welldana i-ExpertLine W PMH Vertikal Inverter Heat Pump User Manual

June 13, 2024
welldana

welldana i-ExpertLine W PMH Vertikal Inverter Heat Pump

PREFACE

  • In order to provide our customers with quality, reliability and versatility, this product has been made to strict production standards. This manual includes all the necessary information about installation, debugging, discharging and maintenance. Please read this manual carefully before you open or maintain the unit. The manufacture of this product will not be held responsible if someone is injured or the unit is damaged, as a result of improper installation, debugging, or unnecessary maintenance. It is vital that the instructions within this manual are adhered to at all times. The unit must be installed by qualified personnel.
  • The unit can only be repaired by qualified installer centre , personnel or an authorised dealer.
  • Maintenance and operation must be carried out according to the recomended time and frequency, as stated in this manual.
  • Use genuine standard spare parts only.
  • Failure to comply with these recommendations will invalidate the warranty.
  • Swimming Pool Heat Pump Unit heats the swimming pool water and keeps the temperature constant. For split type unit, The indoor unit can be Discretely hidden or semi-hidden to suit a luxury house.
    Our heat pump has following characteristics:
  1. Durable
    The heat exchanger is made of PVC & Titanium tube which can withstand prolonged exposure to swimming pool water.

  2. Installation flexibility
    The unit can be installed outdoors.

  3. Quiet operation
    The unit comprises an efficient rotary/ scroll compressor and a low-noise fan motor, which guarantees its quiet operation.

  4. Advanced controlling
    The unit includes micro-computer controlling, allowing all operation parameters to be set. Operation status can be displayed on the LCD wire controller. Remote controller can be chosen as future option.

WARNING

Do not use means to accelerate the defrosting process or to clean, Other than those recimmended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources (for example : open flames, an operating gas appliance Or an operating electric heater.)

Do not pierce or burn.
Be aware that refrigerants may not contain an odour,
2 Appliance shall be installed, operated and stored in a room with a floor area larger than 30 m .

NOTE The manufacturer may provide other suitable examples or may provide additional information about the refrigerant odour.

  • This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

  • The appliance shall be installed in accordance with national wiring regulations.

  • If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

  • Before obtaining access to terminals, all supply circuits must be disconnected.
    Do not operate your air conditioner in a wet room such as a bathroom or laundry room.

  • An all-pole disconnection device which has at least 3mm clearances in all pole have a leakage current that may exceed 10mA the residual current device (RCD) having a rated residual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules

  • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer

  • The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.)

  • Do not pierce or burn

  • Appliance shall be installed, operated and stored in a room with a floor area larger than 30 m2 Be aware that refrigerants may not contain an odour.
    The installation of pipe-work shall be kept to a minimum 30 m2 Spaces where refrigerant pipes shall be compliance with national gas regulations.
    Servicing shall be performed only as recommended by the manufacturer.
    The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. All working procedure that affets safety means shall only be carried by competent persons.

  • Transport of equipment containing flammable refrigerants Compliance with the transport regulations Marking of equipment using signs Compliance with local regulations Disposal of equipment using flammable refrigerants Compliance with national regulations Storage of equipment/appliances The storage of equipment should be in accordance with the manufacturer’s instructions. Storage of packed (unsold) equipment Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge.
    The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

Caution & Warning

  1. The unit can only be repaired by qualified installer centre personnel or an authorised dealer. for Europe market
  2. This appliance is not intended for use by persons (including children) with reduced physical sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. for Europe market Children should be supervised to ensure that they do not play with the appliance.
  3. Please make sure that the unit and power connection have good earthing, otherwise may cause electrical shock.
  4. If the supply cord is damaged, it must be replaced by the manufacturer or our service agent or similarly qualified person in order to avoid a hazard.
  5. Directive 2002/96/EC (WEEE): The symbol depicting a crossed-out waste bin that is underneath the appliance indicates that this product, at the end of its useful life, must be handled separately from domestic waste, must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance.
  6. Directive 2002/95/EC (RoHs): This product is compliant with directive 2002/95/EC (RoHs) concerning restrictions for the use of harmful substances in electric and electronic devices.
  7. The unit CANNOT be installed near the flammable gas. Once there is any leakage of the gas , fire can be occur.
  8. Make sure that there is circuit breaker for the unit, lack of circuit breaker can lead to electrical shock or fire.
  9. The heat pump located inside the unit is equipped with an over-load protection system. It does not allow for the unit to start for at least 3 minutes from a previous stoppage.
  10. The unit can only be repaired by the qualified personnel of an installer center or an authorized dealer. for North America market
  11. Installation must be performed in accordance with the NEC/CEC by authorized person only. for North America market
  12. USE SUPPLY WIRES SUITABLE FOR 75°C .
  13. Caution: Single wall heat exchanger, not suitable for potable water connection.

SPECIFICATION

Performance data of Swimming Pool Heat Pump Unit

*** REFRIGERANT : R32

UNIT 34-180628 34-180630
Heating capacity (27/24.3 kW 3.622-13.38 4.259-16.67
Btu/h 12362-45666 14536-56894
Heating Power Input kW 0.296-2.388 0.271-2.401
COP 12.21-5.60 15.72-6.95
Heating capacity (15/12 kW 2.758-8.447 3.324-11.88
Btu/h 9413-28829 11345-40546
Heating Power Input kW 0.467-2.489 0.488-2.524
COP 5.91-3.39 6.81-4.71
Power Supply Compressor Quantity 220-240V /50Hz 220-240V /50Hz
1 1
Compressor rotary rotary
Fan Number 1 1
Noise dB(A) 40-49 43-52
Water Connection mm 50 50
Water Flow Volume m3/h 6.0 7.3
Water Pressure Drop(max) kPa 5.5 7.4
Unit Net Dimensions(L/W/H) mm See the drawing of the units See the drawing

of the units
Unit Ship Dimensions(L/W/H)| mm| See package lable| See package lable
Net Weight| kg| see nameplate| see nameplate
Shipping Weight| kg| see package label| see package label

Heating: Outdoor air temp: 27°C /24.3 °C , Inlet water temp:26°C

Outdoor air temp : 15°C /12°C , Inlet water temp:26°C

Operating range:

Ambient temperature : -15 43°C
Water temperature: 9-40°C

Performance data of Swimming Pool Heat Pump Unit

*** REFRIGERANT : R32

UNIT 34-180632 34-180640

Heating capacity

(27/24.3

| kW| 6.34-20.89| 7.68-25.13
Btu/h| 21630-71275| 24840-85740
Heating Power Input| kW| 0.43-2.80| 0.48-4.03
COP| | 14.77-7.46| 16.0-6.24
Heating capacity

(15/12

| kW| 4.65-16.00| 5.57-19.2
Btu/h| 15865-54590| 19005-65510
Heating Power Input| kW| 0.63-2.92| 0.80-3.98
COP| | 7.38-5.48| 6.69-4.82
Power Supply Compressor Quantity| | 380~415V /3N/50Hz| 380V /3N/50Hz
| 1| 1
Compressor| | rotary| rotary
Fan Number| | 2| 2
Noise| dB(A)| 44-50| 45-53
Water Connection| mm| 50| 50
Water Flow Volume| m3/h| 6.8| 9.1
Water Pressure Drop(max)| kPa| 5| 7.2
Unit Net Dimensions(L/W/H)| mm| See the drawing of the units| See the drawing of the units
Unit Ship Dimensions(L/W/H)| mm| See package lable| See package lable
Net Weight| kg| see nameplate| see nameplate
Shipping Weight| kg| see package label| see package label

Heating: Outdoor air temp: 27°C /24.3°C , Inlet water temp:26
Outdoor air temp: 15°C/12°C , Inlet water temp:26
Operating range:
Ambient temperature: 15 43°C
Water temperature :9-40°C

Performance data of Swimming Pool Heat Pump Unit

*** REFRIGERANT : R32

UNIT 34-180642
Heating capacity (27/24.3 °C) kW 7.68-29.65
Btu/h 24840-101165
Heating Power Input kW 0.48-5.07
COP 16-5.85
Heating capacity (15/12 °C) kW 5.57-22.70
Btu/h 19005-77450
Heating Power Input kW 0.80-5.04
COP 6.96-4.50

Power Supply

Compressor Quantity

| | 380V /3N/50Hz
| 1
Compressor| | rotary
Fan Number| | 2
Noise| dB(A)| 45-54
Water Connection| mm| 50
Water Flow Volume| m3/h| 9.7
Water Pressure Drop(max)| kPa| 7.2
Unit Net Dimensions(L/W/H)| mm| See the drawing of the units
Unit Ship Dimensions(L/W/H)| mm| See package lable
Net Weight| kg| see nameplate
Shipping Weight| kg| see package label

Heating: Outdoor air temp: 27°C/24.3°C , Inlet water temp:26°C
Outdoor air temp: 15°C /12°C , Inlet water temp:26°C
Operating range:
Ambient temperature:- 15 43°C
Water temperature: 9-40°C
Pump : The maximum current is no more than 5A.

The dimensions for Swimming Pool Heat Pump Unit

UNIT: 34-180628 34-180630

The dimensions for Swimming Pool Heat Pump Unit

UNIT: 34-180632
34-180640
34-180642
Unit mm

INSTALLATION AND CONNECTION

Swimming Pool Heat Pumps Location

The unit will perform well in any outdoor location provided that the following three factors are presented:

  1. Fresh Air – 2. Electricity – 3. Pool filter piping
    The unit may be installed virtually anywhere outdoors. For indoor pools please consult the supplier. Unlike a gas heater, it has no draft or pilot light problem in a windy area. DO NOT place the unit in an enclosed area with a limited air volume, where the units discharge air will be re-circulated.
    DO NOT place the unit to shrubs which can block air inlet. These locations deny the unit of a continuous source of fresh air which reduces it efficiency and may prevent adequate heat delivery.
How Close To Your Pool?

Normally, the pool heat pump is installed within 7.5 metres of the pool. The longer the distance from the pool, the greater the heat loss from the piping. For the most part ,the piping is buried. Therefore, the heat loss is minimal for runs of up to15 meters(15 meters to and from the pump = 30 meters total), unless the ground is wet or the water table is high. A very rough estimate of heat loss per 30 meters is 0.6 kW-hour,(2000BTU) for every 5 difference in temperature between the pool water and the ground surrounding the pipe, which translates to about 3% to 5% increase in run time

Swimming Pool Heat Pumps Plumbing

The Swimming Pool Heat Pumps exclusive rated flow titanium heat exchanger requires no special plumbing arrangements except bypass(please set the flow rate according to the nameplate). The water pressure drop is less than 10kPa at max. Flow rate. Since there is no residual heat or flame Temperatures, The unit does not need copper heat sink piping. PVC pipe can be run straight into the unit.

Location: Connect the unit in the pool pump discharge (return) line downstream of all filter and pool pumps, and upstream of any chlorinators, ozonators or chemical pumps.

Standard model have slip glue fittings which accept 32mm or 50 mm PVC pipe for connection to the pool or spa filtration piping. By using a 50 NB to 40NB you can plumb 40NB Give serious consideration to adding a quick coupler fitting at the unit inlet and outlet to allow easy draining of unit for winterizing and to provide easier access should servicing be required.

Condensation: Since the Heat pump cools down the air about 4 -5 , water may condense on the fins of the horseshoe shaped evaporator. If the relative humidity is very high, this could be as much as several litres an hour. The water will run down the fins into the base pan and drain out through the barbed plastic condensation drain fitting on the side of the base pan. This fitting is designed to accept 20mm clear vinyl tubing which can be pushed on by hand and run to a suitable drain. It is easy to mistake the condensation for a water leak inside the unit.
NB: A quick way to verify that the water is condensation is to shut off the unit and keep the pool pump running. If the water stops running out of the base pan, it is condensation. AN EVEN QUICKER WAY IS to TEST THE DRAIN WATER FOR CHLORINE – if the is no chlorine present, then it’s condensation.

Swimming Pool Heat Pumps Electrical Wiring

NOTE : Although the unit heat exchanger is electrically isolated from the rest of the unit, it simply prevents the flow of electricity to or from the pool water. Grounding the unit is still required to protect you against short circuits inside the unit. Bonding is also required.

The unit has a separate molded-in junction box with a standard electrical conduit nipple already in place. Just remove the screws and the front panel, feed your supply lines in through the conduit nipple and wire-nut the electric supply wires to the three connections already in the junction box (four connections if three phase). To complete electrical hookup, connect Heat Pump by electrical conduit, UF cable or other suitable means as specified (as permitted by local electrical authorities) to a dedicated AC power supply branch circuit equipped with the proper circuit breaker, disconnect or time delay fuse protection.

Disconnect – A disconnect means (circuit breaker , fused or un-fused switch) should be located within sight of and readily accessible from the unit, This is common practice on commercial and residential air conditioners and heat pumps. It prevents remotely-energizing unattended equipment and permits turning off power at the unit while the unit is being serviced.

Initial startup of the Unit

NOTE- In order for the unit to heat the pool or spa, the filter pump must be running to circulate water through the heat exchanger.
Start up Procedure – After installation is completed, you should follow these steps:

  1. Turn on your filter pump. Check for water leaks and verify flow to and from the pool.
  2. Turn on the electrical power supply to the unit, then press the key ON/OFF of wire controller, It should start in several seconds.
  3. After running a few minutes make sure the air leaving the top(side) of the unit is cooler(Between 5-10 )
  4. With the unit operating turn the filter pump off. The unit should also turn off automatically,
  5. Allow the unit and pool pump to run 24 hours per day until desired pool water temperature is reached. When the water-in temperature reaches this setting, the unit will slow down for a period of time, if the temperature is maintained for 45 minutes the unit will turn off. The unit will now automatically restart (as long as your pool pump is running)when the pool temperature drops more than 0.2 below set temperature.

Time Delay – The unit is equipped with a 3 minute built-in solid state restart delay included to protect control circuit components and to eliminate restart cycling and contactor chatter. This time delay will automatically restart the unit approximately 3 minutes after each control circuit interruption. Even a brief power interruption will activate the solid state 3 minute restart delay and prevent the unit from starting until the 5 minute countdown is completed.

OPERATION AND USE

Color screen wire controller interface introduction

Main interface

Button Description

NO. Name The button function

**1**

| ON/OFF| Press to start /shut off the unit

**2**

| Parameter| Click this button to view the unit state and the parameter

3

| CLOCK| Press to set the clock, the timer on or timer off. When the timer was starting,the button is green

**4**

| Fault display| Click to view fault history

**5**

| Silent setting| Click to turn on/off silent function and to set timing Low speed function.

**6**

| MODE| Click to enter mode setting and the target temp. Setting interface

**7**

| Temp.curve| Click to view the temp. and power curve

**8**

| Water

Inlet Temp.

| Click to enter mode setting and the target temp. Setting interface

**9**

| LOCK| Click to lock the screen     Input “22” to unlock the screen by press the “lock button”

Color screen wire controller function introduction

Mode switch and target temperature Setting
Booting and shutdown
In shutdown status, click **1** then the unit will be booted In booting status, click **1** then the unit will be shut down. As shown in figure 1.1:
Mode switch
In the main interface, click mode button or inlet water temperature setting button, interface displays as follows:

Click the refrigeration mode button , automatic mode button or heating mode button then you can select the corresponding mode. Note: when the unit is designed for single automatic mode or single thermal mode, the mode can not be switched.

Target temp. setting

Click the temperature set button **4**, you can set the target temperature.

Clock setting

In the main interface, click on the clock Settings button, interface displays as follows:

The operation of time setting

Click on the time Settings button 1, interface displays as follows:

lick the value to set time directly, the click confirm button to save the Settings.

For example: setup time: the 10-14-2017 09:21:30, input 10 14 17 09 21 30 , the time change then click confirm button.

The operation of timing setting
Click the timing set button **2** to enter timing setinterface

NO. Name Button color Button function

1

| Timing start button| Start: green End: gray| Click this button to start or end timing start setting function

**2**

| Timing on setting| | Click to set start time of the timing

**3**

| Timing end button| Open: red End: gray| Click this button to start or end timing end setting function

**4**

| Timing off setting| | Click to set end time of the timing

When the timer was starting, the clock button is green in the main interface.

Silent setting and silent timing setting

Click the silent setting button ,and the interface displays as follows:

The silent button

Click the silent button **1**, the unit will enter the silent mode, and interface displays as follows:

Click the silent button **1** again, to exit the silent mode.

NO. Name Colour Function

**1**

| Timing silent off| Used: red Unused: gray| Click to use or un use timing off function

**2**

| Timing silent on| Use: green Unused: gray| Click to use or un use timing on function

**3**

| Timing silent start time| | Click this button to set the timing silent start time

**4**

| Timing silent end time| | Click this button to set the timing silent end time

Start time and end time setting value must be among the range of 0:00-23:00,and se ttin g v alue can be prec ise to hour digit.
For example above, click “ON”to use timing silent, the unit will start the silent at 0:00 points and end at 4:00;
click “OFF” to unuse the timing silent, but if the unit is in timing silent mode, it will exit silent timing immediately.

History of the fault

If no failure, main interface displays static “ ”

When fault occurs, the fault icon will flash between the

the failure interface will record time, code, name of the fault.

After troubleshooting, if you do not check the failure record,  the main interface will display static ” “; if you check the failure record, the main interface will displays static , Failure record is in reverse order, according to the happening time.

Press the “Clean” key, you can delete the fault record.

Color Display Calibration

Keep click quickly at the blank area on any interface till you hear a long beep. Then you will enter the calibration interface. Click “+” to start calibration. When you hear the beep again, you will finish calibration and exit

Use and Operation Instruction

Temperature curve

In the main interface, click the curve display button, interface displays as follows:

Temperature recording curve is as follows:

The average power curve

Temperature curve automatically updates every one hour, and the curve record can be stored for 60 days; Start from the latest curve saved time, if power is off and curve data collecting time is less than one hour, the data in this period will not be saved;

Parameter list and breakdown table

Electronic control fault table

Can be judged according to the remote controller failure code and troubleshooting

Protect/fault Fault display Reason Elimination methods
Standby Non
Normal boot Non
Inlet Temp. Sensor Fault P01 The temp. Sensor is broken or short circuit

Check or change the temp. Sensor
Outlet Temp.Sensor Fault| P02| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
Ambient Temp. Sensor Fault| P04| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
Coil Temp. Sensor Fault| P05| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
Suction Temp. Sensor Fault| P07| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
Discharge Temp. Sensor Fault| P081| The temp. Sensor is broken or short circuit| Check or change the temp. Sensor
High Pressure Prot.| E01| The high-pressure switch is broken| Check the pressure switch and cold circuit
Low Pressure Prot.| E02| Low pressure1 protection| Check the pressure switch and cold circuit
Flow Switch Prot.| E03| No water/little water in water system| Check the pipe water flow and water pump
Anti-freezing Prot| E07| Water flow is not enough|
Primary Anti-freezing Prot.| E19| The ambient temp. Is low|
Secondary Anti-freezing Prot.| E29| The ambient temp. Is low|
Inlet and outlet temp. too big| E06| Water flow is not enough and low differential pressure| Check the pipe water flow and whether water system is jammed or not
Low temperature protection| Non| The environment temp. is low|
Comp. Overcurrent Prot.| E051| The compressor is overload| Check whether the system of the compressor running normally
Exhaust Air over Temp Prot.| P082| The compressor is overload| Check whether the system of the compressor running normally
Communication Fault| E08| Communication failure between wire controller and mainboard| Check the wire connection between remote wire controller and main board
Antifreeze Temp. Sensor Fault| P09| antifreeze temp sensor is broken or short circuited| check and replace this temp sensor
Waterway Anti-freezing Prot.| E05| water temp. or ambient temp. is too low|
EC fan feedback Fault| F051| There is something wrong with fan motor and fan motor stops running| Check whether fan motor is broken or locked or not
Pressure sensor Fault| PP| The pressure Sensor is broken| Check or change the pressure Sensor or pressure
Fan Motor1 Fault| F031|

  1. Motor is in locked-rotor state
  2. The wire connection between DC-fan motor module and fan motor is in bad contact

|

  1. Change a new fan motor
  2. Check the wire connection and make sure they are in good contact

Low AT Protection| TP| Ambient temp is too low|
Fan Motor 2 Fault| F032|

  1. Motor is in locked-rotor state 2.The wire connection between DC-fan motor module and fan motor is in bad contact

|

  1. Change a new fan motor
  2. Check the wire connection and make sure they are in good contact

Communication Fault (speed control module)| E081| Speed Control Module and main board communication fail| Check the communication connection

Frequency conversion board fault table:

Protection/fault| Fault display| Reason| Elimination methods
---|---|---|---
Drv1 MOP alarm| F01| MOP drive alarm| Recovery after the 150s
Inverter offline| F02| Frequency conversion board and main board communication failure| Check the communication connection
IPM protection| F03| IPM modular protection| Recovery after the 150s
Comp. Driver Failure| F04| Lack of phase, step or drive hardware damage| Check the measuring voltage check frequency conversion board hardware
DC Fan Fault| F05| Motor current feedback open circuit or short circuit| Check whether current return wires connected motor
IPM Overcurrent| F06| IPM Input current is large| Check and adjust the current measurement
Inv. DC Overvoltage| F07| DC bus voltage>Dc bus over-voltage protection value| Check the input voltage measurement
Inv. DC Less voltage| F08| DC bus voltage<Dc bus over-voltage protection value| Check the input voltage measurement
Inv. Input Less Volt.| F09| The input voltage is low, causing the input current is high| Check the input voltage measurement
Inv. Input Overvolt.| F10| The input voltage is too high, more than outage protection current RMS| Check the input voltage measurement
Inv. Sampling Volt.| F11| The input voltage sampling fault| Check and adjust the current measurement
Comm. Err DSP-PFC| F12| DSP and PFC connect fault| Check the communication connection
Input Over Cur.| F26| The equipment load is too large|
PFC fault| F27| The PFC circuit protection| Check the PFC switch tube short circuit or not
IPM Over heating| F15| The IPM module is overheat| Check and adjust the current measurement
Weak Magnetic Warn| F16| Compressor magnetic force is not enough|
Inv. Input Out Phase| F17| The input voltage lost phase| Check and measure the voltage adjustment
IPM Sampling Cur.| F18| IPM sampling electricity is fault| Check and adjust the current measurement
Inv. Temp. Probe Fail| F19| Sensor is short circuit or open circuit| Inspect and replace the sensor
Inverter Overheating| F20| The transducer is overheat| Check and adjust the current measurement
Inv. Overheating Warn| F22| Transducer temperature is too high| Check and adjust the current measurement
Comp. OverCur. Warn| F23| Compressor electricity is large| The compressor over protection
Input Over Cur. Warn| F24| Input current is too large| Check and adjust the current measurement
EEPROM Error Warn| F25| MCU error| Check whether the chip is damaged Replace the chip
V15V over/under voltage fault| F28| The V15V is overload or under voltage| Check the V15V input voltage in range 13.5v~16.5v or not

Main board (Q20)

Controller interface diagram and definition
(2) Parameter list

Meaning Default Remarks
Refrigeration target temperature set point 27 °C Adjustable
Heating the target temperature set point 27 °C Adjustable
Automatic target temperature set point 27 °C Adjustable
Interface drawing

(1) Wire control interface diagram and definition

Sign Meaning
V 12V power +
R No use
T No use
A 485A
B 485B
G GND(power-)

(2) Controller interface diagram and definition
UNIT: 34-180628 34-180630

(2) Controller interface diagram and definition
UNIT: 34-180632
34-180640
34-180642

Main board of the input and output interface instructions below: 2AC32I1WO1

Number Sign Meaning
01 P10-1/2/3(U/V/W) Compressor
02 CN66 Compressor signal
03 CN97 DC motor
04 CN11 4-way valve
05 CN18 Water pump
06 CN13 reserved
07 CN96-H High speed of fan
08 CN96-L Low speed of fan
09 CN24 Electronic expansion valve
10 P1 P2 Live wire Neutral wire
11 ACL1 ACN1 Switching power module
12 CN10 Program download interface
13 CN401 reserved
14 CN15 reserved
15 P13(L)/P14(L) resistance
16 P00/P01/P03 ground
17 RS485 Color line controller communication
18 CN29 Water flow switch
19 CN30 System high pressure
20 CN31 System low pressure
21 CN21 Water input temperature
22 CN7 System suction temperature
23 CN8 System fan coil temperature
24 CN99 Low pressure sensor
25 CN22 Water output temperature
26 CN9 System Exhaust temperature
27 CN12 Ambient temperature

Main board of the input and output interface instructions below :PC1004

Number Sign Meaning
01 OUT1 Compressor ( output 220-230VAC
02 OUT2 Water pump ( output 220-230VAC
03 OUT3 4-way valve ( output 220-230VAC
04 OUT4 High speed of fan ( output 220-230VAC
05 OUT5 Low speed of fan (output 220-230VAC
06 AC-L Live wire ( input 220-230VAC
07 AC-N Neutral wire ( input 220-230VAC
08 AI/DI01 Emergency switch input
09 AI/DI02 Water flow switch    input
10 AI/DI03 System low pressure input
11 AI/DI04 System high pressure input
12 AI/DI05 System suction temperature input
13 AI/DI06 Water input temperature      input
14 AI/DI07 Water output temperature ( input )
15 AI/DI08 System fan coil temperature     input
16 AI/DI09 Ambient temperature input
17 AI/DI10 Mode switch input
18 AI/DI11 Master-slave machine switch / Antifreeze
temperature input
19 AI12(50K) System Exhaust temperature input
20 0_5V_IN Compressor current detection/Pressure sensor(input)
21 PWM_IN Master-slave machine switch / Feedback signal of EC fan ( input )
22 PWM_OUT AC fan control ( output )
23 0_10V_OUT EC fan control ( output )
24 +5V +5V ( output )
25 +12V +12V ( output )
26 GND 485_B1 485_A1 12V Frequency conversion board communications

27
28
29
30| GND 485_B2 485_A2 12V| Color line controller communication
31
32
33
34| CN9| Electronic expansion valve
35| GND 485_B3 485_A3 12V| The port for centralized control system
36
37
38

MAINTENANCE AND INSPECTION

  • Check the water supply device and the release often. You should avoid the condition of no water or air entering into system, as this will influence unit’s performance and reliability. You should clear the pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.

  • The area around the unit should be dry, clean and well ventilated. Clean the side heating exchanger regularly to maintain good heat exchange as conserve energy .

  • The operation pressure of the refrigerant system should only be serviced by a certified technician .
    Discharge all water in the water pump and water system ,so that freezing of the water in the pump or water system does not occur. You should discharge the water at the bottom of water pump if the unit will not be used for an extended period of time. You should check the unit thoroughly and fill the system with water fully before using it for the first time after a Check the power supply and cable connection often,. Should the unit begin to operate abnormally, switch it off and contact the qualified technician.

  • Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. prolonged period of no usage.

  • Work procedure
    Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.

  • Work procedure
    Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.

  • General work area
    All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

  • General work area
    All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

  • Checking for presence of refrigerant
    The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

  • Presence of fire extinguisher
    If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging No ignition sources No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.

  • Ventilated area
    Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere. prolonged period of no usage.

  • Checks to the area
    Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. prolonged period of no usage.

  • Checks to the refrigeration equipment
    Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance.
    The following checks shall be applied to installations using flammable refrigerants:
    The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
    The ventilation machinery and outlets are operating adequately and are not obstructed;
    If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
    Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
    Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

  • Checks to electrical devices
    Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised
    Initial safety checks shall include:

    • That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;
    • That there no live electrical components and wiring are exposed while charging, recovering or purging the system; . That there is continuity of earth bonding.
  • Repairs to sealed components
    1) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
    2) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected.
    This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely.

  • Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
    NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to

  • Repair to intrinsically safe components
    Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
    Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

  • Cabling
    Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

  • Detection of flammable refrigerants
    Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

  • Leak detection methods
    The following leak detection methods are deemed acceptable for systems containing flammable refrigerants.
    Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed.
    Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.
    If a leak is suspected, all naked flames shall be removed/ extinguished.
    If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall berecovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

  • Removal and evacuation
    When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:

    • Remove refrigerant;
    • Purge the circuit with inert gas;
    • Evacuate;
    • Purge again with inert gas;
    • Open the circuit by cutting or brazing.
  • The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task.
    Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.
    Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. working on them.

  • Labelling
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

  • Recovery
    When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
    When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shutoff valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
    The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
    The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
    If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

  • Decommissioning
    Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
    a) Become familiar with the equipment and its operation.
    b) Isolate system electrically.
    c) Before attempting the procedure ensure that:

    • Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
    • All personal protective equipment is available and being used correctly;
    • The recovery process is supervised at all times by a competent person;
    • Recovery equipment and cylinders conform to the appropriate standards.
      d) Pump down refrigerant system, if possible.
      e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
      f) Make sure that cylinder is situated on the scales before recovery takes place.
      g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
      h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
      i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
      j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
      k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
  • Charging procedures
    In addition to conventional charging procedures, the following requirements shall be followed.
    Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
    Cylinders shall be kept upright.
    Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
    Label the system when charging is complete (if not already).
    Extreme care shall be taken not to overfill the refrigeration system.
    Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

  • The safety wire model is 5*20_5A/250VAC,And must meet the explosion-proof requirements

APPENDIX

Cable specification

(1) Single phase unit

Nameplate maximum current| Phase line| Earth line| MCB| Creepage protector| Signal line
---|---|---|---|---|---
No more

than 10A

| 2| 1.5mm2| 1.5mm2| 20A| 30mA less than 0.1 sec| n * 0.5mm2|
10~16A| 2| 2.5mm2| 2.5mm2| 32A| 30mA less than 0.1 sec
16~25A| 2| 4mm2| 4mm2| 40A| 30mA less than 0.1 sec
25~32A| 2| 6mm2| 6mm2| 40A| 30mA less than 0.1 sec
32~40A| 2| 10mm2| 10mm2| 63A| 30mA less than 0.1 sec
40 ~63A| 2| 16mm2| 16mm2| 80A| 30mA less than 0.1 sec
63~75A| 2| 25mm2| 25mm2| 100A| 30mA less than 0.1 sec
75~101A| 2| 25mm2| 25mm2| 125A| 30mA less than 0.1 sec
101~123A| 2| 35mm2| 35mm2| 160A| 30mA less than 0.1 sec
123~148A| 2| 50mm2| 50mm2| 225A| 30mA less than 0.1 sec
148~186A| 2| 70mm2| 70mm2| 250A| 30mA less than 0.1 sec
186~224A| 2| 95mm2| 95mm2| 280A| 30mA less than 0.1 sec

(2) Three phase unit

Nameplate maximum current| Phase line| Earth line| MCB| Creepage protector| Signal line
---|---|---|---|---|---
No more

than 10A

| 3| 1.5mm2| 1.5mm2| 20A| 30mA less than 0.1 sec| n*0.5mm2|
10~16A| 3| 2.5mm2| 2.5mm2| 32A| 30mA less than 0.1 sec
16~25A| 3| 4mm2| 4mm2| 40A| 30mA less than 0.1 sec
25~32A| 3| 6mm2| 6mm2| 40A| 30mA less than 0.1 sec
32~40A| 3| 10mm2| 10mm2| 63A| 30mA less than 0.1 sec
40 ~63A| 3| 16mm2| 16mm2| 80A| 30mA less than 0.1 sec
63~75A| 3| 25mm2| 25mm2| 100A| 30mA less than 0.1 sec
75~101A| 3| 25mm2| 25mm2| 125A| 30mA less than 0.1 sec
101~123A| 3| 35mm2| 35mm2| 160A| 30mA less than 0.1 sec
123~148A| 3| 50mm2| 50mm2| 225A| 30mA less than 0.1 sec
148~186A| 3| 70mm2| 70mm2| 250A| 30mA less than 0.1 sec
186~224A| 3| 95mm2| 95mm2| 280A| 30mA less than 0.1 sec

When the unit will be installed at outdoor, please use the cable which can against UV.

Comparison table of refrigerant saturation temperature
Pressure (MPa ) 0 0.3 0.5 0.8 1 1.3 1.5 1.8 2 2.3
Temperature (R410A)(    ) -51.3 -20 -9 4 11 19 24 31 35 39
Temperature (R32)(    ) -52.5 -20 -9 3.5 10 18 23 29.5 33.3 38.7
Pressure (MPa ) 2.5 2.8 3 3.3 3.5 3.8 4 4.5 5 5.5
Temperature (R410A)(    ) 43 47 51 55 57 61 64 70 74 80
Temperature (R32)(    ) 42 46.5 49.5 53.5 56 60 62 67.5 72.5 77.4

Code 20191022-0004