FLUIGENT LINEUP P-SWITCH Pneumatic Valve Controller User Manual
- June 4, 2024
- FLUIGENT
Table of Contents
USER’S
MANUAL
LINEUP™P-SWITCH
USER’S MANUAL
LINEUP P-SWITCH Pneumatic Valve Controller
The P-SWITCH is a LineUp Aria is a perfusion system that automates perfusion or timed injection protocols. It allows for the sequential delivery of up to 10 different solutions at the desired flow rate into a microfluidic chip, perfusion chamber or petri dish. TM module containing eight 3-port / 2-position solenoid valves. It can be used to actuate pneumatic or quake valves and to deliver different pressures or vacuum. It can be used to pressurize up to 8 reservoirs per module.
The LineUp P-SWITCH ™
allows one to switch 8 pressure outlets between two different supplied
pressures P1 and P2. Those pressures are common to all the valves and can be
dispensed within the range
-800 mbar to 2000 mbar.
Manual control
Power ON Power ON the module using the
LineUp Supply Kit and/or LINK module. Once done, the P-SWITCH LEDs will turn
orange, and the default dispense pressure is set on P1.
Pressure supply
The LineUp TM P-SWITCH requires pressure or vacuum supply to be used. Each
inlet can be supplied with positive pressure up to 2000 bar, a vacuum down to
-800 mbar. Note: If an inlet remains unsupplied, the atmospheric pressure
will be dispensed through this one.
The LineUp P-SWITCH TM is designed to work with another LineUp module such as
Push-Pull or Flow EZ TM to provide regulated pressure or vacuum. Provide
supply to the pressure controllers and connect their outlets to the P-SWITCH
inlets.
Configurations
- LINK module
- Flow EZ TM / Push-Pull
- P-SWITCH
- LineUp Supply Kit to the compressor
- Supply P1 inlet from Flow EZ / Push-Pull
In the configuration above, the LineUp P-SWITCH TM allows one to switch between the P1 regulated pressure supplied by the Flow EZ TM or Push-Pull and the P2 atmospheric pressure.
- LINK module
- P-SWITCH
- Negative Flow EZ TM / Push-Pull
- LineUp Supply Kit to a vacuum pump
- Supply P2 inlet from Flow EZ neg / Push-Pull
In the configuration above, the LineUp P-SWITCH TM allows one to switch between the P2 vacuum supplied by the negative Flow EZ TM or Push-Pull and the P1 atmospheric pressure.
- LINK module
- Flow EZ TM / Push-Pull
- P-SWITCH
- Negative Flow EZ TM / Push-Pull
- LineUp Supply Kit to the requested compressor
- Supply P1 and P2 from Flow EZ / Push-Pull
In the configuration above, the LineUp P-SWITCH TM allows one to switch between the P1 regulated pressure or the P2 vacuum both supplied by each Flow EZ TM or Push-Pull.
Switching valve position
To switch any valve position from P1 to P2 or P2 to P1, press the
corresponding button of the valve. Once done, the led will change color either
in orange or in blue to indicate the new current position. Note: Several
valves can be actuated at the same time.
P1 to P2 button
By pressing the “P1 <-> P2” button, one can set every valve at the same time to the same position. By pressing it again, one can set every valve on the second position. (LEDs color indicates the supplied pressure)
Computer first ensure
First of all, ensure the P-SWITCH is stacked to a LINK connected to the
computer.
In addition to the local control, Fluigent newest software allows one to
automate any protocol and easily program sequences of pressure steps.
Note: A cable is provided with the LINK to enable connection to
PC.
To be compatible with the LineUp TM P-SWITCH, the LINK module version needs to be at least ver 1.06
Microfluidic Automation Tool (MAT)
In this section will be presented the use of Fluigent Microfluidic Automation
Tool (MAT) in order to automate LineUp TM P-SWITCH pressure steps.
For this example will be considered the following set-up
1 PC with MAT software
2 Flowstretch chip (CEA)
3 Power supply
4 Pressure supply
5 Vacuum supply| 6 LINK module
7 2 Flow EZ TM
8 2 P-SWITCH (A and B)
9 Negative Flow EZ TM
---|---
Step 1 Select the sequence block in the Function blocks section, then drag and drop it on the protocol section.
Block Description
Step 2 To create a sequence, first one can upload any picture from a directory as a guide to building the protocol. This picture is a reminder to know which part of the chip/microfluidic set-up is connected to which valve.
Step 3 Drag and drop the valve numbers on the picture. By using the slider (1) on the right one can resize the numbers. Step 4 Use the right click or double click to change the valve position and edit the step sequence. When the valves are displayed in green, it corresponds to the pressure P2, on the contrary, if displayed in orange the pressure dispensed is P1. One can edit the step name and set a duration
Step 5 To add a step, click on the “add step” button (1) or “duplicate step” button (2) on the right.
Create a sequence on several modules
Click on “Super P-SWITCH”, then drag and drop the sequence. The block will adapt to the number of modules connected to the LINK.
Switch every valve at once
Use the “set all” block to switch every valve to the same position at once.
Click on P1 to set every valve to P1 position and click on P2 to set every
valve to P2 position.
Note: Once a valve is set on a position, it will dispense the supplied
pressure through the corresponding outlet.
Remote operation
The following part details the serial RS-232 communication information for the
use of the LineUp TM P-SWITCH with the LINK COM.
The RS-232 interface is a 9-pin D-Sub socket used for remote communication The
voltage level is ±10 V (pin 5: GND; pin 2: RX +-10V; pin 3: TX +- 10V).
Serial communication parameters should be set as follows:
Baud Rate | 115 200 bps |
---|---|
Stop Bits | 1 |
Parity | No parity |
Flow control | None |
This remote command set is the default set available on the instrument. All
commands must be terminated with a
A query command ends with a question mark “?” for queries. The data column
represents the response of the instrument. All response strings are terminated
with a
Queries related to an instrument connected at index “X” return “ERROR NO
MODULE” in case there is no instrument at the index they refer to or the
instrument at the index is not compatible with the query (e.g a query for a
Flow EZ TM will not work if there is a P-SWITCH at the index poled).
The following table describes the P-SWITCH remote command set:
Query | Data | Function / Response |
---|
SWEZ
:X:READ:Y?|
Valve ON : position bit is 1
Valve OFF : position bit is 0.
Examples :
00 : all valves are OFF
01 : only valve 1 is ON
FF : all valves are ON
F0 : only valves 5 to 8 are ON
:X:SET:
Example of remote commands : PSWI:1:SET:F0:80 : Forces the valves 5 to 7 to OFF state, valve 8 to ON state, and valves 1 to 4 unchanged on the P-Switch at index 1. (Note : F0 = 1111 0000 and 80 = 1000 0000 in binary). If state was 0101 0101 (55), after this command it is now 1000 0101 (85)
VERSION
MAR. 202
Documents / Resources
|
FLUIGENT LINEUP P-SWITCH Pneumatic Valve
Controller
[pdf] User Manual
LINEUP P-SWITCH, Pneumatic Valve Controller, Valve Controller, Pneumatic
Controller, Controller, LINEUP P-SWITCH
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>