MASONS J001592 Intertenancy Wall System User Guide
- June 14, 2024
- MASONS
Table of Contents
**MASONS J001592 Intertenancy Wall System
**
GENERAL
GENERAL
This specification relates to the installation of the Masons Intertenancy Wall System.
RELATED WORK
The installation of the Masons Intertenancy Wall System relies on:
▶a primary structure (not including the Masons IntertenancyWall System) that complies with the NZ Building Code and is designed and installed in accordance with the buildingconsent and construction drawings and:
- NZS 3604:2011; or
- NASH Standard Part 2: May 2019 Light Steel Framed Buildings; or
- is designed to AS/NZS 1170 Structural design actions, NZS 3603:2003 or NZS 3404:1997; or
▶in the case of an existing building, where the designer and installer have satisfied themselves that the primary structure of the existing building is suitable for the intended building work.
DOCUMENTS
Refer to the following manufacturer’s documents:
▶the Masons Intertenancy Wall System pass™
▶the relevant Masons Intertenancy Wall System details
▶the Masons Intertenancy Wall System Installation guide
▶the Masons Intertenancy Wall System warranty
Refer to the following related documents:
▶NASH Standard Part 2: May 2019 Light Steel Frame Buildings
▶AS/NZS 1170 Structural design actions
▶NZS 3604: Timber-framed buildings.
GENERAL DESIGN CONSIDERATIONS
The system must be specified in accordance with the Masons Intertenancy Wall System Design guide and details.
PRODUCTS
PRODUCT DESCRIPTION
The Masons Intertenancy Wall System is an intertenancy acoustic and fire wall system:
NOTE
▶90 mm timber framing or 92 mm steel framing
▶75 mm R2.0, non-combustible moisture-resistant, non-corrosive, mildew proof
insulation. Where acoustic performance required a minimum density of 9kg/m3
applies.
▶50 mm Masons Enviro™ AAC panel.
The Masons Enviro™ AAC panel is a 50 mm thick AAC panel, manufactured from
cement, sand, lime and water and aerated by the addition of an expanding
agent. Soft blocks are moulded using the mixture and then sliced into the
required panel size and cured in a steam pressure autoclave for up to 12
hours. The Masons Intertenancy Wall System has a fire rating of 90/90/90 and
an estimated laboratory acoustic STC performance of 64 dB.
ASSEMBLY COMPONENTS
The following assembly components are supplied by Masons Plastabrick:
▶Masons 50 mm thick Enviro™ AAC panel
▶Masons Enviro™ AAC adhesive mortar
▶Masons 1.5 BMT 75 mm x 45 mm x 50 mm aluminium angle bracket
▶Masons 0.55 BMT 51 mm x 35 mm galvanised steel H-jointer
▶Masons 0.55 BMT 51 mm x 35 mm galvanised steel C channel.
ACCESSORY COMPONENTS
The following accessory components are required:
▶75 mm R2.0, non-combustible, moisture-resistant, mineralwool, fiberglass or
polyester insulation
▶90 mm deep timber framing or 92 mm deep steel framing
▶10 mm thick plasterboard
▶non-combustible, moisture-resistant, mineral wool insulation
▶12 g x 45 mm Hex head SDS Type 17, Class 3 screws (angle bracket to Masons
Enviro™ AAC panel)
▶12 g x 20 mm Hex head self drilling, Class 3 screws (angle bracket to steel
framing)
▶12 g x 35 mm Hex head Type 17 self drilling Class 3 screws (angle bracket to
timber framing)
▶fire retardant sealant
▶corrosion protection touch up paint.
SUBSTITUTIONS
Substitutions are not permitted to any of the specified components listed in this section.
EXECUTION
QUALIFICATIONS
The installation of the Masons Intertenancy Wall System must be carried out by a competent and experienced builder.
RESTRICTED BUILDING WORK
Where Restricted Building Work applies, the installer shall be a Licensed Building Practitioner (LBP) or be supervised by an LBP with the relevant license class.
CHECK RELATED WORK
Confirm the primary structure has been constructed in accordance with the building consent and construction drawings or, in the case of an existing building, that the existing building is suitable for the intended building work
APPLICATION
GENERAL
The installation of the Masons Intertenancy Wall System must be completed in
accordance with the instructions in the Masons Intertenancy Wall System
Installation guide, the relevant details and the building consent
documentation.
All conditions contained in the building consent documentation must be met.
RECEIPT OF PRODUCT
Ensure that all product supplied is:
▶free of defects at the time of delivery and
▶handled and stored in accordance with all of the relevant manufacturer or
supplier’s requirements and instructions.
COMPLETION
QUALITY CHECK
Check to ensure all components are installed correctly and in accordance with the Masons Intertenancy Wall System requirements.
WARRANTIES
For warranty information refer to www.mpb.co.nz
INFORMATION FOR CARE AND MAINTENANCE
The system requires minimal care and maintenance to maintain the performance and appearance of the system. Refer to www.mpb.co.nz for further information.
PROJE
PROJEPROJECT-SPECIFIC SELECTIONS
PROJECT DETAILS
Project address
Lot/DP number Date of plans
Purpose of plans
Description of building work and reference to drawing numbers
DOCUMENTS SUPPLIED (CHECK WHICH APPLIES)
- Masons Intertenancy Wall System pass™
- Masons Intertenancy Wall System Warranty
- Masons Intertenancy Wall System Installation Guide
DESIGNER CONFIRMATION (CHECK WHICH APPLIES)
Building
Framing
-
Timber Lightweight steel
-
Lightweight steel
-
Existing building assessed at equivalent stiffness to NZS 3604:2011
Specific fire engineering -
Yes
-
No
Distance to boundry
-
Less than 1 m
-
Greater than 1 m
Building
Framing -
Timber
-
Lightweight steel
-
Existing building assessed at equivalent stiffness to NZS 3604:2011
ASSEMBLY COMPONENT SELECTIONS
- Masons 50 mm thick Enviro™ AAC panel
- Masons Enviro™ AAC adhesive mortar
- Masons 1.5 BMT 75 mm x 45 mm x 50 mm aluminium angle bracket
- Masons 0.55 BMT 51 mm x 35 mm galvanised steel H joiner
- Masons 0.55 BMT 51 mm x 35 mm galvanised steel C channel.
ACCESSORY COMPONENT SELECTIONS
- 75 mm R2.0, non-combustible, moisture-resistant, non-corrosive, mildew-proof mineral wall insulation – product to be used:
- 90 mm deep timber framing
- 92 mm deep steel framing
- 10 mm thick plasterboard – product to be used:
- Non-combustible, moisture-resistant, mineral wool insulation for the top of the wall– product to be used:
- 12 g x 45 mm Hex head SDS Type 17, Class 3 screws (angle bracket to Masons Enviro™ AAC panel)
- 12 g x 20 mm Hex head self drilling, Class 3 screws (angle bracket to steel framing) 12 g x 35 mm Hex head Type 17 self drilling Class 3 screws (angle bracket to timber
- framing)
- fire retardant sealant
- corrosion protection touch up paint
FIRE ENGINEERING
DETAILS SELECTION
CUSTOMER SUPPORT