HYDROLEVEL 3200-Plus Wireless Outdoor Sensor Instruction Manual
- June 13, 2024
- HYDROLEVEL
Table of Contents
- HYDROLEVEL 3200-Plus Wireless Outdoor Sensor
- Installation Instructions and Operating Manual
- FCC STATEMENT
- INSTALL RECEIVER
- PROVIDE POWER
- Outdoor Sensor Terminals
- HOW THE OUTDOOR SENSOR WORKS
- LED OPERATION
- SENSOR RESISTANCE SETTINGS
- TECHNICAL DATA
- WARRANTY
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HYDROLEVEL 3200-Plus Wireless Outdoor Sensor
- The Hydrolevel Wireless Outdoor Sensor OS-200 provides outdoor temperature measurement in any application without exterior wiring.
- The transmitter and receiver are sold pre-linked and are installation-ready.
- With exceptional range and a 10-year battery life, the Wireless Outdoor Sensor OS-200 provides maximum accuracy, convenience and reliability.
Installation Instructions and Operating Manual
- Low Transmitter battery status indicator on the Receiver
- Power and communication indicator lights
- Transmitter temperature range of -40°F to 140°F (-40°C to 60°C)
- Long battery life (minimum 10 years) with included 1.5V lithium AA batteries
- 5000 ft. (1500 m) open range
- 8 walls / 250 ft. (75 m) indoor range
- Transmits outdoor temperature every 10 minutes
WARNING Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before installing or servicing
control.
Only qualified personnel may install or service this control in accordance
with local codes and ordinances. Read instructions completely before
proceeding.
CAUTION To prevent serious burns, boiler should be thoroughly cooled
before installing or servicing control.
WARNING Frozen pipes/water damage. Central heating systems are prone to
shut down as a result of power or fuel outages, safety related fault
conditions or equipment failure. Installation of freeze protection monitoring
or other precautions is recommended for unattended dwellings in climates
subject to sustain below-freezing temperatures.
FCC STATEMENT
This product has been tested and found to comply with FCC part 15 subpart C. Operation is subject to the following two conditions:
- this device may not cause Harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation of the device.
However, there is no guarantee that interference will not occur in a particular installation. If this device does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on. The user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Warning: Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment.
Industry Canada
This Device complies with Industry Canada License-exempt RSS standard(s).
Operation is subject to the following two conditions:
- this device may not cause interference, and
- this device must accept any interference, including interference that may cause undesired operation of the device under Industry Canada regulations.
Warning: FCC and IC Radiation Exposure Statement
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. The antenna(s) used for this equipment must be
installed to provide a separation distance of at least 8 inches (20 cm) from
all persons.
WARNING
- It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. Hydrolevel is not responsible for damages resulting from improper installation and/or maintenance.
To avoid serious personal injury and damage to the equipment:
- Read manual and all product labels BEFORE using the equipment. Do not use unless you know the safe and proper operation of this equipment.
- Keep this manual available for easy access by all users.
- Replacement manuals are available at hydrolevel.com
- Disconnect all power before opening the control.
- Do not attempt to service the control. There are no user serviceable parts inside the control. Attempting to do so voids warranty.
NOTICE
This symbol identifies practices, actions, or failure to act which could result in property damage or damage to the equipment.
This product is packaged with two AA lithium metal batteries and must be transported in accordance with all relevant and international regulations. Contact your freight company for more information. Hydrolevel is not responsible for damages resulting from improper transportation, installation and/or maintenance.
INSTALL RECEIVER
STEP 1
When choosing the location for the receiver unit, consider the following:
- Interior wall.
- Keep dry. Avoid potential leakage onto the unit.
- Relative humidity less than 90%. Non-condensing environment.
- No exposure to extreme temperatures beyond 32° to 122°F (0° – 50°C).
- Away from equipment, appliances, or other sources of electrical interference.
- Easy access for wiring.
- Approximately 5 feet (1.5 m) off the finished floor.
- Grasp the front cover by the fingertip grips on the top and bottom of the enclosure and pull the front cover off.
- The enclosure is either mounted flush onto a wall or it can be placed onto a 2″ x 4″ non-conductive electrical box.
- The mounting holes in the enclosure accept #6 screws.
- Wiring to the control enters the wiring chamber through the back or bottom of the enclosure.
PROVIDE POWER
STEP 2
NOTICE: The receiver unit must be powered with 24 VAC.
Wiring to HydroStat Model 3200-Plus (Gas applications)
- The 3200-Plus provides a 24 volt power supply in the thermostat terminal block located at the top left hand corner of the control. Make connections as shown below.
Wiring to HydroStat-IC Model 4200
- The modeal 4200 is not equipped with a 24 VAC power supply. Locate an existing 24 volt power supply or add a transformer (supplied by others) as shown below.
Batteries in the Transmitter unit
- Remove the cover from the transmitter unit. Insert the included batteries as marked on the battery holder.
- 1.5V lithium batteries are required to provide the specified battery life and temperature range. Alkaline batteries have short life spans and may fail during cold weather.
Wiring to HydroStat Model 3250-Plus (Oil applications)
- The 3250-Plus is not equipped with a 24 VAC power supply. Locate an existing 24 volt power supply or add a transformer (supplied by others) as shown below.
STEP 3 – CONFIRM LINK
- If the communication light is displayed on the control, the transmitter is linked properly.
- If the light is not on, the devices will need to be linked.
- To link the transmitter and receiver, remove the cover on the transmitter so that the button below the battery terminals can be accessed.
- Press and hold both the button on the transmitter and the button on the receiver simultaneously for 5 seconds and release. Upon release, the linkup process will begin; the communication LED on the receiver will flash 8 times. Linking is successful when the communication LED is steady on.
The link button on the receiver can also be used as a reset. If pushed, the receiver will revert to a power-up condition; a temperature of 75°F (24°C) will be reported until the first transmission is received (up to 10 minutes).
STEP 4 – INSTALL TRANSMITTER
The transmitter should be mounted on a northern exterior wall away from direct sunlight. In order to prevent heat transmitted through the wall from affecting the sensor reading, it may be necessary to install an insulating barrier behind the enclosure.
- The OS-200 should not be exposed to heat sources such as ventilation or window openings.
- The OS-200 should be installed at an elevation above the ground that will prevent accidental damage or tampering.
- Do not install the transmitter on a conductive surface.
- The transmitter will send outdoor temperature data every 10 minutes.
STEP 5 – SENSOR TERMINAL WIRING
Connect 2-conductor wire between the HydroStat control and the sensor
terminals (3 and 4) on the receiver. This connection is polarity sensitive.
Wire the output Com terminal on the receiver to the C terminal on the
HydroStat control. Wire the output Sen terminal on the receiver to the OR (or
WWSD) terminal on the HydroStat control. At power-up the receiver will report
a temperature of 75°F (24°C) until the first temperature transmission is
received (up to 10 minutes). Wait up to 10 minutes to verify that the
temperature at the control is accurate. If the temperature displayed at the
control is unreasonably hot the wires may be reversed.
Outdoor Sensor Terminals
STEP 6 – SETTING THE HYDROSTAT CONTROL
IMPORTANT: The OS-200 must be plugged in to the HydroStat prior to
setting the control.
SETTING WARM WEATHER SHUTDOWN
The warm weather shutdown feature prevents the boiler from providing space
heating when the outside temperature reaches a level that you select.
Available settings range from OFF or 40°- 70°F. The boiler will still operate
to satisfy a call for domestic hot water. The factory default setting for the
warm weather shutdown is 70°F.
To set the desired warm weather shutdown temperature:
Press and hold the TEST/SETTING BUTTON and simultaneously adjust the ECONOMY
dial to the desired setting. To turn the feature off – which will allow space
heating regardless of outdoor temperature – press and hold the TEST/SETTING
BUTTON and simultaneously turn the ECONOMY dial fully counter-clockwise.
Release the TEST/SETTING BUTTON. Be sure to reset the ECONOMY dial to the
correct setting. Any time the outdoor temp exceeds the WWSD setpoint, the
display will toggle boiler temperature (8 seconds), outdoor temperature (2
seconds), and OFF (2 seconds).
SETTING THE OUTDOOR RESET
- The outdoor reset will regulate the boiler’s temperature based on the temperature outside. On cold days, the boiler will run at higher temperatures to meet the heating load in the house. On warmer days, the boiler will run cooler to save energy while still meeting the heating needs of the
- house. The HydroStat control uses a Reset Ratio to calculate and maintain the proper boiler temperature.
To set the desired outdoor Reset Ratio
- Determine the Reset Ratio using the table below:
- Locate the Outdoor Design Temperature for the system on the bottom of the Reset Ratio Chart below. Round down to the next lowest number.
- Locate the Boiler Design Temperature (supply temperature needed to meet heating load at the Outdoor Design Temperature) on the left of the Reset Ratio Chart below.
- Adjust the ECONOMY dial on the HydroStat control to the Reset Ratio determined by the intersection of a. and b. above.
Example: For a house located in Springfield MA (Design Temperature of 0°F) with baseboard heat (that was sized for the house based on the 180°F baseboard rating), the reset ratio is 1.50.
RESET RATIO CHARTOUTDOOR
Refer to the HydroStat instructions for other control settings.
HOW THE OUTDOOR SENSOR WORKS
Outdoor Temperature Reset
The outdoor reset feature monitors outdoor temperature to continuously adjust
the boiler water to the minimum temperature required to satisfy the heat
demand. The feature is activated automatically when the Hydrolevel OS-100 or
OS-200 is wired to the OR and C spade connects on the HydroStat. When
connected, Outdoor Reset overrides the Thermal Targeting temperature reset
method which is built into the HydroStat. The display will toggle between
boiler temperature (8 seconds) and outdoor temperature (2 seconds). If the
sensor becomes damaged or disconnected, the control will automatically revert
back to the Thermal Targeting reset method. The display will no longer toggle
outdoor temperature.
Reset Ratio
The HydroStat control’s Outdoor Reset feature uses a reset ratio method to
control the boiler temperature. The reset ratio determines how much the boiler
temperature is adjusted for changes in outdoor temperature. A reset ratio of
2.0 means that for each 1 degree increase in outdoor temperature, the boiler
temperature will decrease 2 degrees. Conversely, for each 1 degree drop in
outdoor temperature, the boiler temperature will increase 2 degrees. The
control adds 10 degrees to the calculated reset temperature and provides a 20
degree differential for burner operation. So, if the control calculates a
reset temperature of 150°F, it will set a target temperature of 160°F. It will
then allow the burner to fire up to 160°F and draw down to 140°F before re-
firing. This operation will maintain the desired average temperature of 150°F.
You can check the current target temperature at any time, by pressing the
Test/Settings button in 4 short intervals.
Thermal Boost
To insure that the heating system always satisfies a call for heat, the
HydroStat control is equipped with a thermal boost feature. If the thermostat
is not satisfied thirty minutes after the boiler reaches the reset
temperature, the control will boost the reset temperature by 10 degrees. It
will continue to boost at 30 minute intervals until the call is satisfied.
Once the call is satisfied, the control reverts to normal operation, utilizing
the calculated reset temperature.
LOSS OF COMMUNICATION / TROUBLESHOOTING
If the Communication LED is not on, try the following:
- Confirm that the receiver is powered with 24 VAC by observing that the green Power LED is on.
- Locate the transmitter. Remove the cover, and push the button located below the battery terminals. The LED will flash once to indicate transmission. Locate the receiver, and see if the Communication LED is on. If it does not come on, it may be one of three problems:
- The transmitter may be out of range. Try moving the transmitter closer to the receiver. Push the transmission button inside the transmitter and confirm that the communication LED turns green.
- The battery life of the transmitter batteries may have expired. This is likely the issue if the batteries have been in extended service. They can be replaced with 1.5V lithium batteries.
- The link may have been interrupted. Try re-linking the devices, as described on page 4.
- If the communication LED remains off for over 30 minutes, please call Tech Support at 203-776-0473.
LED OPERATION
LED Indicator | Status | Description |
---|
Power
| Green| Normal operation
Off| No power. Check that the wires are securely connected to the device.
Communication
| Green| Signal is good.
Off| No signal. There is a loss of communication or the Transmitter battery is
dead, resulting in an open circuit error on the control.
Flashing| Signal is weak. Consider relocating a device to obtain a stronger
signal.
SENSOR RESISTANCE SETTINGS
10K Type 2 NTC Thermistor
Resistance | Temperature |
---|---|
336095 | -40°F (-40°C) |
242426 | -31°F (-35°C) |
176801 | -22°F (-30°C) |
130307 | -13°F (-25°C) |
97007 | -4°F (-20°C) |
72910 | 5°F (-15°C) |
55303 | 14°F (-10°C) |
42316 | 23°F (-5°C) |
32651 | 32°F (0°C) |
25395 | 41°F (5°C) |
19903 | 50°F (10°C) |
15714 | 59°F (15°C) |
12493 | 68°F (20°C) |
10000 | 77°F (25°C) |
8056 | 86°F (30°C) |
6530 | 95°F (35°C) |
5325 | 104°F (40°C) |
4367 | 113°F (45°C) |
3601 | 122°F (50°C) |
2985 | 131°F (55°C) |
2487 | 140°F (60°C) |
TECHNICAL DATA
Wireless Outdoor Sensor OS-200
Dimensions
| Transmitter: 5–3/16″ H x 2–3/4″ W x 2″ D (132 x 70 x 50 mm)
Receiver: 4–3/4″ H x 2–7/8″ W x 7/8″ D (120 x 74 x 23 mm)
Enclosure| Transmitter: White ABS plastic, NEMA 4X Receiver: White PVC
plastic, NEMA Type 1
Packaged Weight| 0.92 lb. (420g)
Sensor| 10K Type 2
Approvals| FCC and IC
Operating range
| Transmitter: -40 to 140°F (-40 to 60°C)
Receiver: Indoor use only, 32 to 122°F (0 to 50°C), RH
£90% non-condensing
Receiver power| 24 V (ac) +/- 10%, 1 VA
WARRANTY
LIMITED MANUFACTURER’S WARRANTY
We warrant products manufactured by Hydrolevel Company to be free from defects
in material and workmanship for a period of two years from the date of
manufacture or one year from the date of installation, whichever occurs first.
In the event of any claim under this warranty or otherwise with respect to our
products which is made within such period, we will, at our option, repair or
replace such products or refund the purchase price paid to us by you for such
products. In no event shall Hydrolevel Company be liable for any other loss or
damage, whether direct, indirect, incidental or consequential. This warranty
is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or
guarantee, express or implied, including, without limitation, any warranty of
MERCHANTABILITY or fitness for a particular purpose. This warranty may not be
assigned or transferred and any unauthorized transfer or assignment thereof
shall be void and of no force or effect.
CONTACT
- 126 Bailey Road
- North Haven, CT 06473
- 203-776-0473
- FAX 203-764-1711
- www.hydrolevel.com.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>