Schneider Electric Acti9 Combi Surge protector Instruction Manual
- June 4, 2024
- Schneider Electric
Table of Contents
Schneider Electric Acti9 Combi Surge protector
PLEASE NOTE
- The installation, maintenance, and eventual replacement of this device must only be carried out by a qualified electrician.
- This device must not be repaired.
- All applicable local, regional and national regulations must be complied with during the installation, use, maintenance, and replacement of this device.
- This device should not be installed if, when unpacking it, you observe that is damaged.
- Schneider Electric cannot be held responsible in the event of non-compliance with the instructions in this document and in the documents to which it refers.
- The service instruction must be observed throughout the product life time of this device.
Description
- End-of-life indicator:
- Green: ok
- Red: end of life
- Overvoltage indication:
- White: no overvoltage
- Red: overvoltage detected
- Earth terminal
Connection
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Turn off all power supplying this device before working on it.
- Use a voltage tester with a suitable rated voltage in order to check that all active conductors aren’t energized.
Failure to follow these instructions will result in death or serious injury
3PN| Cable cross-section for flexible and rigid cables in mm²|
Tightening torque (N.m)
---|---|---
Product Reference /| Designation /| L1 / L2 / L3| N| PE| L1 / L2 / L3| N| PE
A9L20716| Acti9 Combi SPU 3P+N C curve 16A SPD| | | Rigid cables: 4…35
mm²
Flexible cables: 4…25 mm²
| 2.5| 2.5| 3.5
A9L20720| Acti9 Combi SPU 3P+N C curve 20A SPD| | | 2.5| 2.5| 3.5
| | Rigid cables:6…25 mm²| Rigid cables:6…25 mm²
A9L20725| Acti9 Combi SPU 3P+N C curve 25A SPD| 2.5| 2.5| 3.5
| | |
A9L20732| Acti9 Combi SPU 3P+N C curve 32A SPD| 3.5| 3.5| 3.5
| | Flexible cables: 6…16 mm²| Flexible cables:6…16 mm²
A9L20740| Acti9 Combi SPU 3P+N C curve 40A SPD| 3.5| 3.5| 3.5
| | |
A9L20750| Acti9 Combi SPU 3P+N C curve 50A SPD| 3.5| 3.5| 3.5
A9L20763| Acti9 Combi SPU 3P+N C curve 63A SPD| | | 3.5| 3.5| 3.5
End of life
Schneider Electric Industries SAS
35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex
www.se.com
GDE9796206-02