 20:8X, C 10:8X, C 10:4X and C 5:4X. References to C Series in this document may or may not apply to these C…X models.
5 C SERIES Operation Manual rev 3.0.0

2. Introduction
2.2. Main Features
Your new C Series amplifier incorporates a number of sophisticated technologies ­ many of them proprietary to LAB GRUPPEN ­ that are provided to ensure the best possible performance and many years of reliable operation. Familiarizing yourself with these technologies will prove invaluable in setting up and optimizing your loudspeaker system.
2.2.1. Class TD amplifier and Regulated Switch Mode Power Supply (R.SMPS)
LAB GRUPPEN’s patented Class TD technology combines the exceptional efficiency of a Class D amplifier with the high sonic quality associated with Class B designs. Class TD also incorporates the same basic concepts behind Class H designs, but here they are refined and pushed to a higher level to achieve much greater efficiency. The Class TD output sections work in concert with LAB GRUPPEN’s unique, regulated switch-mode power supply (R.SMPS) to create a superior overall power amplifier topology. This ensures stable, full output power over an extremely wide range of mains voltage levels. Sagging or fluctuating mains voltage will not affect the power output delivered to the loudspeakers.
2.2.2. Amplifier gain
For greater flexibility in system integration, C Series amplifiers allow gain adjustment from +23 dB to +44 dB in 3 dB steps. This feature accommodates any combination of input device and loudspeaker type. For example, if the input signal is weak, the gain can be boosted to maintain maximum power output while avoiding a poor signalto-noise ratio. This gain adjustment feature makes it easier to achieve an optimal balance between headroom and noise floor.
2.2.3. Voltage Peak Limiter (VPL)
The Voltage Peak Limiter (VPL) feature allows user adjustments that determine maximum voltage output, thus matching the amplifier to the connected speaker load. Whether the connected load is low impedance (2 to 16 ohms) or high impedance (70 V / 100 V), the VPL feature can be set to ensure that neither temperature nor current limitations are exceeded before reaching the desired voltage threshold.
2.2.4. Protection and performance optimization
Appropriate and reliable power amplification is vital to any audio system. Inadequate or faulty power amplification could cause damage to the loudspeakers, or in some cases to the power amplifiers themselves. To prevent any damage or costly service interruptions, C Series amplifiers offer advanced features to protect both internal circuits and any connected loads. These features even protect the mains fuse that, in extreme cases, could be overloaded.
6 C SERIES Operation Manual rev 3.0.0

2. Introduction
Following are short descriptions of standard built-in C Series protection features:
· CPL (Current Peak Limiter) ensures that the amplifier’s output does not exceed the safe current handling parameters of amplifier components.
· Temperature protection ensures that the amplifier will not be damaged by exceeding thermal limits. · PAL (Power Average Limiter) limits the maximum average power consumption according to the power supply
and mains-breaker capabilities. · VHF (Very High Frequency) protection circuits mute the output of the amplifier when nondynamic continuous
signals above 10 kHz are detected. · DC protection ensures destructive DC signals will not appear at the amplifier outputs. If such conditions occur
an internal fuse opens and fault indication is displayed. · Low-impedance (short circuit) protection provides a fault warning indication and shuts down the output stage
when, for example, an input signal is present and a malfunctioning cable or driver is short circuiting the output. · High-impedance warning reports an alert when, at the same time, output signal is high and no current draw is
measured. This situation might occur when no speakers are connected, or when a driver is blown. · Low inrush current ensures that the mains breaker will not trip when several power amplifiers are turned on
simultaneously.
2.2.6. NomadLink / Ethernet control and monitoring network
The NomadLink network allows easy setup and control of C Series power amplifiers and other devices. The patented network topology allows automatic detection and addressing of multiple amplifiers, and is controlled from a PC via an NLB 60E NomadLink Bridge & Network Controller using standard TCP/IP communication. Phantom powering through the network cables allows the software to detect devices that are not currently turned on or connected to the mains. This ensures very high reliability and redundancy levels while allowing connected amplifiers to remain on standby with no power consumption.
Cable connections can be daisy-chained for easier system setup. This also reduces total component costs, simplifies installation, and makes daily operation more convenient. There is no need to create a star topology using many switches as with, for example, an Ethernet system. Individual amplifier addresses do not need to be manually entered: you will automatically know where an individual amplifier resides in the network.
A daisy chain network-loop, in combination with the automatic addressing of devices, enables LAB GRUPPEN’s proprietary DeviceControl software to automatically create a precise picture of all connected devices and their relative position in the chain. By quickly creating a clear overview of the entire system configuration, DeviceControl provides flexible control over very large amplifier systems. Set-up time is minimized, and critical information is readily available for monitoring performance and solving problems during operation.
Via NomadLink, you can simultaneously monitor all metering data as well as any fault or warning indications.. NomadLink also allows you to remotely control power on and power off, as well as engage Mute and Solo functions on individual channels.

C SERIES Operation Manual rev 3.0.0

7

3. Installation
3. Installation
3.1. Unpacking
Carefully open the shipping carton and check for any noticeable damage. Every LAB GRUPPEN amplifier is tested and inspected before leaving the factory and should arrive in perfect condition. If any damage is discovered, please notify the shipping company immediately. Only the consignee may institute a claim with the carrier for damage incurred during shipping. Save the carton and packing materials for the carrier’s inspection. Should you ever need to ship the amplifier, always use the original packaging materials.
3.2. Mounting
The amplifier is two rack units high (2U) and will fit into a standard EIA 19″ rack. The depth is 343 mm (13.5″). The weight is approximately 8.5 kg (18.75 lbs.) depending on model type.
Free airflow from front-to-rear of the amplifier must be possible. Therefore, no doors or rack-lids should be mounted in front of or behind the amplifiers.
Amplifiers may be stacked directly on top of each other. There is no need for spacing in between units, though this might enable more convenient installation of cabling on the rear panel.
3.3. Cooling
The amplifier uses a forced-air cooling system with air flow from front to rear, maintaining a low operating temperature within defined limits. Front-to- rear airflow is preferred as cooler air is present at the front in nearly all applications. (This allows higher continuous power levels without encountering thermal problems.) Never attempt to reverse the airflow. The amplifier modules require a pressure chamber between the fans and heat sink, and this effect functions only in one direction.
Make sure that there is an adequate air supply in front of the amplifier, and that the rear of the amplifier has sufficient space to allow the exhaust to escape. If the amplifier is rack-mounted, do not use covers or doors on the front or rear of the rack.
Should a heat sink overheat, the temperature sensing circuits will mute the overheating channel. If the power supply overheats, another sensing circuit will mute all output channels until the power supply cools to safe operating temperature. An early warning before shut down will be indicated on the front panel LEDs, and a warning will be sent through the NomadLink network.
Always make sure that the dust-filters behind the detachable front panel are clean to ensure maximum possible airflow.
NOTE: If the amplifier malfunctions due to dirty dust filters, any required repairs are not covered by the warranty.
8 C SERIES Operation Manual rev 3.0.0

3. Installation

To calculate the maximum heat emission value when installing the amplifiers in rooms with an air-conditioning system, please refer to the Current Draw and Thermal Emissions specifications provided in the Appendix (section 6.4).

3.4. Operating Voltage
The label placed to the right of the mains cable on the rear of the amplifier indicates the AC mains voltage for which the amplifier is wired and approved: 115 V or 230 V. Connect the power cable only to the AC source type referred to on the label. The warranty will not cover damage caused by connecting to an incorrect type of AC mains.

LAB GRUPPEN switch-mode amplifiers use primary switching. Because the mains power is rectified directly in front of the transformer, the amplifier is insensitive to mains frequency. It may be connected to 50 or 60 Hz sources, and actually will operate on line frequencies from DC to 400 Hz.

If the power plug mounted at the factory is not appropriate for your country, it can be removed and the proper connector wired in its place as follows:

BLACK or BROWN WHITE or BLUE GREEN or GREEN/YELLOW

LIVE NEUTRAL EARTH (GROUND)

If you are not 100% confident of your competence to replace the mains plug, engage qualified personnel to do the job.

Once a suitable AC supply is connected, the amplifier can be turned on using the front-panel power switch. The amplifier then goes through a soft-start sequence as it self-checks its circuits. The fans will blow at high speed before dropping to idle, and the “power” LED will illuminate.

Inrush power is controlled and limited during “soft start”, enabling multiple amplifiers to be powered up simultaneously.

3.5. Grounding
There is no ground lift switch or terminal on the C Series amplifiers. The signal ground is always floating, via a resistor, to chassis and therefore the grounding system is automatic.
In the interests of safety, never disconnect the earth (ground) pin on the AC power cord.
Use balanced input connections to avoid hum and interference.

9 C SERIES Operation Manual rev 3.0.0

4. Product Overview
4. Product Overview
4.1. Front Panel Overview
The amplifier’s front panel presents the performance and fault condition indicators, power and remote switches, and a removable dust-filter cover. Four level potentiometers located behind the cover provide individual attenuation for the four amplifier channels. Range is 0 dB to – infinity. The 12 o’clock position indicates -10 dB attenuation. A label area is located beneath the LED display. To remove the dust-filter cover, loosen the thumbscrew at the far left. This allows removal of the dust-filters for cleaning, and provides access to channel attenuation. The front cover may be made “tamper resistant” by replacing the thumbscrew with a Philips head or safety Torx screw. Thread size is M3.
NOTE: Never operate the amplifier without the dust-filters in place.
4.1.1. Power on/off and remote switch
The Power on/off switch is located on the right side. A second switch, labeled “REMOTE,” is located above the Power switch. When the Remote switch is on, (with the mains connected and power switch turned on) the yellow LED above it will illuminate indicating that external power on/off commands from the NomadLink network connection will switch the amplifier on or off. When Remote is activated the amplifier will not switch on until a “Power On” command is received from the network. When the remote switch is off, it is not possible to switch amplifier power on or off using NomadLink network control.
10 C SERIES Operation Manual rev 3.0.0

4.1.2. Front-panel LED’s
The front-panel LED area includes the following indicators per channel:

4. Product Overview

· Temperature mute (Yellow constant) · VHF (Very High Frequency) protection active (output muted) (Yellow) · Mute channel via NomadLink network (2x Yellow) · CPL (Current Peak Limiter) active (Orange flashing) · CPL (Orange constant with output muted): constant (output muted): Low impedance / short circuit
detection · Fault (Yellow plus Orange) · VPL (Voltage Peak Limiter) active, VPL/Clip (Red) · 4 dB signal level (Green) · -10 dB signal level (Green) · -40 dB signal level (Green) · Hi-Imp open load detected (Red) · Bridge mode operation on (Yellow). Ch. A+B, C+D, E+F, G+H bridged.
(PWR) Power on (Green) (PAL) Power Average Limiter active (Red)
PAL
Option active (Yellow) NomadLink network active (Blue)
NOTE: When no VPL, CPL or PAL indicators are illuminated, and the VPL DIP- switch is set to maximum at the specified nominal load, the amplifier channel is able to deliver maximum rated output power.
NOTE: When the network is connected, the blue NomadLink LED will illuminate even when mains power is not connected. NomadLink receives phantom power from the network supplied by the NLB 60E.
11 C SERIES Operation Manual rev 3.0.0

4. Product Overview 4.2. Rear panel

C 88:4 200-240V 50-60Hz :2500W
Must be grounded/earthed Made in Sweden

44dB 41dB 38dB 35dB 32dB 29dB 26dB 23dB

141V*

71V

118V

59V

100V**

50V

85V

42V

CH D

Ser. N:o Removed!

BALANCED INPUTS

CH C

CH B

CH A

*100Vrms

**70Vrms

SPEAKER OUTPUTS
WIRING NORMAL: CLASS 2 BRIDGED: CLASS 3

Mains input 115 V and 230 V operation
(Not selectable)

NomadLink network In and Out on
EtherCon-housed RJ45 connections

DIP-switches for adjusting key features
(see below)

3-pole Phoenix input connectors

2-pole screw terminal output
connections

4.2.1. The DIP-switch features

The following features may be adjusted using the DIP-switches on the rear- panel of the amplifier. Gain – Set for all four or eight channels from +29 to +38 dB in 3 dB steps. Fan Masked – When on, engages the intelligent fan feature; fan speed is lowered when no signal is present. Bridge Mode – Switches the channel pairs into bridge mode operation. An automatic -6 dB gain compensation is applied. VPL – Voltage Peak Limiter adjustment is provided for 8 individual levels. Select the setting most appropriate for connected speakers. See Appendix for details. Mode – Select VPL mode between Hard and Soft. For channels driving sub-woofers and low-end frequencies, it is recommended to use the Hard setting for optimal operation. For mid- and high- frequency drivers, always select Soft.
12 C SERIES Operation Manual rev 3.0.0

4. Product Overview
4.3. NomadLink / Ethernet network setup
The amplifier includes, as a standard feature, internal facilities for the NomadLink monitoring and control network. All features of the NomadLink network are accessible via a PC running LAB GRUPPEN’s proprietary DeviceControl software. A single rackspace NLB 60E NomadLink Bridge & Network Controller accepts the TCP/IP data stream from the computer and converts it to the NomadLink protocols. Even when no computer is connected, the NLB 60E can initiate stand-alone power on/off and muting functions, as well as report any fault or warning conditions. The PC is connected to the NLB 60E using a standard Ethernet interface and a crossed Cat-5 cable (peer-topeer setup). If a hub or switch is in the network, standard “straight” Cat-5 cables must be used. The front and rear Ethernet connections on the NLB 60E can be used individually, but only one PC at a time running DeviceControl can access the subnet.
NOTE: Many newer laptop computers will allow peer-to-peer connection with the NLB 60E using a standard “straight” Cat-5 cable instead of a crossed cable.
The default fixed TCP/IP address of the NLB 60E is 192.168.1.166. The subnet mask is 255.255.255.0. For further system configuration details, please refer to instructions supplied with the NLB 60E unit. The NomadLink connections between amplifiers use standard “straight” Cat-5/RJ45 equipped cables.
NOTE: US National Differences cl.16.3 requires that NomadLink network cables must be rated VW-1.
The OUT port from the NLB 60E must be connected to the IN port of the first amplifier. The OUT port from the first amplifier in turn connects to the next amplifier’s IN port to form a daisy-chain The OUT port on the last amplifier is connected to the IN port on the NLB 60E to close the loop.
NOTE: There are performance limitations to cable lengths on a NomadLink network, both in terms of total cable length in the loop and between any two devices. These limitations follow standard Ethernet cabling protocols. Read the Operation and Performance chapter in this manual, or the Operation Manual supplied with the NLB 60E, to ensure the network is configured within these constraints.
TIP: Although the network will function as an open loop under most circumstances, it is strongly recommended that the loop be closed by connecting the last amplifier’s OUT port to the NLB 60E’s IN port. Doing so will improve redundancy and communication speed.
External contact closures and 24 V low/high triggers can be connected to the GPI connectors on the NLB 60E for control of fire-alarm systems or external power sequencers. For more details read the instructions supplied with the NLB 60E.
13 C SERIES Operation Manual rev 3.0.0

4. Product Overview

GENERAL NOMADLINK PURPOSE ETHERNET IN OUT INPUT, GPI
ETHERNET
1

1
Crossed RJ45 Ethernet cable between NLB 60E and PC. If bridge is connected to switch of HUB, use ” straight ” cable. PC can also be connected on front panel.
2
” Straight ” RJ45 cables between bridge and amplifiers

IN OUT NOMADLINK 2
IN OUT NOMADLINK

14 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5. Operation and performance
5.1. Introduction
The following sections provide comprehensive information on amplifier connection, setup, operation, and performance. The detailed information included here is essential to realizing the full functionality of the C Series amplifiers.
5.2. Operation precautions
· Make sure that the Power switch and the Remote switch on the amplifier front-panel are set to “off” before making any input, output or network connections, and also before manipulating the DIP-switches on the rear-panel.
· Make sure that the AC mains voltage is correct and matches the voltage printed on the rear-panel of the amplifier (115 V or 230 V).
· Make sure that no signal is present at the input to the amplifier when powering up. This could produce an unintentionally loud initial volume from the speakers.
5.3. Signal flow and headroom
5.3.1. Signal flow blocks
All C Series amplifiers have the same signal flow and feature set. The only difference is the amplifier’s maximum output current per channel.
The input stage of all C Series amplifiers has a high sensitivity to provide ample system headroom. This in effect means that the input stage is almost impossible to clip.
Overall amplifier input gain is adjusted using the input stage DIP-switches. Please note that the gain setting is global, affecting all four channels. Following the input stage, the dedicated level control on each channel allows signal attenuation from 0 dB to minus infinity.
The CPL (Current Peak Limiter) section dynamically limits the input signal based on three parameters: sensed current level, feedback from the output stage, and sensed voltage clip from the VPL (and output amplifier voltage clip if “Soft Clip” activated). This ensures that power output is maintained within the design limits of the amplifier.
The adjustable VPL (Voltage Peak Limiter) sets the maximum output voltage and therefore also the maximum output power. Eight (8) different voltage stages are available using the DIP-switches on the rear-panel. See table in Appendix section with VPL ratings at typical loads.
The sophisticated output section monitors faults and generates appropriate warnings, which are displayed on the amplifier front-panel and transmitted through the NomadLink network. These alerts allow the operator to
15 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
adjust system settings and thereby avoid problems. In the rare event that conditions are extraordinarily severe, the amplifier will shut down until the fault or problem setting has been rectified or adjusted. These sensing circuits are also employed to feed back voltage and current level information, via a side chain, to the limiters. Sensing circuits also transmit local amplifier module temperature and power supply temperature to the appropriate protection mechanisms. Read the Protection, Faults and Warnings section for further details.
5.3.2. Headroom, sensitivity and VPL / Gain settings
The input amplifier and limiter system is designed to accommodate extremes of performance. Typically, exceeding maximum input by much as +10 dB will only result in a 1% increase in distortion. The following schematics illustrate how the adjusable VPL and Gain circuitry affect input sensitivity and output power: The tables to the left of the drawing below show input sensitivity for a C 68:4 with an 8 ohm load and 141 V peak (max.) and 42 V peak (min.) respectively for the eight different gain stages between +23 dB and +44 dB. The resulting output power is displayed in dBu, Vrms and Watts in the tables to the far right. Complete input sensitivity tables for all VPL and Gain settings for as applicable to C Series models can be found at www.labgruppen.com. The headroom available through the input stage to the clip limiter is shown by the dotted lines as +10 dB at 141 V peak and +20.4 dB at 42 V peak. These lines illustrate the additional signal level that can be accepted at the input before any significant distortion will appear at the input stage.
NOTE: If you use the level potentiometer in the signal chain to reduce the level by an amount greater than the headroom relative to input sensitivity, AND you drive the amplifier to clip level, you are in danger of clipping the input stage before the current or voltage peak limiters are activated.
NOTE: When bridging two channels, you must add +6 dB to the input sensitivity to achieve maximum output voltage due to the automatic -6 dB gain compensation inserted by the amplifier.
16 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5.4. Audio Input and Output connections, setup and features
5.4.1. Balanced / Unbalanced Input connection
Two electronically balanced Phoenix-type inputs are available. Follow the +,­ and Ground labels when connecting the input signal.
If an unbalanced connection is desired this can be achieved by summing the minus (“COLD”) and Ground terminals and using the + terminal as the “HOT” signal. For the best possible performance, the summing of ground and minus wires should be done at the source unit end of the cable (e.g. a CD player). Four connectors are supplied for attaching cables to the inputs. The type of connector used is: Phoenix Contacts, Part number MSTB 2,5/3-STZ-5,08.
17 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
NOTE: When linking the same source signal to several input channels, be aware that there is a limit to the number of channels an output source can “drive”. A typical output source (e.g. a DSP crossover unit) can drive up to four amplifier channels before external line-drivers might be required to buffer the signal.
5.4.2. Output operation and connection
Screw-terminal connectors with + and ­ poles are provided at each channel output for connection of the speakers.
Make sure that the speaker cables are connected correctly and tightly, and that accurate polarity is maintained to all speakers in the system. As the amplifier outputs produce high voltage, do not connect or disconnect speaker cables when the mains power is on. Also, attach the safety cover on the speaker terminals for safe operation and to comply with electrical product approvals.
5.4.3. Output bridge mode
It is possible to bridge channels in pairs of two (A+B and C+D for example). When bridged, the input source must be connected to input A (A+B) or C (C+D) respectively. Output speaker cables must be connected to the plus pole on channel A or C and the minus pole on B or D. The main benefit of bridging the output is a doubling of output voltage. Bridging can be used to turn the amplifier into a three-channel amplifier with, for example, 2 x 1200 W and 1 x 2400 W at 4 ohms utilizing the C 48:4, or simply to achieve an impressive 200 Vrms supply per channel. Most power amplifier designs, when bridged, automatically introduce a +6 dB input gain boost which can lead the user to conclude that said amplifier delivers “more than double the power” when in bridge mode. This is clearly not the case, as the gain boost artificially enhances perceived power at the cost of headroom. The C Series amplifiers work on globally set constant gain, and automatically compensate the input gain by -6 dB. For example, if the amplifier is configured in a three-channel mode, then the selected gain is maintained from input to output on all channels.
18 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5.4.4. Amplifier Input Gain
All C Series amplifiers feature adjustable input gain. This versatility enables the amplifier to accommodate a multitude of system configurations with various input sources and speaker layouts. Amplifier gain is set globally for all four channels. The range is +23 dB to +44 dB in 3 dB steps. Individual channel fine level adjustment is available using the potentiometers on the front panel. The unique adjustable input gain feature of the C Series makes it easier to attain the optimum balance between headroom and signal-to-noise ratio in the signal path. A weak signal at the input might require the gain to be raised in order to achieve maximum output power with the lowest signal-to- noise ratio. A “hot” input signal, however, would require a lowering of the gain to avoid sending the amplifier into Voltage or Current clipping. See Appendix to review the table containing Gain versus VPL setting implications for input sensitivity and output power.
NOTE: Bridge mode operation automatically compensates by -6 dB, keeping all channels at the same gain.
5.4.4.1. Channel gain/level (front-panel pots)
Individual channel gain (level) may be adjusted using the potentiometers located on the front-panel behind the dust filter cover. Range is from 0 dB to -infinity in 21 steps. The attenuation is logarithmic, with the 12 o’clock position indicating -10 dB. Use your fingers or a screwdriver to adjust the potentiometers.
NOTE: If the level control is used to attenuate to a lower level than the headroom relative to input sensitivity AND the amplifier input is driven into clip, there is a danger of clipping the input stage before the current or voltage peak limiters are activated.
5.4.4.2. Amplifier sensitivity
Sensitivity is defined as how many volts (rms) or dBu (referred to 0.775 Vrms) are required to achieve full (maximum) output power. As the output power varies with the load impedance, 4 ohms is usually the common reference. Since C Series amplifiers are capable of providing multiple maximum output power levels through use of the VPL feature, many sensitivity calculations may be required for a single amplifier. We recommend use of the DeviceControl software to simplify this process. DeviceControl’s Device View page, used in combination with the DIP-switch settings display, will automatically produce a sensitivity calculation from the given data (VPL, Gain and load).
19 C SERIES Operation Manual rev 3.0.0

5. Operation and performance

5.4.5. Output Voltage Peak Limiter (VPL)
The Voltage Peak Limiter (VPL) is a unique feature in C Series amplifiers. It is used to select the maximum power available on each output channel. Four levels can be set using the DIP-switches on the amplifier’s rear panel.

V peak
141 118 100 85 71 59 50 42

Vrms
100 84 70 60 50 42 35 30

The values for VPL are displayed as maximum Voltage Peak. To translate Voltage Peak into Vrms, you must divide the Voltage Peak values by 1.41 (see table).
The VPL allows you to set the correct maximum output peak power for optimum performance with the connected speakers. The correct setting depends on the system type (low or high impedance) and the specific load connected to the channel. Since each channel can be configured to deliver either very high voltage peak power OR high current draw at low impedances, it is important to set the VPL correctly.
To configure an individual output channel for a constant voltage system, you simply adjust the DIP-switches to the desired voltage. However, when using an output for a low-impedance system ( 4, 8 or 16 ohms), then you may need to adjust the VPL to a lower setting to avoid either delivering excessively high continuous power to the speaker or overheating of the output channel through high current draw. For example, with a very “hot” continuous output signal, the temperature could rise to a critical level and activate Temp warning or even Temp Mute. Lowering the VPL setting usually will solve this situation.
If the Current Peak Limiter is active or indicates low impedance, lowering the VPL setting can rectify this situation as well.

5.4.6. Constant voltage 70 V and 100 V systems setup and operation
When using C Series amplifiers to drive constant voltage (high-impedance) speaker systems at 70 Vrms or 100 V peak, you can in most cases simply connect the speakers to the amplifier output terminals, select the correct VPL setting, and place the amplifier in service.

5.4.8. Output Current Peak Limiter (CPL)
The Current Peak Limiter (CPL) ensures that the amplifier will not be damaged by trying to deliver current to the outputs exceeding the physical limitations the transistors. The CPL keeps the amplifier within the Safe Operating Area. The CPL is non-adjustable and has different limit values depending on model type. The maximum output current values for the four C…X models are:

20 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
· C 88:4, 35.5 Arms per channel · C 68:4, 24.5 Arms per channel · C 48:4, 17.5 Arms per channel · C 28:4, 12 Arms per channel · C 16:4, 8.5 Arms per channel CPL activity is indicated by illumination of an orange LED for each channel on the front-panel. Warnings also are shown in the DeviceControl software’s GUI. A steadily illuminated orange CPL LED indicates a short circuit situation (or very low impedance). The output will mute for 6 seconds before measuring the output impedance again. This will continue until the short circuit is fixed, at which time the output will automatically un-mute. An input signal must be present to allow detection of short circuit or low impedance conditions.
TIP: If the CPL LED is steadily illuminated orange while the output is muted and the -4 dB signal LED is NOT on, then the amplifier output is detecting a short circuit or low impedance condition. The problem can be solved by checking input and output cables and examining the state of the loudspeaker load. If there is no short circuit present, then the condition may be rectified by lowering the VPL or input levels.
If the CPL indicator is lit continuously, then the amplifier is delivering excessive current and is being forced into a current limiting state (output muted).
21 C SERIES Operation Manual rev 3.0.0

5. Operation and performance

5.5. GPIO connection and operation
5.5.1. Introduction
The C Series amplifiers incorporate a sophisticated and comprehensive set of protection features. Faults and warnings are indicated on the front-panel and reported via the NomadLink network for indication on the DeviceControl GUI.

5.5.2. Safe Operating Area Detector (SOAD)
The Safe Operating Area Detector (SOAD) compares output voltage against output current to ensure that the output transistors are working inside their safe operating area.
The SOAD provides fault monitoring and input to the Current Peak Limiter (CPL). The SOAD has no dedicated indicator, and its operation is revealed only in conjunction with features such as the CPL.

5.5.3. Very High Frequency protection
All C Series amplifiers include protection circuits that detect continuous Very High Frequency (VHF) content in the input signals. The detection begins at approximately 10 kHz and moves upwards to include ultrasonic signals. If VHF signals are detected, the output will mute for 6 seconds before re- measuring. Once no continuing VHF signal is detected, the output un-mutes and returns to normal operation.
This feature recognizes that continuous full-scale VHF signals do not appear in “natural” sources such as music. Any such signals can therefore be considered as a fault when present. VHF protection is essential for avoiding damage to high frequency drivers.
The VHF protection operational area is dependent on output power level and frequency. The illustration below shows a decreasing threshold on the output power level, starting at approximately 10 kHz and rising with a -6 dB slope. This defines the VHF protection area. When continuous output power above the threshold line is detected the VHF protection becomes active.

Output power

VHF protection operation area – 6 dB slope

Max. Peak output power
Max. Continous output power

20 Hz Slow

10 kHz

20 kHz
Attack time VHF protection

30 kHz

Fast 20 Hz

10 kHz

20 kHz

30 kHz

22 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
The Attack time for the VHF protection is increasingly shorter at higher frequencies. For example, an ultrasonic continuous signal will cause the outputs to mute rapidly, where it will take several milliseconds for a 10 kHz continuous signal to trigger the output mute. This is shown in the illustration above. The VHF protection is NOT a limiter and does not alter the amplifier’s frequency response. It is implemented solely to detect continuous VHF content. The amplifier will always pass VHF peaks at full power, with no effect on musical “transients”. The VHF protection is indicated by a yellow LED on the amplifier front-panel, with output muting for six seconds when in action. It is reported as a fault via the NomadLink network on the DeviceControl GUI.
TIP: If you bench test the amplifier using a continuous, full scale sine-wave input above 10 kHz, the VHF protection will activate and prevent measurement of full peak output power. (Output will be muted long before maximum output power is attained.) To measure the true peak output power, use a burst signal.
5.5.4. DC protection
DC protection is implemented on each output to prevent damage to connected loudspeakers. DC present at the output will trigger muting and illuminate the fault LED indicator. Any DC present at the output indicates a hardware malfunction that requires servicing of the amplifier.
5.5.5. High-impedance warning (open load)
A high-impedance (open load) condition is indicated when an input signal above approximately -29 dB is detected and no functioning loudspeakers are connected to the amplifier. The fault in indicated by a red Sig/Hi-imp LED. The indicator is green when a valid load is present under the same input signal conditions.
NOTE: Since the high-impedance detection initially triggers only when the input signal rises above -29 dB, it might cause the indicator to first turn green, and then red, even in situations where no speaker is connected.
5.5.6. Low-impedance protection (short circuit)
A low-impedance or short-circuit fault is detected when current draw is high (Current Peak Limiter active) and when, simultaneously, output signal is low (-4 dB LED does not illuminate). When this occurs, the amplifier protects the output stage from damage by muting the output signal and bypassing the circuits. Indication of this fault is a constant orange illumination of the Current Peak Limiter (CPL) LED on the front-panel. The protection will sequence
23 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
at six second intervals to re-measure conditions. If the low-impedance fault is no longer detected, the amplifier will un-mute.
NOTE: If the CPL turns constant orange, the output is muted, and the -4 dB signal LED is ON, then the amplifier has gone into maximum current protection. This situation is caused by an excessive input signal and is not due to a short circuit. Turn down the input signal to avoid or remedy this situation.
5.5.7. Temperature protection
Thermal measurement points are provided on each output channel as well as on the power supply. If these sensors detect temperatures above the specified maximums, a high temperature warning will be indicated by a flashing Temp LED on the front panel. The warning also will be transmitted to the Device Control GUI via the NomadLink network. As the amplifier approaches a thermal protection threshold, the warning LED sequence will start with short “ontime” bursts. If the amplifier continues to overheat and approaches the temperature limit, the flashing sequence will be defined by longer and longer on-time bursts until the protection mode is activated. If the temperature becomes too high to continue safe operation, the overheated output channel(s) will be muted until the temperature returns to an acceptable level. Fully active temperature protection (with muting) is indicated by a constantly illuminated Temp LED. It will also be indicated as a fault via the NomadLink network on the DeviceControl GUI. Temperature measurements will continue at six second intervals. The output will un-mute when the channel or power supply returns to a safe operating temperature.
5.5.8. Power Average Limiter (PAL)
The Power Average Limiter (PAL) controls the current-drawing relationship between the power supply and the mains inlet. PAL limits the maximum average power consumption according to the power supply capabilities, ensuring that the PSU will not overload. In addition, in the larger models that potentially could pull more current from the mains than the mains fuses are specified to handle (more than 16 A), PAL limits the amplifier’s maximum current draw to prevent blowing the mains fuse.
5.5.9. Soft-Start
High powered amplifiers with inadequate inrush limiting can pull considerable current from the mains at turnon. This can result in fast acting mains breakers tripping. Such is not the case with C Series amplifiers in most circumstances.. The C Series amplifiers have very low inrush power as the capacitors are charged slowly, and in a controlled manner, ensuring that breakers will not trip.
24 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
Several amplifiers will, under normal conditions, be able to be powered up simultaneously. If you do experience problems powering up multiple amplifiers simultaneously (normally experienced only in very large installations), use the NomadLink network and the NLB60E to establish a power sequence with pre- set delays before the start-up of each subsequent amplifier.
5.6. Front-panel monitoring
5.6.1. Level indicators
Four signal/level/clip LEDs per channel are contained on the C Series front panels
· Orange CPL (Current Peak Limiter) flashing indicates signal exceeds the limits of the output devices and limiting is in effect.
· Red VPL/CLIP indicates that the signal has exceeded maximum output voltage. (Maximum voltage is determined by rear-panel VPL settings.)
· Green – 4 dB indicates output signal has reached this level. · Green – 10 dB indicates output signal has reached this level. · Signal / Hi-Imp (Green/red) indicates an output signal above -44 dB. If it turns RED, this indicates that a
high-impedance (“open” connection) has been detected at the output. This can be a fault such as a disconnected cable or malfunctioning loudspeaker driver. However, it could indicate acceptable high impedance, such as a sub-bass enclosure with high impedance at a certain frequency. When the -10 dB signal LED is on AND the Hi-Imp LED turns red then the amplifier has detected an open load (no speaker is connected). For more detailed signal level indications use the DeviceControl software application.
25 C SERIES Operation Manual rev 3.0.0

5. Operation and performance

5.6.2. Level adjust
Level adjust potentiometers (one per channel) are located behind the removable dust-filter cover on the amplifier’s front-panel. It is not possible to adjust the level settings with the cover in place.

Step
1 (Min) 2 3 4 5 6 7 8 9 10 11

Attenuation
-Inf. dB -Inf. dB -50 dB -40 dB -35 dB -21.5 dB -21.5 dB -14.7 dB -12.9 dB -11.4 dB -10.0 dB

Step
12 13 14 15 16 17 18 19 20 21 (Max)

Attenuation
-8.7 dB -7.4 dB -6.0 dB -4.5 dB -2.7 dB -0.6 dB -0.3 dB -0.1 dB
0 dB 0 dB

Level adjust potentiometers (one per channel) are located behind the removable dust-filter cover on the amplifier’s front-panel. It is not possible to adjust the level settings with the cover in place.
The potentiometer’s operational range is 0 dB to -infinity in 31 steps. Attenuation is logarithmic, with 12 o’clock position being -10 dB. See table to the above with increments.
It is not possible to adjust the individual channel attenuation from the NomadLink network or elsewhere on the amplifier.
Use fingers or a screwdriver to adjust the potentiometers.

5.6.3. Mute indication
Individual channel Mute is indicated by illumination of the two yellow LEDs at the top of the channel’s LED bargraph. If both LEDs are illuminated and all other indications are normal, then the channel has been muted by a command from the NLB 60E front-panel or the DeviceControl application. Otherwise, a Mute could indicate a fault condition.

5.6.4. Performance, Warning and Fault indicators
· Power on/off (green) indicates that mains power is switched on. · NomadLink (blue) indicates that the network is connected. The NomadLink LED will light up even before the
mains power is connected and switched on as it takes phantom power from the NomadLink network cable. · Bridge mode (yellow) indicates if two channels are bridged using the DIP-switch on the rear panel.
26 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
· CPL, Current Peak Limiter (orange), when flashing indicates the maximum possible current draw has been reached.
· CPL, Current Peak Limiter (orange), when constant indicates excessive current draw caused by a short circuit on the output or very low operational impedance. When detected, the output will mute for six seconds before re- measuring the output impedance. This will continue until the short circuit is removed. CPL remains constant orange in a fault condition only when an input signal is present.
· Temperature (yellow) warning is indicated by a flashing LED. If the amplifier goes into thermal protect (output muted) the LED illuminates constant yellow.
· VHF, Very High Frequency protection (yellow), indicates that potentially harmful continuous high frequencies have been detected on the input signal. The output is muted.
· PAL, Power Average Limiter (red), indicates that the amplifier is limiting because the power supply and/or the mains-inlet fuse has reached maximum capability.
· Hardware fault is indicated when both the CPL and VHF indicators light up simultaneously. The amplifier requires servicing before being placed back in operation.
5.7. NomadLink network and DeviceControl software
5.7.1. NomadLink network in the amplifiers
All C Series amplifiers are equipped with the proprietary NomadLink network interface. This includes two RJ45 connections in standard housings: one IN and one OUT. Use standard straight Cat-5 Ethernet cables with RJ45 connectors to connect the amplifier to the NLB 60E NomadLink Bridge and Network Controller or to daisy-chain multiple amplifiers.
NOTE: It is very important that two IN or two OUT ports are NEVER connected to each other. This will cause the NomadLink communication and DeviceControl to exhibit erratic behavior and display inaccurate data. However, this situation will not damage the amplifier circuitry.
Up to 60 amplifiers can be connected to one NLB 60E in a daisy-chain or closed loop. When the NLB 60E is powered up, the NomadLink network receives phantom power. This causes the blue NomadLink LED on the amplifier front panel and the NomadLink LED on the rear panel to light up. NomadLink is active even when the amplifier has mains power disconnected or is not yet powered up. The amplifier does not have a stand-by power supply for the network. The network is solely powered from the NLB 60E. Should an amplifier fail or be inadvertently disconnected from the mains, network integrity is fully maintained and all amplifiers remain visible on the system.
27 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5.7.2. Connection and setup
The NomadLink network requires use of an NLB 60E NomadLink Bridge & Network Controller. The NomadLink network is established by connecting the NLB 60E OUT port to the first amplifier’s IN port. Then a daisy-chain is established by connecting the first amplifier’s OUT port to the next amplifier’s IN port, and so on. If a closed loop network is desired for improved redundancy (highly recommended), the last amplifier’s OUT port must be connected to the NLB 60E’s IN port. For all connections, straight Cat-5 RJ45-equipped Ethernet cables should be used.
TIP: Optimal NomadLink performance can only be assured when using Cat-5 cables. However, as NomadLink is only using two wires + ground for communication and phantom power it is possible to create converters from RJ45 to, for example, XLR connectors using 2-wire shielded cable. The NomadLink network can then be operated using a standard tie-line in a multicore signal distribution system. See the drawing below for an example of how to create a converter.
NOTE: If any cable format or connection other than Cat-5 (or better) and RJ45 is utilized, network performance may be compromised. In this event LAB GRUPPEN cannot guarantee that the NomadLink network will be fully operational.
5.7.3. NomadLink network cable lengths
The connection between the NLB 60E and your PC is a standard Ethernet network running the TCP/IP protocol. Cable distances between NLB 60E and your PC follow standard rules for Ethernet systems. In situations where the amplifiers and the NLB 60E will be positioned in different locations at some distance from each other, or where groups of amplifiers within a single subnet with up to 60 units will be installed with a distance in between, these general rules applying to Ethernet cabling limitations may be considered. · Rule 1: The maximum cable length in between any two devices may not exceed 300 meters / 980 feet. · Rule 2: In a non-closed-loop daisy-chained subnet the total maximum cable length is 400 meters / 1300 feet. · Rule 3: In a closed-loop subnet the total maximum cable length is 700 meters / 2300 feet.
28 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5.7.4. Ethernet network cable lengths
The connection between the NLB 60E and your PC is a standard Ethernet network running the TCP/IP protocol. Cable distances between NLB 60E and your PC follow standard rules for Ethernet systems. Contact your an IT expert or an authoritative source for more details. Below are typical examples of NomadLink network setups:
NomadLink daisy chain configuration NomadLink closed loop configuration
NomadLink closed loop daisy chain configuration
NomadLink dual daisy chain closed loop configuration
29 C SERIES Operation Manual rev 3.0.0

5. Operation and performance
5.7.5. DeviceControl software
DeviceControl is LAB GRUPPEN’s proprietary software application for monitoring and controlling networked FP+ Series and other LAB GRUPPEN NomadLink-ready power amplifier. DeviceControl runs on a Windows PC, which connects via Ethernet to the NLB 60E NomadLink Bridge & Network Controller. DeviceControl provides comprehensive monitoring of amplifier status as well as control of amplifier power on/off and individual channel mute and solo functions. Please review the DeviceControl Operation Manual for more detailed information.
5.7.6. Third Party Control and Monitoring Capabilities
The NLB 60E NomadLink Bridge & Network Controller can be integrated with third party control systems via its Ethernet connection. All amplifier control functions, fault and warning notifications that would otherwise be displayed via the DeviceControl software can be replicated in a third party control GUI. Please note that NLB 60E Firmware Ver 2.1.0 (or later) must be used in order to utilize the third party control and monitoring capabilities of the NomadLink network. Both the firmware package and the control protocol documentation, which describes the functionality and programming requirements for third party integration, can be found under the Software & Firmware section of our website at: http://labgruppen.com/index.php/support/software_firmware/
30 C SERIES Operation Manual rev 3.0.0

6. Appendix
6. Appendix
6.1. Maintenance
During normal operation your C Series amplifier will provide trouble-free service. The only user maintenance required is to periodically vacuum clean the foam dust filters behind the front grille.
In some extreme cases it may be necessary for authorized service personnel to clean the inside of the amplifier. These conditions usually occur after prolonged use in extreme environments such as those using “cracked oil” smoke machines. If you are using your amplifier in a heavy duty application, it is recommended to have your amplifier serviced every three years purely as a preventative action.
6.2. FAQ
Following are common questions asked about LAB GRUPPEN C Series power amplifiers together with helpful answers.
Q: What is the input sensitivity of the amplifiers? A: Input sensitivity is calculated from the amplifier gain, maximum output voltage and load. As gain and output voltage are adjustable in C Series amplifiers, you need to look this information up in a table found in the Appendix section of this manual. Input sensitivity also is automatically calculated in the DeviceControl software application.
Q: What are the maximum cable lengths allowed when using the NomadLink network? A: NomadLink uses a daisy-chain topology to connect amplifiers and an NLB 60E in a network. Standard RJ45equipped Cat-5 cables are used throughout. The daisy chain may be made into a closed-loop by connecting a return cable to the NLB 60E from the last amplifier.
General rules of cable lengths: · The maximum cable length in between any two devices may not exceed 300 meters / 980 feet. · In a non-closed-loop daisy- chained subnet the maximum cable length is 400 meters / 1300 feet. · In a closed-loop subnet the maximum cable length is 700 meters / 2300 feet.
Exceeding these limits may result in lost contact with the devices, or loss of phantom powering due to cable resistance.
Q: How long can cable-runs be on the Ethernet network connecting the NLB 60E to the PC? A: On the Ethernet side, normal Ethernet cable limits apply. This is typically a maximum of 80 meters / 300 feet between each device. Follow standard installation procedures for Ethernet. Distances beyond 100 meters may require use of a repeater, a format converter, or optical cables.
Q: Why is the NomadLink network a closed-loop topology? A: Technically speaking, the closed loop is optional. The purpose of closing the loop is primarily to provide a secondary path to the amplifiers. If cables are broken or disconnected in either direction, all amplifiers still may be addressed by the network.
31 C SERIES Operation Manual rev 3.0.0

6. Appendix
Q: How can I be sure that no protection circuits or safety functions interfere with the output signal? A: If no Clip or Warning LEDs on the front panel light up, you can be fully confident that the rated maximum output power in the full frequency range is available for your speakers. No limiting or gain-reduction takes place without a warning or fault indication.
6.3. Additional documentation
In case you didn’t find what you were looking for in this Operation Manual, check out the website at www.labgruppen.com, where you can find a multitude of additional documentation for C Series.
32 C SERIES Operation Manual rev 3.0.0

6. Appendix

6.4. Current Draw and Thermal Dissipation Specifications
The following tables contain information on measured current consumption as well as calculated heat dissipation during normal operation (1/8 rated power); and during extreme heavy duty operation (1/4 rated power).

Level

Load

C 88:4

Rated power

Line Current *2)

Watt *1)

Thermal Dissipation

115 VAC

230 VAC

In

Out

Dissipated BTU/hr

kCal/hr

Standby with remote power off via NomadLink Powered on, idling.

Pink noise (1/8 rated power)

8 / Ch. 16 / Bridged 4 / Ch. 8 / Bridged 2 / Ch. 4) 4 / Bridged 4) 100 V / Ch. 200 V / Bridged

1250 x 4 2500 x 2 2100 x 4 4200 x 2 2200 x 4 4400 x 2 2000 x 4
N/R

Amp (I)

17.6

8.8

0 139
1177

0 0
Watt
625

0 139
552

0

0

475

120

1884

475

27

13.5

1914

1050

864

2949

743

33.6

16.8

2221

1150

1071

3655

921

26.2

13.1

1838

1000

838

2860

721

Pink noise (max power) *3)

8 / Ch. 16 / Bridged 4 / Ch. 8 / Bridged 2 / Ch. 4 / Bridged 100 V / Ch. 200 V / Bridged

1250 x 4 2500 x 2 2100 x 4 4200 x 2 2300 x 4 4600 x 2 2000 x 4 4000 x 2

30.0 30.0 30.0 30.0

16.0

2006/2140 1145/1221 860/918 2935/3133 739/789

16.0

2127/2268 1230/1312 896/956 3058/3263 770/822

16.0

1983/2115 1016/1084 966/1031 3297/3519 831/886

16.0

5992/2236 3467/1294 883/942 3014/3216 759/810

Mains connector, 230 V CE version Mains connector, 115 V ETL version

16 A, CEE7 30A Twist Lock

1) The amplifier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specified here is what is known as the “Active Power” in the amplifier providing useful, real-world values of power consumption and heat dissipation.
2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
3) Figures measured at maximum sustainable power without tripping the mains fuse. Listed separately for 30 A/115 V and 16 A/230 V operation. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is momentarily in excess of max. ratings.
4) Italics used for conditions that, if sustained over long time periods, may trigger the mains breaker. Therefore these measurements should not be used when calculating cooling requirements as they cannot be sustained by the mains breaker over time.

·

·

·

33 C SERIES Operation Manual rev 3.0.0

6. Appendix

Level

Load

C 68:4

Rated power

Line Current *2)

115 VAC 230 VAC

In

Watt *1)

Out

Dissipated

Thermal Dissipation

BTU/hr

kCal/hr

Standby with remote power off via NomadLink Powered on, idling.

Pink noise (1/8 8 / Ch. rated power) 16 / Bridged
4 / Ch. 8 / Bridged 2 / Ch. 4 / Bridged 100 V / Ch.
200 V / Bridged

1200 x 4 2400 x 2 1700 x 4 3400 x 2 1200 x 4 2400 x 2 1600 x 4 3200 x 2

Amp (I)

16.0

8.0

0 133
1123

0 0
Watt
600

0 133
523

0

0

454

114

1784

450

22.4

11.2

1578

850

728

2484

626

21.2

10.6

1378

600

778

2655

669

21.0

10.5

1463

800

663

2262

570

Pink noise (1/4 rated power) *3)

8 / Ch. 16 / Bridged 4 / Ch.

8 / Bridged

4 / Ch.

8 / Bridged

100 V / Ch.

200 V / Bridged

1200 x 4 2400 x 2 1700 x 4 3400 x 2 1200 x 4 2400 x 2 1600 x 4 3200 x 2

32.6

16.3

2429

1600

829

2829

713

38.8

19.4

2697

1700

997

3402

857

35.2

17.6

2296

1200

1096

3740

942

35.4

17.7

2605

1600

1005

3429

864

Mains connector, 230 V CE version Mains connector, 115 V ETL version

16 A, CEE7 20 A / 5-20P

1) The amplifier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specified here is what is known as the “Active Power” in the amplifier providing useful, real-world values of power consumption and heat dissipation.
2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
*3) Figures measured at maximum power before amplifier protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess of max. ratings.

·

·

·

34 C SERIES Operation Manual rev 3.0.0

6. Appendix

Level

Load

C 48:4

Rated power

Line Current *2)

115 VAC 230 VAC

In

Watt *1)

Out

Dissipated

Thermal Dissipation

BTU/hr

kCal/hr

Standby with remote power off via NomadLink Powered on, idling.

Pink noise (1/8 8 / Ch. rated power) 16 / Bridged
4 / Ch. 8 / Bridged 2 / Ch. 4 / Bridged 100 V / Ch.
200 V / Bridged

1000 x 4 2000 x 2 1200 x 4 2400 x 2
600 x 4 1200 x 2 900 x 4 1800 x 2

Amp (I)

0

0

0

0

0

123

0

123

420

106

Watt

13,8

6,9

945

500

445

1518

383

17,4

8,7

1171

600

571

1948

491

12,4

6,2

769

300

469

1600

403

13,2

6,6

840

450

390

1331

335

Pink noise (1/4 rated power) *3)

8 / Ch. 16 / Bridged 4 / Ch.

8 / Bridged

4 / Ch.

8 / Bridged

100 V / Ch.

200 V / Bridged

1000 x 4 2000 x 2 1200 x 4 2400 x 2
600 x 4 1200 x 2 900 x 4 1800 x 2

28,2

14,1

2116

1333

783

2670

673

30,6

15,3

2168

1200

968

3303

832

21,6

10,8

1368

600

768

2620

660

26,4

13,2

1827

1200

627

2139

539

Mains connector, 230 V CE version Mains connector, 115 V ETL version

16 A, CEE7 20 A / 5-20P

1) The amplifier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specified here is what is known as the “Active Power” in the amplifier providing useful, real-world values of power consumption and heat dissipation.
2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
*3) Figures measured at maximum power before amplifier protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess of max. ratings.

·

·

·

35 C SERIES Operation Manual rev 3.0.0

6. Appendix

Level

Load

C 28:4

Rated power

Line Current *2)

115 VAC 230 VAC

In

Watt *1)

Out

Dissipated

Thermal Dissipation

BTU/hr

kCal/hr

Standby with remote power off via NomadLink Powered on, idling.

Pink noise (1/8 8 / Ch. rated power) 16 / Bridged
4 / Ch. 8 / Bridged 2 / Ch. 4 / Bridged 100 V / Ch.
200 V / Bridged

700 x 4 1400 x 2
700 x 4 1400 x 2
300 x 4 600 x 2 700 x 4 1400 x 2

Amp (I)

0

0

0

0

0

123

0

123

420

106

Watt

11.6

5.8

727

350

377

1286

324

13.0

6.5

775

350

425

1450

365

9.4

4.7

529

150

379

1293

326

10.4

5.2

663

350

313

1068

269

Pink noise (1/4 rated power) *3)

8 / Ch. 16 / Bridged 4 / Ch.

8 / Bridged

4 / Ch.

8 / Bridged

100 V / Ch.

200 V / Bridged

700 x 4 1400 x 2
700 x 4 1400 x 2
300 x 4 600 x 2 700 x 4 1400 x 2

24.0

12.0

1589

933

20.8

10.4

1359

700

14.0

7.0

843

300

21.4

10.7

1458

933

656

2237

564

659

2249

567

543

1853

467

525

1790

451

Mains connector, 230 V CE version Mains connector, 115 V ETL version

16 A, CEE7 20 A / 5-20P

1) The amplifier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specified here is what is known as the “Active Power” in the amplifier providing useful, real-world values of power consumption and heat dissipation.
2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
*3) Figures measured at maximum power before amplifier protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess of max. ratings.

·

·

·

36 C SERIES Operation Manual rev 3.0.0

6. Appendix

Level

Load

C 16:4

Rated power

Line Current *2)

115 VAC 230 VAC

In

Watt *1)

Out

Dissipated

Thermal Dissipation

BTU/hr

kCal/hr

Standby with remote power off via NomadLink Powered on, idling.

Pink noise (1/8 8 / Ch. rated power) 16 / Bridged
4 / Ch. 8 / Bridged 2 / Ch. 4 / Bridged 100V / Ch.
200V / Bridged

400 x 4 800 x 2 300 x 4 600 x 2 n.r. n.r. 400 x 4 800 x 2

Amp (I)

0

0

0

0

0

129

0

129

440

111

Watt

8.6

4.3

526

200

326

1112

280

8.2

4.1

485

150

335

1143

288

7.6

3.8

463

200

263

897

226

Pink noise (1/4 rated power) *3)

8 / Ch. 16 / Bridged 4 / Ch.

8 / Bridged

2 / Ch.

4 / Bridged

100 V / Ch.

200 V / Bridged

400 x 4 800 x 2 300 x 4 600 x 2 n.r. n.r. 400 x 4 800 x 2

16.2 15.2

8.1

1046

533

7.6

953

400

14.4

7.2

944

533

513

1749

441

553

1887

475

411

1401

353

Mains connector, 230 V CE version Mains connector, 115 V ETL version

16 A, CEE7 15 A / 5-15P

1) The amplifier’s PSU operates as a non-resistive load, so the calculation “Volts x Amps = Watts” would not be correct. Instead, measured and specified here is what is known as the “Active Power” in the amplifier providing useful, real-world values of power consumption and heat dissipation.
2) Current draw figures measured at 230 V. 115 V figures are 230 V figures multiplied by two.
*3) Figures measured at maximum power before amplifier protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be tripped even if operation is in excess of max. ratings.

·

·

·

37 C SERIES Operation Manual rev 3.0.0

7. Technical Specifications

7. Technical Specifications

Model Number of channels Peak total output all channels driven Peak output voltage per channel Max. output current per channel
Max Output Power 16 ohms per ch. (all ch.’s driven) 8 ohms per ch. (all ch.’s driven) 4 ohms per ch. (all ch.’s driven) 2 ohms per ch. (all ch.’s driven) Hi-Z per ch. (all ch.’s driven): 70 Vrms / 100 V peak Hi-Z per ch. (all ch.’s driven): 100 Vrms / 141 V peak
16 ohms Bridged per ch.1) 8 ohms Bridged per ch.1) 4 ohms Bridged per ch.1) 2 ohms Bridged per ch.1) Hi-Z Bridged per ch.1): 140 Vrms / 200 V peak

C 88:4 4 8800 W 141 V 35.5 Arms

C 68:4 4 6800 W 141 V 24.5 Arms

C 48:4 4 4800 W 141 V 17.5 Arms

C 28:4 4 2800 W 141 V 12 Arms

C 16:4 4 1600 W 141 V 8.5 Arms

C 20:8X 8 2000 W 100 V 8 Arms

650 W 1250 W 2100 W 2200 W 2200 W 1700 W
2500 W 4200 W 4400 W n.r 4) 4400 W

650 W 1200 W 1700 W 1200 W 1600 W 1200 W
2400 W 3400 W 2400 W n.r 4) 3200 W

625 W 1000 W 1200 W 600 W 1100 W 900 W
2000 W 2400 W 1200 W n.r 4) 1800 W

600 W 700 W 700 W 300 W 700 W 700 W
1400 W 1200 W 600 W n.r 4) 1400 W

400 W 400 W 300 W 140 W 400 W 400 W
800 W 600 W n.r 4) n.r 4) 800 W

250 W 250 W 250 W 125 W 250 W n.a.
500 W 500 W 250 W n.r 4) 500 W

C 10:8X 8 1000 W 100 V 5.6 Arms
125 W 125 W 125 W 60 W 125 W n.a.
250 W 250 W 125 W n.r 4) 250 W

C 10:4X 4 1000 W 100 V 8 Arms
250 W 250 W 250 W 125 W 250 W n.a.
500 W 500 W 250 W n.r 4) 500 W

C 5:4X 4 500 W 100 V 5.6 Arms
125 W 125 W 125 W 60 W 125 W n.a.
250 W 250 W 125 W n.r 4) 250 W

Performance with Gain: THD 20 Hz – 20 kHz for 1 W THD at 1 kHz and 1 dB below clipping Signal To Noise Ratio Channel separation (Crosstalk) at 1 kHz Frequency response (1 W into 8 ohms) +0/-3 dB Input impedance Common Mode Rejection (CMR) Output impedance @ 100 Hz
Voltage Peak Limiter (VPL), max. peak output VPL, selectable per ch. 3) VPL, when bridged 1) 3) Voltage Peak Limiter mode (per ch.)

35 dB and VPL: 100 V / C 88:4: 35 dB and VPL: 141 V <0.1% <0.05% >112 dBA >70 dB 6.8 Hz – 34 kHz 20 kOhm >50 dB, 20 Hz – 20 kHz 30 mOhm
141, 118, 100, 85, 71, 59, 50, 42 V 282, 236, 200, 170, 142, 118, 100, 84 V Hard / Soft

32 dB and VPL: 100 V <0.1% <0.05% >112 dBA >70 dB 6.8 Hz – 34 kHz 20 kOhm >50 dB, 20 Hz – 20 kHz 48 mOhm
100, 63, 45, 32 V 200, 126, 90, 64 V Hard / Soft

Gain and Level Amplifier gain selectable (all channels) 1) ­ rear-panel switches Default gain
Level adjustment (per ch.)

23, 26, 29, 32, 35, 38, 41, 44 dB
35 dB Front-panel potentiometer, 21 position detented from -inf to 0 dB, hidden behind security panel/dust filter grille

29, 32, 35, 38 dB
32 dB Front-panel potentiometer, 21 position detented from -inf to 0 dB, hidden behind security panel/dust filter grille

Connectors and switches Input connectors (per ch.) Output connectors (per ch.) Output bridge mode High pass filter NomadLink network Intelligent fans (on/off) Power on/off and Remote enable on/off Cooling General Purpose Outputs (GPO) General Purpose Inputs (GPI)

3-pin Phoenix, electronically balanced Barrier strip 2-pole screw terminals A+B and/or C+D, inputs A and C are input source N/A On board, 2 x RJ45 connectors IN and OUT Yes, depending on presence of output signal Individual switches on front panel Two fans, front-to-rear airflow, temperature controlled speed N/A N/A

3-pin Phoenix, electronically balanced Barrier strip 2-pole screw terminals A+B, C+D, E+F, G+H, inputs A, C, E, G are signal source Fixed at 35 Hz, switchable per channel On board, 2 x RJ45 connectors, IN and OUT Yes, depending on presence of output signal Individual switches on front panel Two fans, front-to-rear airflow, temperature controlled speed Contact Closure types, 2-pole Phoenix Contact Closure types, 2-pole Phoenix

Front-panel indicators Common
Per channel

NomadLink Network; Power Average Limiter (PAL)2); Power on Signal present / High-impedance; -10 dB and -4 dB output signal;Voltage Peak Limiter (VPL); Current Peak Limiter (CPL): Very High Frequency (VHF); High temperature; Fault; Mute

NomadLink Network; Power Average Limiter (PAL)2); Power on Signal present / High-impedance; Voltage Peak Limiter (VPL); Current Peak Limiter (CPL): Very High Frequency (VHF); High temperature; Fault; Mute

Power Operating voltage, 230 V / 115 V nominal Minimum power-up voltage, 230 V / 115 V Power Average Limiter (PAL) 2) Power Factor Correction (PFC) Soft- start / Inrush Current Draw Mains connector 5)
Dimensions Weight Finish
Approvals

130-265 V / 65 -135 V 6) 171 V / 85 V Yes No Yes / max. 5 A 230 V CE: 16 A, CEE7; 115 V ETL: 20 A / NEMA 5-20P; C16:4: 15A/NEMA 5-15P

Universal power supply 65-265 V 80 V Yes Yes Yes / max. 5 A IEC Inlet

W: 483 mm (19″), H: 88 mm (2 U), D: 343 mm (13.5″) 12 kg (26.4 lbs.) Black painted steel chassis with gray painted steel front

W: 483 mm (19″), H: 88 mm (2 U), D: 343 mm (13.5″) 8.5 kg (18.75 lbs.) Black painted steel chassis with gray painted steel front

CE, ANSI/UL 60065 (ETL), CSA C22.2 NO. 60065, FCC

CE, ANSI/UL 60065 (ETL), CSA C22.2 NO. 60065, FCC

Note 1): Automatic -6 dB gain compensation when bridging channels. Ch.’s A+B and/or C+D, E+F, G+H, can be bridged individually. Note 2): PAL can reduce the maximum output power to keep the power supply operating safely, and/or to prevent excessive current draw tripping the mains breaker. Refer to Operation Manual. Note 3): For sine waves, peak voltage output values translate to Vrms with the formula V/1.41 = Vrms. E.g. 100 V peak equals app. 70 V peak. Hence, outputs can be set for high-impedance loads without
requiring a transformer. Note 4): Regarding n.r. (not recommended) notes: The amplifier will be fully operational in bridge-mode into 2 ohm and high impedance (Hi-Z) loads, but due to physical constraints in the construction, the max.
output power will not be significanty higher than running individual channels and therefore this mode of operation is not recommended. Note 5): C 88:4 mains connector: 30 A Twist lock. Note 6): Separate 230 V or 115 V versions available. Not selectable on the amplifier.
All specifications are subject to change without notice.

38 C SERIES Operation Manual rev 3.0.0

8. Warranty and Support
8. Warranty and Support
8.1. General
This product is manufactured by LAB GRUPPEN, and it is warranted to be free from any defects caused by components or factory workmanship, under normal use and service, for a period of six (6) years from date of purchase from an authorized LAB GRUPPEN dealer. If the product fails to perform as specified during the warranty period, LAB GRUPPEN will undertake to repair, or at its option, replace this product at no charge to its owner, provided the unit is returned undamaged, shipping prepaid, to an authorized service facility or to the factory. This warranty shall be null and void if the product is subjected to: repair work or alteration by a person other than those authorized by us; mechanical damage including shipping accidents; war, civil insurrection, misuse, abuse, operation with incorrect AC voltage; incorrect connections or accessories; operation with faulty associated equipment; or exposure to inclement weather conditions. Damage due to normal wear and tear is not covered by the warranty. Units on which the serial number has been removed or defaced will not be eligible for warranty service. LAB GRUPPEN shall not be responsible for any incidental or consequential damages. LAB GRUPPEN’s responsibility is limited to the product itself. LAB GRUPPEN takes no responsibility for any loss due to cancellation of any events, or rent of replacement equipment or costs due to a third party’s or customer’s loss of profit, or any other indirect cost or losses however incurred. LAB GRUPPEN reserves the right to make changes or improvements in design or manufacturing without assuming any obligation to change or improve products previously manufactured. This warranty is exclusive, and no other warranty is expressed or implied. This warranty does not affect the customer’s statutory rights. International Warranties Please contact your supplier or distributor for this information, as rights and disclaimers may vary from country to country.
8.2. Technical assistance and service
8.2.1. International service
If your LAB GRUPPEN product requires repair, contact your LAB GRUPPEN dealer or distributor, visit http://labgruppen.com/support or contact LAB GRUPPEN by phone or email to obtain details for the nearest authorized service center.
39 C SERIES Operation Manual rev 2.0.0

8. Warranty and Support
8.2.2. Factory service
In the event a LAB GRUPPEN product requires factory service, you may contact LAB GRUPPEN’s service department for return instructions and a Return Authorization number. Please note for product return: 1. Use the original packing. 2. Include a copy of the sales receipt, your name, return address, phone and fax number, email address and
description of the defect. 3. Mark the Return Authorization number on the outside of the packing. Ship the product prepaid to: Music Group Innovation Sweden AB Faktorvägen 1 SE-434 37 Kungsbacka Sweden Phone: +46 300 56 28 00 Fax: +46 300 56 28 99 service@labgruppen.com www.labgruppen.com
40 C SERIES Operation Manual rev 3.0.0

Notes
Notes
41 C SERIES Operation Manual rev 3.0.0

Notes
Notes
42 C SERIES Operation Manual rev 3.0.0

43 C SERIES Operation Manual rev 3.0.0

labgruppen.com
Intercooler, Class TD, R.SMPS, VPL, BEL, UVL and CAL are national and/or international trademarks or registered trademarks of Music Group. All other trademarks remain the property of their respective owners.
Copyright © 2016 MUSIC Group Innovation Sweden AB. All rights reserved.

Item no. OM-CS

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Lab gruppen User Manuals

Related Manuals