LUXOMAT PICO-N-M-1C Miniature Presence Sensor User Manual

June 13, 2024
LUXOMAT

LUXOMAT logo PICO-N-M-1C Miniature Presence Sensor
User Manual

Safety instructions

Work on the mains supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
Disconnect supply before installing!
This device is not to be used to isolate other equipment from the mains supply.
The total number of switchable loads is limited due to high inrush currents of electronic ballasts and LED drivers. In case of a large number of connected loads please use an external contactor.
For all connected loads, proper interference suppression is obligatory (we recommend to use our arc extinction kits).
Read this supplementary sheet and the operating instructions before putting the device into operation. Knowledge of these documents is part of the intended use!

Operation

The device is a remote controlcapable mini occupancy detector for ceiling mounting (interior applications) having a circular detection area.
The occupancy detector controls the light automatically according to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light and compares it with the switch-on threshold set in the detector. If the ambient light is sufficient, lighting will not be switched on. If the ambient light level is below the brightness level, a movement activates the lighting in the room.
The detector switches the light off if there is enough natural light for 15 min. or if no movement was detected within the follow-up time.
Further functions can be accessed with our remote control (see accessories).

Mounting

LUXOMAT PICO N M 1C Miniature Presence Sensor -
Mounting

Mounting hints

The connecting cable must not be shortened.
Fig. 3, d
For mounting in luminaires, use the enclosed clamping ring and remove the spring clips.

Exclude sources of interference

Fig. 3, a
In case the detection area of the detector is too large or areas are being covered that should not be monitored, the range can be reduced or limited by using the enclosed blinds (a).

Self-test cycle
The product enters an initial 60-second self-test cycle when the supply is first connected (LEDs flash). During this time the device does not respond to movement.

LED function indicators after each mains recovery

Factory settings active: – white, red, green flash in quick succession for 10 sec.
Standard mode

  • Detector programmed – red flashes quickly (2x/sec.)
  • Detector not programmed – red flashes (1x/sec.)

LED function indicators
Motion detection – red flashes
Light value higher than switchon threshold: – green LED flashes
Light measurement active: – Green flashes once every 10 s

Technical data

110-240 V ~, 50/60 Hz Voltage
Ø 33 x 60 mm Dimensions
ca./approx. 0.35 W Power input
1.5 mm Wire cross-section
360° Area of coverage
2 m / 5 m / 2.5 m Mounting height min./max./ recommended

▶ Fig. 4
2.5 m
18°C
1  = max. Ø   10 m
2  = max. Ø   6 m
3  = max. Ø   4 m| Range of coverage at mounting height
Ambient temperature
1 accross
2 towards
3 seated
II / IP65| Class / Degree of protection
-25°C – +50°C| Ambient temperature
140 cm| Cable length
C1
μ – NO
2300 W cosφ = 1
1150 VA cosφ=0.5| Relay contact
tungsten pre-make contact
Switching capacity
lp (20ms) = 165 A| max. inrush peak current (relay)
78 m²| Monitored surface, when the detector is mounted at 2.5 m mounting height and for tangential approach
10 min
500 Lux| Factory settings
Follow-up time
Switch-on threshold

Wiring diagram

Schematic diagram – when connecting the detector, please respect the labelling of the terminal connections at the device!LUXOMAT PICO N M 1C Miniature
Presence Sensor - Wiring diagram

L Brown
L‘ Black
N Blue
R Grey

Accessory

93067 BLE-IR-Adapter
92520 IR-PD-1C
92077 IR-PD-1C-E
92159 IR-PD-Mini
10880 Arc extinction kit
10882 Mini-RC-Arc extinction kit

EU Declaration of conformity

This product respects the directives concerning

  1. electromagnetic compatibility (2014/30/EU)
  2. low voltage (2014/35/EU)
  3. restriction of the use of certain hazardous substances in electrical and electronic equipment (2011/65/EU) and (2015/863/EU)

https://www.beg-luxomat.com/qr.php?prtno=93159
Product pages on the Internet
Subject to technical changes ■ 93159M4_Short_MAN_PICO-N-M-1C- DE_93159_sv_fi_no_en_V2 – 070323
Brück Electronic GmbH
Gerberstr. 33
51789 Lindlar
GERMANY
Phone: +49 (0) 2266 90121-0
support@beg.de