Panasonic R410A Air Conditioner Instruction Manual
- June 13, 2024
- Panasonic
Table of Contents
Panasonic R410A Air Conditioner
Product Information
The product is an air conditioner that uses either the refrigerant R32 or R410A. It is important to confirm the room space and the amount of refrigerant before using R32. Additionally, an optional R32 refrigerant leakage detection sensor can be installed if needed.
The model number for the indoor units is as follows:
- U2 4-Way Cassette: S-22MU2E5BN, S-28MU2E5BN, S-36MU2E5BN, S-45MU2E5BN, S-56MU2E5BN, S-60MU2E5BN
- U2 4-Way Cassette: S-73MU2E5BN, S-90MU2E5BN, S-106MU2E5BN, S-112MU2E5BN, S-140MU2E5BN, S-160MU2E5BN
The product also includes optional parts such as panels (CZ-KPU3 series).
Product Usage Instructions
- Read through the Installation Instructions before proceeding with the installation. Pay special attention to the IMPORTANT! section at the top of the page.
- Prepare the necessary tools for installation (not supplied).
- Check the accessories supplied with the unit.
- Determine the type of copper tube and insulation material needed.
- Gather any additional materials required for installation.
- Select the appropriate site for installation, considering the indoor unit.
- Follow the step-by-step instructions to install the indoor unit, including suspending it, placing it inside the ceiling, processing tubing, installing the drain pipe, and wiring for the 4-Way Cassette type.
- Ensure proper electrical wiring, following the general precautions and referring to the wiring system diagrams.
- Process the tubing by connecting the refrigerant tubing, connecting tubing between indoor and outdoor units, insulating the refrigerant tubing, taping the tubes, and finishing the installation.
- If using optional parts like a timer remote controller, high-spec wired remote controller, panel for cassette, or wireless remote controller, refer to their respective installation instructions.
- Take necessary precautions for the test run of the air conditioner.
- Perform a checklist of tasks after completing the installation work.
- Refer to the appendix for care and cleaning instructions, troubleshooting tips, and energy-saving tips.
- Read the important information regarding the refrigerant used.
INSTALLATION INSTRUCTIONS
Air Conditioner
This air conditioner uses the refrigerant R32 or R410A. In case of using R32,
confirm the room space and the amount of refrigerant in advance. Install the
optional “R32 refrigerant leakage detection sensor” as needed. (See Section
“Check of Density Limit”.)
Model No. Indoor Units
Type
Indoor Units Type
U2
4-Way Cassette
Rated Capacity
22
28
36
45
56
60
S-22MU2E5BN S-28MU2E5BN S-36MU2E5BN S-45MU2E5BN S-56MU2E5BN S-60MU2E5BN (CZ- KPU3)* (CZ-KPU3*) (CZ-KPU3)* (CZ-KPU3)* (CZ-KPU3*) (CZ-KPU3)*
Type
Indoor Units Type
73
Rated Capacity
90
106
112
140
160
U2
4-Way Cassette
S-73MU2E5BN S-90MU2E5BN S-106MU2E5BN S-112MU2E5BN S-140MU2E5BN S-160MU2E5BN (CZ-KPU3)* (CZ-KPU3*) (CZ-KPU3)* (CZ-KPU3)* (CZ-KPU3*) (CZ-KPU3)*
- Panel (optional parts) ** CZ-KPU3 series
ENGLISH Read through the Installation Instructions before you proceed with the installation. In particular, you will need to read under the “IMPORTANT!” section at the top of the page.
WEB-ACXF60-50850-00-EN
IMPORTANT! Please Read Before Starting
This air conditioner must be installed by the sales dealer or installer. This
information is provided for use only by authorized persons.
For safe installation and trouble-free operation, you must:
· This Installation Instructions is for the indoor unit and
read the Installation Instructions of the outdoor unit as well.
· Carefully read this instruction booklet before beginning. · This air
conditioner is required to have the remote
controller which is adaptable to nanoeTM X function.
· Follow each installation or repair step exactly as shown. · This air
conditioner shall be installed in accordance with
National Wiring Regulations.
· That compliance with national gas regulations shall be
observed.
· The product meets the technical requirements of
EN/IEC 61000-3-3.
· Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
WARNING
unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and
maintenance conditions. If you require help for a special problem, contact our
sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or
maintenance service, including failure to follow the instructions in this
document.
WARNING
· Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
· The appliance shall be stored in a room without continuously operating
ignition sources (for example: open flames, an operating gas appliance or an
operating electric heater).
· Do not pierce or burn. · Be aware that refrigerants may not contain an
odour. · The following checks shall be applied to installations using
flammable refrigerants.
Appliance shall be installed, operated and stored in a room with a floor area
larger than [Amin] m2. As for [Amin], see Section “Check of Density Limit”.
SPECIAL PRECAUTIONS
WARNING When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
· Do not supply power to the unit until all wiring and tubing are completed or
reconnected and checked.
· Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause accidental injury or death.
· Connect all wiring tightly. Loose wiring may cause overheating at connection
points and a possible fire hazard.
· Provide a power outlet to be used exclusively for each unit. · Provide a
power outlet exclusively for each unit, and full disconnection means having
a contact separation by 3 mm in all poles must be incorporated in the fixed
wiring in accordance with the wiring rules. · To prevent possible hazards from
insulation failure, the unit must be grounded.
3
· Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
· This equipment is strongly recommended to be installed with Earth Leakage
Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may
cause electrical shock and fire in case of equipment breakdown or insulation
breakdown.
When Transporting
· It may need two or more people to carry out the installation work. · Be
careful when picking up and moving the indoor and outdoor units. Get a partner
to
help, and bend your knees when lifting to reduce strain on your back. Sharp
edges or thin aluminum fins on the air conditioner can cut your fingers.
When Storing…
WARNING · The appliance shall be stored in a well-ventilated area where the
room size
corresponds to the room area as specified for operation. · The appliance shall
be stored in a room without continuously operating open
flames (for example: an operating gas appliance) and ignition sources (for
example: an operating electric heater). · The appliance shall be stored so as
to prevent mechanical damage from occurring.
When Installing…
· Select an installation location which is rigid and strong enough to support
or hold the unit, and select a location for easy maintenance.
· In cases that require mechanical ventilation, ventilation openings shall be
kept clear of obstruction.
· An unventilated area where the appliance using flammable refrigerants is
installed shall be so constructed that should any refrigerant leak, it will
not stagnate so as to create a fire or explosion hazard.
…In a Room Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to walls and floors.
CAUTION Keep the fire alarm and the air outlet at least 1.5 m away from the
unit.
…In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to
provide a solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration. …In an Area with High Winds Securely anchor the
outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems) Install the outdoor unit on a
raised platform that is higher than drifting snow. Provide snow vents. …At
Least 2.2 m Installation height for indoor unit shall be at least 2.2 m. …In
Laundry Rooms Do not install in laundry rooms. Indoor unit is not drip proof.
When Connecting Refrigerant Tubing
Pay particular attention to refrigerant leakages.
4
WARNING
· When performing piping work, do not mix air except for specified refrigerant
in refrigeration cycle. It causes capacity down, and risk of explosion and
injury due to high tension inside the refrigerant cycle.
· If the refrigerant comes in contact with a flame, it produces toxic gases
and fires. · Do not add or replace refrigerant other than specified type. It
may cause product
damage, burst and injury, etc. · Ventilate the room immediately in the event
of a refrigerant gas leakage during
installation. Be careful not to allow contact of the refrigerant gas with a
flame as this will cause the generation of toxic gases and fires. · Keep all
tubing runs as short as possible. · Apply refrigerant lubricant to the
matching surfaces of the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection. · Check
carefully for leaks before starting the test run. · Do not leak refrigerant
while piping work for an installation or re-installation, and while repairing
refrigeration parts. Handle liquid refrigerant carefully as it may cause
frostbite. · Under no circumstances shall potential sources of ignition be
used in the searching or detection of refrigerant leaks. · A halide torch (or
any other detector using a naked flame) shall not be used. · Electronic leak
detectors may be used to detect refrigerant leaks but, the sensitivity may not
be adequate, or may need re-calibration. (Detection equipment shall be
calibrated in a refrigerant-free area.) · Ensure that the detector is not a
potential source of ignition and is suitable for the refrigerant used. · Leak
detection equipment shall be set at a percentage of the Lower Flammable Limit
(LFL) of the refrigerant and shall be calibrated to the refrigerant employed
and the appropriate percentage of gas (25% maximum) is confirmed. · Leak
detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with
the refrigerant and corrode the copper pipe-work. · If a leak is suspected,
all naked flames shall be removed/extinguished. · If a leakage of refrigerant
is found which requires brazing, all of the refrigerant shall be recovered
from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak. Oxygen Free Nitrogen (OFN) shall then be purged
through the system both before and during the brazing process. · If
refrigerant R32 is used and the optional “R32 refrigerant leakage detection
sensor” is connected to the indoor unit, do not turn off the ELCB of the
indoor unit except when there is a symptom of abnormality or failure, or when
performing short-term maintenance. (When the ELCB is turned off, R32
refrigerant leakage detection sensor cannot detect the refrigerant leakage
when the refrigerant leaks, and it may lead to cause the generation of toxic
gases and fires.)
5
When Servicing
· Contact the sales dealer or service dealer for a repair. · Ventilate the
room by opening windows before servicing if there is a possibility of a
refrigerant leakage. · Be sure to turn off the power before servicing. · Turn
the power OFF at the main power box (mains), wait at least 5 minutes until it
is discharged, then open the unit to check or repair electrical parts and
wiring. · Keep your fingers and clothing away from any moving parts. · Clean
up the site after you finish, remembering to check that no metal scraps or
bits of
wiring have been left inside the unit.
WARNING · This product must not be modified or disassembled under any
circumstances.
Modified or disassembled unit may cause fire, electric shock or injury. · Do
not clean inside the indoor and outdoor units by users. Engage authorized
dealer or specialist for cleaning. · In case of malfunction of this appliance,
do not repair by yourself. Contact the
sales dealer or service dealer for a repair and disposal.
CAUTION · Ventilate any enclosed areas when installing or testing the
refrigeration system.
Leaked refrigerant gas, on contact with fire or heat, can produce dangerously
toxic gases. · Confirm after installation that no refrigerant gas is leaking.
If the gas comes in contact with a burning stove, gas water heater, electric
room heater or other heat source, it can cause the generation of toxic gases
and fires. Others When disposing of the product, do follow the precautions
referring to Section “Recovery” in the installation instructions supplied with
the outdoor unit and comply with national regulations.
WARNING · Do not sit or step on the unit. You may fall down accidentally.
CAUTION
· Do not touch the air inlet or the sharp aluminum fins of the outdoor unit.
You may get injured.
· Do not stick any object into the FAN CASE. You may be injured and the unit
may be damaged.
· Do not touch the fan because it automatically rotates when it detects a
refrigerant leak. You may be injured.
6
SERVICING
CAUTION
· Any qualified person who is involved with working on or breaking into a
refrigerant circuit should hold a current valid certificate from an industry-
accredited assessment authority, which authorizes their competence to handle
refrigerants safely in accordance with an industry recognised assessment
specification.
· Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent
in the use of flammable refrigerants.
· Servicing shall be performed only as recommended by the manufacturer. ·
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For
repair to the refrigerating system, (2) to (6) shall be completed prior to
conducting work on the system.
(1) Work shall be undertaken under a controlled procedure so as to minimise
the risk of a flammable gas or vapour being present while the work is being
performed.
(2) All maintenance staff and others working in the local area shall be
instructed on the nature of work being carried out. Work in confined spaces
shall be avoided. The area around the workspace shall be sectioned off. Ensure
that the conditions within the area have been made safe by control of
flammable material.
(3) The area shall be checked with an appropriate refrigerant detector prior
to and during work, to ensure the technician is aware of potentially toxic or
flammable atmospheres. Ensure that the leak detection equipment being used is
suitable for use with all applicable refrigerants, i.e. non-sparking,
adequately sealed or intrinsically safe.
(4) If any hot work is to be conducted on the refrigerating equipment or any
associated parts, appropriate fire extinguishing equipment shall be available
to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging
area.
(5) No person carrying out work in relation to a refrigerating system which
involves exposing any pipe work shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept sufficiently far
away from the site of installation, repairing, removing and disposal, during
which refrigerant can possibly be released to the surrounding space. Prior to
work taking place, the area around the equipment is to be surveyed to make
sure that there are no flammable hazards or ignition risks. “No Smoking” signs
shall be displayed.
(6) Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work. A degree of
ventilation shall continue during the period that the work is carried out. The
ventilation should safely disperse any released refrigerant and preferably
expel it externally into the atmosphere.
(7) Where electrical components are being changed, they shall be fit for the
purpose and to the correct specification. At all times the manufacturer’s
maintenance and service guidelines shall be followed. If in doubt, consult the
manufacturer’s technical department for assistance. · The actual refrigerant
charge is in accordance with the room size within which the refrigerant
containing parts are installed. · The ventilation machinery and outlets are
operating adequately and are not obstructed.
7
· Marking to the equipment continues to be visible and legible. Markings and
signs that are illegible shall be corrected.
· Refrigerating pipe or components are installed in a position where they are
unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
(8) Repair and maintenance to electrical components shall include initial
safety checks and component inspection procedures. If a fault exists that
could compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the fault cannot be
corrected immediately but it is necessary to continue operation, an adequate
temporary solution shall be used. This shall be reported to the owner of the
equipment so all parties are advised. Initial safety checks shall include: ·
That capacitors are discharged. This shall be done in a safe manner to avoid
possibility of sparking. · That no live electrical components and wiring are
exposed while charging, recovering or purging the system. · That there is
continuity of earth bonding.
· During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc.
· Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
· Ensure that apparatus is mounted securely. · Ensure that seals or sealing
materials have not degraded such that they no longer
serve the purpose of preventing the ingress of flammable atmospheres. ·
Replacement parts shall be in accordance with the manufacturer’s
specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types
of leak detection equipment. Intrinsically safe components do not have to be
isolated prior to working on them.
· Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
· Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere.
· The test apparatus shall be at the correct rating. · Replace components only
with parts specified by the manufacturer. Unspecified parts
by manufacturer may result ignition of refrigerant in the atmosphere from a
leak.
8
REMOVAL AND EVACUATION
CAUTION
· When breaking into the refrigerant circuit to make repairs or for any
other purpose conventional procedures shall be used. However, it is
important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to: · Remove
refrigerant. · Purge the circuit with inert gas. · Evacuate. · Purge again
with inert gas. · Open the circuit by cutting or brazing.
· The refrigerant charge shall be recovered into the correct recovery
cylinders. · The system shall be “flushed” with Oxygen Free Nitrogen (OFN) to
render the unit safe. · This process may need to be repeated several times. ·
Compressed air or oxygen shall not be used for this task. · Flushing shall be
achieved by breaking the vacuum in the system with OFN
and continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum. · This process shall be
repeated until no refrigerant is within the system. · When the final OFN
charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. · This operation is absolutely vital if brazing
operations on the pipe work are to take place. · Ensure that the outlet for
the vacuum pump is not close to any potential ignition sources and there is
ventilation available.
CHARGING PROCEDURES
NOTE: Refer to the Installation Instructions attached to the outdoor unit.
DECOMMISSIONING
CAUTION
· Before carrying out this procedure, it is essential that the technician is
completely familiar with the equipment and all its details.
· It is recommended good practice that all refrigerants are recovered safely.
· Prior to the task being carried out, an oil and refrigerant sample shall be
taken in
case analysis is required prior to re-use of recovered refrigerant. · It is
essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation. b) Isolate system
electrically. c) Before attempting the procedure ensure that:
· Mechanical handling equipment is available, if required, for handling
refrigerant cylinders.
· All personal protective equipment is available and being used correctly. ·
The recovery process is supervised at all times by a competent person.
9
· Recovery equipment and cylinders conform to the appropriate standards. d)
Pump down refrigerant system, if possible. e) If a vacuum is not possible,
make a manifold so that refrigerant can be removed
from various parts of the system. f) Make sure that cylinder is situated on
the scales before recovery takes place. g) Start the recovery machine and
operate in accordance with instructions. h) Do not overfill cylinders. (No
more than 80% volume liquid charge). i) Do not exceed the maximum working
pressure of the cylinder, even temporarily. j) When the cylinders have been
filled correctly and the process completed, make
sure that the cylinders and the equipment are removed from site promptly and
all isolation valves on the equipment are closed off. k) Recovered refrigerant
shall not be charged into another refrigerating system unless it has been
cleaned and checked. · Electrostatic charge may accumulate and create a
hazardous condition when charging or discharging the refrigerant. To avoid
fire or explosion, dissipate static electricity during transfer by grounding
and bonding containers and equipment before charging / discharging. RECOVERY
NOTE: Refer to the Installation Instructions attached to the outdoor unit.
NOTICE The English text is the original instructions. Other languages are
translations of the original instructions.
10
Check of Density Limit
Check the amount of refrigerant in the system and floor space of the room
according to the legislation on refrigerant drainage. If there is no
applicable legislation, follow the standards described below.
The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for the maximum refrigerant charge amount [mmax] used in the appliance are determined according to installation space of the appliance.
Installation conditions Procedure of preliminary calculation
1. Determine the room space in accordance with the requirements of installation.
2. Calculate the maximum refrigerant charge amount [mmax].
When connecting the refrigerant tubes and installing the
indoor unit in each partitioned room, it is necessary to calculate the allowable refrigerant charge amount in each
IN_1 IN_2
room.
For all indoor units shown in Fig. 1, calculate the
allowable refrigerant charge amount that can be used in Room_1 Room_2
each room [mIN_1, mIN_2,—, mIN_n].
Calculate the maximum refrigerant charge for each indoor
unit from Fig. 2 by referring to the following items.
– Floor area of the room
– Indoor units type
– Capacity of indoor unit
– Installation height of Indoor Unit
– Use or nonuse of R32 refrigerant leakage detection sensor
IN_3
IN_n
IN_n-1
Room_3 Room_m Fig. 1
Room No.
No. of indoor units
Room_1 Room_2 Room_3
–Room_m Room_m
IN_1 IN_2 IN_3
–IN_n-1 IN_n
Indoor units type
4-Way Cassette 60 × 60 Slim Low Static Ducted
4-Way Cassette —
Wall-Mounted 4-Way Cassette
Capacity of indoor
unit
15 56 56 –45 140
Installation height of Indoor Unit: hinst (m)
R32 refrigerant leakage detection
sensor
Floor area of the
room (m2)
Refrigerant charge amount that can be used for each indoor unit (kg)
hinst 2.2
Use
10
hinst 2.2
Nonuse
15
hinst 2.2
Use
20
—
—
—
hinst 1.8
Nonuse
30
hinst 2.2
Use
30
mIN_1 mIN_2 mIN_3
–mIN_n-1 mIN_n
[mmax] = Min (mIN_1, mIN_2, mIN_3, —, mIN_n-1, mIN_n)
The minimum value of the allowable refrigerant charge amount in each room is the maximum value of the maximum refrigerant charge amount [mmax] that can be used in the system.
3. Calculate the maximum refrigerant charge amount [mc] by following details of piping installation. As a reference, refer to Installation Instructions of outdoor unit.
4. Determine from two values [mmax] in Step 2 and [mc] in Step 3.
[mc] [mmax] : Can be installed. [mc] > [mmax] : Return to Steps 1 to 3 and
change the indoor unit type, capacity and pipe
length.
11
< Whether or not to use R32 refrigerant leakage detection sensor > · According to the type of diagrams shown in Fig. 2, it is necessary to install R32 refrigerant leakage detection sensor if the installation space is within the range of using R32 refrigerant leakage detection sensor. · As to installation method of R32 refrigerant leakage detection sensor, refer to the Installation Instructions attached to the indoor unit and R32 refrigerant leakage detection sensor. · When connecting R32 refrigerant leakage detection sensor, group connection with a remote controller is not possible. Be sure to prepare a remote controller for each indoor unit. NOTE In the case of connecting R32 refrigerant leakage detection sensor : · For systems using R32 refrigerant, this unit is equipped with a refrigerant leak detector for safety. To be effective, the unit must be electrically powered at all times after installation, other than when servicing. 12The refrigerant charge amount compared with the floor area of the room is roughly as follows:
Type 22 Type 28 Type 36
Refrigerant charge amount (kg)
4-Way Cassette
Fig. 2
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 45
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32
refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 56
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
13
Type 60
Refrigerant charge amount (kg)
20.0 Use of R32 refrigerant leakage detection sensor
15.0 U-8LZ2E8, U-10LZ2E8
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 73 Type 90
Refrigerant charge amount (kg)
20.0 Use of R32 refrigerant leakage detection sensor
15.0 U-8LZ2E8, U-10LZ2E8
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32
refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 106 Type 112 Type 140 Type 160
Refrigerant charge amount (kg)
20.0 Use of R32 refrigerant leakage detection sensor
15.0 U-8LZ2E8, U-10LZ2E8
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
14
Floor area of the room (m2)
Use or nonuse of R32 refrigerant leakage detection sensor
Capacity of indoor unit
Nonuse 22 ~ 160
0
0.0
2
1.0
4
2.0
6
3.0
8
3.5
10
3.9
12
4.3
14
4.7
16
5.0
18
5.3
20
5.6
22
5.8
24
6.1
26
6.4
28
6.6
30
6.8
32
7.1
34
7.3
36
7.5
38
7.7
40
7.9
42
8.1
44
8.3
46
8.5
48
8.7
50
8.8
52
9.0
54
9.2
56
9.4
58
9.5
60
9.7
62
9.8
64 10.0
66 10.2
68 10.3
70 10.5
72 10.6
74 10.8
76 10.9
78
11.1
80
11.2
4-Way Cassette
Use
~ 36
45
56
60
Refrigerant charge amount (kg)
0.0
0.0
0.0
0.0
1.0
1.0
1.0
1.0
2.0
2.0
2.0
2.0
3.0
3.0
3.0
3.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
6.0
6.0
6.0
6.0
7.0
7.0
7.0
7.0
8.1
8.1
8.1
8.1
8.8
9.1
9.1
9.1
8.8
9.1
9.7
10.1
8.8
9.1
9.7
11.1
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
8.8
9.1
9.7
11.7
9.0
9.1
9.7
11.7
9.2
9.2
9.7
11.7
9.4
9.4
9.7
11.7
9.5
9.5
9.7
11.7
9.7
9.7
9.7
11.7
9.8
9.8
9.8
11.7
10.0
10.0
10.0
11.7
10.2
10.2
10.2
11.7
10.3
10.3
10.3
11.7
10.5
10.5
10.5
11.7
10.6
10.6
10.6
11.7
10.8
10.8
10.8
11.7
10.9
10.9
10.9
11.7
11.1
11.1
11.1
11.7
11.2
11.2
11.2
11.7
15
73, 90
106~
0.0
0.0
1.0
1.0
2.0
2.0
3.0
3.0
4.0
4.0
5.0
5.0
6.0
6.0
7.0
7.0
8.1
8.1
9.1
9.1
10.1
10.1
11.1
11.1
12.0 12.1 (12.0)
12.0 13.1 (12.0)
12.0 14.1 (12.0)
12.0 15.1 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
12.0 15.9 (12.0)
Floor area of the room (m2)
4-Way Cassette
Use or nonuse of R32
refrigerant leakage
Nonuse
Use
detection sensor
22 ~ 160
~ 36
Capacity of indoor unit
45
56
60
Refrigerant charge amount (kg)
73, 90
106~
82
11.3
11.3
11.3
11.3
11.7
12.0 15.9 (12.0)
84
11.5
11.5
11.5
11.5
11.7
12.0 15.9 (12.0)
86
11.6
11.6
11.6
11.6
11.7
12.0 15.9 (12.0)
88
11.7
11.7
11.7
11.7
11.7
12.0 15.9 (12.0)
90
11.9
11.9
11.9
11.9
11.9
12.0 15.9 (12.0)
92 12.0
12.0
12.0
12.0
12.0
12.0 15.9 (12.0)
94 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 15.9 (12.0)
96 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 15.9 (12.0)
98 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 15.9 (12.0)
100 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 15.9 (12.0)
( ) : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5, U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
16
The refrigerant charge amount compared with the floor area of the room is roughly as follows:
Type 22 Type 28 Type 36
Refrigerant charge amount (kg)
4-Way Cassette (3-way airflow)
Fig. 2
20.0 15.0 10.0
5.0 0.0
0
U-8LZ2E8, U-10LZ2E8
Use of R32 refrigerant leakage detection sensor
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 Nonuse of R32
refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 45
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
10.0
5.0
0.0 0
Use of R32 refrigerant leakage detection sensor
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 56
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
10.0
5.0
0.0 0
Use of R32 refrigerant leakage detection sensor
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
17
Type 60
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 73 Type 90
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
Type 106 Type 112 Type 140 Type 160
Refrigerant charge amount (kg)
20.0
Use of R32 refrigerant leakage detection sensor 15.0
U-8LZ2E8, U-10LZ2E8
10.0
5.0
0.0 0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
Nonuse of R32 refrigerant leakage detection sensor
10 20 30 40 50 60 70 80 90 100 Floor area of the room (m2)
18
Floor area of the room (m2)
4-Way Cassette (3-way airflow)
Use or nonuse of R32 refrigerant leakage detection sensor
Nonuse
22 ~ 160
~ 36
Capacity of indoor unit
0
0.0
0.0
2
1.0
1.0
4
2.0
2.0
6
3.0
3.0
8
3.5
4.0
10
3.9
5.0
12
4.3
6.0
14
4.7
7.0
16
5.0
7.3
18
5.3
7.3
20
5.6
7.3
22
5.8
7.3
24
6.1
7.3
26
6.4
7.3
28
6.6
7.3
30
6.8
7.3
32
7.1
7.3
34
7.3
7.3
36
7.5
7.5
38
7.7
7.7
40
7.9
7.9
42
8.1
8.1
44
8.3
8.3
46
8.5
8.5
48
8.7
8.7
50
8.8
8.8
52
9.0
9.0
54
9.2
9.2
56
9.4
9.4
58
9.5
9.5
60
9.7
9.7
62
9.8
9.8
64
10.0
10.0
66
10.2
10.2
68
10.3
10.3
70
10.5
10.5
72
10.6
10.6
74
10.8
10.8
76
10.9
10.9
78
11.1
11.1
80
11.2
11.2
Use
45
56
60
Refrigerant charge amount (kg)
0.0
0.0
0.0
1.0
1.0
1.0
2.0
2.0
2.0
3.0
3.0
3.0
4.0
4.0
4.0
5.0
5.0
5.0
6.0
6.0
6.0
7.0
7.0
7.0
7.6
8.1
8.1
7.6
8.1
9.1
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.6
8.1
9.5
7.7
8.1
9.5
7.9
8.1
9.5
8.1
8.1
9.5
8.3
8.3
9.5
8.5
8.5
9.5
8.7
8.7
9.5
8.8
8.8
9.5
9.0
9.0
9.5
9.2
9.2
9.5
9.4
9.4
9.5
9.5
9.5
9.5
9.7
9.7
9.7
9.8
9.8
9.8
10.0
10.0
10.0
10.2
10.2
10.2
10.3
10.3
10.3
10.5
10.5
10.5
10.6
10.6
10.6
10.8
10.8
10.8
10.9
10.9
10.9
11.1
11.1
11.1
11.2
11.2
11.2
19
73, 90
106~
0.0
0.0
1.0
1.0
2.0
2.0
3.0
3.0
4.0
4.0
5.0
5.0
6.0
6.0
7.0
7.0
8.1
8.1
9.1
9.1
9.7
10.1
9.7
11.1
9.7
12.1 (12.0)
9.7
13.1 (12.0)
9.7
14.1 (12.0)
9.7
15.1 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.7
15.9 (12.0)
9.8
15.9 (12.0)
10.0 15.9 (12.0)
10.2 15.9 (12.0)
10.3 15.9 (12.0)
10.5 15.9 (12.0)
10.6 15.9 (12.0)
10.8 15.9 (12.0)
10.9 15.9 (12.0)
11.1 15.9 (12.0)
11.2 15.9 (12.0)
Floor area of the room (m2)
4-Way Cassette (3-way airflow)
Use or nonuse of R32
refrigerant leakage
Nonuse
Use
detection sensor
22 ~ 160
~ 36
Capacity of indoor unit
45
56
60
Refrigerant charge amount (kg)
73, 90
106~
82
11.3
11.3
11.3
11.3
11.3
11.3 15.9 (12.0)
84
11.5
11.5
11.5
11.5
11.5
11.5 15.9 (12.0)
86
11.6
11.6
11.6
11.6
11.6
11.6 15.9 (12.0)
88
11.7
11.7
11.7
11.7
11.7
11.7 15.9 (12.0)
90
11.9
11.9
11.9
11.9
11.9
11.9 15.9 (12.0)
92 12.0
12.0
12.0
12.0
12.0
12.0 15.9 (12.0)
94 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 15.9 (12.0)
96 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 15.9 (12.0)
98 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 15.9 (12.0)
100 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 15.9 (12.0)
( ) : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5, U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
20
The refrigerant charge amount compared with the floor area of the room is roughly as follows:
Type 22 Type 28 Type 36
Refrigerant charge amount (kg)
4-Way Cassette (2-way airflow)
Fig. 2
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor 10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
Nonuse of R32 refrigerant leakage detection sensor
0.0
0
10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
Type 45
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor 10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
Nonuse of R32 refrigerant leakage detection sensor 0.0
0
10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
Type 56
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor 10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
Nonuse of R32 refrigerant leakage detection sensor 0.0
0
10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
21
Type 60
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor 10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
0.0 0
Nonuse of R32 refrigerant leakage detection sensor 10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
Type 73 Type 90
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor 10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
0.0 0
Nonuse of R32 refrigerant leakage detection sensor 10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
Type 106 Type 112 Type 140 Type 160
Refrigerant charge amount (kg)
20.0
U-8LZ2E8, U-10LZ2E8 15.0
Use of R32 refrigerant leakage detection sensor
10.0
U-4LZ2E5, U-5LZ2E5, U-6LZ2E5 U-4LZ2E8, U-5LZ2E8, U-6LZ2E8 5.0
0.0 0
Nonuse of R32 refrigerant leakage detection sensor 10 20 30 40 50 60 70 80
Floor area of the room (m2)
90 100
22
Floor area of the room (m2)
4-Way Cassette (2-way airflow)
Use or nonuse of R32 refrigerant leakage detection sensor
Nonuse
22 ~ 160
~ 36
Capacity of indoor unit
0
0.0
0.0
2
1.0
1.0
4
2.0
2.0
6
3.0
3.0
8
3.5
4.0
10
3.9
5.0
12
4.3
5.1
14
4.7
5.1
16
5.0
5.1
18
5.3
5.3
20
5.6
5.6
22
5.8
5.8
24
6.1
6.1
26
6.4
6.4
28
6.6
6.6
30
6.8
6.8
32
7.1
7.1
34
7.3
7.3
36
7.5
7.5
38
7.7
7.7
40
7.9
7.9
42
8.1
8.1
44
8.3
8.3
46
8.5
8.5
48
8.7
8.7
50
8.8
8.8
52
9.0
9.0
54
9.2
9.2
56
9.4
9.4
58
9.5
9.5
60
9.7
9.7
62
9.8
9.8
64 10.0
10.0
66 10.2
10.2
68 10.3
10.3
70 10.5
10.5
72 10.6
10.6
74 10.8
10.8
76 10.9
10.9
78
11.1
11.1
80
11.2
11.2
Use
45
56
60
Refrigerant charge amount (kg)
0.0
0.0
0.0
1.0
1.0
1.0
2.0
2.0
2.0
3.0
3.0
3.0
4.0
4.0
4.0
5.0
5.0
5.0
5.2
5.6
6.0
5.2
5.6
6.6
5.2
5.6
6.6
5.3
5.6
6.6
5.6
5.6
6.6
5.8
5.8
6.6
6.1
6.1
6.6
6.4
6.4
6.6
6.6
6.6
6.6
6.8
6.8
6.8
7.1
7.1
7.1
7.3
7.3
7.3
7.5
7.5
7.5
7.7
7.7
7.7
7.9
7.9
7.9
8.1
8.1
8.1
8.3
8.3
8.3
8.5
8.5
8.5
8.7
8.7
8.7
8.8
8.8
8.8
9.0
9.0
9.0
9.2
9.2
9.2
9.4
9.4
9.4
9.5
9.5
9.5
9.7
9.7
9.7
9.8
9.8
9.8
10.0
10.0
10.0
10.2
10.2
10.2
10.3
10.3
10.3
10.5
10.5
10.5
10.6
10.6
10.6
10.8
10.8
10.8
10.9
10.9
10.9
11.1
11.1
11.1
11.2
11.2
11.2
23
73, 90
0.0 1.0 2.0 3.0 4.0 5.0 6.0 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.8 7.1 7.3 7.5
7.7 7.9 8.1 8.3 8.5 8.7 8.8 9.0 9.2 9.4 9.5 9.7 9.8 10.0 10.2 10.3 10.5 10.6
10.8 10.9 11.1 11.2
106~
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.1 9.1 10.1 11.0 11.0 11.0 11.0 11.0 11.0
11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.0
11.0 11.0 11.0 11.0 11.0 11.0 11.0 11.1 11.2
Floor area of the room (m2)
4-Way Cassette (2-way airflow)
Use or nonuse of R32
refrigerant leakage
Nonuse
Use
detection sensor
22 ~ 160
~ 36
Capacity of indoor unit
45
56
60
Refrigerant charge amount (kg)
73, 90
106~
82
11.3
11.3
11.3
11.3
11.3
11.3
11.3
84
11.5
11.5
11.5
11.5
11.5
11.5
11.5
86
11.6
11.6
11.6
11.6
11.6
11.6
11.6
88
11.7
11.7
11.7
11.7
11.7
11.7
11.7
90
11.9
11.9
11.9
11.9
11.9
11.9
11.9
92 12.0
12.0
12.0
12.0
12.0
12.0
12.0
94 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0)
96 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0)
98 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0)
100 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0)
( ) : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5, U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
GENERAL
This booklet briefly outlines where and how to install the air conditioning
system. Please read over the entire set of instructions for the indoor and
outdoor units and make sure all accessory parts listed are with the system
before beginning. The installation of pipe-work shall be kept to a minimum.
This symbol shows that this equipment uses a flammable refrigerant. If the
WARNING refrigerant is leaked, together with an external ignition source,
there is a
possibility of ignition.
CAUTION This symbol shows type of flammable refrigerant contained in the
system.
CAUTION This symbol shows that the Operating Instructions should be read carefully.
CAUTION CAUTION
This symbol shows that a service personnel should be handling this equipment
with reference to the Technical Manual.
This symbol shows that there is information included in the Operating
Instructions and/or Installation Instructions.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver 2. Phillips head screwdriver 3. Knife or wire
stripper 4. Tape measure 5. Carpenter’s level 6. Sabre saw or keyhole saw 7.
Hacksaw 8. Core bits 9. Hammer 10. Drill 11. Tube cutter 12. Tube flaring tool
13. Torque wrench 14. Adjustable wrench 15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
Part Name
Full-scale installation diagram
Figure
Q’ty
Remarks
1
Printed on container box
Washer
Screw Insulating tape
8
For suspension bolts
For full-scale 4 installation
diagram
2
For gas and liquid tube flare nuts
Flare insulator
1 For liquid tube
Flare insulator
1 For gas tube
Drain hose Hose band Packing
1
1
For securing drain hose
1
Drain insulator
Clamper
Operating Instructions Installation Instructions 25
1
4
For electrical wiring
1
1
As for S-60MU2E5BN, S-73MU2E5BN or S-90MU2E5BN, the following accessories are additionally provided.
Part Name
Figure
Q’ty
Remarks
Differentdiameter-tube joint
Insulating tape
1
Gas socket tube A : ø15.88 ø12.7
1
Liquid socket tube B : ø9.52 ø6.35
2
For gas and liquid tube flare nuts
Use M10 for suspension bolts.
Field supply for suspension bolts and nuts.
Take all supplied accessories out of the plastic bag.
If the protection tape for the fan remains, peel off the tape.
Accessories Supplied
Protection tape for the fan
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you
will need: 1. Deoxidized annealed copper tube for refrigerant tubing. 2.
Foamed polyethylene insulation for copper tubes as required to precise length
of tubing.
Wall thickness of the insulation should be not less than 8 mm. 3. Use
insulated copper wire for field wiring. Wire size varies with the total length
of wiring. See
Section “4. ELECTRICAL WIRING” for details.
CAUTION
Check local electrical codes and regulations before obtaining wire. Also,
check any specified instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape 2. Insulated staples or clamps for connecting
wire (See your local codes.) 3. Putty 4. Refrigeration tubing lubricant 5.
Clamps or saddles to secure refrigerant tubing 6. Scale for weighing
26
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID: areas where leakage of flammable gas may be expected. places where
large amounts of oil mist exist. direct sunlight. locations near heat sources
which may affect the performance of the unit. locations where external air may
enter the room directly. This may cause “condensation” on
the air discharge ports, causing them to spray or drip water. locations where
the remote controller will be splashed with water or affected by dampness or
humidity. installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO: select an appropriate position from which every corner of the room can be
uniformly cooled. select a location where the ceiling is strong enough to
support the weight of the unit. select a location where tubing and drain pipe
have the shortest run to the outdoor unit. allow room for operation and
maintenance as well as unrestricted airflow around the unit. Set up the
airflow increase in case of the following conditions.
Ceiling heights are: 2.7 m (Type 22-56) 3.0 m (Type 60-90) 3.6 m (Type
106-160)
If the floor-to-ceiling is high, the wind speed distribution will become poor.
For the setting method, see Section “7-3. Others”. the limitation of the
tubing length between the indoor and the outdoor units should be referred to
the Installation Instructions of the outdoor unit. allow room for mounting the
remote controller about 1 m off the floor, in an area that is not in direct
sunlight or in the flow of cool air from the indoor unit.
4-Way Cassette Type
Indoor unit
Wall min. 1 m Over 2.2 m
1 m 1 m
1 m 1 m
min. 1 m
Ceiling
min. 3 m Obstacles
27
Installation location of R32 refrigerant leakage detection sensor When
installing R32 refrigerant leakage detection sensor away from the indoor unit,
place it at 300 mm or less from a floor surface and satisfy the condition
either (1) or (2) below. (1) If no obstacles exist in a straight line from R32
refrigerant leakage detection sensor to the
indoor unit, wall distance should be within 10 m in horizontal straight line.
A : Top View
A
10 m or less
R32 refrigerant leakage detection sensor
Indoor unit
Indoor unit
B : Front View
10 m or less
Indoor unit
B
R32 refrigerant leakage detection sensor
300 mm or less
R32 refrigerant leakage detection sensor
(2) If obstacles exist in a straight line from R32 refrigerant leakage detection sensor to the indoor unit, wall distance should be within 7 m in horizontal straight line.
A : Top View
Obstacles
A
7 m or less
R32 refrigerant leakage detection sensor
Indoor unit
Indoor unit
B : Front View
7 m or less
Indoor unit
B Obstacles
R32 refrigerant leakage detection sensor
Obstacles 300 mm or less
R32 refrigerant leakage detection sensor
28
3. HOW TO INSTALL THE INDOOR UNIT
Note: For DC Fan Tap Change Procedure for 4-Way Cassette, see Section “7-3.
Others”.
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to check that the unit is
level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using the method shown in
the diagrams, by attaching them to the ceiling support structure, or by any
other method that ensures that the unit will be securely and safely suspended.
(2) Follow the diagram to make the holes in the ceiling.
Hole-in-anchor Hole-in-plug
Concrete
Insert
Suspension bolt (M10 or 3/8″) (field supply)
Indoor Unit View from top
A: 700 mm B: 860 ~ 910 mm
A: 780 mm B: 860 ~ 910 mm
A: (suspension bolt pitch) B: (ceiling opening dimension)
(3) Determine the pitch of the suspension bolts using the supplied full-scale installation diagram (printed on container box). The diagram show the relationship between the positions of the suspension fitting, unit, and panel. Use the nut (field supply) and washer (supplied) for upper and lower position of the suspension lug.
Drain outlet (other side) (VP25)
Refrigerant tubing joint (gas side)
Suspension lug
Refrigerant tubing joint (liquid side) 840 mm
127 mm 177 mm
Type 22 ~ 90: 256 mm Type 106 ~ 160: 319 mm
184 mm 134 mm
33.5 mm
340 mm
272 mm
-
Over 20 mm
-
Over 20 mm
950 mm
50 mm
- The overlapping portion between the ceiling and panel for cassette should be kept over 20 mm.
29
3-3. Placing the Unit Inside the Ceiling
This unit is equipped with a drain pump. Check with a tape measure or
carpenter’s level. Before installing the panel for cassette, complete the work
of drain pipe and refrigerant tube installation.
(1) When placing the unit inside the ceiling, determine the pitch of the
suspension bolts using the supplied full-scale installation diagram. Tubing
and wiring must be laid inside the ceiling when suspending the unit. If the
ceiling is already constructed, lay the tubing and wiring into position for
connection to the unit before placing the unit inside the ceiling.
(2) The length of suspension bolts must be appropriate for a distance between
the bottom of the bolt and the bottom of the unit of more than 18 mm.
Over 18 mm 12 ~ 17 mm
Indoor unit
Indoor unit
Ceiling board
Ceiling board
Screw for attaching paper (4 points)
Open the ceiling board as large as this paper outline
Full-scale installation diagram (printed on top of container box)
(3) Thread the 3 hexagonal nuts and 2 washers onto each of the 4 suspension
bolts. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for
the lower side, so that the unit will not fall off the suspension lugs.
Suspension bolt
Nuts and washers (use for upper and lower)
Suspension lug
Double nut
Notch 12 ~ 17 mm
(4) Adjust so that the distance between the unit and the ceiling bottom is 12
to 17 mm. Tighten the nuts on the upper side and lower side of the suspension
lug.
(5) If the protection tape for the fan during transportation remains, peel off
the tape. (See Section “1-2. Accessories Supplied with Unit”.)
(6) Check with a tape measure or carpenter’s level.
3-4. How to Process Tubing
See Section “5. HOW TO PROCESS TUBING”.
30
3-5. Installing the Drain Pipe
3-5-1. Before Performing the Installation of Drain Piping
(1) Limitations of Raising the Drain Pipe Connection
CAUTION
The drain pipe can be raised to a maximum height of 850 mm from the bottom of the ceiling. Do not attempt to raise it higher than 850 mm. Doing so will result in water leakage.
300 mm or less (as short as possible)
A B
A : 850 mm or lower B : 666 mm or lower
Indoor unit Bottom of the Ceiling board * Length of supplied drain pipe = 250
mm
(2) Limitations of Drain Pipe Connection
CAUTION
Do not install the drain pipe with an upward gradient from the drain port
connection. This will cause the drain water to flow backward and leak when the
unit is not operating.
Do not install an air bleeder as this may cause water to spray from the drain
pipe outlet. Do not provide U-trap or bell-shaped trap in the middle of the
drain pipe. Doing so will cause
abnormal sound.
Air bleeder prohibited Upward gradient prohibited
Trap prohibited
Indoor unit
Make sure the drain pipe has a downward gradient (1/100 or more; downward from
drain port connection).
Separation of support bracket = 1.5 m ~ 2 m
Indoor unit
Downward gradient = 1/100 or more
If there is a centralized drain pipe, be careful to the size of pipe.
31
(3) Limitations of Drain Hose Connection
CAUTION
Do not bend the supplied drain hose 90° or more. Bend it less than 45°.
Bend angle 90° prohibited
Bend angle less than 45°
Do not make a trap in the middle of the supplied drain hose. Doing so will
cause abnormal sound.
Trap prohibited
32
3-5-2. Installing the Drain Pipe
CAUTION
Do not apply force to the drain port when connecting the drain pipe. Install
and fix it near the indoor unit as close as possible.
Do not use adhesive when connecting the drain port pipe and the drain hose.
(1) How to Install the Drain Pipe
- First insert the supplied hose band into the drain port pipe. Then make sure the head of the screw is facing toward a technical engineer when placing the screw of the hose band at an upward angle.
- Insert the soft PVC socket of the supplied drain hose to the drain port pipe. Do not use adhesive when connecting the drain hose to the drain port pipe. Insert it until the tip of the drain hose contacts the uneven surface of the drain port pipe.
- Move the hose band so that the center position of the hose band can be placed approx. 30 mm away from the external plate of the indoor unit. See diagram below.
- Screw the drain hose tightly facing the screw of the hose band upward. (Torque: 2.5 N·m 3.4 N·m) (If the screw is tightened beneath the drain hose, the troubles will be generated.)
- Apply approx. 2 g of adhesive on both sides of the drain hose without connection of the hard PVC socket and the hard PVC pipe joint (VP25) in the field supply.
- Connect the drain hose and the hard PVC pipe joint so that the adhesive area of both sides can be overlapped. Wipe off the protrusion-adhesive with a soft cloth.
Drain port
Hose band (supplied)
(Drainage check section on drain port, transparent)
Soft PVC socket
Hard PVC pipe joint (VP25 field supplied)
Hard PVC socket
Uneven surface Indoor unit
Drain hose (supplied)
- Apply approx. 2 g of adhesive on both sides of supplied the drain hose and the hard PVC pipe joint (VP25) in the field
supply. Wipe off the protrusion-adhesive
- Drain port may possibly
with a soft cloth.
be damaged and cause
the water leakage if PVC adhesive is used.
Adhere with PVC adhesive.
Do not use adhesive here.
Fasten the hose band as shown the diagram below. (Torque: 2.5 N·m – 3.4 N·m)
Indoor unit
Uneven surface 5 mm
Packing (supplied)
57 mm 20 mm or more
Note: Be sure to tightly insert the hard PVC pipe joint (including elbow)
minimum 20 mm or more. * However, do not use the hard PVC pipe joint
allowable more than 55 mm insertion.
Drain insulator (supplied)
- After checking the drainage, wrap the supplied packing and drain pipe insulator around the pipe.
33
3-5-3. Checking the Drainage CAUTION Be careful since the fan will start when
you short the pin on the indoor unit control PCB.
After wiring (see Section “4. ELECTRICAL WIRING”.) and drain piping are
completed, use the following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up
spilled water. (1) Connect power to the power terminal board (L, N terminals)
inside the electrical component
box. (2) Slowly pour about 1 L of water into the drain pan to check drainage.
Drainage check
Over 100 mm
Drain pan outlet Plastic container for water intake Water (Approx. 1 L)
(3) Short the check pin (CHK) (6P : 5-6) on the indoor unit control PCB and
operate the drain pump. Check the water flow through the transparent drain
pipe and see if there is any leakage. * If the check pin (CHK) (6P : 5-6) is
shorted, the fan starts rotating at high speed and could cause injury.
(4) When the check of drainage is complete, open the check pin (CHK) (6P :
5-6) and remount the tube cover.
(5) Checkpoint after installation After installation of indoor and outdoor
units, panels and electrical wiring, check Section “10. CHECKLIST AFTER
INSTALLATION WORK”.
3-6. Important Note for Wiring 4-Way Cassette Type
Power supply inlet
(1) The power supply inlet is located at the lower area of the refrigerant
tubing side of the unit. The electrical component box is located at the air
intake of the bottom of the unit.
(2) Before installing the panel for cassette, be sure to carry out the wiring
connection.
34
(3) Remove the lid located on the bottom of the indoor unit attaching the
electrical component box by unscrewing the Phillips head tapping screws (×2).
Tapping screw position
(4) Lead the wires from the power supply inlet to the unit. Be sure to lead
the wires through the power supply inlet. Make sure that no wire is caught
between the indoor unit and panel for cassette. Otherwise, the unit may cause
a fire.
(5) Connect the wires into the terminals through the power supply inlet for
the electrical component box. Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its original position
with paying attention not to have the wires caught in the lid. See Section “4.
ELECTRICAL WIRING”.
35
4. ELECTRICAL WIRING
4-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its
nameplate, then carry out the wiring closely following the wiring diagram
under Section 4-3. WARNING (2) This equipment is strongly recommended to be
installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device
(RCD). Otherwise, it may cause electrical shock and fire in case of equipment
breakdown or insulation breakdown. The ELCB must be incorporated in the fixed
wiring in accordance with the wiring regulations. The ELCB must be an approved
circuit capacity, having a contact separation in all poles. The ELCB or RCD
suitable for use with inverters, resistant to high frequency noise, is most
suitable. The ELCB’s or RCD’s intended for protection to include high
frequency currents are unnecessary and should be avoided, as potentially
causing nuisance tripping, in this application. (3) To prevent possible
hazards from insulation failure, the unit must be grounded.
(4) Each wiring connection must be done in accordance with the wiring system
diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any
moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The
manufacturer will accept no responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to locality. For field
wiring rules, please refer to your LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant rules and
regulations.
(8) To prevent malfunction of the air conditioner caused by electrical noise,
care must be taken when wiring as follows: The remote control wiring and the
inter-unit control wiring should be wired apart from the inter-unit power
wiring. Use shielded wires for inter-unit control wiring between units and
ground the shield on both sides. CAUTION
Check local electrical codes and regulations before wiring. Also, check any
specified instruction or limitations.
36
4-2. Wire Length and Wire Diameter for Power Supply System
Indoor unit
Type U2
(B) Power supply cable Min. 2.5 mm2 1 Max. 130 m 2
Time delay fuse or circuit capacity 15 A
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring Min. 0.75 mm2
Use shielded wiring *3 Max. 1,000 m
(D) Remote control wiring Min. 0.75 mm2 Max. 500 m
(E) Remote control wiring for group control
Min. 0.75 mm2
Max. 200 m (Total)
NOTE
1 Maximum applicable wire for terminal board of indoor unit : 4 mm2 2 Maximum length shows a 2% voltage drop. *3 With ring-type wire terminal
37
4-3. Wiring System Diagrams
Power supply
L
220-230-240V~ 50-60Hz N
Ground Remote controller
1 2
Indoor unit (No. 1)
L N
B
U1
U2
D
R1 R2
Power supply
L
220-230-240V~ 50-60Hz N
Ground
Remote controller
1 2
Indoor unit (No. 2)
L N
B
U1
U2
D
R1 R2
Power supply
L
220-230-240V~ 50-60Hz N
Ground
Indoor unit (No. 3)
L N
B
U1
U2
E*
R1 R2
C C
C C
ex.)
Outdoor unit : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5
L N
L Power supply N 220-230-240V~ 50Hz
U1
Ground
U2
ex.) Outdoor unit : U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
L1 L2 L3 N
L1 Power supply
L2 L3
380-400-415V 3N~ 50Hz
N
U1
Ground
U2
( : Functional earthing)
4P terminal board
2P terminal board
Power supply
L
220-230-240V~ 50-60Hz N
Ground Remote controller
1 2
Indoor unit (No. n)
L N
B
U1
U2
D
R1 R2
R32 refrigerant leakage
D
detection sensor
1
2
U1 U2
Inter-unit control wiring
R1 R2
Remote control wiring
Type U2
L
N
Power supply cable
NOTE
(1) See Section 4-2 for the explanation of “B”, “C”, “D” and “E” under Section
4-3.
(2) The basic connection diagram of the indoor unit shows the terminal boards,
so the terminal boards in your equipment may differ from the diagram.
(3) Refrigerant Circuit address should be set before turning the power on.
(4) Regarding Refrigerant Circuit address setting, refer to the installation
instructions supplied with the remote controller (Optional). Auto address
setting can be executed by remote controller automatically.
(5) In the case of connecting R32 refrigerant leakage detection sensor :
· Be sure to make wirings through the ceiling or the walls so that the wires
of R32 refrigerant leakage detection sensor cannot be visible from inside the
room.
· A single R32 refrigerant leakage detection sensor cannot be connected to
multiple indoor units.
- Group connection “E” with a remote controller is not possible. Be sure to connect a remote controller to each indoor unit.
38
CAUTION
(1) When linking the outdoor units in a network, disconnect the terminal
extended from the short plug from all outdoor units except any one of the
outdoor units. (When shipping: In shorted condition.) For a system without
link (no wiring connection between outdoor units), do not remove the short
plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
Outdoor unit
Outdoor unit Prohibited
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.
Outdoor unit
Indoor unit
Indoor unit
NO
Indoor unit
Indoor unit Branch point
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Central Controller
Outdoor unit
: Branch point
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
More than 2m required
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
(5) Use shielded wires for inter-unit control wiring
Shielded wire
(C) and ground the shield on both sides,
otherwise misoperation from noise may occur.
Connect wiring as shown in Section 4-3.
(Functional earthing)
(Functional earthing)
(6) Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F
which conform to CENELEC (HAR) rating specifications) or use the cables based on
IEC standard. (60245 IEC57, 60245 IEC66)
39
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction.
A fire hazard may also occur. Therefore, ensure that all wiring is tightly
connected. When connecting each power wire to the terminal, follow the
instructions on “How to connect wiring to the terminal” and fasten the wire
securely with the terminal screw.
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the insulation to expose
the stranded wiring about 10 mm and tightly twist the wire ends. Then attach
the ring pressure terminal.
(2) Using a Phillips head screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using a ring connector fastener or pliers, securely clamp each stripped
wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and tighten the removed
terminal screw using a screwdriver.
Special washer
Wire
Strip 10 mm
Stranded wire
Screw Ring pressure terminal Terminal board
Ring pressure terminal
Screw and Special washer
Ring pressure terminal Wire
Examples of shield wires (1) Remove cable coat not to scratch braided
shield.
(2) Unbraid the braided shield carefully and twist the unbraided shield wires
tightly together. Insulate the shield wires by covering them with an
insulation tube or wrapping insulating tape around them.
(3) Remove coat of signal wire.
(4) Attach ring pressure terminals to the signal wires and the shield wires
insulated in Step (2).
Insulating tape Shield mesh 8 mm
Insulating tape Shield mesh
40
Wiring samples
Functional ground screw (External Electronic Expansion Valve Kit and Schedule Timer)
R32 refrigerant leakage detection sensor wiring
Protective ground screw (External Solenoid Valve Kit for 3WAY)
Remote control wiring
Inter-unit control wiring
Use this screw when connecting the shield for the Inter-unit control wiring to
ground. ( : Functional earthing)
Protective ground screw
Earth wiring: Make the earth wiring 25 – 30 mm longer than power cable.
Power cable Power supply cable
Clamping Clip
Clamper1 (supplied) 1 Fasten tightly.
Clamper*1 (supplied)
41
5. HOW TO PROCESS TUBING
Must ensure mechanical connections be accessible for maintenance purposes.
When connecting the tube size ø19.05 with the system using refrigerant R32, be
sure to connect by brazing.
5-1. Connecting the Refrigerant Tubing
Use of the Flaring Method
Many of conventional split system air conditioners employ the flaring method
to connect refrigerant tubes that run between indoor and outdoor units. In
this method, the copper tubes are flared at each end and connected with flare
nuts.
Flaring Procedure with a Flare Tool (1) Cut the copper tube to the required
length with a tube cutter.
It is recommended to cut approx. 30 50 cm longer than the tubing length you
estimate. (2) Remove burrs at each end of the copper tubing with a tube reamer
or a similar tool. This process is important and should be done carefully to
make a good flare. Be sure to keep any contaminants (moisture, dirt, metal
filings, etc.) from entering the tubing.
NOTE
When reaming, hold the tube end downward and be sure that no copper scraps
fall into the tube.
(3) Remove the flare nut from the unit and be sure to mount it on the copper
tube.
(4) Make a flare at the end of the copper tube with a flare tool.
Deburring
Before
After
Copper tubing Reamer
Flare nut
Copper Flare tool tubing
NOTE
When flared joints are reused, the flare part shall be re-fabricated. A good
flare should have the following characteristics: inside surface is glossy and
smooth edge is smooth tapered sides are of uniform length
Caution Before Connecting Tubes Tightly
(1) Apply a sealing cap or water-proof tape to prevent dust or water from
entering the tubes before they are used.
(2) Use a small amount of ether oil (PVE only) to apply refrigerant lubricant
to the inside of the flare nut when making a flare connection. Pay careful
attention to prevent the ether oil (PVE only) from directly attaching the
screw and resin parts. This is effective for reducing gas leaks.
(3) For proper connection, align the union tube and flare tube straight with
each other, then screw on the flare nut lightly at first to obtain a smooth
match.
Adjust the shape of the liquid tube using a tube bender at the installation
site and connect it to the liquid tubing side valve using a flare.
Apply a small amount of ether oil (PVE only) to the inside of the flare nut.
Union Flare nut
42
Cautions During Brazing
Replace air inside the tube with nitrogen gas to prevent copper oxide film
from forming during the brazing process. (Oxygen, carbon dioxide and Freon are
not acceptable.)
Do not allow the tubing to get too hot during brazing. The nitrogen gas inside
the tubing may overheat, causing refrigerant system valves to become damaged.
Therefore allow the tubing to cool when brazing.
Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the formation of oxide film. These
agents adversely affect the refrigerant and refrigerant oil, and may cause
damage or malfunctions.
5-2. Connecting Tubing Between Indoor and Outdoor Units
NOTE
When connecting to the mini VRF 8HP, 10HP (outdoor units type LE1 only), select the main tube by using the following values. For details, refer to the installation instructions of the outdoor
unit.
Indoor unit Type U2
22 28 36 45 56 60 73 90 106 112 140 160
0.180
0.203
0.288
(1) Tightly connect the indoor-side refrigerant tubing extended from the wall with the outdoor-side tubing.
Indoor Unit Tubing Connection
For R410A
Unit : mm
Indoor unit type 22 28 36 45 56 60 73 90 106 112 140 160
Gas tube
ø12.7
ø15.88
Liquid tube
ø6.35
ø9.52
For R32
Indoor unit type Gas tube Liquid tube
Unit : mm
22 28 36 45 56 60 73 90 106 112 140 160
ø12.7
ø15.88
ø6.35
ø9.52
(2) To fasten the flare nuts, apply specified torque.
When removing the flare nuts from the tubing connections, or when tightening
them after connecting the tubing, be sure to use two spanners. When tightening
the flare nuts, use a torque wrench. If the flare nuts are over-tightened, the
flare may be damaged, which could result in refrigerant leakage and cause
injury or asphyxiation to room occupants.
For the flare nuts at tubing connections, be sure to use the flare nuts that
were supplied with the unit, or else flare nuts for R410A, R32 (type 2). The
refrigerant tubing that is used must be of the correct wall thickness as shown
in the following table.
Because the pressure is approximately 1.6 times higher than conventional
refrigerant R22 pressure, the use of ordinary flare nuts (type 1) or thin-
walled tubes may result in tube rupture, injury, or asphyxiation caused by
refrigerant leakage.
In order to prevent damage to the flare caused by over-tightening of the flare
nuts, use the following table as a guide when tightening.
43
Tube diameter
Tightening torque (approximate)
Tube thickness
ø6.35 (1/4″) ø9.52 (3/8″) ø12.7 (1/2″) ø15.88 (5/8″) ø19.05 (6/8″)*
14 18 N · m {140 180 kgf · cm}
34 42 N · m {340 420 kgf · cm}
49 61 N · m {490 610 kgf · cm}
68 82 N · m {680 820 kgf · cm}
100 120 N · m {1,000 1,200 kgf · cm}
0.8 mm 0.8 mm 0.8 mm 1.0 mm 1.0 mm
- When connecting the tube size ø19.05 with the system using refrigerant R32, be sure to connect by brazing.
When tightening the flare nut on the liquid tube, use an adjustable wrench with a nominal handle length of 200 mm.
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
Must ensure that pipe-work shall be protected from physical damage.
Thermal insulation must be applied to all units tubing, including distribution joint (field supply).
Two tubes arranged together
- For gas tubing, the insulation material must be heat resistant to 120°C or above. For other tubing, it must be heat resistant to 80°C or above.
Liquid tube Insulation
Gas tube
Insulation material thickness must be 10 mm or greater.
If the conditions inside the ceiling exceed DB 30°C and RH 70%, increase the thickness of the gas tubing insulation material by 1 step.
CAUTION If the exterior of the outdoor unit valves has been finished with a
square duct covering, make sure you allow sufficient space to access the
valves and to allow the panels to be attached and removed.
Additional Precautions For R32 Models
Ensure to do the re-flaring of pipes before connecting to units to avoid
leaking.
To prevent the ingress of moisture into the joint which could have the
potential to freeze and then cause leakage, the joint must be sealed with
suitable silicone and insulation material. The joint should be sealed on both
liquid and gas side.
Insulation material and silicone sealant. Please ensure there are no gaps
where moisture can enter the joint.
Silicone Sealant must be neutral cure and ammonia free. Use of silicone
containing ammonia can lead to stress corrosion on the joint and cause
leakage.
Taping the flare nuts Wind the insulating tape around the flare nuts at the
gas / liquid tube connections. Then cover up the tubing connections with the
flare insulator (supplied). Wrap with the flare insulator facing its seam
upward.
44
Flare insulator (supplied)
Insulating tape (supplied)
Different-diameter-tube joint
Insulating tape (supplied)
Unit side
Flare union
Flare nut
Tube insulator (not supplied) Heat resistant 120°C or above
- Illustration shows when using by S-60MU2E5BN, S-73MU2E5BN or S-90MU2E5BN. (Only LZ2 series)
Insulation material
The material used for insulation must have good insulation characteristics, be
easy to use, be age resistant, and must not easily absorb moisture.
NOTE
If noise bothers you from the area between indoor and outdoor units’
connection pipes, it is effective to wind the soundproofing materials (field
supply) to reduce noise.
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve
because it can cause the tube to break or crack. Never grasp the drain or
refrigerant connecting outlets when moving the unit.
5-4. Taping the Tubes
(1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
Clamp Insulated tubes Drain hose
(2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn.
(3) Clamp the tubing bundle to the wall, using 1 clamp approx. each meter.
(4) Limited to Oceania only : Interconnecting refrigerant pipework, i.e. pipework external to the unitary components, should be marked with a Class label (see right figure) every two metres where the pipework is visible. Label size is 50 mm × 50 mm. This includes pipework located in a ceiling space or any void which a person may access for maintenance or repair work within that space.
NOTE
Do not wind the armoring tape too tightly since this will decrease the heat
insulation effect. Also ensure that the condensation drain hose splits away
from the bundle and drips clear of the unit and the tubing.
45
5-5. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to
seal off the hole in the wall to prevent rain and draft from entering.
Apply putty here
Tubing
6. HOW TO INSTALL THE TIMER REMOTE CONTROLLER OR HIGH-SPEC WIRED REMOTE
CONTROLLER (OPTIONAL PART)
NOTE
Refer to the Installation Instructions attached to the optional Timer Remote
Controller or optional High-spec Wired Remote Controller.
46
7. HOW TO INSTALL THE PANEL FOR CASSETTE
Accessories
Panel for cassette ×1
Screws ×4
4 × 12
7-1. Preparation for Panel for Cassette Installation
(1) Checking the unit position 1) Check that the ceiling hole is within this
range: 860 mm × 860 mm to 910 mm × 910 mm
2) Confirm that the position of the indoor unit and the ceiling as shown in
the diagram. If the positions of the ceiling surface and unit do not match,
air leakage, water leakage, flap operation failure, or other problems may
occur.
A Ceiling side
Main unit Ceiling opening dimension
A : Be sure to necessarily make a space within the range of 12 mm ~ 17 mm. If not within this range, malfunction or other trouble may occur.
CAUTION
Never place the panel face-down.
Flap
Either hang it vertically or place it on top of a projecting
object. Placing it face-down will damage the surface.
Do not touch the flap or apply force to it. (This may
cause flap malfunction.)
7-2. How to Install the Panel for Cassette
(1) Removing the air intake grille 1) Remove the 2 screws on the latch of the
air intake grille. (Reattach the air intake grille after installation of the
panel for cassette.) 2) Slide the air intake grille catches in the direction
shown by the arrows 1 to open the grille.
Hinges of air intake grille
Panel for cassette
Air intake grille
Screw Latch
47
- With the air intake grille opened, remove the grille hinge from the panel
for cassette by sliding it in the direction shown by the arrow 2. (Reattach
the air intake grille after
installation of the panel for cassette.)
2
(2) Removing the corner cover Push the latches on the corner cover in the direction of the arrow 1 and remove them by sliding in the direction of the arrow 2.
1
1
Panel for cassette
Corner cover 2
Corner cover
Push latches upward to disengage.
Strap
(3) Installing the panel for cassette The power must be turned ON in order to change the flap angle. (Do not attempt to move the flap by hand. Doing so may damage the flap.) 1) Hang the temporary latches on the inside of the panel for cassette to the receptacle on the unit to temporarily attach the panel for cassette in place. The panel for cassette must be installed in the correct direction relative to the unit. Align the REF. PIPE and DRAIN marks on the panel for cassette corner with the correct positions on the unit. When removing the panel for cassette, push the temporary latches outward while holding the panel for cassette.
Push to disengage.
Receptacle on the main unit
Temporary latch
Temporary latches (×2) 48
- Align the panel installation holes and the unit screw holes. 3) Tighten the
provided washer head screws at the 4 panel installation locations so that the
panel is attached tightly to the unit.
Drain tube corner
Refrigerant tube corner
Marking with DRAIN
Panel for cassette
Marking with REF. PIPE
Washer head screws (preinstalled on the panel for cassette)
- Check that the panel is attached tightly to the ceiling.
At this time, make sure that there are no gaps between the unit and the panel for cassette, or
Do not allow gaps. Main unit
between the panel for cassette and the ceiling
surface.
Ceiling surface Panel for cassette
If there is a gap between the panel and the ceiling, leave the panel for cassette attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling.
Make fine adjustment by a wrench or other tools to the installation height of the unit to eliminate the gap with the ceiling through the holes of the corner cover.
CAUTION
If the screws are not sufficiently tightened, trouble such as that shown in
the figure may occur. Be sure to tighten the screws securely.
Air leakage Air leakage from panel for cassette
Staining
Condensation, water leakage
If a gap remains between the ceiling surface and the panel for cassette even after the screws are tightened, adjust the height of the unit again.
Adjust so that there are no gaps.
If there is no affect to the horizontal of the unit and drain tube, adjustment to the installation height of the unit can be made through the hole of the panel for cassette corner.
49
(4) Wiring the Panel for Cassette 1) Open the cover of the electrical
component box for the indoor unit control PCB. 2) Connect the 22P connector
(white) from the panel for cassette to the connector on the indoor unit
control PCB in the unit electrical component box. In this case, expose the
cutout section of the tube for the wiring protection to the outside from the
electrical component box and fix it with the clamper attached to the
electrical component box.
Insert connector lock facing PCB edge until it is locked in place. (If not
connected completely, the Auto Flap will not operate and “P09” is displayed on
the remote controller. When the connector plugged in the wrong direction,
parts on the PCB may be damaged.)
Check that the wiring connector is not caught between the electrical component
box and the cover.
Check that the wiring connector is not caught between the unit and the panel
for cassette.
Lid of electrical component box
Cutout section of the tube for wiring protection
Wiring diagram (Direction that the unit faces has been changed to facilitate explanation.)
Screws (×2)
22P (white)
Connector
Panel for cassette wiring connector
Lock
(5) How to Attach the Corner & Air Intake Grille
A. Attaching the corner cover 1) Check that the safety strap from the corner
cover is fastened to the panel for cassette pin, as
shown in the figure. 2) Use the supplied screws to attach the corner cover to
the panel for cassette.
Supplied screw
Pin Place the corner cover so that the 5 tabs fit into the holes in the panel
for cassette. Then fasten it in place with the supplied screws.
50
B. Attaching the air intake grille To install the air intake grille, follow
the steps for “Removing the air intake grille” in the
reverse order. By rotating the air intake grille, it is possible to attach the
grille onto the panel for cassette from any of 4 directions. Coordinate the
directions of the air intake grilles when installing multiple units, and
change the directions according to customer’s requests. When attaching the air
intake grille, be careful that the flap lead wire does not become caught. Be
sure to attach the safety strap that prevents the air intake grille from
dropping off to the panel for cassette unit as shown in the figure.
Hole of panel for cassette hook
Hook that prevents the grille from dropping
With this panel for cassette, the directions of the air intake grille lattices when installing multiple units, and the position of the label showing the company name on the corner panel, can be changed according to customer’s requests, as shown in the figure. However, the wireless signal receiver can only be installed at the refrigerant-tubing corner of the ceiling unit.
Refrigerant tube side
Drain pipe side
Locations of air intake grille hinges at shipment
- The grille can be installed with these hinges facing in any of 4 directions.
Optional wireless receiver kit * This position is only possible
for installation.
Electrical component box
Corner cover installation position marked with the Panasonic Logo at shipment.
- Installation possible at any
of 4 corners
Can be installed rotated 90°
7-3. Others
(1) Checking After Installation 1) Check that there are no gaps between the
unit and the panel for cassette, or between the panel for cassette and the
ceiling surface. Gaps may cause water leakage and condensation. 2) Check
that the wiring is securely connected. If it is not securely connected, the
auto flap will not operate. (“P09” is displayed on the remote controller.) In
addition, the water leakage and condensation may occur.
(2) Operating the Wireless Remote Controller For details of installation,
refer to the Installation Instructions attached to the optional Wireless
Remote Controller.
51
(3) Selecting DC Fan Motor Tap (4-Way Cassette) Check the optional parts accordingly in the following table.
Table for DC Fan Motor Tap Settings
Setting No.
Remote controller setting data Item code 5d
Contents & optional parts name
Air-flow blocking kit (for 3-way airflow)23
(1)
0001
Air-flow blocking kit (when a duct is connected.)*2
High-ceiling setting 1*3
(3)
0003
High-ceiling setting 2*3
(6)
0006
Air-flow blocking kit (for 2-way airflow)23
1 When using optional parts in different setting No. in combination with multiple units, conform it to the larger setting No. 2 When using the optional air-flow blocking kit for 3-way airflow and 2-way airflow, maximum refrigerant amount and
minimum installation space will be changed. See Section “Check of Density
Limit”.
*3 Ceiling height (m)
Indoor unit type
22, 28, 36, 45, 56
60, 73, 90
106, 112, 140, 160
Standard (factory setting)
2.7
3.0
3.6
High-ceiling setting 1
3.2
3.3
4.3
High-ceiling setting 2
3.5
3.6
5.0
Air-flow blocking kit (for 3-way airflow)
3.8
3.8
4.7
Air-flow blocking kit (for 2-way airflow)
4.2
4.2
5.0
- When setting on the indoor unit control PCB
Be sure to turn the power OFF before performing this work. 1 Open the electrical component box cover, then check the indoor unit control PCB. 2 Change the DIP switch (SW001) on the indoor unit control PCB in accordance with the setting number which was confirmed in “Table for DC Fan Motor Tap Settings”.
TP6 TP3 TP1 TP6 TP3 TP1 TP6 TP3 TP1
TP6 TP3 TP1
SW001
TP6 TP3 TP1
Setting No.
(1)
DIP switch
ON 1 23
(3)
ON 1 23
(6)
ON 1 23
Setting example : Knob
ON
1: OFF
ON
2: OFF
123
1 2 3 3: ON
Indoor unit control PCB
52
Stop the system before performing these steps.
1 Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD display.
Maintenance func 20:30 (THU)
1. Outdoor unit error data 2. Service contact 3. RC setting mode 4. Test run
Sel.
Page [ ] Confirm
2 Press the
or
button to see each menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “8. Detailed settings” on the LCD display
and press the
button.
The “Detailed settings” screen appears on the LCD display.
3 Select the “Unit no.” by pressing the
or
button for changes.
4 Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “5D” by pressing the
or
button (or keeping it pressed).
5 Select the “Set data” by pressing the
or
button.
Select one of the “Set data” in “Table for DC Fan
Motor Tap Settings” by pressing the
or
button.
Then press the
button.
6 Press the
button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
If you wish to change the selected indoor unit, follow Step 2.
20:30 (THU) [ ] START
Maintenance func 20:30 (THU)
5. Sensor info. 6. Servicing check 7. Simple settings 8. Detailed settings
Sel.
Page [ ] Confirm
Detailed settings
20:30 (THU)
Unit no. Code no. Set data
1-1
10
0001
Sel. Next
Detailed settings
20:30 (THU)
Unit no. Code no. Set data
1-1
5D
0001
Sel. Next
Detailed settings
20:30 (THU)
Unit no. Code no. Set data
1-1
5D
0003
Sel. [ ] Confirm
Detailed settings
20:30 (THU)
Unit noE.xit adneCdtaoriledesedtasnreot?t.tings Set data
ALL
01
0002
YES
NO
Sel. Next
53
Stop the system before performing these steps.
4
°
1 Press and hold the , and buttons
3
°
2
simultaneously for 4 seconds or longer.
2 If group control is in effect, press the
4
button to set.
2
At this time, the fan at the indoor unit begins
A
5
and select the address (unit No.) of the indoor
unit operating.
3 Designate the item code by adjusting the
6
1
Temperature Setting / buttons.
4 Press the timer time / buttons to select the desired setting data. *For item
codes and setting data, see “Table for DC Fan Motor Tap Settings”.
5 Press the button. (The display stops blinking and remains lit, and setting
is completed.) If you wish to change the selected indoor unit, follow Step 2.
6 Press the button to return to normal remote controller display.
54
1 Keep pressing the , and buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the LCD display.
Maintenance func XX / XX
ECONAVI
nanoeX
RC. setting mode
[] []
2 Press the or button to see each menu. Select “Detailed settings” on the LCD display and press the button.
The “Detailed settings” screen appears on the LCD display.
Black
Maintenance func XX / XX
Simple settings
Detailed settings
Auto address
[] []
3 Select the “Unit no.” by pressing the or button. After selecting “Unit no.”,
press the button and proceed to Step 4.
If the button is pressed, proceed to Step 6.
Detailed settings
Unit no.
1-1
Code no. Set data []
000010 0001 []
4 Select the “Code no.” by pressing the or button. Change the value by
pressing the or button to [00005D]. After selecting “Code no.” , press the
button and proceed to Step 5.
5 Select one of the “Set data” in “Table for DC Fan Motor Tap Settings” by
pressing the or button. After selecting “Set data”, press the button. (If
setting continuously, follow the procedures from Step 3.)
Detailed settings
Unit no. Code no. Set data []
1-1 00005D
0001 []
Detailed settings
Unit no.
1-1
Code no. 00005D
Set data 0001 [ ] [ ]Confrm
6 If the button is pressed under the display Step 3, the following display (Detailed setting-end screen) appears. Then select “YES” by pressing the or button and press the button.
Detailed settings Exit detailed
Unit nos.ettings 1-1
Codaenndo.restart?10
YES
Set data 0001
NO
[] []
NOTE
The wired remote controller illustrated below can also be available following the same
procedures as above.
White 55
(4) Setting the Flap Separately 1) The 4-air outlet flap can be adjusted separately during operation. When not adjusted separately, all flaps operate in the same manner.
Air outlet flap (adjustment for up-down airflow direction)
Stop the system before performing these steps.
4
1 Press and hold the , and buttons
3
XX° ° YYYY
2
simultaneously for 4 seconds or longer.
2 If group control is in effect, press the button
4
to set. At this time, the fan at the indoor unit
2
begins and select the address (unit No.) of the
A
5
indoor unit operating.
3 Designate the item code “XX” by adjusting the
6
1
Temperature Setting / buttons.
XX=90
Electrical component box
XX=91
XX=93
XX=92
4 Press the timer time / buttons to select the desired setting data.
- Setting data “YYYY”
Setting data Flap position during operation Without separate setting Swing Move to position 1 and stay Move to position 2 and stay Move to position 3 and stay Move to position 4 and stay Move to position 5 and stay
Flap position
1 2 3 54
NOTE
The flap swings during the operation under “Setting the Flap Separately”. At
this time, the unselected flaps are moved to the position 1 . 5 Press the
button. (The display stops blinking and remains lit, and setting is
completed.) If you wish to change the selected indoor unit, follow Step 2.
6 Press the button to return to normal remote controller display.
56
1 Keep pressing the , and buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the LCD display.
Maintenance func XX / XX
ECONAVI nanoeX RC. setting mode
[] []
2 Press the or button to see each menu. Select “Detailed settings” on the LCD
display and press the button.
The “Detailed settings” screen appears on the LCD display.
3 Select the “Unit no.” by pressing the or button.
After selecting “Unit no.”, press the button and proceed to Step 4. If the
button is pressed, proceed to Step 6.
4 Select the “Code no.” by pressing the or button. Change the value by
pressing the or button to [0000XX].
After selecting “Code no.” , press the button and proceed to Step 5.
XX=90
Electrical component box
XX=91
XX=93
XX=92
Black
Maintenance func XX / XX
Simple settings
Detailed settings
Auto address
[] []
Detailed settings
Unit no.
1-1
Code no. Set data []
000010 0001 []
Detailed settings
Unit no.
1-1
Code no. 0000XX
Set data 0001
[] []
57
5 Select one of the Setting Data “YYYY” by pressing the or button.
- Setting data “YYYY”
Setting data Flap position during operation 0000 Without separate setting 0001 Swing 0002 Move to position 1 and stay 0003 Move to position 2 and stay 0004 Move to position 3 and stay 0005 Move to position 4 and stay 0006 Move to position 5 and stay
Flap position
1
2 3 54
Detailed settings
Unit no.
1-1
Code no. 0000XX
Set data Y0Y00Y1Y [ ] [ ]Confrm
NOTE
The flap swings during the operation under “Setting the Flap Separately”. At
this time, the unselected flaps are moved to the position 1 .
After selecting “Set data”, press the button. (If setting continuously, follow
the procedures from Step 3.)
6 If the button is pressed under the display Step 3, the following display (Detailed setting-end screen) appears. Then select “YES” by pressing the or button and press the button.
Detailed settings Exit detailed
Unit nos.ettings 1-1
Codaenndo.restart?10
YES
Set data 0001
NO
[] []
NOTE
The wired remote controller illustrated below can also be available following the same
procedures as above.
White
8. HOW TO INSTALL WIRELESS REMOTE CONTROLLER
NOTE
Refer to the Installation Instructions attached to the optional Wireless
Remote Controller.
58
9. PRECAUTIONS ON TEST RUN
Request that the customer be present when the test run is performed. At this
time, explain the operation manual and have the customer perform the actual
steps.
Check that the 220 240 VAC power is not connected to the inter-unit control
wiring connector terminal. * If 220 240 VAC is accidentally applied, the
indoor unit control PCB fuse will blow in order to protect the PCB. Correct
the wiring connections. Then disconnect the 2P connectors (OC) that are
connected to the indoor unit control PCB, and replace them with 2P connectors
(EMG). If operation is still not possible after changing the brown connectors,
cut off the jumper on the indoor unit control PCB. (Be sure to turn the power
OFF before performing this work.)
Jumper (JP040)
OC (CN040, blue)
EMG (CN044, brown)
59
10. CHECKLIST AFTER INSTALLATION WORK
Work List No.
Content
Check
Possibility of Failure & Checkpoint
Installation
Are the indoor units installed following the 1 content of Section “2.
SELECTING THE
INSTALLATION SITE”?
There is a possibility of light injure or loss of property.
Is the earth leakage circuit breaker 2 (all-pole switching function provided)
installed?
3
Is there any wrong installation of optional parts or wrong wiring?
Tubing &
Wiring
4 Was the ground wire work performed?
Are there any wrong power supply wiring, 5 wrong connection wire, wrong signal
wire
or loose screw?
Power failure or short circuit may cause electric
shock or fire. Check installation work and ground
wire work.
6
Is the thickness of wire in accordance with rule?
7
Is the power-supply voltage equal to the nameplate of the unit?
Was the check of the airtight test, flared 8 tube fitting and gas leakage on
the
welded portion performed?
If the gas leakage occurs, the unit quality not only becomes inferior but affects environment. Repair it
as quickly as possible.
Drain Check
Has the adhesive been applied to the 9 drain connecting portion (resin
portion) of
the indoor unit?
10 Is there water leakage?
Indoor unit drain pipe has a downward 11 gradient (1/100 or more) by rule. Is
the
drain water flowing smoothly?
The resin portion cracks after a few months and it may cause water drain.
Since there is a possibility of water drain, repair the
drain pipe if the drain failure or water drain occurs.
Heat Insulation
Was the heat insulation work at a suitable
12
location including the flared tube fitting (refrigerant tube & drain pipe) performed
properly?
The quality of unit not only becomes inferior but there is a possibility of the water drain. So, perform the heat insulation work properly.
Optional Parts
Was the short-circuit connector connected 13 or the fan tap changed when
installing the
air-blocking material?
The discharge temperature decreases in cooling mode according to the reduction of air volume and there is a possibility of dew drops. Be sure to change settings.
Test Run
14 Did the abnormal sound occur?
15
Did the cool and warm airflow discharge from the indoor unit?
Check if there is a fan contact or distortion of the indoor unit.
Check if the unit does not operate or there is a wrong tubing or wiring connection with another
system.
60
11. APPENDIX
Care and Cleaning
WARNING
For safety, be sure to turn the air conditioner off and also to disconnect the
power before cleaning.
Do not pour water on the indoor unit to clean it. This will damage the
internal components and cause an electric shock hazard.
Air intake and outlet side (Indoor unit) Clean the air intake and outlet side
of the indoor unit with a vacuum cleaner brush, or wipe them with a clean,
soft cloth. If these parts are stained, use a clean cloth moistened with
water. When cleaning the air outlet side, be careful not to force the vanes
out of place.
CAUTION
Never use solvents or harsh chemicals when cleaning the indoor unit. Do not
wipe plastic parts using very hot water.
Some metal edges and the fins are sharp and may cause injury if handled
improperly; be especially careful when you clean these parts.
The internal coil and other components of outdoor unit must be cleaned
regularly. Consult your dealer or service center.
Air filter
The air filter collects dust and other particles from the air and should be
cleaned at regular intervals or when the filter indication ( ) on the display
of the remote controller (wired type) shows that the filter needs cleaning. If
the filter gets blocked, the efficiency of the air conditioner drops greatly.
Type
U2
Period 6 months
After Cleaning
1. After the air filter is cleaned, reinstall it in its original position.
Be sure to reinstall in reverse order.
2. [In the case of Timer Remote Controller]
Timer Remote Controller
Press the Filter reset button. The (Filter) indicator on the display goes out.
°
Filter indicator
A
Filter reset button
[In the case of High-spec Wired Remote Controller and Wired Remote Controller] Refer to the Operating Instructions attached to the optional High-spec Wired Remote Controller or optional Wired Remote Controller.
High-spec Wired Remote Controller
Filter indicator
Wired Remote Controller
Filter indicator
Filter indicator
Black
White
61
NOTE
The frequency with which the filter should be cleaned depends on the
environment in which the unit is used. Clean the filter frequently for best
performance in the area of dusty or oil spots regardless of filter status.
CAUTION
When cleaning the air filter, never remove the safety strap. If it is
necessary to remove it for servicing and maintenance inside, be sure to
reinstall the safety strap securely (hook on the grille side) after the work.
When the filter has been removed, rotating parts (such as the fan),
electrically charged areas, etc. will be exposed in the unit’s opening. Bear
in mind the dangers that these parts and areas pose, and proceed with the work
carefully.
4. Push the side of the air filter marked with the indication arrow and pull
it toward you. The air filter will be disengaged.
Air intake grille
Safety strap
Marking with , for air intake grille
Latch Screw
Latches (×2)
Marking with Marking with
Air filter
CAUTION
Certain metal edges and the condenser fins are sharp and may cause injury if
handled improperly; special care should be taken when you clean these parts.
Periodically check the outdoor unit to see if the air outlet or air intake is
clogged with dirt or soot.
The internal coil and other components must also be cleaned periodically.
Consult your dealer or service center.
62
Care: After a prolonged idle period
Check the indoor and outdoor unit air intakes and outlets for blockage; if
there is a blockage, remove it.
Care: Before a prolonged idle period
Operate the fan for half a day to dry out the inside. Disconnect the power
supply and also turn off the circuit breaker. Clean the air filter and replace
it in its original position. Outdoor unit internal components must be checked
and cleaned periodically. Contact your
local dealer for this service.
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center.
Indoor unit
Symptom
Cause
Noise
Sound like streaming water during operation or after operation
Sound of refrigerant liquid flowing inside unit Sound of drainage water through drain pipe
Cracking noise during operation or Cracking sound due to temperature changes of parts when operation stops.
Odor
Discharged air is smelled during operation.
Indoor odor components, cigarette odor and cosmetic odor accumulated in the air conditioner and its air is discharged. Unit inside is dusty. Consult your dealer.
Dewdrop
Dewdrop gets accumulated near air Indoor moisture is cooled by cool wind and accumulated by dewdrop. discharge during operation
Fog
Fog occurs during operation in
Cleaning is necessary because unit inside (heat exchanger) is dirty.
cooling mode.
Consult your dealer as technical engineering is required.
(Places where large amounts of oil During defrost operation
mist exist at restaurants.)
Fan is rotating for a while even though operation stops.
Fan rotating makes operation smoothly. Fan may sometimes rotate because of
drying heat exchanger due to
settings. Fan may sometimes rotate in internal cleaning operation mode for a
while.
The indoor unit fan is running and does not stop The refrigerant may be leaking. If R32 refrigerant leakage detection
when ON/OFF operation button on remote controller sensor is connected and the refrigerant leaks, P08 alarm and
is pressed.
inspection mark will be displayed on the remote controller and the fan
will automatically operate. Please ventilate the room without turning
off the earth leakage circuit breaker and contact the service dealer for
assistance.
Are you using gas equipment (propane, butane, methane, etc.) and
sprays near R32 refrigerant leakage detection sensor? R32 refrigerant
leakage detection sensor could lead to false detection and the fan
may start rotating. Please contact the service dealer for assistance.
Wind-direction changes while operating. Wind-direction setting cannot be made. Wind-direction cannot be changed.
When air discharge temperature is low or during defrost operation, horizontal
wind flow is made automatically.
Flap position is occasionally set up individually.
When wind-direction is changed, flap operates several times and stops at designated position.
When wind-direction is changed, flap operates after searching for standard position.
Dust
Dust accumulation inside indoor unit is discharged.
Humming noise comes out.
This is the sound of nanoeTM X being discharged.
is not displayed on the remote controller. Has nanoeTM X been set to OFF? Set to ON.
is displayed on the remote controller. nanoeTM X is considered abnormal. (Contact your dealer.)
63
Symptom Poor cooling or heating performance
Cause
The indoor unit is initially designed to control the indoor temperature
detected by the built-in room sensor inside the indoor unit. Due to indoor
unit installation position, however, the built-in sensor may occasionally
sense temperature improperly; for example, temperature difference between the
ceiling and floor, lighting apparatus, electric fan, windows or waist-high
partition walls, etc. In this case, the unit does not operate properly at the
desired temperature. You may change the use of the temperature sensor inside
the indoor unit to that of the remote controller. Then the desired room
temperature can be controlled properly. For details, consult your dealer.
Check Before Requiring Services
Symptom
Cause
Remedy
Air conditioner does not run at Power failure or after power failure
all although power is turned
on.
Operation button is turned off.
Fuse blow out.
Press ON/OFF operation button on remote controller again.
Switch on power if breaker is turned off. If breaker has been tripped, consult
your dealer
without turning it on.
If blown out, consult your dealer.
Poor cooling or heating performance
Air intake or air discharge port of indoor Remove dust or obstruction. and outdoor units is clogged with dust or obstacles.
Fan speed switch is set to “Low”.*
Change to “Medium” or “High”.*
Improper temperature settings
See Section ” Tips for Energy Saving”.
Room is exposed to direct sunlight in cooling mode.
Doors and /or windows are open.
Air filter is clogged.
See Section ” Care and Cleaning”.
Too much heat sources in room in cooling mode.
Use minimum heat sources and in a short time.
Too many people in room in cooling mode.
Reduce temperature settings or change to “Medium” or “High”.*
- Fan speed display on the remote controller
High :
(CZ-RTC4),
(CZ-RTC5B, CZ-RTC6 series)
Medium :
(CZ-RTC4),
(CZ-RTC5B, CZ-RTC6 series)
Low :
(CZ-RTC4),
(CZ-RTC5B, CZ-RTC6 series)
If the P08 alarm and inspection mark are displayed on the remote controller
and the fan automatically operates and does not stop even when you press
ON/OFF operation button on remote controller, R32 refrigerant leakage
detection sensor connected to the indoor unit has detected refrigerant
leakage. In such a case, do not turn off the earth leakage circuit breaker,
ventilate the room, and contact the service dealer immediately.
If your air conditioner still does not work properly although you checked the
points as described above, first stop the operation and turn off the power
switch. Then contact your dealer and report the serial number and symptom.
Never repair your air conditioner by yourself since it is very dangerous for
you to do so. You also report if the inspection mark and the letters E, F, H,
J, L, P in combination with the numbers appear on the LCD of the remote
controller.
64
Tips for Energy Saving
Avoid Do not block the air intake and outlet of the unit. If either is
obstructed, the unit will
not work well, and may be damaged. Do not let direct sunlight into the room.
Use sunshades, blinds or curtains. If the walls and
ceiling of the room are warmed by the sun, it will take longer to cool the
room. Do Always try to keep the air filter clean. (See Section ” Care and
Cleaning”.) A clogged filter
will impair the performance of the unit. To prevent conditioned air from
escaping, keep windows, doors and any other openings
closed.
NOTE
Should the power fail while the unit is running If the power supply for this
unit is temporarily cut off, the unit will automatically resume operation once
power is restored using the same settings before the power was interrupted.
Important Information Regarding The Refrigerant Used
NOTE
Refer to the Installation Instructions attached to the outdoor unit.
65
WEB-ACXF60-50850-00-EN DC0223-0
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>