PICO-N-M-1C Miniature Presence Sensor
User Manual
Safety instructions
Work on the mains supply may only be carried out by qualified professionals or
by instructed persons under the direction and supervision of qualified skilled
electrical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not to be used to isolate other equipment from the mains
supply.
The total number of switchable loads is limited due to high inrush currents of
electronic ballasts and LED drivers. In case of a large number of connected
loads please use an external contactor.
For all connected loads, proper interference suppression is obligatory (we
recommend to use our arc extinction kits).
Read this supplementary sheet and the operating instructions before putting
the device into operation. Knowledge of these documents is part of the
intended use!
Operation
The device is a remote controlcapable mini occupancy detector for ceiling
mounting (interior applications) having a circular detection area.
The occupancy detector controls the light automatically according to people
present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light and compares
it with the switch-on threshold set in the detector. If the ambient light is
sufficient, lighting will not be switched on. If the ambient light level is
below the brightness level, a movement activates the lighting in the room.
The detector switches the light off if there is enough natural light for 15
min. or if no movement was detected within the follow-up time.
Further functions can be accessed with our remote control (see accessories).
Mounting
Mounting hints
The connecting cable must not be shortened.
Fig. 3, d
For mounting in luminaires, use the enclosed clamping ring and remove the
spring clips.
Exclude sources of interference
Fig. 3, a
In case the detection area of the detector is too large or areas are being
covered that should not be monitored, the range can be reduced or limited by
using the enclosed blinds (a).
Self-test cycle
The product enters an initial 60-second self-test cycle when the supply is
first connected (LEDs flash). During this time the device does not respond to
movement.
LED function indicators after each mains recovery
Factory settings active: – white, red, green flash in quick succession for 10
sec.
Standard mode
- Detector programmed – red flashes quickly (2x/sec.)
- Detector not programmed – red flashes (1x/sec.)
LED function indicators
Motion detection – red flashes
Light value higher than switchon threshold: – green LED flashes
Light measurement active: – Green flashes once every 10 s
Technical data
110-240 V ~, 50/60 Hz | Voltage |
---|---|
Ø 33 x 60 mm | Dimensions |
ca./approx. 0.35 W | Power input |
1.5 mm | Wire cross-section |
360° | Area of coverage |
2 m / 5 m / 2.5 m | Mounting height min./max./ recommended |
▶ Fig. 4
2.5 m
18°C
1 = max. Ø 10 m
2 = max. Ø 6 m
3 = max. Ø 4 m| Range of coverage at mounting height
Ambient temperature
1 accross
2 towards
3 seated
II / IP65| Class / Degree of protection
-25°C – +50°C| Ambient temperature
140 cm| Cable length
C1
μ – NO
2300 W cosφ = 1
1150 VA cosφ=0.5| Relay contact
tungsten pre-make contact
Switching capacity
lp (20ms) = 165 A| max. inrush peak current (relay)
78 m²| Monitored surface, when the detector is mounted at 2.5 m mounting
height and for tangential approach
10 min
500 Lux| Factory settings
Follow-up time
Switch-on threshold
Wiring diagram
Schematic diagram – when connecting the detector, please respect the labelling of the terminal connections at the device!
L | Brown |
---|---|
L‘ | Black |
N | Blue |
R | Grey |
Accessory
93067 | BLE-IR-Adapter |
---|---|
92520 | IR-PD-1C |
92077 | IR-PD-1C-E |
92159 | IR-PD-Mini |
10880 | Arc extinction kit |
10882 | Mini-RC-Arc extinction kit |
EU Declaration of conformity
This product respects the directives concerning
- electromagnetic compatibility (2014/30/EU)
- low voltage (2014/35/EU)
- restriction of the use of certain hazardous substances in electrical and electronic equipment (2011/65/EU) and (2015/863/EU)
https://www.beg-luxomat.com/qr.php?prtno=93159
Product pages on the Internet
Subject to technical changes ■ 93159M4_Short_MAN_PICO-N-M-1C-
DE_93159_sv_fi_no_en_V2 – 070323