CAVIUS 2113 Optical Smoke Alarm Device Instruction Manual

June 13, 2024
CAVIUS

CAVIUS 2113 Optical Smoke Alarm Device

CAVIUS-2113-Optical-Smoke-Alarm-Device-product

Product Information

The product is an optical smoke alarm device designed for use in private homes. It has a model number of 2113. The smoke alarm is powered by a replaceable 3V CR123A lithium battery. The maximum number of alarms that can be interlinked within a house group is 32, using alarms from the CAVIUS Wireless Alarm Family. The diameter of the alarm is 65mm and its height is 44mm. The minimum battery life is 5 years, but severe RF interferences may affect battery life.

Product Usage Instructions

  1. Before installation, read the user guide carefully and retain it for future use.
  2. Handle the lithium battery with care and keep battery-powered devices out of reach of children. Do not attempt to recharge or burn the batteries.
  3. For interlinking alarms within a house group, put all alarms into “Learn Mode” by sliding the switch on the back of the alarm to the “Learn Mode” position. The red LED will light up to indicate that “Learn Mode” has been selected.
  4. Do not remove the product label, as it contains important information regarding the product.
  5. Press and hold the test button on one alarm until it beeps and the LED flashes. This alarm will become the master and send out a specific house code to the other alarms.
  6. Do not remove the battery during “Learn Mode” as it will interrupt the learning process.
  7. Place the alarms in areas where not to install smoke alarms: avoid corners and within 50cm of a wall.
  8. For ceiling installation, place the smoke alarm a minimum of 50cm from the wall. For cathedral or peak ceiling or wall installation, place it a minimum of 30cm and a maximum of 50cm from the ceiling.
  9. Detach the alarm from the mounting base by twisting it counterclockwise.
  10. Use the mounting base ring to mark the screw holes on the ceiling or wall.
  11. Use the enclosed screws and plugs to install the smoke alarm.
  12. Ensure a minimum of one smoke alarm per floor and a maximum distance between smoke alarms of 10 meters.
  13. Once all alarms receive the specific house code, they will flash the LED light. When the red LED light flashes on all alarms, they are connected and must be switched out of “Learn Mode” and installed.
  14. Label the original Learn alarm in order to easily add new CAVIUS Wireless Family alarms to the system.

Optical smoke alarm device

  • Model no.: 2113

The smoke alarm is designed for private homes.

PLEASE READ THE USER GUIDE CAREFULLY BEFORE INSTALLATION AND RETAIN FOR FUTURE USE.

SAFETY INSTRUCTIONS

The device comes with a 3V lithium battery. Batteries are to be handled with care and battery-powered devices should be kept out of reach of children. Do not try to recharge or burn the batteries.

TECHNICAL INFORMATION:
The maximum number of alarms that can be interlinked within a house group is 32.

Please note:
These must be alarms from the CAVIUS Wireless Alarm Family.

  • The distance between interlinked alarms depends on the house layout and they should always be tested after installation. It is not advised to get more than 10m distance between two smoke alarms.
    • Diameter: 65mm.
    • Height: 44mm.
  • The alarm is powered by a replaceable 3v CR123A lithium battery.
  • In normal situations, the minimum battery life is 5 years, but severe RF interferences may affect the battery life of your device.

HOW TO SET UP AND CONNECT ALARMS

  • Start by pulling out the battery isolation strip as shown.
    Please note:
    The product label must not be removed as it contains important information regarding the product.

  • All alarms that need to be connected in the house should be put into ‘Learn Mode’ by sliding the switch on the back of the alarm to the ‘Learn Mode’ position.

  • The red LED will light up to indicate that ‘Learn Mode’ has been selected.

  • Please note that when the alarms are placed in ‘Learn Mode’ they can’t be inserted into the mounting base.

  • Do not take out the battery during ‘Learn Mode’ as this will interrupt the learning process.

  • Press and hold the test button at one alarm only, until it beeps and the LED flashes. This alarm will become the master and will start sending out a specific house code to the other alarms.

  • As the other alarms receive the specific house code, they will also flash the LED light.

  • When the red LED light flashes on all alarms, they are connected and MUST BE SWITCHED OUT OF ‘LEARN MODE’ and installed.

  • Label the original “Learn” alarm in order to easily add new CAVIUS Wireless Family alarms to the system.

THE BEST AREAS TO INSTALL THE SMOKE ALARM

  • Install an alarm between possible fire sources and bedrooms as a minimum.
  • Install alarms on each floor of the house, in hallways and stairways.
  • Alarms in each room such as bedrooms and living rooms.

Additional alarms increase security.

AREAS WHERE NOT TO INSTALL SMOKE ALARMS

  • In dusty rooms.
  • At the top of a high pointed ceiling, in ceiling corners, and within 50cm of a wall.
  • In rooms where the temperature goes outside +4o to 38oC or above 90% relative humidity does not condense.
  • In kitchens, garages, laundries, or too close to fireplaces; areas where either dampness, gases, or smoke could occur.

Place the alarm where it is reachable in order to test the battery and for maintenance.

PLACEMENT

The smoke alarm is designed to be installed on a ceiling or wall.

For ceiling installation:
The smoke alarm should be a minimum of 50cm from the wall.

For cathedral or peak ceiling or wall installation:

CAVIUS-2113-Optical-Smoke-Alarm-Device-fig- \(8\)

With a minimum of one smoke alarm per floor and a maximum distance between smoke alarms of 10 meters.

INSTALLING THE SMOKE ALARM

  • Detach the alarm from the mounting base by twisting it counterclockwise.
  • Use the mounting base ring to mark the screw holes on the ceiling or the wall.
  • Once the mounting base is installed, attach the alarm by twisting it clockwise until it clicks. If the battery is either missing or inserted incorrectly, or the switch is in ‘Learn Mode’, the smoke alarm will not be able to click into the mounting base.

TEST FUNCTION

  • After installation, and at least once per quarter, test all of your alarms to ensure they are operating correctly and are within range of each other.
  • It is recommended to check visually every week if the LED flashes correctly (every 48 seconds.)
  • Press the test button on any alarm for at least 10 seconds. This will send out a test signal from the alarm; all other connected alarms should receive the signal within a short time. The alarms will emit a short beep and the LED will flash every 8 seconds for 2 minutes.
  • NOTE: The test function also allows to sending of a depleted RF signal to ensure optimal operation in normal conditions.

When the test signal is sent out, the alarms will respond in two ways:

  1. A single beep every 8 seconds indicates that the alarms are connected and functioning.
  2. Three short beeps every 8 seconds indicate a smoke sensor fault. The alarm should be cleaned by running the vacuum (on a low setting) around the smoke alarm chamber and tested again.
    • If required this indication can be stopped early on each alarm by a short press of the test button.
    • TIP: It is safe to cover the sound output hole with your finger during the testing to minimize the sound level emitted.
    • If the problem continues, please visit www.cavius.com for any troubleshooting.

NORMAL MODE

  • In normal mode, the LED will flash every 48 seconds to show the correct operation.

ALARM MODE

  • When a concentration of smoke is detected, the smoke alarm will go into ‘Alarm Mode’. It will sound the alarm signal and the LED will flash.
  • The smoke alarm will also transmit the alarm signal to the other connected alarms, which will also sound the alarm signal after a short delay.

The CAVIUS Wireless Family has two different alarm signals:

  • Alarm signal 1 (— — —) is a life-threatening alarm, like a smoke alarm.
  • Alarm signal 2 (- – -) is a non-life-threatening alarm, like a flooding alarm:
    • Smoke alarm signal: — — —
    • Heat alarm signal: — — —
    • Flood alarm signal: – – –

Please note that only the originating alarm’s LED will flash, so it can be identified.

PAUSE/HUSH FUNCTION

  • If the smoke alarms are to set into a false alarm by cooking, fireplace, etc. they can be paused for 10 minutes by pressing the test button on the originating smoke alarm only (indicated by the flashing LED).
  • The reason for this is that it is necessary to locate the source of the alarm before using the hush function. This is to make sure that it is not a life-threatening situation.

ADD EXTRA DEVICE

  • All CAVIUS interconnected alarms within the Wireless Alarm Family can be added to the system as they run on the same frequency and use the same data protocol. This means that the wireless system can consist of a combination of smoke, heat, flood, etc.
  • Place all alarms into ‘Learn Mode’ and repeat section 1.
  • Always test the connection to all devices by repeating test function section 7 after adding devices

LOW BATTERY SIGNAL

  • Your product has a 5Y battery life. When the battery is starting its end of life, a short beep will sound out every 48 seconds for 30 days.
  • The alarm affected by the low battery will only beep, no other connected alarms will sound.
  • It is safe to change batteries in the alarms without going through the learning process again – they will not forget the codes during the battery change process.

BATTERY REPLACEMENT

  • To replace the battery, detach the smoke alarm from the mounting base by twisting it counterclockwise. Replace the battery respecting the polarities.
  • Caution: There is a risk of explosion if the batteries are replaced by an incorrect type.
  • Attach the alarm in the mounting base by twisting it clockwise until it clicks, and test the alarm.

MAINTENANCE & TROUBLESHOOTING

  • The smoke alarm should be vacuum cleaned once per quarter, to remove dust particles, and it can be wiped with a damp cloth. (Do not open the alarm).
  • High humidity condensing which can be resolved by drying the smoke alarm.
  • If the smoke alarm does not work when the test button is pushed, the probable cause is a faulty battery. Check if the battery is worn out and replace it. Always test the alarm after the replacement of the battery.
  • If the problem continues, please visit www.cavius.com for any troubleshooting.

OTHER INFORMATION

  • Do not paint the alarm.
  • Disposal: For battery and product, please dispose properly at the end of life. This is electronic waste that should be recycled.
  • Please note local regulations about information to your insurance company regarding the installed smoke alarms.
  • Complies to the Radio Equipment Directive 2014/53/EU
  • RF Frequency: 868 MHz.
  • Maximum radio-frequency power transmitted: 20 dBm.
  • Full DoC to 2014/53/EU (RED) can be downloaded at www.cavius.com.
  • WARNING: All alarms should be assumed as due to actual fire and the dwelling should be evacuated immediately.
  • WARNING: To prevent injury, this apparatus must be permanently fixed to the ceiling/wall in accordance with the installation instructions.
  • WARNING: Batteries shall not be exposed to excessive heat such as shine, fire, or the like. Note the local country regulations regarding installation.
  • Hereby, Cavius declares that the radio equipment type 2113 is in compliance with Directive 2014/53/ EU.
  • The full text of the EU Declaration of Conformity is available at the following internet address: www.cavius.com.

EN 14604:2005 + AC :2008
DoP no.: 102.0016

  • The CE and RED declaration of conformity and DoP can be downloaded from: http://www.cavius.com.
  • The paper version of the DoP is available free of charge upon request.

Carrier assumes no responsibility for any errors, which may appear in this manual. Furthermore, Carrier reserves the right to alter the hardware, software, and/or specifications detailed herein at any time without notice, and Carrier does not make any commitment to update the information contained herein.

Manufacturer:
Carrier Fire & Security Danmark A/S, Ellekær 9A, 2. Th, DK-2730. Manufactured in P.R.C.

©2023 Carrier. All Rights Reserved.
All trademarks and service marks referred to herein are the property of their respective owners.