HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners Instruction Manual

June 14, 2024
Hitachi

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners

HITACHI RAM-125FPS Multi Split System Heat Pump Air
Conditioners

The unit is filled with refrigerant, the quantity of refrigerant is adequate for pipes up to 30m long. If the piping length is out of range, then additional refrigerant is needed. As the filling volume varies according to piping length and model differences,for the i in details, lease refer to the refri erant i in work of installation manual.

  • Make sure to hand over this manual to workers of the next stage and finally to the customer. (Transportation and Handling)–+(Refrigerant Piping Work)–+(Electrical Wiring)–+(Test Run)–+(Customer) m ortant Notice
  • For general use of the air conditioner. Do not use for special purposes, such as food, animals and plants, precision machinery, and artwork storage.
  • Do not install the unit in the following places. If you have gas and oil droplets exist around, it may cause fire, machine deformation, corrosion or damage.
    • Places having oil (including machine oil) droplets and oil gas.
    • Places having sulfur gas such as hot springs.
    • Do not install the unit in the following places, it may cause corrosion.
    • Near in the sea (in a salty environment).
    • An acid or alkaline environment.
  • Please pay attention to the following situations when the unit is installed in a hospital or other facilities where electromagnetic wave is radiated from medical equipment.
  • Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box.
  • Do not install the indoor unit, outdoor unit, controller and cable within approximately 3 meters from strong electromagnetic waves such as medical equipment.
  • Do not install the unit in the place where wind directly blows on animals or plants. It could adversely affect the animals or plants.
  • Using wireless remote controller, the receiver may fail to receive signals due to effect of the lighting equipment. Therefore keep the receiver away from the lighting equipment for more than 1 meter as possible.

Safet Summary

  • Before installation, carefully read the “Safety Precautions” for correct installation.
  • This manual contains R & Dange~. This symbol indicates a hazardous situation which if installed incorrectly, it may result in death or serious injury. Therefore, make sure to observe important messages of safety.
  • While checking for any abnormality during the test run after installation, explain to the customer the correct methods of usage and maintenance according to the user’s manual. Then hand over the installation manual and user’s manual to the customer.

Definition for signal words

  • DANGER : Indications hazardous situation which may result In severe personal Injury or death.
  • Enforcement matters; Machine with a ground termlnal, the user must follow the instructions for ground work.
  • Enforcement matters; Indicate Instructing behavior of general users.

About lnstallation

  • in installation, maka sure to follow the installation manual. If the insbuctions are not followed, it may 0 result in a water leakaae, electric shock or a fire.
  • In Installation, use the special R410A tools and piping materials, and follow the installation insbuctions actually and correctty executed. Since the use of HFC type refrigerant R410A Is 1.4 times higher than the R22 refrigerant, if not using correct piping materials and if the instructions are not actually followed, it may 0 result in a water leakage, electric shock or fire.
  • Please do not install in a location where flammable gas may be produced or flow in, it may cause fire and ·, other accidents.
  • Please install the unit in a location that can provide full support of the unit’s weight. Otherwise, the unit 0 mav fall and cause iniury.
  • Do not climb or put objects on the air-conditioner ID prevent collapse or overturning, which may cause injury. “
  • Make sure that refrigerant leakage test should be performed. Refrtgerant (Fluorocarbon) for this unit Is ±1 incombustible, non-toxic and odorless. However if the refrigerant leaks and comes contact with spark, 0 DANGER toxic gas will generate. Also the fluorocarbon is heavier than the air, it will cause oxygen insufficiency near the floor.
  • Use the adequate non-flammable refrigerant (R41 OA) to the outdoor unit in 18frigerant cycle. Do not charge Oxygen, acetylene or other flammable and poisonous gases. These types of gases are extremely  danaerous that can cause an e1mlosion and fire.
  • Make sure to remove all flammable objects on-site before a welding operation, and then -weldlng can be implemented, otherwise it may cause fire. Also, always weer leather gloves before handling refrigerant to prevent frosbite of the hand or the bodv.
  • In cleaning the unit, use non-flammable, non-toxic cleaning fluid. If you use flammable cleaning fluid, it may cause an exolosion, fire and other accidents.
  • Make sure to have sufficient venttlatlon when working In confined spaces to prevent oxygen Insufficiency.
  • When cleanlna aaents are mmosad to soa.rk at a hlan temoaratura toxic aases mav be oroduced.
  • Please be sure to recover the cleaning agent after use. Do not freely dllute the HFC In the atmosphere.

About electrical works

  • Perform elecb1cal work according to lnstallatlon Manual and all the relevant regulation and standard. If the instructions are not followed correctly, an electrical shock or fire may occur due to insufficient capacity and 0 inadeauate performance.
  • Use specified cables between units and choose the cables correctly. Use of incol’Ted wires may cause an electrical shock or tire may occur.
  • Ensure that the wiring terminals are tightened securely with the specified torques. If not, a fire or electrical 0 shock at the terminals connection Dart mav occur.
  • Fix the cables securely. External forces on the tenninals could lead to a fire.
  • Check If the ground wire Is securely connected. If the unit Is not correctly grounded, It may lead to 0 DANGER electrical shock. Do not connect the ground wiring to gas piping, water piping, lighting conductor or ground wirina and teleohone wire.
  • Installation of an ELB(Earth Leakage Breaker) is necessary : If and ELB is not installed, an electric shock or a fire may occur.
  • When opening the service cover due to need of wiring work or inspection, make sure to completely cut off the 0 power before working, to avoid electrtc shock.
  • Keep away from places where rats and other animals may bite the wires. Once the wires are bitten, it may 0 lead to flre or other accidents.
  • When installing the panel cover,avoid jamming the wires together in order to prevent elecbic shock, fire and other accidents.

Transportation and Handling

  1. When transporting the outdoor unit, observe the following items. Please transport the unit to the installation location under packed condition.
  2. When using a crane for hanging the outdoor unit, please keep the unit under packed condition. Use two ropes for hanging operation. Please use cloth ropes material products ( do not use steel wire or chain). Please use corrugated board or cloth in order to prevent scratches and damage to some parts with paint.
    • Put the unit in a flat surface when it is in handling in order to avoid inclining.
    • Do not remove any packing materials.
    • In order to prevent damage in the unit, please handle it carefully.

Before installation

The units use no ozone-depleting HFC type refrigerant (R410A).

  • D1) The pressure of refrigerant R41 OA is 1.4 times higher than R22 refrigerant, it is contaminated easily by moisture, oxide, oil and other impurities. New refrigerant is adopted, so the refrigerant oil also needs to be changed. Therefore, during installation, make sure that no water and impurities inside, if not, the existing use of the refrigerant and refrigerant oil will be mixed in the cycle system.
  • D2) To avoid accidental mixing of different refrigerant or different refrigerant oil, the sizes of the charging connections have been changed. It is necessary to prepare the following special R410A tools before performing the installation work.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
2

  • Use special parts for R410A in piping and connection. Both the flare nut and pipe flare are different, choose the correct size according to the specifications below.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
3

Selection of pipe thicknus
The thickness of pipes must be changed according to the design pressure change.

New Refrigerant Piping Thickness(mm)

Pipe Size d

|

A Size

---|---
R407C, R22| R410A
6.35| 9.0| 9.1
9.53| 13.0| 13.2
12.7| 16.2| 16.6
15.88| 19.4| 19.7
19.05| 23.3| *Cannot be proceaeed (1/2H matertal)

Pipe Size

| Existent Type| New Refrigerant
---|---|---
R22| R407C| R410A
TI1i<:kness| Material| Thickness| Material| Thickness| Material

<1>6.35| 0.6| 0| 0.8| 0| 0.8| 0 <1>9.53| 0.8| 0| 0.8| 0| 0.8| 0 <1>12.7| 0.8| 0| 0.8| 0| O.B| 0 <1>15.8B| 1.0| 0| 1.0| 0| 1.0| 0 <1>19.05| 1.0| 0| 1.0| 0| 1.0| 1/2H <1>22.2| 1.2| 0| 1.15| 0| 1.0| 1/2H 25A| 1.2| 0| 1.0| 112H| 1.0| 112H <1>28.6| 1.4| 0| 1.0| 1/2H| 1.0| 1/2H <1>31.75| 1.4| 0| 1.1| 1/2H| 1.1| 1/2H <1>38.1| 1.85| 0| 1.15| 1/2H| 1.35| 1/2H

Selection of connector
The thickness of connectors (elbows and tubing) must be changed according to the design pressure change. As 1/2H parts cannot be bend or expanded, select the appropriate tubing according to the minimum thickness below. Please note that the sizes of flare nuts also change.

Connection minimum thickness(mm)

Pipe Size R407C• R22 R410A Pipa Size R407C, R22 R410A
4>6.35 0.5 0.5 <1>22.2 0.9 0.9
4>9.53 0.8 0.6 <1>25.4 0.95 0.95
<1>12.7 0.7 0.7 ci,28.6 1.0 1.0
4>15.88 0.8 0.8 «1>31.75 1.05 1.1
<1>19.05 0.8 0.8 Cl>38.1 1.25 1.35

Flare Nut size B{mm)

Pipe Size

| Flare Nut Size B(mm)|

Pipe Size

| Flare Nut Size B(mm)
---|---|---|---
R407C • R22| R410A| R407C • R22| R410A

<1>6.35| 17| 17| <1>15.88| 27| 29 <1>9.53| 22| 22| Cl>19.05| 36| 36 4>12.7| 24| 26|

Factory-Supplied Accessories
The following is accessory parts of the outdoor unit. Please confirm it before installation. HITACHI RAM-125FPS Multi Split System Heat Pump Air
Conditioners 6

Combination of Indoor Unit and Outdoor Unit

  1. Select the quantity and capacity of indoor unit for outdoor unit as shown below. (Please pay attention! When the indoor unit does not fit the “Minimum Individual Operation Capacity”, the outdoor unit will not run.)
    Accessory| Q’ty| Use Place| Use Method
    ---|---|---|---
    Special Washer                                       @

n

|

4

|

Unit base to fix

| Please refer to installation instructions on page 6.

Drain Connector

|

1

|

Base condensation water exhaust

|

<1>26 drain holes to exhaust (Please refer to installation instructions on page 6.)

Washer

|

1

Stop Gap Material

|

4

| For 4-<1>24 drain holes to stop gap (Please refer to installation instructions on page 6.)
2. Cooling operating instructions.
The same refrigerant system of indoor unit, the cooling shall be operated.

  1. NOTE:
    This unit will not operate in the first 4 hours after power connection. The error code will be “d 1-22”. Follow the steps below to deactivate protection if you need to operate the unit within four hours after power connection.

  2. Connect the power of both the indoor and outdoor units.

  3. Wait for 30 seconds.

  4. Press the PSW1 and PSW3 switches simultaneously on the main board of outdoor unit for three seconds.

Outdoor Unit Installation

NOTICE

  1. Do not install the outdoor unit where there is a high level of oil mist, salty air or harmful gases such as sulphur. (Fault may occur more easily when installing in such locations/environments. Apply special protection if it is necessary to install the air-conditioner in these locations/environments.)
  2. Do not install the outdoor unit where the electromagnetic wave is directly radiated to the electrical box.
  3. Install the outdoor unit as far as at least 3 meters from the electromagnetic wave radiator.
  4. Do not install the outdoor unit in the indoor.

Installation Space
Retain maintenance space for the outdoor unit as shown belowHITACHI RAM-
125FPS Multi Split System Heat Pump Air Conditioners 8

Installation place

  1. Install the outdoor unit where good ventilation is available, and where it is dry.
  2. Install the outdoor unit where it is in the shade or it will not be exposed to direct sunshine or direct radiation from high temperature heat.
  3. The sound from the outdoor unit must not disturb your neighbors. (The operating sound at the rear sides is 3 to 5 db (A) higher than the value in the catalog at the front side).
  4. Unit air outlet must not directly flow to the plants or your neighbor’s windows.
  5. Do not install the heal exchanger in places where dust or scrap paper can enter easily. Add a wind guard (see below) as necessary to deflect wind.
  6. Avoid installing the unit in places with headwind (wind directly blowing against the fan). Add a wind guard when installing in places with strong wind.
  7. During installation, please note the following:
  8. To prevent the outdoor unit from falllng, shaklng, and producing noise In a strong wind or an earthquake, Install the unit using appropriate methods. Determine the required installation strength by calculating the seismic strength. Do not install the unit at locations where strong wind may blow off the roof or wall. Secure the unit with steal wire if necessary.
  9. Add rubber cushions to the four legs of the unit stand, please use anti-vibration rubber.
  10. The locatlon should be convenient for draining rainwater and condensate from defrosting. For good drainage, the outdoor unit should be installed in places with draining facilities. (When installing under roofs where condensate drips, this may wet the floor to cause fall in winter.) Also, using central draining pipes is easier. (In frigid zones, condensate from defrosting may freeze easily in winter, do not use central draining pipes.)
  11. Provide a foundation so that the entire footing of the outdoor unit can be mounted on the foundation. The height of the foundation should be 100mm to 300mm higher than the ground level.

Strong wind blowlng dlrectly against the product lnstallatlon method
Follow the instructions below when installing the unit on the roof with strong winds in the absence of obstruction:

  • Do not face the unit’s air ouUet gr111 toward the strong winds. This will interfere the air ventilation of the unit and will cause damage to the unit.
  • When strong winds dlrectty blowlng against the air outlet grille.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
9

Note : When strong winds continuously blow toward the air outlet of the outdoor unit, the ventilation fan will rotate in reverse and become damaged.

  • Whan on the roof or open space, the strong winds will damage the unit. Please make steel wire cable and others to fixed the unit.

Installation Work
Securely fix the outdoor unit on the foundation to prevent noise and collapse by strong wind or an earthquake due to loss of level (leaning aside).

  1. Secure the outdoor unit with the anchor bolts.

  2. Installation size of anchor bolts

  3. Example of fixing the stand with anchor bolts:
    Make sure to cut off section A when using this type of anchor bolts. Otherwise, it will be difficult to remove thepipe cover.

  4. Confirm lnstallatlon of drainage and drain elbow:

    • When defrost operation, the condensate water will be discharged, select the best location for the water discharge to the drainage ditch. Also, avoid installing the unit ovemead as water will drip from the unit. Plan drainage for the secondary oondensate tray If overhead lnstallatlon Is necessary.
    • If the overhead lnstallatton Is required, please use condensatton water drain pipes kit (option) Concentration Drain Pipes Kit
      Type : DBS-26(L)
  5. To avoid dumping the body resulting In noise, or due to gusts and earthquakes caused by inclination. Be sure to make the outdoor unit fixed securely.HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners 15

  6. When using ordinary frames whose legs are narrower than the legs of the outdoor unit, add a board under the legs of the outdoor unit as shown in the figure before installation to ensure all legs of the outdoor unit are adequately supported on the frame.

Refrigerant Piping Work

Refrigerant Piping Work

  1. Please refer to the following table for Pipe Size, Length and Lift difference between the indoor and outdoor unit.
    .

Example of Systems  .

,. These figures show examples of 4 indoor units

combined with one outdoor unit.

The refrigerant pipes are shown as single line in the diagrams.

However, liquid line piping and gas line piping are

.., required in the field.

| | |
---|---|---|---
The Total Length of Piping| LO+ L1+ L2+ L3+ L4       95m
Maximum Piping Length(Actual Length)| From the outdoor unit to the indoor unit’s piping length.| L t 75m



Maximum Lift between

Outdoor Unit and Indoor Unit

| In the case that the position of outdoor unit is higher than that of indoor unit.| ****

H1 30m

In the case that the position of outdoor unit is lower than that of indoor unit.| ****

H1 20m

Maximum Lift between Each Indoor Unit, or Multi-kit and Indoor Unit| ****

H2 3m

Maximum Piping Length between Multi-kit and Indoor Unit| L1 ,L2,L3,L4 10m
Choice of each Multi-kit| “a~c” Use MW-NP282A


Note the common

| 1. Liquid, gas of the piping length and piping path to be the same.

2. Multi-kit pipe have to install around the indoor unit.

  1. Piping Size
    • Indoor Unit

Horse-Power

| Piping Size(mm)
---|---
Gas| Liquid
0.8~1.5HP

22~45 Level

|

<1>12.7

|

<1>6.35

2.0~2.3HP

56 Level

|

<1>15.88

2.5~3.0HP

63~90 Level

|

<1>9.53

4.0~6.0HP

112~160 Level

  * Outdoor Unit  

Model

| Piping Size (mm)
---|---
Gas| Liquid

RAM-125, 140FPS(B)

|

<1>15.88

|

<1>9.53
  1. Cautions for Refrigerant Piping Work (For Example)
    Select clean copper pipes. Maka sure that there Is no dust and moisture Inside the pipes. When cuffing off the refrigerant piping, use the Pipe Cutter. Blow the inside of the pipes with nitrogen or dry air to remove any dust or foreign materials before connecting pipes. (Avoid using e saw or grinding stone tools that is easy to produce powder.)

  2. Prepare locally-supplied copper pipeHITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners 18

  3. Connect the multi-kit to the indoor unit, be sure to use the option parts of the multi-kit , do not use connectors. In multi-kit lnstalla11on, please keep columns, walls, callings and other surfaces to maintain a hortzontal direction for fixing the multi-kit.HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners 19

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
20

< Caution for maaaurlng pressure data from the check Joints.>
Read the pressure data from the check joints of the gas line stop valve (right figure®) and the check joints of piping line (right figure(ID) after you connect. And please read the details in changing high and low pressure position of the connection according to the different operation state, please refer to the following descrintion of the table.

Piping DirectionHITACHI RAM-125FPS Multi Split System Heat Pump Air
Conditioners 22

After removing the knock-out hole, please ‘bim burrs. To protect the wiring and piping, use the insulation material (Field-supplied materials) to wrap.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
23

  1. In using rubber plugs and wire tubes, make sure to check the size of the gap Lower Right Rear Cover referred to the knock-out hole.

  2. When removing the front and right piping, please pay more attention when lnstalllng In order to ensure the wlrtng removing space.
    Example : When Nmoving the rear piping and the right wiring, remove the part of piping to make the gap of the upper part (A division). The unirs internal piping and wiring shall not interfere with each other.

  3. For connection piping bending, use the pipe bender.

  4. In order to metel plate’s burrs does not cut the wiring and piping, use the insulation material (field-supplied materials) to protect them.

  5. In order to prevent rainwater intrusion in the unit, be sure to install the piping cover. When you install the cover, be sure to install the insulation material (field-supplied materials) to the piping through the hole to resist clearance. At the same time, remove the part under the side of the pipe cover to install it easily.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
24

Piping Connection .. Insulation

  1. Check if the stop valves of the outdoor unit is closed.
  2. Please connect the piping between the indoor and outdoor unit. When tightening the joints of piping, please insert the inside and outside of flare piping, coated with a layer of refrigerant oil, and in accordance with the provisions of tightening torque with double spanner to tighten. After tightening, please check for gas leakage once more. During brazing, please blow nitrogen into the piping.
  3. Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched, abnormal sound may occur due to the vibration of the piping. Pay special attention in case of short piping length.)
  4. Please confirm any gas leakage at the flare nut connections or brazed parts.
  5. Completely insulate the unions and flare-nuts at the piping connections. Insulate the liquid piping and gas piping completaly to avoid decreasing of performance and dewing on the surface of the pipe.

Piping Connection .. lnaulation

  1. Check if the stop valves of the outdoor unit is closed.
  2. Please connect the piping between the indoor and outdoor unit. When tightening the joints of piping, please insert the inside and outside of flare piping, coated with a layer of refrigerant oil, and in accordance with the provisions of tightening torque with double spanner to tighten. After tightening, please check for gas leakage once more. During brazing, please blow nitrogen into the piping.
  3. Connect the indoor unit and the outdoor unit with field-supplied refrigerant piping. Suspend the refrigerant piping at certain points and prevent the refrigerant piping from touching the weak part of the building such as wall, ceiling, etc.( If touched, abnormal sound may occur due to the vibration of the piping. Pay special attention in case of short piping length.)
  4. Please confirm any gas leakage at the flare nut connections or brazed parts.
  5. Completely insulate the unions and flare-nuts at the piping connections. Insulate the liquid piping and gas piping completaly to avoid decreasing of performance and dewing on the surface of the pipe.
  6. Air-tight Teat
  7. Before performing the air-tight test, please close the spindle valve of gas stop valve and liquid stop valve.
  8. Connect the gauge manifold using charging hoses with a vacuum pump or a nitrogen cylinder to the check Joints of the llquld llne and the gas llne stop valves. Perform the air-tight tasl Connect a manifold gauge to the check joints of the liquid and gas stop valves in the outdoor unit Do not open the stop valves. Apply nitrogen gas pressure of 4.15 Mpa.

The Vacuum, Filling Refrigerant

  1. Yacuum

  2. For the details of stop valve operation, please refer to the attention of nameplate inside service cover description.

  3. Connect a manifold gauge to 1he check joints at the both sides. Continue vacuum pumping wort until the pressure reaches -0.1MPa (-750mmHg) or lower for one to two hours.

  4. After vacuum pumping work, stop the mani-fold valve, stop the vacuum pump and leave it for one hour. Check to ensure that the pressure In the manlfold gauge does not Increase.

  5. The check joints and flare nut cannot connect, so please use the charging hose. After connecting, please tighten the flare nut with 15 – 16N • m of torque.

  6. Check for any gas leakage at the flare nut connections, or brazed parts by gas leakage tester or foaming agent. The following table is recommended for foam tasting fluid, component is not clear if will use the general household cleaner liquid as a foam testing.

  7. Fillng Refrigerant

  8. The unit has been filled with refrigerant, if the connecting pipe is longer than the length of setting standard refrigerant volume, please add the appropriate amount of refrigerant (Please refer to page.12).

  9. Fully open the gas line stop valve and slightly open the liquid line stop valve.

  10. In cooling operation, connect the gauge manifold using charging hose with a refrigerant charging cylinder to the check joint of the liquid line stop valve, and then charge the refrigerant.

  11. Fully open the liquid line stop valve after completing refrigerant charge.

  12. Please be sure to perform the air-tight test.
    Note :

  13. The spindle valve cap of stop valve is removed, due to internal 0-ring end thread will be opened, the whistle caused by gas emitting, which has nothing to do with the leakage.

  14. Use tools and measuring Instruments only for the new refrigerant (R41 OA) which directly touch refrtgerant.

  15. When pressure does not drop below-0.1 MPa (-750mmHg), it is considered that leakage exist&. Check for any gas leakage once again. If no leakage exists, operate the vacuum pump for one to two hoursHITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners 25

DSW Setting With The Piping Length
When the piping length is below Sm or above 30m, DSW2 setting must be adjusted. Please follow the instructions below to reset.HITACHI RAM-125FPS
Multi Split System Heat Pump Air Conditioners 26

Quantity Refrigerant Filling

  1. The factory refrigerant charging weight of each model and standard piping length
    Calculate the additional piping length before filling additional refrigerant to ensure the required quantity of refrigerant. And then charge the appropriate amount of additional refrigerant. Please follow the calculation of additional refrigerant as shown below and 3-2 guidelines for additional refrigerant filling.

  2. Calculating method of additional refrigerant.
    The calculation formula of piping length L (m)

  3. If the length L (m) is less than 30m, it doesn’t need additional refrigerant.

  4. If the length L (m) is more than 30m, it needs additional refrigerant.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
27

Please charge the addltlonal refrigerant quantity W by the calculating method (2).

Refrigerant Recovery Methods
Follow the steps below to recover refrigerant from the outdoor unit before relocating the indoor and/or outdoor unit(s).

  1. Please close the gas line stop valve, liquid line stop valve and the manifold gauge ..
  2. Tum the AJC power.
  3. Set DSW1-1 on the outdoor unit to ON (unit operation starts). Close the liquid line stop valve. Start refrigerant recovery.
  4. When the low pressure (gas Hna stop valve) dlsplay–0.01 MPa (-75mmHg), quickly run the following actions:
  5. Close the gas Interceptor valve.
  6. Set DSW1-1 to OFF (unit operation stops).
  7. Please tum off the power source.

Caution : Make sure pressure is not below -0.0lMPa. Presmre below -0.0tMPaG will cause compressor damage.

Electrlcal Wiring

CAUTION : All the fteld wiring and electrlcal components muet comply with local codea.

  1. Electrlcal Work
    Please entrust qualified distributors, and according to relevant national laws and regulations for cons1ruction.

  2. In electrical wiring, please use 3-phase /single-phase 220V ways. Select the wiring capacity according to the following essentials of wiring, power source wiring has two ways:

  3. Power supply from the outdoor unit.

  4. Power supply from indoor unit and outdoor unit separately.

Power supply from the outdoor unit. HITACHI RAM-125FPS Multi
Split System Heat Pump Air Conditioners 29

In dual spllt or trtple split combination of operation, the Indoor unit can be operated individually. The indoor unit can be operated simultaneously. Please set to OFF the outdoor unit elecbical board dip switches(DSW6-1 ).

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
30

Precautions for Iha H-LINK system connection:

  • Before the unit leaves the factory, set the termlnal resistance state (set to ON the DIP Switch DSW5-1) as shown in the right figure. When the H-LINK connects two or more of the outdoor unit, the second outdoor unit end tenninal resistance settings must be released (setting to OFF of the DIP switch DSW5-1). Pleese keep a stem of the tenninal resistance setting numbers: when only one outdoor unit, please keep the original factory settings.
  • For the same combination of H-LINK system, use the same type of cable. HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners 32
  • Caution for indoor and outdoor unit connection wiring construction. Be sure to keep the distance of more than 5-6an of the transmission cable of indoor and outdoor unit to the 220V power source cord. Therefore, do not use the coaxlal cable. Also keep the distance of more than 1.5m, if the air conditioner’s cable is in parallel with the power source lines of the other machines . If cannot be separated, please lay in metal conduit pipes (one side grounding) outside of the power source lines to separate.
    HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
33

Wiring connection port

  1. The indoor unit wiring connection port, please connect the wirings according to the indoor unit installation manual instruction.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
34

Indoor unit and outdoor unit electrical wiring

  1. Please follow the electrlcal wiring Instructions In connecting the power source cables of indoor and outdoor unit at page 13. (No connection forTsingle-phase indoor units.) In addition, lock the terminal screw with the tightening torque as shown in the right table.
  2. Please refer to the elecbical wiring construction to implement the electrical equipment benchmark.
  3. Do not connect a 230V power supply to terminal (D , ® of the outdoor unit, misconnection wlll cause damage tc the electrlcal circuit board.

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
35

  1. Does the power supply voltage match the rated voltage? The unit wlll be damaged due to higher or lower voltage.
  2. Check the capacity of the electrical wires. If the power source capacity is too low, the system cannot be started due to the voltage drop.
  3. If the indoor and outdoor unit is not grounded, electric shock and other accidents may occur, be sure to implement grounding protecttons. The grounding resistance must be100a or less according to the three kinds of grounding protection. This wok must be done by a qualffied electrldan.
  4. Please tum off the power supply before opening the seivlca cover for electrlcal wiring, maintenance and other opera11on to prevent elecbic shock.

Test Run

Caution before test running

  1. Please use lhe 500V elecbical resistance tester to chack lhe electrical parts between terminals and earth, the electrical resistance must be more than 1 MO. If It Is 1 MO or below, please check Iha alectr1cal resistance once again.
  2. Make sure that Iha step valves of the outdoor unit are fully opened, and than start the system.
  3. Dua to power source line phase loss, Iha controller appaans abnormal alarm coda “05” in Iha operation of the unit, check Iha pawar supply and power equipment.
  4. Check if the oil heater have power.
  5. Check to ensure lhat swttch on the main power 110urce has been ON for more than 12 hours, to warm the comp1’81180r ell by the ell heater.
  6. In cooling test running, Iha room temperature must be DB21.5qC, WB1~C. and an outdoor air temperature or more than DB O”C
  7.  In reading the data of pressure from the check joints,please refer to the precaution piping work to connect pressure gauge (page 9).

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
36

Function To Select The Setting

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
37

External Input and oulpul setting

HITACHI RAM-125FPS Multi Split System Heat Pump Air Conditioners
38

Alarm Code

Code Content of Abnormality Leading Cause

01

| Indoor Unit Activation of Protection Device(Float Switch)| Activation of Float Switch(High water Level.D tn Pan, Abnonnality of Drain Pipe, Float Switch or Drain Pan)

02

| Outdoor UnltActlvatlon of Protectfon Device(Except Exception Code 41, 42)| Activation of High pressure switch (4.15MPa); Air Conditioner Outdoor Unit Fan Motor Lock.

03

| Transmission Abnonnality between Indoor and Outdoor| Incorrect Wiring, Loose Tenninals, Disconnect Wire, Blowout of Fuse, Outdoor Unit Power OFF.

04

| Transmission Abnonnality between Inverter PCB and Outdoor PCB| Inverter PCB – Outdoor PCB Transmission Failure(Loose Connector, Wire

Breaking, Blowout of Fuse)

05

|

Abnonnallty Power Source Phases

| Incorrect Power Source Phases, Connection to Reversed Phases, Open- Phases.
06| Abnonnality Inverter Voltage| Outdoor Voltage Drop, Insufficient Power Capacity.

07

|

Decrease in Discharge Gae Superheat

| Excessive Refrigerant Charge, Fallure of Thermistor, Incorrect Wiring,

Incorrect Piping Connection, Expansion Valve Locking at Opened Position (Disconnect Connector).

08

|

Increase in Discharge Gas Temperature

| Insufficient·Refrigerant Charge, Pipe Clogging, Failure| .of Thennistor,
Incorrect Wiring, lnconree’I Piping Connection, Expansion Valve Locking at

Closed Position (Disconnect Connector).

11| Abnonnality Inlet Air Thennistor {Indoor)| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
12| Abnonnatity Outlet Air Thermistor (Indoor)| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
13| Abnonnality Freeze Protection Thennistor (Indoor)| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
14| Abnormality Gas Piping Thermistor (Indoor)| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.
19| Activation of Protection for Indoor Fan Motor| Fan Motor overheat, Locking.(49FE)(OFF:130°C)
20| Abnonnatity Thennistor on Top of Compressor

(Outdoor)

|

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.

22| Abnormality Outdoor Air Thennistor| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.

24

| Abnonnatity Keat Exchanger Liquid Pipe Thennistor (Outdoor)|

Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit

31

| Incorrect Capacity Setting oT Outdoor and.Indoor Unit| Incorrect Capacity Code Setting of Combination; ExceS!ilVe or In.sufficient Indoor Unit Total Capacity Code {outside of 80-120%)

35

|

Incorrect Setting of Indoor Unit No.

| Duplication of Indoor Unit No. In Sama Ref.Gr., or The Conneciion Unit Number Exceeds The Maximum Number of Combination.

38

| Abnormality of Picking Up Circuit for Protection (Outdoor)| Failure of Pr0te·ct1on Dettictlng Devlce{lncorrect Wlrtng of Outdoor PCB)

41

| Cooling overtoad operation

(Activation of High Pressure Protection Device)

| Activation of,Protection Devrce, The Compressor Surface Temperature above
95°C, and Outdoor Piping| , Temperature above 55°C.

42

| Heating overtoad operation

(Activation of High Pressure Protection Device)

| Activation of Protection Device , The Compressor Surface Temperature

above 95°C, and Outdoor Piping Temperature above 55°C.

47

| Activation of Low Pressure Decrease Protection Device {Vacuum Operation Protection)| Insufficient Refrigerant, Pipe Clogging, Expansion’Valve Locking at Open Position {Loose Connector).
48| Activation of Inverter OVercurrent Protection Device| OVertoad Operation, Compressor Failure.
51| Abnonnatity Inverter Current Sensor| Current Sensor Failure.
53| 1PM Protection Activation| Driver IC Error Signal Detection(Protection for Overcurrent, Low Voltage)
54| Activation of Inverter Fin Thennistor Protection| Abnonnatity Fin Thennistor, Heat Exchanger Clogging, Fan Motor Failure.
55| Inverter Failure| Inverter PCB Failure
57| Activation of Outdoor Fan Controller Protection| Abnonnality Fan Controller Protection(OVercurrent),Fin Overheat
59| Abnonnatity of Inverter Fin Thennistor| Incorrect Wiring, Disconnecting Wiring, Breaking Wire, Short Circuit.

b1

| Incorrect Outdoor Unit Address Number or Unit Number Setting|

Over 64 ‘Number Is Set for Address or Refrigerant Cycle.

EE| Compressor protection alann| Compressor Occurred Three Times of Abnonnality within 6 Hour.

Note : Remote control operation indicator flashes once every 2 seconds, this means there is a signal transfer error between the indoor unit and the remote control (connector loss, loose, incorrect wiring, and disconnection).

  • During the period of test running, check the air ou11et temperature of each indoor unit, if the temperature difference exceeds 1o•c. this may be a refrigerant piping problem, please recheck the refrigerant piping again.
  •  Finally, please hand over the guarantee, operation manual, and installation manual, etc. to the customer to keep it.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals