hager ARM906U MCB with Dangerous Arc Detection Instruction Manual
- June 4, 2024
- hager
Table of Contents
hager ARM906U MCB with Dangerous Arc Detection
-
ARMxxxU
MCB with dangerous arc detection -
ARM906U
MCB with dangerous arc detection 1M 6A B 6kA -
ARM910U
MCB with dangerous arc detection 1M 10A B 6kA -
ARM916U
MCB with dangerous arc detection 1M 16A B 6kA -
ARM920U
MCB with dangerous arc detection 1M 20A B 6kA -
ARM925U
MCB with dangerous arc detection 1M 25A B 6kA -
ARM932U
MCB with dangerous arc detection 1M 32A B 6kA
Safety notice
The AFDD (Arc Fault Detection Device) may only be installed, connected and ser-viced by a qualified electrician. Before mounting, the AFDD must be checked for external damage. If any damage or other defect is found, the device must not be mounted. The national regulations, safety regula-tions and installation standards BS 7671 must be observed.
Design and layout of the device
- Test button
- LED status display
- Handle
- Yellow flag
- Mounting metal DIN rail clip
Function
MCB-AFD in 1 module ARMxxxU is a sin-gle device consisting of a miniature
circuit breaker (MCB) unit with integrated Arc fault detection (AFD) unit (2
in 1).
The AFDD mitigates the risk of a fire in the final electrical circuits of a
fixed installation due to arcing fault currents, which under certain
conditions present a fire ignition risk due to dangerous arc Fault, complaint
ac-cording to BS 7671 installation Standards.
Correct use
Mounting on DIN rail after TH 35 7.5- 15 according to IEC 60715:2017 / EN
60715:2017
Tools
Installation and electricial connection
DANGER !
Electric shock when touching live parts! Electric shock can lead to death!
Before working on the unit, disconnect the connecting cables and cover live
parts in the vicinity!
Mount device
- Open the din rail clip.
- Insert the AFDD until it is inked.
- Put the AFDD on the rail.
- Press the metal clamp down. The AFDD is fixed on the rail.
Connect device
Wiring diagram
Disassembly
Testing
The test button T is used for testing the device. If the circuit is
interruped, operate the handle provided for this purpose.
Test device
ATTENTION !
High voltage tests may damage this product! If the handle is OFF you dont have
to disconnect the cable.
Notice
- The AFDD function must be tested after installation. The supply voltage must be present.
- The MCB- AFDD must trip within one second. If the device does not trip, it must be replaced by an experienced electrician.
- Short press the test button only when the yellow flag is present. This ensures that the device has not been triggered by the user.
Short press the test button T. The MCB-AFDD tripped, i.e. the cir- cuit must switch off.
Notice
If the AFDD does not trip, check the status of the LED (table 1).
LED status for troubleshooting
The handle is in the OFF position. Short press the test button T to open the color code.
LED status display for a standard troubleshooting
Steady GREEN | AFDD is ON |
---|---|
LED is OFF | AFDD is OFF |
Blinking RED/ GREEN + yellow flag absence | AFDD |
manual tripped
Blinking RED/ GREEN + yellow flag presence| Overload or Short-Circuit
Blinking RED/ YELLOW| Series arc fault
Blinking RED| Parallel arc fault
Steady YELLOW| Overvoltage
Blinking YELLOW| Internal failure
Notice
In case of an internal Failure, re-place the AFDD and contact the Hager
technical support.
Connection to mobilephone
A mobile phone ( iphone, operating with IOS14 or above, or Android, operating
with Android 7 or above) is required to use those functions.
Notice
Using the connected functions with your mobile phone requires to activate
network functions (Bluetooth, WiFi) and to accept the application terms of use
& privacy notice. Only bluetooth 4.2 or above is supported.
- Install the Hager Pilot mobile application on your mobilephone.
- Follow further instructions on the mobile application.
LED status for Bluetooth® connection
The handle is in the ON position. Press the test button T for 5 seconds to open the color code.
LED status display for Bluetooth® connection
Blinking BLUE| Bluetooth enabled|
---|---|---
Steady BLUE| Bluetooth connected|
Blinking RED/BLUE| Update mode (only overload and short-circuit protection in
this mode)|
Blinking BLUE/ YELLOW| Trace mode (use for technical Hager support)|
Blinking (BLUE/ GREEN)| Product localisation request|
EU and UKCA Declaration
Hereby, Hager Electro SAS , declares that the AFDD products are in compliance with SI 2017/1206 Radio Equipment Regulations 2017 and with radio emission directive 2014/53/EU
- Operating frequency 2.4 to 2.483 GHz.
- Maximum radio frequency 10mW. Declarations of conformity can be downloaded on www.hager.com
- T +44 1 952 677 899
- technical@hager.co.uk
- Technical Support: 01952 675689
- www.hager.com/uk
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>