LUXOMAT DALI-2 Ultra Flat Multi Sensor False Ceiling Instruction Manual
- June 13, 2024
- LUXOMAT
Table of Contents
- LUXOMAT DALI-2 Ultra Flat Multi Sensor False Ceiling
- Product Information
- Product Usage Instructions
- Safety instructions
- Function
- Mounting
- LED function indicators
- Technical data
- Schematic diagram
- UK Declaration of Conformity
- Accessory
- Troubleshooting
- Contact Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
LUXOMAT DALI-2 Ultra Flat Multi Sensor False Ceiling
Product Information
- Product Code: 93542
- Safety Instructions: Work on the main supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
- Function: Particularly flat DALI-2 multisensor (Input Device) with a visible height of only 0.85 mm. Power supply via DALI bus.
- Addressable: Addressable according to IEC 62386 Part 103 (control device). Instance 0 provides information regarding occupancy and movement for the DALI bus according to IEC 62386 part 303. Instance 1 provides LUX values for the DALI bus according to IEC 62386 part 304. Parameterization is possible via the mandatory Multimaster-Application-Controller of any manufacturer. This controller must support IEC 62386 parts 101/103/303/304.
Product Usage Instructions
- Mounting: The device is inserted into a false ceiling. Follow the mounting instructions shown in Fig. 1, Fig. 2, Fig. 3, and Fig. 4.
- Mounting Hints: Connect the DALI wires using a small slotted screwdriver.
- Initial Operation: The device can be put into service directly after mounting, following the software instructions from the relevant controller manufacturer.
Safety instructions
- Work on the main supply may only be carried out by qualified professionals or by instructed persons under the direction and supervision of qualified skilled electrical personnel in accordance with electrotechnical regulations.
- Disconnect the supply before installing! This device is not to be used to isolate other equipment from the main supply.
- DALI is not SELV – the installation instructions for low voltage apply. The DALI screw clamps must not be connected to 230 VAC!
- Read this supplementary sheet and the operating instructions before putting the device into operation. Knowledge of these documents is part of the intended use!
Function
- Particularly flat DALI-2 multi-sensor (Input Device) with a visible height of only 0.85 mm. Power supply via DALI bus.
- Addressable according to IEC 62386 Part 103 (control device). Instance 0 provides information regarding occupancy and movement for the DALI bus according to IEC 62386 part 303. Instance 1 provides LUX values for the DALI bus according to IEC 62386 part 304. Parameterization is possible via the mandatory Multimaster-Ap-plication-Controller of any manufacturer. This controller must support IEC 62386 parts 101/103/303/304.
Mounting
Mounting hints
- DALI wires are connected with a small slotted screwdriver Fig. 1
- The device is inserted into the false ceiling. Fig. 2
Initial operation
General: The device can be put into service directly after mounting, following the software instructions from the relevant controller manufacturer.
Exclude sources of interference
In case the detection area of the detector is too large or areas are being
covered that should not be monitored, the range can be reduced or limited by
using the enclosed blinds.
Self-test cycle
During the first 20 sec after connecting to the DALI bus power, the product
will enter a self-test cycle. During this time the device does not respond to
movement.
LED function indicators
-
Shortly on:
A. Green Movement -
Flashing:
-
A. Green Localisation
-
B. Red Initialisation
-
C. White Localisation
-
D. Red Localisation
Technical data
- Settings: via an application that supports DALI multisensors (IEC 62386 parts 101/103/303/304).
- DALI-BUS max. 22.5 V Voltage
- 7 mA Typ. power input
- 0.5 W Power consumption
- 0.5 – 2.5mm2 Terminal clamps: for solid one-wire conductors
- 360° Area of coverage
- 2 m / 5 m / 2.5 m Mounting height min./max./recommended
- 2.5 m Range of coverage at mounting height
- 18°C Ambient temperature
1. = Ø 9m accross
2. = Ø 6m towards
3. = Ø 3m seated activities **Fig. 4**
- 64m2 Monitored surface, when the detector is mounted at 2.5 m mounting height and for tangential approach
- II / IP20 Class/Degree of protection
- Ø 52 x 48mm Dimensions
- -25°C – +50°C Ambient temperature
- 0 – 4095 Lux Measured light output
Schematic diagram
Schematic diagram
When connecting the detector, please respect the labeling of the terminal
connections at the device!
UK Declaration of Conformity
This product respects the directives concerning
- Electrical Equipment Safety Regulation 2016
- Electromagnetic Compatibility Regulation 2016
- The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulation 2012
Contact
B.E.G. UK Ltd., Apex Court–Grove House • Camphill Road • West Byfleet, Surrey
KT14 6SQ.
Accessory
- Cover ring PD11 Ø 100 mm, white
- Cover ring PD11 Ø 52 mm, white
- In-wall mounting set / PD11, white
- Square design frame PD11-FC, white matt, similar to RAL 9010
Troubleshooting
-
Power consumption on the DALI line is too high
Please be aware of the total power consumption of all the DALI units in your system. -
Heat sources in the vicinity
If, for example, the detector is located in the immediate vicinity of ventilation slits or a projector, the warm air currents can trigger motion detection. Place the detector at a sufficient distance from potential sources of interference such as ventilation slits, projectors, beamers, etc.